i-PCGRID 2019, San Francisco, March 27-29 1 resilient and Cyber Secure Centralized Substation Protection (rCSP) Sakis Meliopoulos Georgia Power Distinguished Professor Georgia Institute of Technology, Atlanta, Georgia USA resilient and Cyber Secure Centralized Substation Protection (rCSP) Sakis Meliopoulos Georgia Power Distinguished Professor Georgia Institute of Technology, Atlanta, Georgia USA

resilient and Cyber Secure Centralized Substation ... · resilient and Cyber Secure Centralized Substation Protection (rCSP) SakisMeliopoulos Georgia Power Distinguished Professor

  • Upload
    others

  • View
    10

  • Download
    0

Embed Size (px)

Citation preview

Page 1: resilient and Cyber Secure Centralized Substation ... · resilient and Cyber Secure Centralized Substation Protection (rCSP) SakisMeliopoulos Georgia Power Distinguished Professor

i-PCGRID 2019, San Francisco, March 27-29 1

resilient and Cyber Secure Centralized Substation Protection (rCSP)

Sakis Meliopoulos Georgia Power Distinguished Professor

Georgia Institute of Technology, Atlanta, Georgia USA

resilient and Cyber Secure Centralized Substation Protection (rCSP)

Sakis Meliopoulos Georgia Power Distinguished Professor

Georgia Institute of Technology, Atlanta, Georgia USA

Page 2: resilient and Cyber Secure Centralized Substation ... · resilient and Cyber Secure Centralized Substation Protection (rCSP) SakisMeliopoulos Georgia Power Distinguished Professor

i-PCGRID 2019, San Francisco, March 27-29 2

Presentation SummaryOver the years several new concepts and technologies were developed:

Estimation Based Protection (aka setting-less relay)Error Correction Within Merging Units (IMU)Dynamic State Estimation (Time and Q Domain)Cyber-Physical Intrusion Detection

We are presently integrating all these technologies into the rCSP (ARPAe project under OPEN 2018) – Demo on NYPA, SoCo

Page 3: resilient and Cyber Secure Centralized Substation ... · resilient and Cyber Secure Centralized Substation Protection (rCSP) SakisMeliopoulos Georgia Power Distinguished Professor

i-PCGRID 2019, San Francisco, March 27-29 3

Performance StatisticsMis-Operations, Data Integrity &

Protection Gaps

Performance StatisticsMis-Operations, Data Integrity &

Protection Gaps

Page 4: resilient and Cyber Secure Centralized Substation ... · resilient and Cyber Secure Centralized Substation Protection (rCSP) SakisMeliopoulos Georgia Power Distinguished Professor

i-PCGRID 2019, San Francisco, March 27-29 4

Performance Statistics: DoERelay Mis-operations: 10%

Of These 65% are related to hidden failures

Page 5: resilient and Cyber Secure Centralized Substation ... · resilient and Cyber Secure Centralized Substation Protection (rCSP) SakisMeliopoulos Georgia Power Distinguished Professor

i-PCGRID 2019, San Francisco, March 27-29 5

Causes of Mis-Operation• Complexity

Relay SettingsCoordination Issues

• Data Integrity• Hidden Failures• Cyber Attacks• Protection Gaps

(HIF, Faults near neutrals, etc.)• Unusual Events

Page 6: resilient and Cyber Secure Centralized Substation ... · resilient and Cyber Secure Centralized Substation Protection (rCSP) SakisMeliopoulos Georgia Power Distinguished Professor

i-PCGRID 2019, San Francisco, March 27-29 6

The Digital Substation Concept

The Digital Substation Concept

Page 7: resilient and Cyber Secure Centralized Substation ... · resilient and Cyber Secure Centralized Substation Protection (rCSP) SakisMeliopoulos Georgia Power Distinguished Professor

i-PCGRID 2019, San Francisco, March 27-29 7

The Digital Substation ConceptThe Digital Substation Concept

Page 8: resilient and Cyber Secure Centralized Substation ... · resilient and Cyber Secure Centralized Substation Protection (rCSP) SakisMeliopoulos Georgia Power Distinguished Professor

i-PCGRID 2019, San Francisco, March 27-29 8

Dynamic State Estimation Based CentralizedProtection Scheme

Resilient CentralizedSubstationProtection(rCSP)

New ARPAeProject(GT, NYPA, SoCo, EPRI)

