5 6 4 1 2 3 Insulated Panels May 2008 Installation Guide KS1000 XD Longspan X-dek® Roof Panel Multiple Panels Eaves to Ridge j l f h c b a m g e d i k Fix fourth panel (P4) horizontally with 6 main fasteners and spreader plates to every rafter Stitch top sheet with 51mm long low profile stitching screw (i.e SFS, ‘Irius’ or simliar at max. 500mm centres (see detail e) Stitch flashing with low profile stitching screw at max. 500mm centres Fix third panel (P3) horizontally with 6 main fasteners and spreader plates to every rafter Stitch top sheet with 51mm long low profile stitching screw (i.e SFS, ‘Irius’ or simliar at max. 500mm centres) Lay second panel (P2) horizontally with 6 main fasteners and spreader plates to every rafter. The first of the 6 main fasteners is to be fixed through panel (P1) at panel side lap. Panel should be butt jointed tightly together 2 runs of 9 x 3mm butyl rubber sealant tape (see item a) Install additional main fasteners at 500mm centres at the eaves 2 runs of 9 x 3mm butyl rubber sealant tape Eaves Verge Fix first panel (P1) horizontally at eaves with initial 5 main fasteners and spreader plates to every rafter. For steel supports less than typically 12mm thickness use a low profile self drilling fastener is available (i.e SFS ‘Irius’ or similar recommended main fastener). For thicker steelwork a low profile hexagonal fastener can be used with pre-drilling Stitch top sheet with 51mm long low profile stitching screw (i.e SFS, ‘Irius’ or simliar at max. 500mm centres (see detail e) 2 runs of 9 x 3mm butyl rubber sealant tape (see detail a) 9x3mm rooflight panel Galvanised steel speader plates KS1000 XD - Insulated roof deck Initial 5 No. main fasteners min. per support positioned in line with the centre of the profile crown dependent upon wind uplift. Fully sealed profile filler Support member Support member Support member 75mm min. bearing 75mm min. bearing KS1000 XD - Insulated roof deck 9 x 3mm butyl rubber sealant 333.3mm centres 333.3mm centres KS1000 XD - Insulated roof deck Galvanised steel spreader plate Main fasteners min. 6 No. per panel per support dependent upon wind uplift 75mm min. bearing Parapet post Internal laminate closure flashing Internal laminate closure flashing 70mm PIR insulation board Main fastener into eavesbeam at max. 500mm centres Support member Air seal - 6mm Ø butyl rubber sealant Air seal - 6mm Ø butyl rubber sealant 8mm Ø butyl rubber or gun-grade sealant KS1000 XD - Insulated roof deck Main fasteners min. 6 No. per panel per support dependent upon wind uplift. Support member 9 x 3mm butyl rubber sealant Side lap stitching screws maximum 250mm centres using standard 22mm stitcher with bonded washer Side lap stitching screws 51mm long low profile max. 500mm centres Ridge flashing with 150mm sealed laps Air seal - Expanding foam sealant 1.6mm galvanised zed support flashing (variable sizes) Site applied PIR insulation or gun applied fire rated canister insulation Fastener with spreader plate Galvanised steel spreader plates Main fasteners min. 6 No. per panel per support dependent upon wind uplift Min.bearing 75mm 35mm Nominal 35mm Nominal Min.bearing 75mm Galvanised steel spreader plates KS1000 XD - Insulated roof deck KS1000 XD - Insulated roof deck Hot rolled fasteners at 500mm centres Ridge supporting member Gutter outlet by others KS1000 XD - Insulated roof deck Note: Indicative design subject to project specific design loadings. Note: Indicative design subject to project specific design loadings. Note: This design is purely indicative to provide an example of panels which need to be cut at the ridge. This detail remains subject to the project specific design loadings. Drip flashing Drip flashing KS1000 XD - Insulated roof deck Support member 70mm PIR insulation board Fully sealed profile filler P4 P2 P1 P3 P3 P3 P3 P4 P4 P3 P2 P2 P2 P1 P1 P1 P4 P2 P2 P1 P1 P1 Note: Ensure steel work is suitably lined, levelled and within tolerance. The steel design used on this guide is purely indicative. Subject to project specific design loadings and proposed finishes Kingspan X-dek® can span up to 8m. Gun-grade sealant type - non-setting butyl sealant. Note: Panels P2 & P3 are detailed in single span to provide an example of staggered end laps across the roof. This detail remains subject to the project specific design loadings. Components KS1000 XD Roof Panel Primary/Main Fasteners Secondary/Stitching Screws Butyl Rubber Tape Sealants Gun-grade Sealant Fire-rated Canister Insulation Zed Support Spreader Plate Closure Filler This installation guide should be read in conjunction with the ‘project specific’ design drawings and method statements. Although this ‘installation guide’ is deemed to be correct at the time of publication, Kingspan reserve the right to amend the information at any time in the future. Installation Guides are available for the full range of Kingspan Insulated Roof, Wall and Facade Systems Please call Kingspan on: UK: +44 (0) 1352 716100 Ire: +353 (0) 42 96 98500 Direction of lay Direction of lay Direction of lay Direction of lay Direction of lay Direction of lay Direction of lay Insulation Built-in.

speader plates Installation Guide 3 Fix third panel

  • Upload
    others

  • View
    10

  • Download
    0

Embed Size (px)

Citation preview

Page 1: speader plates Installation Guide 3 Fix third panel

5 6

4

1

2

3

Insulated Panels

May 2008

Installation GuideKS1000 XD Longspan X-dek® Roof PanelMultiple Panels Eaves to Ridge

j

l

f

h

c

b

a

m

g

e

d

ik

Fix fourth panel (P4)horizontally with 6 mainfasteners and spreaderplates to every rafter

Stitch top sheet with 51mm longlow profi le stitching screw(i.e SFS, ‘Irius’ or simliar at max.500mm centres (see detail e)

Stitch fl ashing with low profi lestitching screw at max.

