8
PRODUCT DATA 65-0237-06 C6097A,B Pressure Switches APPLICATION The C6097 Pressure Switches are safety devices used in positive-pressure or differential-pressure systems to sense gas or air pressure changes. FEATURES For use with natural gas, liquid propane (LP) gas, or air. Diaphragm-actuated safety-limit switch. Switch can be wired to turn on alarm. C6097A models break control circuit at setpoint on pressure fall. C6097B models break control circuit at setpoint on pressure rise. Lockout with manual reset and recycle options. Lockout models have external manual reset button. Removable transparent cover protects scaleplate and adjusting knob. Pipe tappings allow selection of positive pressure, differential pressure (air only) or venting connections (NPT mount only). 1/4 in. NPT or flange mount models for direct mounting to Honeywell Integrated Valve Train. Optional switch position indicator lamp available. IP54 enclosure standard. Ranges: 0.4 to 5 in. wc, 3 to 21 in. wc, 12 to 60 in. wc or 1.5 to 7 psi. Surge orifice. Integral Vent Limiter (all models). Contents Application ........................................................................ 1 Features ........................................................................... 1 Specifications ................................................................... 2 Ordering Information ........................................................ 2 Installation ........................................................................ 4 Optional Switch Position Indication Lamp ........................ 4 Wiring ............................................................................... 6 Settings and Adjustments ................................................. 6 Operation and Checkout .................................................. 7

65-0237 06 - C6097A,B Pressure Switches · C6097A,B Pressure Switches APPLICATION The C6097 Pressure Switches are safety devices used in positive-pressure or differential-pressure

  • Upload
    others

  • View
    26

  • Download
    0

Embed Size (px)

Citation preview

Page 1: 65-0237 06 - C6097A,B Pressure Switches · C6097A,B Pressure Switches APPLICATION The C6097 Pressure Switches are safety devices used in positive-pressure or differential-pressure

PRODUCT DATA

65-0237-06

C6097A,B Pressure Switches

APPLICATION

The C6097 Pressure Switches are safety devices used in positive-pressure or differential-pressure systems to sense gas or air pressure changes.

FEATURES

• For use with natural gas, liquid propane (LP) gas, or air.

• Diaphragm-actuated safety-limit switch.

• Switch can be wired to turn on alarm.

• C6097A models break control circuit at setpoint on pressure fall.

• C6097B models break control circuit at setpoint on pressure rise.

• Lockout with manual reset and recycle options.

• Lockout models have external manual reset button.

• Removable transparent cover protects scaleplate and adjusting knob.

• Pipe tappings allow selection of positive pressure, differential pressure (air only) or venting connections (NPT mount only).

• 1/4 in. NPT or flange mount models for direct mounting to Honeywell Integrated Valve Train.

• Optional switch position indicator lamp available.

• IP54 enclosure standard.

• Ranges: 0.4 to 5 in. wc, 3 to 21 in. wc, 12 to 60 in. wc or 1.5 to 7 psi.

• Surge orifice.

• Integral Vent Limiter (all models).

ContentsApplication ........................................................................ 1Features ........................................................................... 1Specifications ................................................................... 2Ordering Information ........................................................ 2Installation ........................................................................ 4Optional Switch Position Indication Lamp ........................ 4Wiring ............................................................................... 6Settings and Adjustments ................................................. 6Operation and Checkout .................................................. 7

Page 2: 65-0237 06 - C6097A,B Pressure Switches · C6097A,B Pressure Switches APPLICATION The C6097 Pressure Switches are safety devices used in positive-pressure or differential-pressure

C6097A,B PRESSURE SWITCHES

65-0237—06 2

ORDERING INFORMATION

When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number.

If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:

1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).2. Honeywell Customer Care

1885 Douglas Drive NorthMinneapolis, Minnesota 55422-4386

In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Toronto, Ontario M1V 4Z9.International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.

SPECIFICATIONS

Models:C6097A Pressure Switch: Breaks a circuit when pressure falls

to scale setting. See Table 1.C6097B Pressure Switch: Breaks a circuit when pressure

rises to scale setting. See Table 1.Table 2 shows switch ratings and Table 3 shows alternate

electrical ratings when used with Honeywell Flame Safeguard Programmers.

Minimum Ambient Temperature: -40°F (-40°C).

Maximum Ambient Temperature: 140°F (60°C).

Connections (Depending on Model):1/4-18 NPT tapping for main or high-pressure connection.1/8-27 NPT tapping for vent or low-pressure connection

(air only).Flange mount for connection to Honeywell Integrated Valve

Train (internal vent only, no external connections).

