Upflow/ Horizontal Downflow /Horizontal Condensing, Direct Vent Gas-Fired Furnace PUB. NO. 22-1859-01 XT 95 TUH1B040A9H21A, TUH1B060A9H31A, TUH1B080A9H31A, TUH1C100A9H41A, TUH1D120A9H51A TDH1B040A9H21A, TDH1B065A9H31A, TDH1C085A9H41A, TDH1D110A9H51A High Efficiency Single-Stage Fan Assisted Combustion System TDH1-H DOWNFLOW DOWNFLOW/HORIZONTAL TUH1-H UPFLOW TUH1-H UPFLOW/HORIZONTAL TDH1-H

Upflow/ Horizontal Downflow /Horizontal Condensing, … Horizontal Downflow /Horizontal Condensing, Direct Vent Gas-Fired Furnace PUB. NO. 22-1859-01 XT 95

Embed Size (px)

Citation preview

Page 1: Upflow/ Horizontal Downflow /Horizontal Condensing, … Horizontal Downflow /Horizontal Condensing, Direct Vent Gas-Fired Furnace PUB. NO. 22-1859-01 XT 95

Upflow/ Horizontal Downflow /Horizontal Condensing, Direct Vent Gas-Fired Furnace

PUB. NO. 22-1859-01

XT 95TUH1B040A9H21A, TUH1B060A9H31A, TUH1B080A9H31A, TUH1C100A9H41A, TUH1D120A9H51A TDH1B040A9H21A, TDH1B065A9H31A, TDH1C085A9H41A, TDH1D110A9H51A

High Efficiency Single-Stage Fan Assisted Combustion System

TDH1-HDOWNFLOW

DOWNFLOW/HORIZONTAL

TUH1-HUPFLOW

TUH1-HUPFLOW/HORIZONTAL

TDH1-H

Page 2: Upflow/ Horizontal Downflow /Horizontal Condensing, … Horizontal Downflow /Horizontal Condensing, Direct Vent Gas-Fired Furnace PUB. NO. 22-1859-01 XT 95

© 2011 Trane All Rights Reserved 2 22-1859-01

GeneralFeatures

NATURAL GAS MODELSCentral Heating furnace designs are certified to ANSI Z21.47 / CSA 2.3 for both natural and L.P. gas. Limit setting and rating data were established and approved under standard rating condi-tions using American National Stan-dards Institute standards.

SAFE OPERATIONThe Integrated System Control has solid state devices, which continuously monitor for presence of flame, when the system is in the heating mode of operation. Dual solenoid combination gas valve and regulator provide extra safety.

QUICK HEATINGDurable, cycle tested, heavy gauge alu-minized steel heat exchanger quickly transfers heat to provide warm condi-tioned air to the structure. Low energy power vent blower, to increase effi-ciency and provide a positive discharge of gas fumes to the outside.

BURNERSMultiport Inshot burners will give years of quiet and efficient service. All models can be converted to L.P. gas without changing burners.

INTEGRATED SYSTEM CONTROLExclusively designed operational pro-gram provides total control of furnace limit sensors, blowers, gas valve, flame control and includes self diagnostics for ease of service. Also contains connec-tion points for E.A.C./humidifier.

AIR DELIVERYThe four speed, direct drive blower motor, has sufficient airflow for most heating and cooling requirements, will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed.

STYLINGHeavy gauge steel and “wrap-around” cabinet construction is used in the cabinet with baked-on enamel finish for strength and beauty. The heat exchang-er section of the cabinet is completely lined with foil faced fiberglass insulation. This results in quiet and efficient opera-tion due to the excellent acoustical and insulating qualities of fiberglass. Built-in bottom pan and alternate bottom, left or right side return air connection provision.

FEATURES AND GENERAL OPERATIONThe XT95 High Efficiency Gas Furnaces employ a Silicon Nitride Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a demand for heat from the room thermostat. Complete front service access.

a. Low energy power venter

b. Vent proving pressure switch.