Page 9: resilient and Cyber Secure Centralized Substation ... · resilient and Cyber Secure Centralized Substation Protection (rCSP) SakisMeliopoulos Georgia Power Distinguished Professor

i-PCGRID 2019, San Francisco, March 27-29 9

Architectural Notes: Simplify, Simplify, Simplify

GPS-Synchronized Samples

Page 10: resilient and Cyber Secure Centralized Substation ... · resilient and Cyber Secure Centralized Substation Protection (rCSP) SakisMeliopoulos Georgia Power Distinguished Professor

i-PCGRID 2019, San Francisco, March 27-29 10

Data Integrity1. Instrumentation Channel Errors2. Hidden Failures3. Cyber Data Attacks

Data Integrity1. Instrumentation Channel Errors2. Hidden Failures3. Cyber Data Attacks

Page 11: resilient and Cyber Secure Centralized Substation ... · resilient and Cyber Secure Centralized Substation Protection (rCSP) SakisMeliopoulos Georgia Power Distinguished Professor

i-PCGRID 2019, San Francisco, March 27-29 11

Effects of Input Data Accuracy Quality of Data is Affected from (a) Instrumentation Channel Errors, (b) Hidden Failures and (c) cyber data attacks. All sources compromise protection performance.

Relays and merging units are becoming more accurate by using higher resolution in data acquisition and higher sampling rates. Merging units reduce lengths of cables and eliminate some error sources.

Errors from instrumentation channels remain practically the same. Instrumentation channel errors have been much higher than the errors introduced by the data acquisition even in earlier generations of sensor less systems.

Merging Units offer a unique opportunity to perform error correction within a merging unit MU provides corrected data in primary quantities.

Page 12: resilient and Cyber Secure Centralized Substation ... · resilient and Cyber Secure Centralized Substation Protection (rCSP) SakisMeliopoulos Georgia Power Distinguished Professor

i-PCGRID 2019, San Francisco, March 27-29 12

Intelligent Merging Units Provide Corrected Primary Values

Error Correction Integrated into Merging Units (alternative: in substation computers)

Page 13: resilient and Cyber Secure Centralized Substation ... · resilient and Cyber Secure Centralized Substation Protection (rCSP) SakisMeliopoulos Georgia Power Distinguished Professor

i-PCGRID 2019, San Francisco, March 27-29 13

Estimated results match actual primary current with less than 1% error

Example System Results – Mild CT SaturationError Correction Performance

Estimated Primary Current

Actual Primary Current

Secondary Current x CT Ratio

Page 14: resilient and Cyber Secure Centralized Substation ... · resilient and Cyber Secure Centralized Substation Protection (rCSP) SakisMeliopoulos Georgia Power Distinguished Professor

i-PCGRID 2019, San Francisco, March 27-29 14

Data Integrity1. Instrumentation Channel Errors2. Hidden Failures3. Cyber Data Attacks

Data Integrity1. Instrumentation Channel Errors2. Hidden Failures3. Cyber Data Attacks

Page 15: resilient and Cyber Secure Centralized Substation ... · resilient and Cyber Secure Centralized Substation Protection (rCSP) SakisMeliopoulos Georgia Power Distinguished Professor

i-PCGRID 2019, San Francisco, March 27-29 15

Impact of Hidden Failures/Cyber Attacks

Hidden failures and cyber attacks corrupt the data “seen” by a relay, legacy relay or setting-less protective relay.

Hidden failures/cyber attacks will cause relay mis-operation whether it is a legacy protective relay or a setting-less relay.

Need to identify hidden failures/cyber attacks and avert relay mis-operations.

Present State of Art: Some legacy relaying schemes can identify some hidden failures and inhibit relay operation. No capability to take corrective action. No capability to detect hidden failures if the occur simultaneously with a fault.

Page 16: resilient and Cyber Secure Centralized Substation ... · resilient and Cyber Secure Centralized Substation Protection (rCSP) SakisMeliopoulos Georgia Power Distinguished Professor

i-PCGRID 2019, San Francisco, March 27-29 16

Proposed Method for Securing Data

Page 17: resilient and Cyber Secure Centralized Substation ... · resilient and Cyber Secure Centralized Substation Protection (rCSP) SakisMeliopoulos Georgia Power Distinguished Professor

i-PCGRID 2019, San Francisco, March 27-29 17

Proposed Method for Securing Data

Page 18: resilient and Cyber Secure Centralized Substation ... · resilient and Cyber Secure Centralized Substation Protection (rCSP) SakisMeliopoulos Georgia Power Distinguished Professor

i-PCGRID 2019, San Francisco, March 27-29 18

Dynamic State Estimation Based Centralized Protection Scheme (rCSP)

Hypothesis Testing: Observations

At substation level redundancy is high (over 2000%)

System is continuously running.

