Upload
others
View
2
Download
0
Embed Size (px)
Citation preview
PRESSURE SWITCHES FOR WATER PUMPS
PM-PT PM/5-3W PT/5-3W LP/3
TYPE PRESSURERANGE
RATEDCURRENT
DIF. MIN/DIF. MAX
PM/5 1-5 bar 250V 16(10A) 0,6 / 2,3 bar
PM/6 1,5-5,5 bar 250V 16(10A) 0,8 / 2,2 bar
PM/12 3-12 bar 250V 16(10A) 1,5 / 5 bar
PT/5 1-5 bar 500V 16(10A) 0,6 / 2,3 bar
PT/6 1,5-5,5 bar 500V 16(10A) 0,8/ 2,2 bar
PT/12 3-12 bar 500V 16(10A) 1,5 / 5 bar
TYPE PRESSURE RANGE
RATEDCURRENT
DIFF. MIN /DIFF. MAX
PM/5-3W 1-5 bar 250V 16(10A) 0,6 / 2,3 bar
PT5-3W 1-5 bar 500V 16(10A) 0,6/2,3 bar
TYPE PRESSURERANGE
RATED CURRENT
LP/3 0,05-0,4 bar 250V 16(10A)
LP/3-18 0,5-2,0 bar 250V 16(10A)
PM= for single phase motor pumpPT = for three phase motor pump
DIF. MIN= minimum difference between cut-in and cut-outDIF. MAX= maximum difference between cut-in and cut-out
Applicazioni
PM/5-3W
INSTALLATIONS
ADVANTAGES
DIFFERENT SETTINGS AVAILABLE
SUITABLE IN VARIOUS SYSTEMS WITH DIFFERENT PUMPS
OPTIONAL GRADUATED SCALE
MORE SAFETY
REVOLVING NUT
QUICK CONNECTIONTEAR-RESISTANT CABLE CLAMPS
MORE SAFETY
FULLY INSULATED TERMINALS
PROTECTION DEGREE IP54
CONTACTS 20 A ON/OFF BUTTON
GRADUATED SCALE
EXTERNALLY VISIBLE CUT-IN PRESSURE
ELECTRONIC FLOW AND PRESSURE CONTROLLERS
BRIO 2000-MBRIO TANK BRIO TOP
CONTROLLER
Power supply 115-230V 50-60Hz
Max rated current 12A
Starting pressure range
1 - 3,5 bar
Protection degree IP 65
Max pressure 10 bar
CONTROLLER WITH INTEGRATED PRESSURE TANK
Power supply 230V 50-60Hz
Max rated current 12A
Starting pressure range
1 - 3,5 bar
Protection degree IP 65
Max pressure 10 bar
DIGITAL CONTROLLER
Power supply 230V 50-60Hz
Max rated current 16A
Starting pressure range
0,5 - 8 bar
Protection degree IP 65
Max pressure 10 bar
VERTICAL AND HORIZONTAL INSTALLATION BY-PASS INSTALLATION FOR HOSES BIGGER THAN 1"
INSTALLATION WITH THREE-PHASE MOTOR WITH RELAY
APPLICATIONS
IRRIGATION DOMESTIC WATER SYSTEMS
INDUSTRIALRESIDENTIAL
BRIO TOPLCD DISPLAY– 5 LANGUAGES
DIGITAL DISPLAY OF PRESSURE AND CURRENT
EASY SETTING OF PARAMETERS
CURRENT CONTROL
IT PROTECTS THE PUMP AGAINST OVERLOAD
MAX RATED 16A
SUITABLE FOR SURFACE PUMPS, SUBMERSIBLE PUMPS, VERTICAL PUMPS UP TO 3HP
I/O CONNECTIONS
IT CAN BE CONNECTED TO BMS AND OTHER EQUIPMENTS FOR REMOTE CONTROL
TWIN BOOSTER SYSTEM WITH TWO BRIO TOP OR ONE BRIO TOP AND ONE SIRIO IN ALTERNATING FUNCTIONING
ERROR LOG
ERROR LOGGING FOR AN EASIER AND COMPLETE TROUBLESHOOTING
STOP DELAYED ADJUSTABLE UP TO 120 SECONDS
PERFECT FOR DEEP WELL SUMBERSIBLE PUMPS
WHY CHOOSE BRIO TOP?
