17-11-2014 1 Geotechnical Investigation Reports and Foundation Recommendations -Present status in India -Examples Prof. V.S.Raju (Formerly: Director, IIT Delhi & Professor and Dean, IIT Madras) Email: [email protected] Prof. V.S. Raju 1 CHOICE OF APPROPRIATE FOUNDATION AND EXECUTION Optimum foundation design should ensure: technical adequacy, cost effectiveness and ease of execution. This is not easy, because of many variables including insufficient and inaccurate information at the time of design. Variation in strata and changes in project requirement during execution Prof.V.S.Raju 2

Geotechnical Investigation Reports and Foundation Recommendations ... Investigation... · 17-11-2014 1 Geotechnical Investigation Reports and Foundation Recommendations -Present status

  • Upload
    votruc

  • View
    224

  • Download
    2

Embed Size (px)

Citation preview

Page 1: Geotechnical Investigation Reports and Foundation Recommendations ... Investigation... · 17-11-2014 1 Geotechnical Investigation Reports and Foundation Recommendations -Present status

17-11-2014

1

Geotechnical Investigation Reports

and

Foundation Recommendations

-Present status in India

-Examples

Prof. V.S.Raju

(Formerly: Director, IIT Delhi & Professor and Dean, IIT Madras)

Email: [email protected] Prof. V.S. Raju

1

CHOICE OF APPROPRIATE FOUNDATION AND EXECUTION

Optimum foundation design should ensure: technical

adequacy, cost effectiveness and ease of execution.

This is not easy, because of many variables including insufficient and inaccurate information at the time of design.

Variation in strata and changes in project requirement during execution

Prof.V.S.Raju 2

Page 2: Geotechnical Investigation Reports and Foundation Recommendations ... Investigation... · 17-11-2014 1 Geotechnical Investigation Reports and Foundation Recommendations -Present status

17-11-2014

2

TOPICS COVERED

Inadequacy of the Investigations and Inappropriate Foundation Recommendations with Illustrative Examples 1. Fertilizer Plant on the East Coast

2. Fertilizer Plant in Gangetic Belt

3. Office cum Residential Complex at Jodhpur

4. University Campus at Adilabad District

5. L&T Serene County (Residential Campus)

Prof.V.S.Raju

3

FERTILIZER PLANT ON THE EAST COAST

The average soil strata consists of : top layer of dense fine sand 4 to 8 m thick.

followed by soft marine clay up to a depth of 14 to 18 m below ground level.

very stiff clay up to 30 to 40 m below ground level.

Prof.V.S.Raju 4

Page 3: Geotechnical Investigation Reports and Foundation Recommendations ... Investigation... · 17-11-2014 1 Geotechnical Investigation Reports and Foundation Recommendations -Present status

17-11-2014

3

Prof.V.S.Raju 5

PROBLEMS DUE TO THE PRESENCE OF SOFT CLAY LAYER For site grading, 1- 2 m fill is required - results in a settlement of 12 cm of soft clay. - Along with clay, sand layer also moves down.

In case of pile foundation, large negative drag on piles from soft clay and sand layer.

Considerable reduction in pile capacity (upto 50%), and hence increase in the number of piles.

For structures like bulk storage with large area loads, the stability of soft clay layer and lateral flow to be checked.

Large settlements of floors and lateral forces on neighbouring pile foundations.

Prof.V.S.Raju 6

Page 4: Geotechnical Investigation Reports and Foundation Recommendations ... Investigation... · 17-11-2014 1 Geotechnical Investigation Reports and Foundation Recommendations -Present status

17-11-2014

4

FOUNDATIONS ADOPTED Precast driven piles were chosen, with bitumen coat in the top layers to reduce the negative drag.

All light structures, not sensitive to settlements, are supported on shallow foundations.

For structures having distributed loads over large areas (silos, water storages), surcharge provided on the periphery to achieve reduced shear stresses on soft clay.

Prof.V.S.Raju 7

The original recommendation was to go for bored piles, 45 cm in diameter. Two alternative pile types have been tested.

a) Precast driven piles 40 cm x 40 cm, 22 m long (to be able to drive). b) Bored cast in situ piles, 45cm dia, 22 m long

Full scale tests for a final decision on the choice of the pile type.

6 test piles, 3 each of the 2 types, installed in 3 different locations in close proximity. Bored cast in-situ piles were installed by bailer boring method.