Scale Range:0.4 to 5 in. wc (0.10 kPa to 1.25 kPa).3 to 21 in. wc (0.75 to 5.23 kPa).12 to 60 in. wc (3.0 kPa to 15 kPa).1.5 to 7 psi (10.3 kPa to 48 kPa).

Approvals:Underwriters Laboratories Inc. listed.Canadian Standards Association listed.Factory Mutual: Approved.Industrial Risk Insurers: Acceptable.CSD-1 AFB: Acceptable.

Accessories:32003041-001 C6097 Cover for manual reset models.32003040-001 C6097 Cover for recycle models.32003039-001 Position Indication Lamp Kit (for 120 Vac only)

Dimensions: See Fig. 1 and 2.

Fig. 1. C6097 1/4 in. NPT Mount dimensions in in. (mm).

27/32 (22) HOLE

HOUSING

GAS CONNECTION 1/4 NPT WITH DUST SEAL

2-1/4(57)

3-3/16(81)

1-17/32(90)

2-21/32 (68)2-21/32 (68)

31/32(25)

25/32(21)

15/32 (12)1-3/32 (28)

13/32 (11)

2-23/32 (69)2-23/32 (69)

1-3/4 (45)

2-13/32(61)

ATMOSPHERIC PRESSURE REFERENCE PORT OR DIFFERENTIALCONNECTION 1/8 NPT

INDICATOR

M29773

1 2 3

P

NO

NC

COM

TERMINAL DIAGRAM

Page 3: 65-0237 06 - C6097A,B Pressure Switches · C6097A,B Pressure Switches APPLICATION The C6097 Pressure Switches are safety devices used in positive-pressure or differential-pressure

C6097A,B PRESSURE SWITCHES

3 65-0237—06

a Acceptable media: Natural gas, liquid propane (LP) gas, and air.

Table 1. Pressure Switch Model Selection.

Model

Operating Pressure

Range

Manual Reset Differential

Non-Manual Reset Differential

Differential Type

Maximum Rated

Pressure (continuous)

(psi)Manual Reset Mediaa

Switch Action at Setpoint Comments

Maximum at

Minimum Setpoint

Maximum at

Maximum Setpoint Nominal Maximum

C6097A1004 0.4 to 5 in. wc

— — 0.16 in. wc

0.24 in. wc Additive 2.9 No Air/Gas Breaks N.O. to C. connection on pressure fall.

1/4 in. NPT Mount

C6097A1012 3 to 21 in. wc

2.4 in. wc 4.2 in. wc — — 5.0 Yes Air/Gas 1/4 in. NPT Mount

C6097A1020 3 to 21 in. wc

2.4 in. wc 4.2 in. wc — — 5.0 Yes Air/Gas Flange Mount

C6097A1038 12 to 60 in. wc

10 in. wc 12 in. wc — — 5.0 Yes Air/Gas 1/4 in. NPT Mount

C6097A1046 12 to 60 in. wc

10 in. wc 12 in. wc — — 5.0 Yes Air/Gas Flange Mount

C6097A1053 3 to 21 in. wc

— 0.24 in. wc

0.48 in. wc 5.0 No Air/Gas 1/4 in. NPT Mount

C6097A1061 3 to 21 in. wc

— — 0.24 in. wc

0.48 in. wc 5.0 No Air/Gas Flange Mount

C6097A1079 12 to 60 in. wc

— — 1.1 in. wc 2.4 in. wc 5.0 No Air/Gas 1/4 in. NPT Mount

C6097A1087 12 to 60 in. wc

— — 1.1 in. wc 2.4 in. wc 5.0 No Air/Gas Flange Mount

C6097A1095 0.4 to 5 in. wc

0.6 in. wc 1.0 in. wc — — 2.9 Yes Air/Gas 1/4 in. NPT Mount

C6097A1103 1.5 to 7 psi

1.1 psi 1.4 psi — — 9.3 Yes Air/Gas Flange Mount

C6097A1111 1.5 to 7 psi

1.1 psi 1.4 psi — — 9.3 Yes Air/Gas 14 in. NPT Mount

C6097A1129 1.5 to 7 psi

— — 0.1 psi 0.3 9.3 No Air/Gas Flange Mount

C6097A1137 1.5 to 7 psi

— — 0.1 psi 0.3 9.3 No Air/Gas 1/4 in. NPT Mount

C6097A1210 0.4 to 5 in. wc

— — 0.16 in. wc

0.24 in. wc 2.9 No Air/Gas Flange Mount

C6097A1228 0.4 to 5 in. wc

— — — — 2.9 Yes Air/Gas Flange Mount

C6097B1002 12 to 60 in. wc

10 in. wc 12 in. wc — — Subtractive 5.0 Yes Air/Gas Breaks N.C. to C. connection on pressure rise.