MODE P+F
PUMP STARTS ON PRESSURE DROP AND STOPS ON ZERO FLOW
MAXIMUM PRESSURE CANNOT BE ADJUSTED.
NO NEED OF PRESSURE TANK
MODE P+P
PUMP STARTS AND STOPS ACCORDING TO PRESSURE THRESHOLD
CUT-IN AND CUT-OFF PRESSURE CAN BE REGULATED (MIN. DIFFERENTIAL 0,3 BAR)
IT MUST BE USED WITH A PRESSURE TANK, AT LEAST OF 24LT
2 PRODUCTS IN ONE!
ModeP + F
ModeP + P
WHY CHOOSE BRIO TOP?
BOOSTER SETS WITHOUT CONTROL BOX
P+P MODE
WHEN USED IN P+P MODE WITH A PRESSURE TANK, 2 DEVICES CAN BE INTERCONNECTED TO GET A BOOSTER SET
PUMPS START IN SWAPPED MODE ON WATER DEMAND
PUMPS CAN RUN TOGETHER IN CASE OF HIGH WATER REQUEST FROM THE USERS
JUST A 4 WIRE CABLE IS NEEDED FOR INTERCONNECTION
WHY CHOOSE BRIO TOP?
POSSIBLE CONNECTION WITH OTHER DEVICES
AUXILIARY I/O
INPUT CAN BE USED TO CONNECT A FLOAT SWITCH OR A TIMER
IT CAN BE REMOTELY OPERATED FROM ANOTHER DEVICE (PLC, COMPUTER WITH «CAFM», ETC.)
OUTPUT RELAY CAN SIGNAL ERROR CONDITIONS OR CAN BE USED TO START OTHER EQUIPMENT (UV UNITS, CHLORINE PUMPS, ETC.)
IT CAN BE USED TO INTERFACE THE PUMP TO BMS (BUILDING MANAGEMENT SYSTEMS)
PROTECTIONS
OVER CURRENT
IT STOPS THE PUMP WHEN THE CURRENT OVERCOMES THE MAXIMUM PROGRAMMED VALUE (LOCKED ROTOR)
OVER PRESSURE
IT STOPS THE PUMP WHEN THE PRESSURE OVERCOMES THE MAXIMUM PROGRAMMED VALUE (USEFUL FOR APPLICATIONS WITH VARIABLE SUCTION DEPTH)
ICE PROTECTION
IF THE PRESSURE FALLS BELOW 4°C,PUMP STARTS AUTOMATICALLY FOR 15” EVERY 15 MINUTES TO PREVENT FREEZING OF WATER INSIDE THE IMPELLERS
ANTI-SEIZE FUNCTION
WHEN THE PUMP IS NOT USED FOR A PERIOD LONGER THAN 24H, BRIO TOP WILL START THE MOTOR AUTOMATICALLY TO PREVENT ROTOR SEIZURE
WHY CHOOSE BRIO TOP?
