Weishaupt Gas burners model “G”Combination Gas/Oil burners models“GL” and “RGL” Sizes 1 and 3
1/2000 CA
2
The Weishaupt Research andDevelopment Institute was establishedin 1962 with the aim to develop excep-tional products in terms of quality andperformance. This commitment wasmade at a time when the concepts of“energy savings” and “environmentalprotection” were not yet consideredissues of social and political importance.
The Weishaupt company and its pro-ducts are founded on the principles ofquality design and performance.
● Certified to international quality stan-dard ISO 9001
● Listed by ETL (UL795/296) and CGA ● Annual sales in excess of 150,000
burners
Burner Design● Forced draft automatic burner● Cast aluminum, hinged monobloc
design● Burner swings open to the left or right● Stainless steel flame tube capable of
withstanding temperatures up to1450° F
● Precision cam arrangement controlsthe fuel and combustion air
● Single servomotor drives the camarrangement and controls the indivi-dual set point for:– High fire position gas/oil– Air damper closed – Ignition position gas– Ignition position oil (RGL)– Low fire position gas– Low fire position oil (RGL)– Stage 2 oil solenoid (GL)– Low fire position gas/oil (GL)
FuelsFollowing fuels can be burned with theburner models G, GL, RGL● Gas
– Natural gas– Liquid gas (Propane)– Manufactured gas– Special gases on request
e.g. digester / sewer gas
● Oil– No.2 Oil (model GL and RGL)
Oil ViscositiesNo.2 OilMaximum viscosity 3.5 cSt at 100°F
Combination Gas/Oil burners aredesigned so that the operation can beswithed from one fuel to the other, either
automatically or manually without furtheradjustments to the burner. Dual gasburners are available on special request.
Electro-Magnetic ClutchThe coupling between the oil pump andthe motor shaft is automatically discon-nected when operating on gas, protect-ing the oil pump from unnecessary wear.
Gas TrainsWeishaupt Gas and CombinationGas/Oil burners are always suppliedwith two (2) safety shut off valves inboth the pilot and main gas trains.
Burner Version and Capacity RegulationGas models “G”– Low/High/Low version ZD controlled
by a servomotor with a running time of8 seconds
– Modulating version ZMD controlled bya servomotor with a running time of 42 seconds
Combination Gas/Oil models “GL”– Low/High/Low gas/oil version ZD
controlled by a servomotor with a running time of 8 seconds
– Modulating gas, Low/High/Low oil version ZMD controlled by a servo-motor with a running time of 20 seconds
Combination Gas/Oil models “RGL”– Modulating gas/Modulating oil version
ZMD controlled by a servomotor witha running time of 42 seconds
Air/Fuel RegulationLow/High/Low and Modulating gasThe adjustable cam arrangement on theburner results in a simultaneous move-ment of the air damper and gas butterfly.The air quantity can be matched to thegas quantity throughout the firing range.This precise regulation results in an opti-mum fuel/air ratio and improved turndown figures.
Low/High/Low oilThe low fire (stage 1) and high fire(stage 2) oil solenoid valves are con-trolled by micro switch set points on theservomotor, which permit preciseadjustment of fuel and air.
Modulating oilThe adjustable cam arrangement resultsin a simultaneous movement of the airdamper and oil flow regulator. The air
quantity can be matched to the oil quan-tity throughout the firing range andimproved turn down figures.
Controlled shut downThe control system is designed toensure a controlled shut down of theburner at the low fire position. After acontrolled shut down the air damper dri-ves automatically closed.
Ignition positionBurner models “G” and “GL” provide anindependent ignition position, in additionto the low fire position, when operatingon gas.
Burner model “RGL” provides a sepa-rate ignition position and separate lowfire positions for both gas and oil.
This feature permits the burner to betuned to the appliance, allowing only avery small quantity of gas (or oil) to be released for light off.
Flame supervisionStandard methods of flame monitoringare: ● a flame rod for Gas ● a UV scanner for Combination
Gas/Oil
Flame Monitoring SystemsThe burner flame monitor sequencesand controls the operation of the burnerautomatically. The flame monitor can be located in either the burner control panelor mounted directly on the burner. Thestandard flame monitoring system usedis manufactured by Landis & Staefa.