1/4 in. NPT Mount

C6097B1010 12 to 60 in. wc

10 in. wc 12 in. wc — — 5.0 Yes Air/Gas Flange Mount

C6097B1028 3 to 21 in. wc

2.4 in. wc 4.2 in. wc — — 5.0 Yes Air/Gas 1/4 in. NPT Mount

C6097B1036 3 to 21 in. wc

2.4 in. wc 4.2 in. wc — — 5.0 Yes Air/Gas Flange Mount

C6097B1044 1.5 to 7 psi

1.1 psi 1.4 psi — — 9.3 Yes Air/Gas Flange Mount

C6097B1051 1.5 to 7 psi

1.1 psi 1.4 psi — — 9.3 Yes Air/Gas 1/4 in. NPT Mount

C6097B1069 3 to 21 in. wc

— — 0.24 in. wc

0.48 in. wc 5.0 No Air/Gas Flange Mount

C6097B1077 12 to 60 in. wc

— — 1.1 in. wc 2.4 in. wc 5.0 No Air/Gas Flange Mount

C6097B1085 12 to 60 in. wc

— — 1.1 in. wc 2.4 in. wc 5.0 No Air/Gas 1/4 in. NPT Mount

C6097B1093 1.5 to 7 psi

— — 0.1 psi 0.3 psi 9.3 No Air/Gas Flange Mount

C6097B1101 1.5 to 7 psi

— — 0.1 psi 0.3 psi 9.3 No Air/Gas 1/4 in. NPT Mount

C6097B1119 3 to 21 in. wc

— — 0.24 in. wc

0.48 in. wc 5.0 No Air/Gas 1/4 in. NPT Mount

Page 4: 65-0237 06 - C6097A,B Pressure Switches · C6097A,B Pressure Switches APPLICATION The C6097 Pressure Switches are safety devices used in positive-pressure or differential-pressure

C6097A,B PRESSURE SWITCHES

65-0237—06 4

Table 2. Switch Ratings (Amperes).

Table 3. Alternate Electrical Ratings when used with Honeywell Flame Safeguard Programmers.

Fig. 2. C6097 Flange Mount dimensions in in. (mm).

INSTALLATION

WARNINGExplosion or Fire Hazard.Can cause severe personal injury, death or property damage.Observe all safety requirements each time a control is installed on a burner.

When Installing this Product...1. Read these instructions carefully. Failure to follow

them can damage the product or cause a hazardous condition.

2. Check the ratings given in the instructions and on the product to make sure that the product is suitable for your application.

3. Installer must be a trained, experienced service technician.

4. After installation is completed, check out product operation as provided in these instructions.

WARNINGElectrical Shock Hazard.Can cause serious personal injury or death.Disconnect power supply before beginning installation. More than one disconnection can be involved.

Mounting

NOTE: On flange models, remove the label holding theO-ring in place and make sure O-ring seal is in place before mounting the pressure switch on the valve.

The C6097 models allow NPT or flange (directly to valve) mounting. The NPT models have a hexagonal fitting with a 1/4 in. NPT tapping, which is the high pressure connection, in differential applications. The Atmospheric Pressure Reference Port is 1/8 in. NPT tapped. In differential pressure control applications using air only, connect the lower pressure to this Atmospheric Pressure Reference Port. See Fig. 1.

Both the flange mount and NPT mount models are supplied with an Integral Vent Limiter. External vent line is not required. If necessary, this 1/8-in. atmospheric vent fitting can be used for the vent line connection.

C6097 models with flange mount can be fitted directly to Honeywell Integrated Valve Train (model specific). See Fig. 2 and Table 1. The flange mount models vent internally, with no external tap.

Mount the C6097A,B in any position.

