Drawing: 950-207484 WirelessSensor_TH_THCO2_THVOC_ES1060Version / Rev. 1.0Date: 7/3-2019Drawn by: BJ/dfManufactured by: LS Control A/S Industrivej 12, DK-4160 Herlufmagle, Denmark
Technical data:Supply: 3 x 1.5V Alkaline battery AASurrounding temperature: 0 - 40°CEnclosure: IP 22Dimensions: 85x85x30 mm
Calculated average battery lifetimeT-RH: 3 yearsT-RH-CO : 2 years2
T-RH-VOC: 1.5 year
Description:
Sensor measures in intervals of 2min, though 2,5min for VOC. Signal is transmitted wireless to Receiver, if necessary via Repeater. Where signal is translated to ModBus or 0-10V signal for controller.
Measurement Areas and AccuracyCO sensor: 0-10000ppm via ModBus. Accuracy: ±10%2
0-2000ppm via 0-10Volt output. Accuracy: ±50ppm RH sensor: 0–80% RH. Accuracy ± 4% RHTemperature sensor: 0-50°C. ±2% VOC sensor: measurement area 0-100%. 0 good Air Quality 100 very bad Air Quality
Sensor-to-sensor deviation ±15%
Mounting:For wall mounting on stable non vibrating surface. Avoid direct sunlightand thermal stress.
Adjustment:
The CO sensor uses the widely used ABC algorithm, which ensures 2
long life without calibration. Only the room cannot be used constantly, but must regularly get sufficient airflow to lower the CO to fresh air 2
level.
[email protected] tel. +45 5550 5550 fax +45 5550 2265
Wireless Sensors / ES 1060 T-RH (-CO2/VOC)
Connection - Setting the Dip-Switches
SW1 SW2
S e n s o r n u m m e r S W 1 _ 1
S W 1 _ 2 S W 1 _ 3 S W 1 _ 4 S W 2 _ 1
0 O F F O F F O F F O F F O F F
1 O N O F F O F F O F F O F F
2 O F F O N O F F O F F O F F
3 O N O N O F F O F F O F F
4 O F F O F F O N O F F O F F
5 O N O F F O N O F F O F F
6 O F F O N O N O F F O F F
7 O N O N O N O F F O F F
8 O F F O F F O F F O N O F F
9 O N O F F O F F O N O F F
1 0 O F F O N O F F O N O F F
1 1 O N O N O F F O N O F F
1 2 O F F O F F O N O N O F F
1 3 O N O F F O N O N O F F
1 4 O F F O N O N O N O F F
1 5 O N O N O N O N O F F
1 6 O F F O F F O F F O F F O N
1 7 O N O F F O F F O F F O N
1 8 O F F O N O F F O F F O N
1 9 O N O N O F F O F F O N
2 0 O F F O F F O N O F F O N
2 1 O N O F F O N O F F O N
2 2 O F F O N O N O F F O N
2 3 O N O N O N O F F O N
2 4 O F F O F F O F F O N O N
2 5 O N O F F O F F O N O N
2 6 O F F O N O F F O N O N
2 7 O N O N O F F O N O N
2 8 O F F O F F O N O N O N
2 9 O N O F F O N O N O N
3 0 O F F O N O N O N O N
3 1 O N O N O N O N O N
N e tvæ r k s n u m m e r S W 2 _ 2
S W 2 _ 3 S W 2 _ 4
0 O F F O F F O F F
1 O N O F F O F F
2 O F F O N O F F
3 O N O N O F F
4 O F F O F F O N
5 O N O F F O N
6 O F F O N O N
7 O N O N O N
Setting of the dip-switches determine a sensors number within a network of sensors. If only one sensor is to be used, all switches are set in pos. OFF.
It is possible to set-up up to 7 networks including 31 sensors in each network. Every network needs its own receiver and potential repeaters. All sensors in a network must have set the same network number.
Network number is set using dip-switch SW2_2, SW2_3 and SW2_4. If only one network is used all switches are set to OFF.
Sensor Number
Network Number SW2_2 SW2_3 SW2_4