Features and Benefits

XT95 Standard Equipment• Powersupply115/1/60

• Convertibletohorizontalwithleftofright airflow

• Type 29-4C™ stainless steel second-ary heat exchanger

• Innerblowerdoors

• ConstanttorqueECMblowermotor

• SiliconNitrideigniterwithadaptiveheat up

• Accessoryhook-upcapability– Hum and EAC

• Quietinduceddraftblower

• Blowerdoorsafetyswitch

• Dualsolenoidcombinationgasvalve&regulator

• PVCventing–1or2pipeventoption

• Left/rightgasconnection

• Selectablecoolingfanoffdelayelimi-nates need for BAY24X045 time delay relay

• Singlewiretwinning

• Integratedsolidstatecontrolwithself-diagnostics

• 24voltfuse

• Manualresetburnerboxlimit

• Optional extended warranties

Page 3: Upflow/ Horizontal Downflow /Horizontal Condensing, … Horizontal Downflow /Horizontal Condensing, Direct Vent Gas-Fired Furnace PUB. NO. 22-1859-01 XT 95

22-1859-01 3

Contents

General Features 2Features and Benefits 2

XT95 Standard Equipment 2XT95 Optional Equipment 4

General Data 5TUH1B040A9H21A 5TUH1B060A9H31A 5TUH1B080A9H31A 5TUH1C100A9H41A 6TUH1D120A9H51A 6TDH1B040A9H21A 7TDH1B065A9H31A 7TDH1C085A9H41A 7TDH1D110A9H51A 7

Performance Data 8Electrical Data 10Field Wiring 14Twinning Field Wiring 15Dimensions 16

Page 4: Upflow/ Horizontal Downflow /Horizontal Condensing, … Horizontal Downflow /Horizontal Condensing, Direct Vent Gas-Fired Furnace PUB. NO. 22-1859-01 XT 95

4 22-1859-01

Features and Benefits

XT95 Optional EquipmentComfort Control, XL803, Programmable 7 Day, 3-Ht, 2-Cl ...........................................................................TCONT803AS32DA [ ]Comfort Control, XR402, Electric, 3-Ht, 2-Cl (Non-programmable) ..............................................................TCONT402AN32DA [ ]For additional comfort control choices, see the product catalog or quick select handbookPropane Conversion Kit ........................................................................................................................................BAYLPKT210B [ ]Propane Conversion Kit (stainless steel burners).................................................................................................BAYLPSS210B [ ]Downflow Subbase .................................................................................................................................................BAYBASE205 [ ]Filter Access Door Kit ..............................................................................................................................................BAYFLTR206[ ]Side Filter Rack .......................................................................................................................................................BAYFLTR200 [ ]High Altitude Pressure Switch Kit TUH1B040, TDH1B040, TDH1C085 .......................................................BAYSWT01AHALTA [ ]HighAltitudePressureSwitchKitTUH1B060,TUH1D100,TUH1D120 ......................................................BAYSWT04AHALTA [ ]High Altitude Pressure Switch Kit TUH1B080, TUH1C100, TDH1D110 ...................................................BAYSWT05AHALTA [ ]High Altitude Pressure Switch Kit TUH1C080 ..........................................................................................BAYSWT11AHALTA [ ]HighAltitudePressureSwitchKitTDH1B065 ..........................................................................................BAYSWT12AHALTA [ ]Concentric Vent Kit .........................................................................................................................................BAYAIR30AVENTA [ ]Sidewall Vent Termination Kit ............................................................................................................................... BAYVENT200B [ ]Manufactured/Mobile Home Kit .......................................................................................................................... BAYMFGH100A [ ]

Page 5: Upflow/ Horizontal Downflow /Horizontal Condensing, … Horizontal Downflow /Horizontal Condensing, Direct Vent Gas-Fired Furnace PUB. NO. 22-1859-01 XT 95