Probability of simultaneous failure events is low

Hypothesis Testing: Mechanics Identify suspect measurements from residuals

Group suspect data with certain criteria (see paper)

Determine “faulted devices” from setting-less relays output

Page 19: resilient and Cyber Secure Centralized Substation ... · resilient and Cyber Secure Centralized Substation Protection (rCSP) SakisMeliopoulos Georgia Power Distinguished Professor

i-PCGRID 2019, San Francisco, March 27-29 19

Dynamic State Estimation Based Centralized Protection Scheme (rCSP)

Hypothesis Type 1 (H1): Remove suspect measurements and rerun DSE. If probability high removed measurements are bad identify root cause issue diagnostics replace bad data with estimated values. End hypothesis testing. Otherwise go to H2.

Hypothesis Type 2 (H2): (determine if a fault decision is correct). For the reported faulted device, remove all internal device measurements and remove the faulted device model from the substation model. Then rerun DSE. If probability high the device is truly experiencing an internal fault. Allow zone relay to trip the faulted device. End hypothesis testing.

Hypothesis Type 3 (H3): This test combines type 1 and type 2 hypothesis testing to cover the case of a simultaneous fault and a hidden failure.

Hypothesis Type 4 (H4): This test assumes that data have been altered (example: GPS signal, CT ratios, etc.). Use estimated CT ratios and repeat state estimation. If probability high, replace CT ratios with correct ones.

Page 20: resilient and Cyber Secure Centralized Substation ... · resilient and Cyber Secure Centralized Substation Protection (rCSP) SakisMeliopoulos Georgia Power Distinguished Professor

i-PCGRID 2019, San Francisco, March 27-29 20

Without GPS Spoofing With GPS Spoofing

Numerical Example of

GPS Spoofing Detection

Page 21: resilient and Cyber Secure Centralized Substation ... · resilient and Cyber Secure Centralized Substation Protection (rCSP) SakisMeliopoulos Georgia Power Distinguished Professor

i-PCGRID 2019, San Francisco, March 27-29 21

Key Issue for SuccessAn Integrated Physical System Model &

Cyber Infrastructure

Physical System Model: multi-phase model, neutral, grounds included, instrumentation channel inclusive.

Cyber Infrastructure: interface model to the physical system, communication model at all seven levels, logical node models.

Integration: seamless access of either model in the same platform. Automated EBP relay, Substation SE.

By Product: Continuous Real Time Model Validation

Page 22: resilient and Cyber Secure Centralized Substation ... · resilient and Cyber Secure Centralized Substation Protection (rCSP) SakisMeliopoulos Georgia Power Distinguished Professor

i-PCGRID 2019, San Francisco, March 27-29 22

Concluding RemarksCentralized Substation Protection innovations:

Innovation 1: Setting-less Protective Relay

Innovation 2: Merging Units can provide corrected primary values via instrumentation error correction embedded in intelligent Merging Units

Innovation 3: Supervision of protection functions (logical nodes) to determine that hidden failures do not exist. In case of hidden failures use real time dynamic model to replace compromised data with estimated data enable resiliency

Innovation 4: Supervision of data integrity to determine data attacks. In case of cyber data attack, use real time model to replace false data enable resiliency.

Page 23: resilient and Cyber Secure Centralized Substation ... · resilient and Cyber Secure Centralized Substation Protection (rCSP) SakisMeliopoulos Georgia Power Distinguished Professor

i-PCGRID 2019, San Francisco, March 27-29 23

ΤέλοςΤέλος

AcknowledgementsThe support of ARPAe, DoE, EPRI, NYSERDA,

PSERC and numerous industry partners Southern Company, NYPA, USVI-WAPA, PG&E, TVA and Burbank Water & Power is greatly appreciated

AcknowledgementsThe support of ARPAe, DoE, EPRI, NYSERDA,

PSERC and numerous industry partners Southern Company, NYPA, USVI-WAPA, PG&E, TVA and Burbank Water & Power is greatly appreciated

Page 24: resilient and Cyber Secure Centralized Substation ... · resilient and Cyber Secure Centralized Substation Protection (rCSP) SakisMeliopoulos Georgia Power Distinguished Professor

i-PCGRID 2019, San Francisco, March 27-29 24

Major Additional Benefit: Perpetual Model Calibration and Validation

A Ubiquitous System for Perpetual Model Validation

Protection is Ubiquitous• Makes Economic Sense to Use

Relays for Distributed Model Data Base• Capability of Perpetual Model

Validation• Component Real Time Model with GPS

Time Stamp – enables distributed approaches

Protection is Ubiquitous• Makes Economic Sense to Use

Relays for Distributed Model Data Base• Capability of Perpetual Model

Validation• Component Real Time Model with GPS

Time Stamp – enables distributed approaches