Prof.V.S.Raju

CHOICE OF THE PILE

8

Page 5: Geotechnical Investigation Reports and Foundation Recommendations ... Investigation... · 17-11-2014 1 Geotechnical Investigation Reports and Foundation Recommendations -Present status

17-11-2014

5

RESULTS OF PILE LOAD TESTS

Prof.V.S.Raju 9

10

60 60 120 65 B6

82 82 164 85 P5

27 27 54 32 B4

97 97 194 110 P3

54 54 108 55 B2

73 (100)* 80 160 73 P1

Working Load (smaller of 2 and 4) (5)

Half of Failure Load (4)

Failure Load (3)

2 / 3 of Load at 12 mm settlement (2)

Pile No. (1)

The pile length is 19.5 m, and failure load extrapolated for 22 m length is 100 tons.

Table 1: WORKING LOAD IN TONS AS PER IS 2911

Prof.V.S.Raju

Page 6: Geotechnical Investigation Reports and Foundation Recommendations ... Investigation... · 17-11-2014 1 Geotechnical Investigation Reports and Foundation Recommendations -Present status

17-11-2014

6

CONCLUSIONS

Precast driven piles with design load of 70 to 100 tonnes adopted for the following reasons :

For comparable dimensions, the precast pile has 50 to

80% higher capacity than a bored pile.

Precast pile offers better protection to reinforcement. This is particularly important under the present saline ground water conditions.

The jetting of precast pile up to 12 m will reduce the friction over this depth, and consequently the effects of negative drag.

In case of precast piles, the negative drag can be reduced by applying a slip layer of bitumen.

Prof.V.S.Raju 11

Lower Capacity

Boring operations through stiff fissured clay will result

in softening of this layer, thereby limiting the load

carrying capacity of piles.

There is no possibility of applying any slip layer and to

reduce the negative drag.

Prof.V.S.Raju

Bored piles not preferred for the following reasons:

Conclusions (Contd.)

12

Page 7: Geotechnical Investigation Reports and Foundation Recommendations ... Investigation... · 17-11-2014 1 Geotechnical Investigation Reports and Foundation Recommendations -Present status

17-11-2014

7

ANTICIPATED NEGATIVE DRAG

40 tonnes based on theoretical consideration.

Field load tests on

i) Short piles resting on soft clay,

ii) Instrumented piles, where the load distribution with depth has been measured.

Model tests for the proper choice of bitumen coating to reduce negative drag.

i) Precast concrete 10 cm dia and 50 cm long piles were used.

ii) Bitumen coatings using different grades of bitumen were applied, and results showed 80 to 90% reduction in friction.

iii) Finally SAE 80 grade bitumen was adopted. Prof.V.S.Raju

13

Page 8: Geotechnical Investigation Reports and Foundation Recommendations ... Investigation... · 17-11-2014 1 Geotechnical Investigation Reports and Foundation Recommendations -Present status

17-11-2014

8

Page 9: Geotechnical Investigation Reports and Foundation Recommendations ... Investigation... · 17-11-2014 1 Geotechnical Investigation Reports and Foundation Recommendations -Present status

17-11-2014

9

Page 10: Geotechnical Investigation Reports and Foundation Recommendations ... Investigation... · 17-11-2014 1 Geotechnical Investigation Reports and Foundation Recommendations -Present status

17-11-2014

10

Page 11: Geotechnical Investigation Reports and Foundation Recommendations ... Investigation... · 17-11-2014 1 Geotechnical Investigation Reports and Foundation Recommendations -Present status

17-11-2014

11

Page 12: Geotechnical Investigation Reports and Foundation Recommendations ... Investigation... · 17-11-2014 1 Geotechnical Investigation Reports and Foundation Recommendations -Present status

17-11-2014

12

Page 13: Geotechnical Investigation Reports and Foundation Recommendations ... Investigation... · 17-11-2014 1 Geotechnical Investigation Reports and Foundation Recommendations -Present status

17-11-2014

13

Page 14: Geotechnical Investigation Reports and Foundation Recommendations ... Investigation... · 17-11-2014 1 Geotechnical Investigation Reports and Foundation Recommendations -Present status

17-11-2014

14

Page 15: Geotechnical Investigation Reports and Foundation Recommendations ... Investigation... · 17-11-2014 1 Geotechnical Investigation Reports and Foundation Recommendations -Present status

17-11-2014

15

The Soil Strata:

Silty sand with low N values (<10) upto 10 m depth,

N > 20 beyond 20 m depth.

N-values ranging between 10 to 20 for the layer between 10 to 20 m depth.

High water table with possibility of liquefaction during earthquake.