PLASTIC FITTINGSFOR AN EASIER AND QUICK INSTALLATION
CURVAMG RC1M/G
• Ideal for the installation of all our electronic devices with 1inch connection
• They replace the traditional connections in brass or cast iron• Revolving nut with joint• Ideal for by-pass connection when the hose is bigger than 1inch
INVERTERVARIABLE FREQUENCY DRIVES
SIRIO SIRIO ENTRY – ENTRY XP NETTUNO UNIVERSAL
1-PH 230V INPUT / 3-PH 230V OUTPUT
FOR 3-PHASE PUMPSDELTA CONNECTIONOUTPUT MAX. 9,7A
WATER COOLINGPIPE MOUNTING
1-PH 230V INPUT / 1-PH 230V OUTPUT
FOR 1-PHASE PUMPS WITH CAPACITOROUTPUT MAX 10,5 A - SIRIO ENTRYOUTPUT MAX 14 A – SIRIO ENTRY XP
WATER COOLINGPIPE MOUNTING
1-PH 230 V INPUT1-PH 230V 10,5A / 3-PH 230V 9,7 AOUTPUT SELECTABLE BY SOFTWARE
AIR COOLINGWALL OR PIPE MOUNTING
3-PH 400V INPUT / 3-PH 400V OUTPUT MAX 13 AOUTPUT MAX 9 AOUTPUT MAX 6 A
AIR COOLING WALL OR PIPE MOUNTING
NETTUNO
SIRIO & SIRIO ENTRY
COMPACT DESIGN
IT CAN BE INSTALLED IN VERTICAL OR HORIZONTAL POSITION
DISPLAY LCD – 8 LANGUAGES
DIGITAL DISPLAY OF PRESSURE AND CURRENT
EASY SETTING OF THE PARAMETERS
ERROR LOG
INTEGRATED FLOW AND PRESSURE SENSORS
NO NEED OF EXTERNAL SENSOR
CHECK VALVE WITH INTEGRATED FLOW SENSOR
WATER COOLING
LONG LIFE OF POWER ELECTRONIC CIRCUITS
BIG HEAT DISSIPITION PLATE
HIGH POWER RATINGS IN A SMALL DESIGN
VARIABLE MOTOR SPEED
CONSTANT PRESSURE ENERGY SAVING
SOFT-START
GRADUAL START AND STOP OF THE PUMP
DISPLAY SIRIO 2.0
3.0 BAR 40 Hz
V= 230VI= 6.0A
Tm=45°CTa=45°C
LanguageEN
- ALL FUNCTIONING VARIABLES AVAILABLE ON THE LCD
(PRESSURE, VOLTAGE, CURRENT, TEMPERATURE)
- END USER CAN CHANGE THE LANGUAGE ONLY (TO
PREVENT UNAUTHORIZED VARIATION OF PARAMETERS)
ADVANCED USE OF SIRIO 2.0IMPROVED I/O
OPTIONAL I/O CARD:1 DIGITAL INPUT FOR EXTERNAL START, EXTERNAL ERROR OF DOUBLE SET-POINT
1 DIGITAL OUTPUT FOR “ERROR” SIGNALING, “PUMP IN FUNCTION” SIGNALING OR FOR AUXILIARY FIXED SPEED PUMP
STANDARD AUX. CONNECTOR- IT ALLOWS THE CONNECTION OF 2 SIRIO IN A BOOSTER SET- IT CAN BE USED FOR EXTERNAL START OR DOUBLE SET-POINT
COMMAND
I/O input‘2’
I/O outputERR.
Con. Aus.1 <->
ADVANCED USE OF SIRIO 2.0USE WITH DIRTY WATER
- FLOW SENSOR CAN BE DISABLED
- SIRIO CAN BE OPERATED ACCORDING TO THE PRESSURE ONLY
- USEFUL FOR APPLICATION WITH SAND AND IRON
- DRY RUNNING PRESSURE MUST BE SET TO CORRECTLY STOP THE PUMP IN ABSENCE OF WATER
Flow sens.OFF
Dry ru.Press0,5 BAR
INVERTER
INPUT OUTPUT
NETTUNO 3P 13A 3X400V 3X400V – 13A max.
NETTUNO 3P 9A 3X400V 3X400V – 9A max.
NETTUNO 3P 6A 3X400V 3X400V – 6A max.
NETTUNO
INPUT OUTPUT
NETTUNOUNIVERSAL
1X230V 1X230V – 10,5A max.
3X230V – 9,7A max.(SELECTABLE)
NETTUNO UNIVERSAL
NETTUNO
WALL MOUNTING(fixing bracket standard provided)
PIPE MOUNTING(Kit of fixing collars by request)
NETTUNO and NETTUNO UNIVERSAL
ANALOG INPUTS
4-20mA (PRESSURE SENSOR)0-10V (AUXILIARY)
RS 485
BOOSTER SET UP TO 8 PUMPS.ONLY ONE PRESSURE TRANSDUCER CAN BE CONNECTED TO ANY INVERTER
2 x OUTPUTS (ERROR, PUMP ON, DOL PUMP)
AUXILIARY SINGLE PHASE PUMP CONTROL
DIGITAL INPUTS
1X ENABLE (FLOW SWITCH, TIMER)1X ERROR1X SECONDARY SET-POINT
BIG DISPLAY
LCD 16X2EASY CONFIGURATION
DIGITAL OUTPUTS