500mm centres

Fix third panel (P3) horizontallywith 6 main fasteners and

spreader plates to every rafter

Stitch top sheet with 51mmlong low profi le stitching screw

(i.e SFS, ‘Irius’ or simliar atmax. 500mm centres)

Lay second panel (P2) horizontallywith 6 main fasteners and spreaderplates to every rafter. The fi rst of the

6 main fasteners is to be fi xedthrough panel (P1) at panel side lap.

Panel should be buttjointed tightly together

2 runs of 9 x 3mm butylrubber sealant tape(see item a)

Install additional mainfasteners at 500mm centresat the eaves

2 runs of 9 x 3mmbutyl rubbersealant tape

Eaves

Verge

Fix fi rst panel (P1) horizontally at eaves with initial 5 main fastenersand spreader plates to every rafter. For steel supports less thantypically 12mm thickness use a low profi le self drillingfastener is available (i.e SFS ‘Irius’ or similar recommendedmain fastener). For thicker steelwork a low profi lehexagonal fastener canbe used with pre-drilling

Stitch top sheet with 51mmlong low profi le stitching screw

(i.e SFS, ‘Irius’ or simliar at max.500mm centres (see detail e)2 runs of 9 x 3mm

butyl rubber sealanttape (see detail a)

9x3mm

roofl ight

panel

Galvanised steelspeader plates

KS1000 XD -Insulated roof deck

Initial 5 No. mainfasteners min.per supportpositioned in linewith the centre ofthe profi le crowndependent uponwind uplift.

Fully sealedprofi le fi ller

Support member

Support member

Support member

75mm min.bearing

75mm min.bearing

KS1000 XD -Insulated roof deck

9 x 3mm butylrubber sealant

333.3mm centres 333.3mm centres

KS1000 XD -Insulated roof deck

Galvanised steelspreader plate

Main fasteners min.6 No. per panel persupport dependentupon wind uplift

75mm min.bearing

Parapet post

Internal laminateclosure fl ashing

Internal laminateclosure fl ashing

70mm PIRinsulation board

Main fastener into eavesbeamat max. 500mm centres

Support member

Air seal - 6mm Ø butylrubber sealant

Air seal - 6mm Øbutyl rubber sealant

8mm Ø butyl rubberor gun-grade sealant

KS1000 XD -Insulated roof deck

Main fasteners min. 6 No. perpanel per support dependent

upon wind uplift.

Support member

9 x 3mm butylrubber sealant

Side lap stitchingscrews maximum250mm centres usingstandard 22mm stitcherwith bonded washer

Side lap stitching screws51mm long low profi lemax. 500mm centres

Ridge fl ashing with150mm sealed laps

Air seal - Expandingfoam sealant

1.6mm galvanised zed supportfl ashing (variable sizes)

Site applied PIR insulationor gun applied fi re ratedcanister insulationFastener with spreader plate

Galvanised steelspreader plates

Main fasteners min.6 No. per panel persupport dependentupon wind uplift

Min.bearing75mm

35mmNominal

35mmNominal

Min.bearing75mm

Galvanised steelspreader plates

KS1000 XD -Insulated roof deck

KS1000 XD - Insulatedroof deck

Hot rolled fasteners at500mm centres

Ridge supporting member

Gutter outlet by others

KS1000 XD - Insulatedroof deck

Note: Indicative design subject to project specifi c design loadings.

Note: Indicative design subject to project specifi c design loadings.

Note: This design is purely indicative to provide an exampleof panels which need to be cut at the ridge. This detailremains subject to the project specifi c design loadings.

Drip fl ashing

Drip fl ashing

KS1000 XD - Insulatedroof deck

Support member

70mm PIRinsulation board

Fully sealed profi le fi ller

P4

P2P1

P3

P3

P3

P3

P4

P4P3

P2

P2

P2

P1

P1

P1

P4

P2

P2

P1

P1

P1

Note: Ensure steel work is suitably lined, levelled andwithin tolerance.

The steel design used on this guide is purely indicative.

Subject to project speci� c design loadings and proposed� nishes Kingspan X-dek® can span up to 8m.

Gun-grade sealant type - non-setting butyl sealant.

Note: Panels P2 & P3 are detailed insingle span to provide an exampleof staggered end laps across theroof. This detail remains subject tothe project speci� c design loadings.

Components

KS1000 XD Roof Panel

Primary/Main Fasteners Secondary/Stitching Screws

Butyl RubberTape Sealants

Gun-gradeSealant

Fire-ratedCanisterInsulation

Zed Support

Spreader Plate

Closure Filler

This installation guide should be read inconjunction with the ‘project specifi c’design drawings and method statements.Although this ‘installation guide’ is deemedto be correct at the time of publication,Kingspan reserve the right to amend theinformation at any time in the future.Installation Guides are available for the fullrange of Kingspan Insulated Roof, Wall andFacade SystemsPlease call Kingspan on:UK: +44 (0) 1352 716100Ire: +353 (0) 42 96 98500

Direction of lay

Direction of lay

Direction of lay

Direction of lay

Direction of lay

Direction of lay

Direction of lay

Insulation Built-in.