Prof.V.S.Raju

FERTILIZER PLANT IN GANGETIC BELT

30

Page 16: Geotechnical Investigation Reports and Foundation Recommendations ... Investigation... · 17-11-2014 1 Geotechnical Investigation Reports and Foundation Recommendations -Present status

17-11-2014

16

Prof.V.S.Raju

PHASE I : INITIAL FOUNDATION DESIGN

RCC Piles, Driven Cast-in situ, 400 mm dia

Sand Compaction Piles, 2-3 Rows Around RCC Piles,

Pile capacities

Vertical downward : 50 t, Tension : 5t, Lateral : 2.5t,

Result – Total Requirement

16,000 RCC Piles

32,000 Compaction Piles

Problem of execution on time

31

Prof.V.S.Raju

REVIEW AND FURTHER INVESTIGATION (Pile Load Tests)

Revised Pile Capacities

Vertical : 65t

Tension : 25t

Lateral : 3.5t

Reduction in RCC Piles : 40%

Increase in spacing of compaction piles from 3d to 4 d ;

reduction in Compaction Piles : 50%

Saving in construction time : 6 months

Substantial cost savings as well. 32

Page 17: Geotechnical Investigation Reports and Foundation Recommendations ... Investigation... · 17-11-2014 1 Geotechnical Investigation Reports and Foundation Recommendations -Present status

17-11-2014

17

Prof.V.S.Raju

PHASE II OF THE PLANT

No RCC Piles.

900 mm dia Vibro-Stone Columns with varied spacing (2d,2.25d and 2.5d) to suit the foundation requirement.

Full scale field trials.

Several Footing tests for confirmation.

Substantial savings in time and cost.

33

34 Prof.V.S.Raju

0

2

4

6

8

10

12

0 5 10 15 20 25 30 35 40 45

LOAD kg / m2 x 103

SE

TT

LE

ME

NT

(m

m)

7.5

11.77

LOAD SETTLEMENT CURVES FOR SINGLE COLUMN LOAD TEST

Page 18: Geotechnical Investigation Reports and Foundation Recommendations ... Investigation... · 17-11-2014 1 Geotechnical Investigation Reports and Foundation Recommendations -Present status

17-11-2014

18

Prof.V.S.Raju

LOAD SETTLEMENT CURVES FOR SINGLE AND THREE COLUMN TEST

0

2

4

6

8

10

12

0 5 10 15 20 25 30 35 40 LOAD kg / m2 x 103

SE

TT

LE

ME

NT

(m

m)

10.5 10

8.6

Aonla (Benefield) Aonla (Prill Tower)

Aonla (Compressor House)

Single column Test

Three Column Test

Prof.V.S.Raju 35

Page 19: Geotechnical Investigation Reports and Foundation Recommendations ... Investigation... · 17-11-2014 1 Geotechnical Investigation Reports and Foundation Recommendations -Present status

17-11-2014

19

2 -3 Storeyed Buildings Investigations Done

8 Bore holes drilled to 6 m depth each.

As per bore logs Rocky strata. Strata starts at Ground level (GL) in all bore holes except in Bore hole 5, where it starts at 1.5 m. BH 5 is at the extreme corner of the plot where nothing is planned to be built. Bore logs do not give the core recovery, which is a must to be given.

Office cum Residential Complex at Jodhpur

Prof.V.S.Raju 37

Recommendations by Investigation Agency

1. Open foundations (footings)

2. Unconfined compressive strength of rock

range given 650 to 850 t/m2

3. Calculated safe bearing capacity (SBC) 80 to

100 t/m2

Prof.V.S.Raju 38

Page 20: Geotechnical Investigation Reports and Foundation Recommendations ... Investigation... · 17-11-2014 1 Geotechnical Investigation Reports and Foundation Recommendations -Present status

17-11-2014

20

FOUNDATION RECOMMENDATIONS (Contd…)

4. Recommended SBC is 40 t/m2 at 1m

below GL, except in BH 5; where SBC

is 10 t/m2 at 1.2 m depth and 40 t/m2

from 2 m depth onwards.

5. The SBC adopted in Design is not

known. It should have been written on

the drawings.

Prof.V.S.Raju 39

1. Foundation Depth adopted: 1.5m.

2. Foundation sizes 1.5m x 1.5m to 2.3m x 2.3m

3. For excavation Rock Blasting has been done

4. Instead of excavating / blasting individual pits

for each footing, the entire foot print of all the

buildings has been blasted and excavated.

WHAT HAPPENED AT SITE

Prof.V.S.Raju 40

Page 21: Geotechnical Investigation Reports and Foundation Recommendations ... Investigation... · 17-11-2014 1 Geotechnical Investigation Reports and Foundation Recommendations -Present status

17-11-2014

21

5. This resulted in excavated rock material ranging

from huge boulders to rubble of volume of about

25,000 m3 (Actually needed ≈ 10% of this).

6. Additional issues:

(a) How to dispose of the excavated material.

(b) Huge quantity of soil material for plinth

filling needed.

What Happened at Site (Contd…)

Prof.V.S.Raju 41

Basis : Site visit

Inspection of the strata in the

excavated pits

Study of the soil report

1. The investigation is not as per the

relevant Indian Standards.