22-1859-01 5

General Data

PRODUCT SPECIFICATIONS 1MODELTYPERATINGS 2Input BTUH 3Capacity BTUH (ICS) 3AFUETemp. rise (Min.-Max.) °F.BLOWER DRIVE 8Diameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HP 5R.P.M.Volts/Ph/HzCOMBUSTION FAN — TypeDrive - No. SpeedsMotor HP - RPMVolts/Ph/HzFLAFILTER — Furnished?Type RecommendedShipped(No.-Size-Thk.)VENT PIPE DIAMETER - Min (in.)67

HEAT EXCHANGERType - Fired - UnfiredGauge (Fired)ORIFICES — MainNat.Gas.Qty.—DrillSizeL.P.GasQty.—DrillSizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)

1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea

level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above

sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.5 Constant torque ECM blower motor6 Refer to the Vent Length Table in the Installer's Guide or the Allowable Vent Length label located on the furnace.7 All TUH1 and TDH1 furnace models have a vent outlet diameter that equals 2".8 4 Speed, direct drive X13 style high efficiency DC motor

TUH1B040A9H21AUpflow/Horizontal

40,00038,000

9530-60

DIRECT10 x 7

14

See Fan Performance Table1/2

1075115/1/60

CentrifugalDirect - 1

1/55 - 3000115/1/60

1.00Yes

High Velocity1 - 17x25 - 1in.

2 Round

Alum. Steel

20

2—452—56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

2115/1/60

9.7151/2

H x W x D41-3/4 x 19-1/2 x 30-1/2

139 / 129

TUH1B060A9H31AUpflow/Horizontal

60,00057,000

9530-60

DIRECT10 x 7

14

See Fan Performance Table1/2

1075115/1/60

CentrifugalDirect - 1

1/15 - 3450115/1/60

1.75Yes

High Velocity1 - 17x25 - 1in.

2 Round

Alum. Steel

20

3—453—56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

3115/1/60

10.4151/2

H x W x D41-3/4 x 19-1/2 x 30-1/2

150 / 140

TUH1B080A9H31AUpflow/Horizontal

80,00076,000

9535-65

DIRECT10 x 8

14

See Fan Performance Table1/2

1075115/1/60

CentrifugalDirect - 1

1/20 - 3450115/1/60

0.71Yes

High Velocity1 - 17x25 - 1in.

3 Round

Alum. Steel

20

4—454—56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

4115/1/60

9.4151/2

H x W x D41-3/4 x 19-1/2 x 30-1/2

158 / 148

Page 6: Upflow/ Horizontal Downflow /Horizontal Condensing, … Horizontal Downflow /Horizontal Condensing, Direct Vent Gas-Fired Furnace PUB. NO. 22-1859-01 XT 95

6 22-1859-01

General Data

TUH1D120A9H51AUpflow/Horizontal

110,000104,500

9540 - 70

DIRECT11 x 10

14

See Fan Performance Table1

1100115/1/60

CentrifugalDirect - 1

1/20 - 3450115/1/60

.71Yes

High Velocity1 - 24x25 - 1in.

3 Round

Alum. Steel

20

6—456—56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

6115/1/60

14.1201/2

H x W x D41-3/4x26-1/2x30-1/2

205 / 193

TDH1B040A9H21AUpflow/Horizontal

40,00038,000

9530-60

DIRECT10 x 7

14

See Fan Performance Table1/2

1080115/1/60

CentrifugalDirect - 1

1/55 - 3000115/1/60

1.14Yes

High Velocity1 - 14x20 - 1in.

2 Round

Alum. Steel

20

2—452—56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

2115/1/60

9.7151/2

H x W x D41-3/4 x 19-1/2 x 30-1/2

145 / 135

TUH1C100A9H41AUpflow/Horizontal

97,00092,105

9535-65

DIRECT11 x 10

14

See Fan Performance Table3/4

1100115/1/60

CentrifugalDirect - 1

1/20 - 3450115/1/60

.71Yes

High Velocity1 - 20x25 - 1in.