Alternative flame monitoring systems utilizing configurations of the Honeywell7800 series and Fireye E 110 are available upon request.
Site of InstallationThe standard version of Weishaupt burn-ers is designed for operation in enclosedareas with ambient temperatures from15°F to 100°F (-10°C to +40°C)
Description
3
Gas burner G, sliding two stage ZM and modulating
Pressure side air regulating damper Gas burner G, sliding two stage Z
Electro magnetic clutch Dual fuel burner GL, sliding two stage ZM and modulating
Gas burner G with integrated switch gear Servomotor on Dual fuel burner RGL: Gas- and Oil part sliding two stage ZM
4
Dual fuel burner
Model G L 3 / 1 – E, version Z E
ZM D
Index Motor typeCode for E ~ Single phasecapacity range D ~ Three phase
Size 1 - 3 Control typeFuel = #2 Oil Z = sliding two stage (Gas)
Fuel = Gas and two stage (Oil)(Servomotor with 8 sec. runtime)
Model RGL3/1-E, version ZMD ZM = sliding two stage (Gas)R = modulating burner and two stage (Oil) ZM = sliding two stage (Servomotor with
(Servomotor with 20 sec. runtime) 20 sec. runtime) or or modulating modulating (Gas) (Servomotor with 42 sec. runtime) and twostage (Oil)
(Servomotor with 20 sec. runtime)
Overview of Weishaupt Gas- and Dual fuel burners
G1-G3Z. GL1-GL3Z. G1-G3ZM.. GL1-GL3ZM.. RGL3ZM..
fast capacity regulation slow capacity regulation
Burner nomenclature
Gas burner
Model G 1 / 1 – E, version Z E
ZM D
Index Motor typeCode for E = Single phasecapacity range D = 3 Phases
Size 1 - 3 Regulation typeFuel = Gas Z = Z= sliding two stage
(Servomotor with 8 sec. runningtime)
ZM = ZM= sliding twostage(Servomotor with 20 sec. runningime) or modulating (Servomotorwith 20 or 42 sec. running time)
Model designationScope of supply
Scope of supplyBurner model G1-G3Z G1-G3ZM GL1-GL3Z GL1-GL3ZM RGL3
Burner casing with integral air intake guide, hinged flange, ● ● ● ● ●casing cover with sight glass, Weishaupt burner motor, pressure side air regulation, blower wheel, air pressure switch, Servomotor, Gas/air-compound regulation with regulating cam(s), Combustion head, ignition transformer, ignition cable, ignition electrodes, terminal strip, flange gasket, mounting bolts
Flange interlock switch ● ● ● ● ●
Flame safeguard with flame sensor (ionization electrode) ● ●loose for installation in a remote panel or mounted on the burner
Flame safeguard with flame sensor (UV cell) ● ● ●loose for installation in a remote panel
Double gas valves ● ● ● ● ●
Gas butterfly valve ● ● ● ● ●
Pressure switch(es) for Gas ● ● ● ● ●
Oil pump , solenoid valve, nozzle head, nozzles, oil hoses, ● ● ●Oil/Air-compound regulation with regulating cam(s)
Pressure switch(es) für Oil ●
Electro-Magnetic clutch (on GL1-GL3 as an option available) ●
Gas burner Dual fuelburner
sliding-twostage
Gas: slid.twostageOil: twostage
Servomotor with8 sec. running time
Servomotor with8 sec. running time
Gas burner
sliding-twostage
modulating
Servomotor with20 sec. running time
Dual fuel burner
Servomotorwith 20 sec.running time
Servomotor with42 sec. running time
(20 sec only withheat exchanger withquick load changes)
Gas: modulatingOil: twostage
Gas and Oil:slid.twostage
Gas and Oil:modulating
Servomotor with8 sec. running
time
Servomotor with8 sec. running
time
Servomotor with42 sec. running
time
Gas: slid.twostageOil: twostage
5
The capacity graphs are representa-tive of tests performed under condi-tions as stated below.