Prof. V.S. Raju’s Investigation of the Situation

and Foundation Recommendations

Prof.V.S.Raju 42

Page 22: Geotechnical Investigation Reports and Foundation Recommendations ... Investigation... · 17-11-2014 1 Geotechnical Investigation Reports and Foundation Recommendations -Present status

17-11-2014

22

2. The recommendations in the report are

wrong and are less by a Factor 3 to 4.

3. The correct SBC values are 150 t/m2 (on a

conservative side) with a minimum size of

footing as 0.8m x 0.8m.

Depth of footing 0.5m to 1m.

Prof. V.S. Raju’s Recommendations (Contd …)

Prof.V.S.Raju 43

4. There is absolutely no justification to stipulate

a foundation depth of 1.5m for the entire site.

5. There was no need at all to make the footing

sizes so big as given (1.5m x 1.5m to 2.3m x

2.3m)

6. There is no need to blast the strata over the

entire foot print of the building.

Prof. V.S. Raju’s Recommendations (Contd …)

Prof.V.S.Raju 44

Page 23: Geotechnical Investigation Reports and Foundation Recommendations ... Investigation... · 17-11-2014 1 Geotechnical Investigation Reports and Foundation Recommendations -Present status

17-11-2014

23

7. No need to blast for the individual footings also as the required likely sizes are 0.8m x 0.8m to 1.2m x 1.2m, depth 0.5 m to 1.0m only.

Pavement breakers (jack hammers) will do the job.

Prof. V.S. Raju’s Recommendations (Contd …)

Prof.V.S.Raju 45

Photographs of Blasted Rocks Prof.V.S.Raju

46

Page 24: Geotechnical Investigation Reports and Foundation Recommendations ... Investigation... · 17-11-2014 1 Geotechnical Investigation Reports and Foundation Recommendations -Present status

17-11-2014

24

rap

Photographs of Blasted Rocks Prof.V.S.Raju

47

University Campus at Adilabad District

Total area ~ 300 acres For Phase I development, Only 7 boreholes Bore logs improper and inadequate. First SPT at 10 m below GL. Pile Foundations recommended and executed, which are not at all required. Pile safe capacity for 600 mm dia, 12 m length : 83 tons (Very low) - Settlement of pile up to 10 % of pile diameter could not be attained

by 3 times the design load.

48 Prof. V.S. Raju

Page 25: Geotechnical Investigation Reports and Foundation Recommendations ... Investigation... · 17-11-2014 1 Geotechnical Investigation Reports and Foundation Recommendations -Present status

17-11-2014

25

5.8

m t

o 2

5m

soft

ro

ck

1.80 mto 5.80 m yellow clay & Murrum

0.00 to 1.80 m Brown clay

First SPT at 10m below G.L ,

Required every 1m to 1.5m

Typical Bore Profile Prof. V.S. Raju

49

Pile Load Tests:

Five Initial Load Tests

At 3 times the design load, settlements are only 2 mm to 27 mm as against permitted 45 mm to 60 mm.

Pile capacities are not revised.

Piles, which are not required in the first place are grossly over designed.

50 Prof. V.S. Raju

Page 26: Geotechnical Investigation Reports and Foundation Recommendations ... Investigation... · 17-11-2014 1 Geotechnical Investigation Reports and Foundation Recommendations -Present status

17-11-2014

26

• 30 Acres site

• Strata – Rocks and Boulders with local depressions, highly uneven.

• 10 towers between 11 and 14 floors

• Recommended SBC by the soil Investigation Agency 30 t/m2

- One value for the entire site?

L&T Serene County

Prof.V.S.Raju 51

L&T Serene County

52 Prof. V.S. Raju

Page 27: Geotechnical Investigation Reports and Foundation Recommendations ... Investigation... · 17-11-2014 1 Geotechnical Investigation Reports and Foundation Recommendations -Present status

17-11-2014

27

Extreme Issue was with one of the 10 towers built

Tower Dimension : 75 m x 30 m

Highly variable strata at Founding Level.

Hard Rock SBC 400 t/m2

Hard Murrum 80 t/m2

Soft Clay 4 m thick 0 t/m2

75 m

30 m

Tower Foot Print 53 Prof. V.S. Raju

Important:

• These type of variations do occur in rocky and bouldry strata

• The soft clay is due to a old pond, which normally gets covered up during site grading.

Prof.V.S.Raju 54

Page 28: Geotechnical Investigation Reports and Foundation Recommendations ... Investigation... · 17-11-2014 1 Geotechnical Investigation Reports and Foundation Recommendations -Present status

17-11-2014

28

All these examples reaffirm the requirement of high quality Geotechnical Investigation, Interpretation by a qualified Foundation Engineer in close collaboration with the Structural Designer.

Prof.V.S.Raju 55