21
PRIMENA NOVIH TEHNOLOGIJA U BEOGRADSKIM ELEKTRANAMA U OKVIRU PROGRAMA HORIZON 2020 – PROJEKAT RELATED dr Ljubisa Vladi ć , dr Radmilo Savi ć , Vladimir Tanasi ć JKP Beogradske elektrane TRIBINA DRUŠTVA TERMIČARA MAŠINSKI FAKULTET U BEOGRAD 14.11.2019.

PRIMENA NOVIH TEHNOLOGIJA U BEOGRADSKIM …

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

PRIMENA NOVIH TEHNOLOGIJA U BEOGRADSKIM ELEKTRANAMA U OKVIRU PROGRAMA HORIZON

2020 – PROJEKAT RELATED

dr Ljubisa Vladić, dr Radmilo Savić, Vladimir Tanasić

JKP Beogradske elektrane

TRIBINA DRUŠTVA TERMIČARAMAŠINSKI FAKULTET U BEOGRAD

14.11.2019.

• Haga clic para modificar el estilo de texto del patrón

– Segundo nivel

• Tercer nivel

– Cuarto nivel

» Quinto nivel

• Haga clic para modificar el estilo de texto del patrón

UVOD

O R GA N I S AT I O N 2

JKP “Beogradske elektrane” – Osnovane - 1965.

Broj toplotnih izvora 48

Toplotni kapacitet 3.000 MW

Dužina trase mreže 730km (1.460km cevovoda)

Broj podstanica 8.800

Ukupna grejna površina 22.000.000 m2

Broj stanova na grejanju 330,000

Godišnja proizvodnja 3,000 GWh

51% grada koristi daljinsko grejanje

3

Ciljevi projekta RELATED na primeru JKP BE:

• Konverzija mreže daljinskog grejanja u niskotemperatusku• Primena solarnog grejanja u sistemu daljinskog grejanja

Pilot lokacije:

• Vinogradski Venac 36 - Rekonstrukcija podstanice za 5 stambenih zgrada• OŠ Ujedinjene nacije, ul. Borova 8 - Primena solar termala kroz 2 funkcionalnu podstanicu

Program HORIZON 2020 – Evropski program za istraživanje i inovacije u okviru kojeg JKP BE participiraju sa 3 projekta:

1. HOLISDER2. MOEEBIUS3. RELATED √

Koncept RELaTED

4

- Snižavanje odlazne temeprature u mreži

- Decentralizacija mreže DG

- Definisanje kritičnih energetskih tačaka uzgradama

- Povećanje udela energije iz niskotemperaturnihizvora

- Korišćenje otpadne toplote, solarnih kolektora itoplotnih pumpi

5

Nove tehnologije i mogućnost primene u BE

6

• Nivoi temperaturskih režima u mreži DG

- visokotemperatuski sistemi 100/50 °C

- niskotemperaturski sistemi 80/40 °C

- vrlo niskotemperaturski sistemi 60/30 °C

- ultra niskotemperaturski sistemi 45/30 °C

- daljinsko hlađenje 10/15 °C

• Sekudnarna instalacija• - 100/50ºC -> 90/50ºC -> Radijatorski sistem

- 80/40ºC -> 70/40ºC -> Radijatorski sistem- 60/30ºC -> 55/30ºC -> Radijatorski sistem- 45/35ºC -> 35/30ºC -> Podno grejanje

7

Pilot lokacije

1. PS Vinogradski venac 36 sa grejnim objektima

8

9

10

Šema veze

DHW

SPACE HEATING

Subsystem Power [kW]

Radiators 1.105

DHW 274

TOTAL 1380

11

PS Vinogradski Venac 36 – osnovni podaci

Operation conditions

heating

Primary circuit

District heating side

Secondary circuit

Radiators heating

Tsupply [C] 120 90

Treturn [C] 65 70

Nominal flow [m3/h] 18,07 62

Operation conditions

DHW

Primary circuit

District heating side

Secondary circuit

DHW

Tsupply [C] 65 55

Treturn [C] 22 10

Nominal flow [m3/h] 5,61 7,8

12

Energetsko modeliranje objekata

Vinogradski Venac 29

Ground level + 9

38 flats

13

Vinogradski Venac 29

Vinogradski Venac 31

Vinogradski Venac 36

Vinogradski Venac 38

Vinogradski Venac 40

Planirane aktivnosti:

- Zamena postojećeg cevnog razmenjivača toplote za grejanje pločastim

- Odvajanje svake zgrade pojedinačnim uređajima za merenje i regulaciju

- Povećanje protoka u sekundarnoj mreži uz sniženje odlazne temperature

- Verifikacija kontinulanim merenjem temperature u kritičnim stanovima u svim zgradama i upoređivanje sa prethodnim stanjem

14

15

2. PS Borova 8 – OŠ Ujedinjene nacije

16

17

Šema veze

Subsystem Power [kW]

Radiators 550

Air heating 400

DHW 140

DHW

RADIATORS

AIR HEATING

18

Osnovni podaci

Operating coditions

Space heating

Primary circuit

District heating side

Secondary circuit

Radiators heating

Tsupply [C] 120 90

Treturn [C] 65 70

Nominal flow [m3/h] 8,8 30,1

Operating conditions

Air heating

Primary circuit

District heating side

Secondary circuit

Air heating

Tsupply [C] 120 90

Treturn [C] 65 70

Nominal flow [m3/h] 6,4 20Operating conditions

DHW

Primary circuit

District heating side

Secondary circuit

DHW

Tsupply [C] 65 55

Treturn [C] 22 10

Nominal flow [m3/h] 1,62 2

19

Planirane aktivnosti:

- Zamena postojeće podstanice 2 fukcionalnom podstanicom

- Ugradnja solarnih kolektora na krovu škole i povezivanje sa 2 funkcionalnom podstanicom

- Povećanje konzuma za PTV

- Ugradnja termostatskih ventila na svim radijatorima

20

Šema nove 2F podstanice

Ljubiša Vladić[email protected]

Radmilo Savić[email protected]

Vladimir Tanasić[email protected]

HVALA NA PAŽNJI