3 Round

Alum. Steel

20

5—455—56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

5115/1/60

11.4151/2

H x W x D41-3/4 x 23 x 30-1/2

171/160

1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea

level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above

sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.5 Constant torque ECM blower motor6 Refer to the Vent Length Table in the Installer's Guide or the Allowable Vent Length label located on the furnace.7 All TUH1 and TDH1 furnace models have a vent outlet diameter that equals 2".8 4 Speed, direct drive X13 style high efficiency DC motor

PRODUCT SPECIFICATIONS 1

MODELTYPERATINGS 2Input BTUH 3Capacity BTUH (ICS) 3AFUETemp. rise (Min.-Max.) °F.BLOWER DRIVE 8Diameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HP 5R.P.M.Volts/Ph/HzCOMBUSTION FAN — TypeDrive - No. SpeedsMotor HP - RPMVolts/Ph/HzFLAFILTER — Furnished?Type RecommendedShipped(No.-Size-Thk.)VENT PIPE DIAMETER - Min (in.)67

HEAT EXCHANGERType - Fired - UnfiredGauge (Fired)ORIFICES — MainNat.Gas.Qty.—DrillSizeL.P.GasQty.—DrillSizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)

Page 7: Upflow/ Horizontal Downflow /Horizontal Condensing, … Horizontal Downflow /Horizontal Condensing, Direct Vent Gas-Fired Furnace PUB. NO. 22-1859-01 XT 95

22-1859-01 7

PRODUCT SPECIFICATIONS 1

MODELTYPERATINGS 2Input BTUH 3Capacity BTUH (ICS) 3AFUETemp. rise (Min.-Max.) °F.BLOWER DRIVE 8Diameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HP 5R.P.M.Volts/Ph/HzCOMBUSTION FAN — TypeDrive - No. SpeedsMotor HP - RPMVolts/Ph/HzFLAFILTER — Furnished?Type RecommendedShipped(No.-Size-Thk.)VENT PIPE DIAMETER - Min (in.)67

HEAT EXCHANGERType - Fired - UnfiredGauge (Fired)ORIFICES — MainNat.Gas.Qty.—DrillSizeL.P.GasQty.—DrillSizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)

General Data

TDH1B065A9H31AUpflow/Horizontal

60,00057,000

9525 - 55

DIRECT10 x 8

14

See Fan Performance Table3/4

1075115/1/60

CentrifugalDirect - 1

1/25 - 3200115/1/60

1.35Yes

High Velocity2 - 14x20 - 1in.

2 Round

Alum. Steel

20

4—484—56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

4115/1/60

10.0151/2

H x W x D41-3/4 x 19-1/2 x 30-1/2

158 / 148

1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea

level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above

sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.5 Constant torque ECM blower motor6 Refer to the Vent Length Table in the Installer's Guide or the Allowable Vent Length label located on the furnace.7 All TUH1 and TDH1 furnace models have a vent outlet diameter that equals 2".8 4 Speed, direct drive X13 style high efficiency DC motor

TDH1C085A9H41ADownflow/Horizontal

80,00076,000

9530-60

DIRECT11 x 10

14

See Fan Performance Table3/4

1075115/1/60

CentrifugalDirect - 1

1/20 - 3450115/1/60

.71Yes

High Velocity2-16x20-1in.

2.5 Round

Alum. Steel

20

5—485—56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

5115/1/60

11.4151/2

H x W x D41-3/4 x 23 x 30-1/2

171/160

TDH1D110A9H51BDownflow/Horizontal

110,000104,500

9535-65

DIRECT11 x 10

14

See Fan Performance Table1

1075115/1/60

CentrifugalDirect - 1

1/20 - 3450115/1/60

.71Yes

High Velocity2-16x20-1in.