The minimum firing rate may varyfrom application to application. In cer-tain cases, a greater turn down ratiois possible.
Test Criteria:All figures relate to an ambient tem-perature of 70ºF (20ºC) and a site ele-vation of 1,650 ft (500m) above sealevel.
The capacity graphs are based on fuelwith low calorific value.
Gas burner version LN Using the especially low emission gasburners G1 and G3, version LN, themost stringent regulation and limits ofvarious emission regulating standardscan be achieved.
The capacity graphs show the burnerrating at:
Flame tube “open”Flame tube “closed”
Burner selection gas and dual fuel burnersBurner capacity/combustion chamber pressure
[“WC ] Burner model G1/1-ECombustion head G1/2a- 115 - 95KMBH Natural gas/ Propane 205 – 1,145
[MBH] 0 200 400 600 800 1,000 1,200 1,400
2.0
1.5
1.0
0.5
0
-0.5
-1.0
Nat
gas
/ Pro
pane
[“WC ] Burner model GL1/1-ECombustion head G1/2a- 115 - 95KMBH Natural gas/ Propane 205 – 1,145GPH #2 Oil 2.9 – 8.1
[MBH] 0 200 400 600 800 1,000 1,200 1,400
2.0
1.5
1.0
0.5
0
-0.5
-1.0
Nat
gas
/ Pro
pane
#2
oil
[“WC ] Burner model G3/1-ECombustion head G3/1a- 133 - 100KMBH Natural gas/ Propane 310 – 2,150
[MBH] 0 200 400 600 800 1,000 1,200 1,400 1,600 1,800 2,000 2,200
3.0
2.5
2.0
1.5
1.0
0.5
0
-0.5
-1.0
Nat
gas
/ Pro
pane
Nat
gas
/ Pro
pane
[“WC ] Burner model GL3/1-E and RGL3/1-ECombustion head G3/1a- 133 - 100KMBH Natural gas/ Propane 310 – 2,150GPH #2 Oil 4.6 – 15.3
[MBH] 0 200 400 600 800 1,000 1,200 1,400 1,600 1,800 2,000 2,200
3.0
2.5
2.0
1.5
1.0
0.5
0
-0.5
-1.0
Nat
gas
/ Pro
pane
Nat
gas
/ Pr
opan
e
#2
oil
#2
oil
6
Accessories
Description G1 G3 GL1 GL3
RGL3
1 Interlock switch on burner flange standard standard
2 Downward firing standard standard
3 Air intake flange for connection to an air duct ● ●
4 Oil hoses 51” (1300mm) instead of 39” (1000mm) GL/RGL ● ●
5 Discharge oil pressure gauge with manual isolating ball valve GL ● ●RGL – ●
6 Oil vacuum gauge with manual isolating ball valve GL/RGL ● ●
7 Combustion head extension G1-G3 4” (100 mm) ● ●8” ( 200 mm) ● ●12” (300 mm) ● ●
GL1-GL3 4” (100 mm) ● ●8” (200 mm) ● ●12” (300 mm) ● ●
RGL3 4” (100 mm) – ●8” (200 mm) – ●12” (300 mm) – ●
8 Integrated Switch Gear (ISG) version G, version ZE ● ●with LFL, without magnetic clutch G, version ZD ● ●
G, version ZME ● ●G, version ZMD ● ●
GL, version ZE ● ●GL, version ZD ● ●
9 Integrated Switch Gear (ISG) version GL, version ZE ● ●with LFL and magnetic clutch GL, version ZD ● ●
GL, version ZME – ●GL, version ZMD – ●
10 Electro-magnetic clutch (optional for GL, standard for RGL ● ●
11 Flame sensor (UV-cell) — instead of flame rod (standard on GL and RGL) ● ●
12 Potentiometer installed in Servomotor (ZM) 1000 Ohm ● ●
13 Solenoid valve for continuous motor run or post purge ● ●
7
Description for Burner for Burner G1/GL1 G3/GL3/RGL3