2.5 Round

Alum. Steel

20

6—486—56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

6115/1/60

14.1201/2

H x W x D41-3/4x26-1/2x30-1/2

205 / 193

Page 8: Upflow/ Horizontal Downflow /Horizontal Condensing, … Horizontal Downflow /Horizontal Condensing, Direct Vent Gas-Fired Furnace PUB. NO. 22-1859-01 XT 95

8 22-1859-01

Performance Data

CFM VS. TEMPERATURE RISE

MODELCFM (CUBIC FEET PER MINUTE)

600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300

TUH1B040A9H21A 59 50 44 39 35 32 29

TUH1B060A9H31A 59 53 48 44 41 38

TUH1B080A9H31A 64 59 54 50 47 44 41

TUH1C100A9H41A 66 61 57 53 50 47 45 43

TUH1D120A9H51A 65 60 57 54 51 48 46 44

FURNACE AIRFLOW (CFM) VS. STATIC PRESSURE (ins.w.g.)MODEL SPEED TAP 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9

TUH1B040A9H21A

4 - HIGH - Black 1159 1131 1102 1077 1052 1022 992 961 9303 - MED-HIGH - Blue 938 910 881 851 820 786 751 717 6622 - MED-LOW - Yellow 844 814 783 750 717 681 645 604 563

1 - LOW - Red** 772 732 691 656 621 581 540 497 454

TUH1B060A9H31A

4 - HIGH - Black 1402 1362 1318 1267 1214 1157 1095 1033 9603 - MED-HIGH - Blue** 1199 1174 1149 1127 1099 1075 1028 973 8972 - MED-LOW - Yellow 1104 1080 1053 1031 1002 980 955 931 890

1 - LOW - Red 834 808 770 750 712 677 641 599 566

TUH1B080A9H31A

4 - HIGH - Black 1328 1304 1277 1253 1224 1182 1127 1057 9593 - MED-HIGH - Blue** 1519 1493 1464 1422 1368 1306 1242 1161 10542 - MED-LOW - Yellow 1072 1039 1015 991 956 928 891 858 828

1 - LOW - Red 810 782 759 729 703 668 643 612 582

TUH1C100A9H41A

4 - HIGH - Black 1586 1552 1517 1477 1443 1410 1366 1331 12893 - MED-HIGH - Blue** 1893 1858 1826 1793 1759 1724 1691 1646 15822 - MED-LOW - Yellow 1364 1320 1282 1241 1205 1167 1120 1078 1045

1 - LOW - Red 1107 1060 1003 959 919 863 825 782 730

TUH1D120A9H51A

4 - HIGH - Black 2141 2108 2076 2041 2009 1976 1939 1894 18263 - MED-HIGH - Blue** 2072 2038 2007 1975 1938 1910 1880 1845 17972 - MED-LOW - Yellow 1886 1853 1816 1785 1754 1718 1688 1652 1619

1 - LOW - Red 1647 1609 1573 1540 1497 1465 1429 1391 1358

** = HEATING SPEED TAP

Page 9: Upflow/ Horizontal Downflow /Horizontal Condensing, … Horizontal Downflow /Horizontal Condensing, Direct Vent Gas-Fired Furnace PUB. NO. 22-1859-01 XT 95

22-1859-01 9

Performance Data

FURNACE AIRFLOW (CFM) VS. STATIC PRESSURE (ins.w.g.)