Burner motor single phase, 60Hz Model EC 90/50-2 EC 90/90-2Motor Rating HP (kW) 0.8 (0.60) 2 (1.5)Motor Full Load Amp at 120V A 7.5 16Speed rpm 3450 3450Capacitor µF 16 32
Burner motor three phase, 60Hz Model D 90/50-2 D 90/50-2Motor Rating HP (kW) 1.14 (0.85) 1.14 (0.85)Motor Full Load Amp at 460V A 2.3 2.3Speed rpm 3400 3400
Blower wheel plated platedIgnition unit Type W-ZG 02/2 W-ZG 02/2
Standard flame safeguard Model LFL 1.335 LFL 1.335
Servomotor– one stage, sliding-twostage Z (Running time 8 sec.) Model -w- 1055/80 -w- 1055/80– sliding-twostage ZM (Running time 20 sec.) Model SQM 10.15561 SQM 10.15561– modulating (Running time 42 sec.) Model SQM 10.16561 SQM 10.16561
Oil pump GL Model AE67C AE97C(on dual fuel burner) RGL Model – AJ6CE
Oil solenoid valve 110V 1/8” GL (qty: 3) Model 121 C 2323 121 C 232355V 1/4” RGL (qty: 2) Model – 121 K 622055V 1/8” RGL (qty: 2) Model – 121 K 2423
Oil-pressure switch 14.5 - 145 PSI (1 - 10 bar) Type – 900.2378
Oil hoses Diameter/LengthID/inches 5/16”/ 39” 5/16”/ 39”DN/mm 8/1000 8/1000
WeightGas burners without gas train approx. lbs/ kg 86/ 39 95/ 43Dual fuel burners without gas train approx. lbs/ kg 93/ 42 104/ 47
Technical Data
8
9
12
P
3 4
P
5
Sliding two stage and modulating burnerGas part
Dual fuel burner GL1-GL3 Oil part: two stage
Dual fuel burner RGL3Oil part: sliding two stage or modulating
Fuel supply schematics
Legend1 Isolating valve2 Main gas pressure regulator3 Low gas pressure switch4 Double main gas valves5 High gas pressure switch8 Integrated gas butterfly valve9 Burner10 Oil pump
11 Oil solenoid valve, normally closed12 Oil pressure switch13 Oil regulator14 Oil nozzles
NoteThe actual gas train arrangement may differdepending on applicable code and regulation
Dimensions Weishaupt Corporation6280 Danville RoadMississauga, ON L5T 2H7Ph.: (905) 564 0946, Fax.: (905) 564 0949www.weishaupt-corp.com
Print No. 83002616, June 2004Printed in Germany. All rights reserved.
Dimensions of burner mounting plate
Size Dimensions in inches (mm)I1 I2 I3 I4 I5 I6 I7 I8➀ I8➁ I9➀ I9➁ b1 b2 b3 b4 b5➀
1 27.0 6.6 4.4 6.6 1.4 3.5 0.3 12.3 13.5 4.3 4.7 25.8 19.6 10.8 9.8 21.4(685) (168) (112) (168) (35) (88) (8) (312) (342) (110) (120) (655) (497) (275) (248) (543)
3 31.7 7.4 6.0 7.4 1.1 3.9 0.3 15.4 15.0 4.3 4.7 28.9 20.7 11.6 11.0 22.4(805) (188) (153) (188) (28) (98) (8) (392) (382) (110) (120) (735) (525) (295) (280) (570)
b5➁ b5➂ h1 h2 h3 h4 h5 d1 d2 d3 d4 d5 d6 d7 r1 r2
1 25.7 – 15.3 11.4 5.9 6.9 5.1 7.7 5.1 5.1 6.3-6.7 5.3 21.7 24.8(653) – (388) (290) (150) (175) (130) (195) (129) DN25 (130) M8 (160-170) (135) (550) (630)
3 26.8 29.5 16.9 12.8 6.7 6.9 5.5 8.7 6.1 6.3 7.3 6.5 25.6 27.6(680) (750) (430) (325) (170) (175) (140) (220) (154) DN40 (160) M10 (186) (165) (650) (700)
Flange connection
➀ Sliding twostage burner version Z➁ Sliding twostage burner version ZM➂ Sliding twostage RGL burner