MODEL SPEED TAP 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9

TDH1B040A9H21A

4 - HIGH - Black3 - MED-HIGH - Blue2 - MED-LOW - Yellow**1 - LOW - Red

1156935835752

1128859803726

1100859771700

1072828736648

1043797701596

1012757652554

981717602511

917679569471

852641536431

TDH1B065A9H31A

4 - HIGH - Black3 - MED-HIGH - Blue**2 - MED-LOW - Yellow1 - LOW - Red

145513751099838

140413501076799

135213201044773

129912701021744

12321215994706

11741153968675

11011099941628

10251014904599

916934874558

TDH1C085A9H41A

4 - HIGH - Black3 - MED-HIGH - Blue**2 - MED-LOW - Yellow1 - LOW - Red

1795168613951179

1763165513621141

1732161913281094

1701158612891059

1669155412581019

162715251225970

157514941186931

151414581151888

145114151115846

TDH1D110A9H51A

4 - HIGH - Black3 - MED-HIGH - Blue**2 - MED-LOW - Yellow1 - LOW - Red

2105188017561582

2063185317181553

2010181716881509

1951178516471473

1880174716161433

1802170815761397

1721164915461362

1630157915051317

1543149914681282

** = HEATING SPEED TAP

CFM VS. TEMPERATURE RISE

MODELCFM (CUBIC FEET PER MINUTE)

600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300

TDH1B040A9H21A 59 50 44 39 35 32 29

TDH1B065A9H31A 53 48 44 41 38 35

TDH1C085A9H41A 59 54 50 47 44 41 39

TDH1D110A9H51A 65 60 57 54 51 48 46

Page 10: Upflow/ Horizontal Downflow /Horizontal Condensing, … Horizontal Downflow /Horizontal Condensing, Direct Vent Gas-Fired Furnace PUB. NO. 22-1859-01 XT 95

10 22-1859-01

Electrical Data

TUH1-H Wiring

From Dwg. D342491

Page 11: Upflow/ Horizontal Downflow /Horizontal Condensing, … Horizontal Downflow /Horizontal Condensing, Direct Vent Gas-Fired Furnace PUB. NO. 22-1859-01 XT 95

22-1859-01 11

TUH1-H Schematic

Electrical Data

From Dwg. D342491

Page 12: Upflow/ Horizontal Downflow /Horizontal Condensing, … Horizontal Downflow /Horizontal Condensing, Direct Vent Gas-Fired Furnace PUB. NO. 22-1859-01 XT 95

12 22-1859-01

Electrical Data

TDH1-H Wiring

From Dwg. D342800P01

Page 13: Upflow/ Horizontal Downflow /Horizontal Condensing, … Horizontal Downflow /Horizontal Condensing, Direct Vent Gas-Fired Furnace PUB. NO. 22-1859-01 XT 95

22-1859-01 13

Electrical Data

TDH1-H Schematic

From Dwg. D342800P01

Page 14: Upflow/ Horizontal Downflow /Horizontal Condensing, … Horizontal Downflow /Horizontal Condensing, Direct Vent Gas-Fired Furnace PUB. NO. 22-1859-01 XT 95

14 22-1859-01

Field Wiring

SEE NOTE 6

From Dwg. B341437 Rev. 1

FURNACE

TWIN

SEE NOTE 7

B/CB/C

TO 115 V 1 PH.,60 HZ., POWERSUPPLY PERLOCAL CODES

HUM SEENOTE 5

EAC SEENOTE 5

FIELD WIRING DIAGRAM FOR 1 STAGE FURNACE1 STAGE HEATING

USING A 1 STAGE HEATING THERMOSTATNO COOLING

OUTDOOR UNIT (NO TRANSFORMER)

SEE NOTE 6

From drawing B340388 Rv 2

SEE NOTE 8

FURNACE

B/CB/C

TO 115 V 1 PH.,60 HZ., POWERSUPPLY PERLOCAL CODES

HUM SEENOTE 5

EAC SEENOTE 5

FIELD WIRING DIAGRAM FOR 1 STAGE FURNACE1 STAGE HEATING, 1 STAGE COOLING

USING A 1 STAGE HEATING, 1 STAGE COOLING THERMOSTAT(OUTDOOR SECTION WITHOUT TRANSFORMER)

Page 15: Upflow/ Horizontal Downflow /Horizontal Condensing, … Horizontal Downflow /Horizontal Condensing, Direct Vent Gas-Fired Furnace PUB. NO. 22-1859-01 XT 95

22-1859-01 15

Twinning Field Wiring

TWIN TWIN

R1 R1

TWINNING CONNECTION DIAGRAMFOR TWINNING 1 STAGE FURNACES WITH

SINGLE WIRE TWINNING FEATURE1 STAGE HEATING ONLY THERMOSTAT1 STAGE HEAT

ONLYTHERMOSTAT

(WITH FAN SWITCH) FURNACE NO. 1 FURNACE NO. 2

BLOWER OPERATION OF UNIT NO. 2 IS SYNCRONIZEDWITH UNIT NO. 1 VIA SIGNALS

FROM TWIN CONNECTION.

SEE NOTE 4

SEE NOTE 3

ISOLATION RELAY(FIELD SUPPLIED)

SEE NOTE 4

ISOLATION RELAYSEE NOTE 4

B/CB/CB/C

From Dwg. 21B341422 Rev. 3

TWIN TWIN

R1

R1

TWINNING CONNECTION DIAGRAMFOR TWINNING 1 STAGE FURNACES WITH

SINGLE WIRE TWINNING FEATURE1 STAGE HEAT / 1 STAGE COOL THERMOSTAT

1 STAGEHEATING / COOLING

THERMOSTAT FURNACE NO. 1 FURNACE NO. 2

BLOWER OPERATION OF UNIT NO. 2 IS SYNCRONIZEDWITH UNIT NO. 1 VIA SIGNALS

FROM TWIN CONNECTION.

SEE NOTE 4

SEE NOTE 5

ISOLATION RELAY(FIELD SUPPLIED)

SEE NOTE 4

ISOLATION RELAYSEE NOTE 4

OUTDOOR UNIT(NO TRANSFORMER)

OUTDOOR UNIT(WITH TRANSFORMER)

RC

ISOLATION RELAY(FIELD SUPPLIED)

SEE NOTE 3

B/CB/CB/C

From Dwg. 21B341423 Rev. 2

Page 16: Upflow/ Horizontal Downflow /Horizontal Condensing, … Horizontal Downflow /Horizontal Condensing, Direct Vent Gas-Fired Furnace PUB. NO. 22-1859-01 XT 95

16 22-1859-01

Dimensions

From

Dw

g. 2

1C34

1884

TU

H1-

H O

UT

LIN

E D

RA

WIN

G(A

LL

DIM

EN

SIO

NS

AR

E IN

INC

HE

S)

NO

TES

: 1.

*U

H1B

080A

9H31

, *U

H1C

100A

9H41

, & *

UH

1D12

0A9H

51R

EQ

UIR

E 3

” DIA

ME

TER

VE

NT

PIP

E.

2. D

IAM

ETE

R O

F V

EN

T P

IPE

MAY

BE

LIM

ITE

D T

O 2

-1/2

”O

R 3

” ON

SO

ME

MO

DE

LS A

T D

IFFE

RE

NT

ALT

ITU

DE

S.

RE

FER

TO

TH

E V

EN

T LE

NG

TH T

AB

LE F

OR

PR

OP

ER

AP

PLI

CAT

ION

.

Page 17: Upflow/ Horizontal Downflow /Horizontal Condensing, … Horizontal Downflow /Horizontal Condensing, Direct Vent Gas-Fired Furnace PUB. NO. 22-1859-01 XT 95

22-1859-01 17

Dimensions

From

Dw

g. 2

1C34

1885

TD

H1-

H O

UT

LIN

E D

RA

WIN

G(A

LL

DIM

EN

SIO

NS

AR

E IN

INC

HE

S)

Page 18: Upflow/ Horizontal Downflow /Horizontal Condensing, … Horizontal Downflow /Horizontal Condensing, Direct Vent Gas-Fired Furnace PUB. NO. 22-1859-01 XT 95

Trane has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice.

Trane6200TroupHighwayTyler, TX 75707www.trane.com

Literature Order Number 22-1859-01

File Number 22-1859-01

Supersedes New

Date 11/11