Leak CheckAfter installation, perform a leak check on the pressure switch:

1. Turn on main gas. Make sure gas has reached the pressure switch (e.g., high gas pressure switch)

2. Check installation for gas leaks using a gas leak detector or a soap solution.

OPTIONAL SWITCH POSITION INDICATION LAMP

The 32003039-001 Switch Position Indicator Lamp Kit consists of a plastic bag containing the following parts (see Fig. 1):

1. Lamp and wires.2. Terminal plate.3. Captive screw and nut.4. Screw.

120/240 Vac, 50/60 Hz

Inductive Full Load 3.0

Locked Rotor 18.0

Resistive 5.0

Device Rating

Ignition Transformer 540 VA

Pilot Valve 50 VA

Main Valve 400 VA with 2-1/2 times inrush.

27/32 (22) HOLE

PRESSURE INLET

5/8 (16)

2-1/4(57)

2(52)

2 (52)

1-1/4(32)

1/32 (1)

2-21/32 (68)

2-23/32 (69)

2-23/32 (69)

INDICATOR

M17124

1 2 3

P

NO

NC

COM

TERMINAL DIAGRAM

Page 5: 65-0237 06 - C6097A,B Pressure Switches · C6097A,B Pressure Switches APPLICATION The C6097 Pressure Switches are safety devices used in positive-pressure or differential-pressure

C6097A,B PRESSURE SWITCHES

5 65-0237—06

Fig. 3. 32003039-001 Position Indication Lamp Kit.

Installation

WARNINGExplosion or Fire Hazard.Can cause severe personal injury, death or property damage.Observe all safety requirements each time a control is installed on a burner.

WARNINGElectrical Shock Hazard.Can cause serious personal injury or death.Disconnect power supply before beginning installation. More than one disconnection can be involved.

Installing the Position Indication Lamp Kit (See Fig. 4)

1. Remove the cover from the C6097 by removing the screws in the upper left and lower right quadrants of the cover.

2. Place the lamp in the slot to the right of the dial, in the upper right-hand corner of the C6097, with the base down. Run the two lamp wires through the slit in the upper left corner of the lamp slot.

3. Place the nut in the hexagonal depression in the lower left-hand corner of the C6097.

4. Place the terminal plate over the nut and fasten the terminal plate to the C6097 with the screw through the bottom hole in the terminal plate.

5. Place the captive screw through the terminal lug on the shorter wire and fasten the wire to the terminal plate with the captive screw secured by the nut under the terminal plate.

6. Using Fig. 5 or 6 for reference, fasten the terminal lug on the longer lamp wire to either the normally open (NO) or normally closed (NC) terminal of the C6097. Fig. 4. Installing the Position Indicator Lamp Kit.

1-19/32 (40) 3-11/32 (85)

4-1/8 (105)

1/2(13)

1/4 (6)

LAMP AND WIRES

TERMINALPLATE

CAPTIVE SCREWAND NUT

SCREW

M16523

M16522

C6097BODY

C6097COVER

SLIDE TWO LAMP WIRESTHROUGH SLOT

LAMP

CONNECTIONS FORLAMP LEADWIRES

1

1NC

NO

L2

CONNECT L1 (HOT) LEAD TO THE NO OR NC TERMINALBASED ON MODEL AND DESIRED LAMP FUNCTION.

Page 6: 65-0237 06 - C6097A,B Pressure Switches · C6097A,B Pressure Switches APPLICATION The C6097 Pressure Switches are safety devices used in positive-pressure or differential-pressure

C6097A,B PRESSURE SWITCHES

65-0237—06 6

Fig. 5. Wiring the Position Indicator Lamp Kit in the C6097A.

Fig. 6. Wiring the Position Indicator Lamp Kit in the C6097B.

Position Indicator Lamp OperationThe Position Indicator Lamp will light when the C6097 Pressure Switch opens and provides power to the lamp (see Fig. 5or 6). An option alarm circuit can also be connected as shown in the same figures.

WIRING

WARNINGElectrical Shock Hazard.Can cause serious personal injury or death.Disconnect power supply before beginning installation. More than one disconnection can be involved.

Make sure that all wiring agrees with all applicable local codes, ordinances and regulations. An opening is provided to accommodate rigid conduit or armored cable for line voltage operation (see Fig. 3 and 4). Do not overload the switch contacts (see Switch Ratings in the Specifications section). The switching schematic is shown in Fig. 5.

Fig. 7. C6097 (manual reset switch model) with cover removed.

Fig. 8. C6097 (recycle model) with cover removed.

SETTINGS AND ADJUSTMENTS

Pressure Setpoint AdjustmentTo adjust the pressure setting, turn the setpoint adjustment dial (Fig. 3, 4 and 5) clockwise to increase the pressure setting and counterclockwise to decrease the pressure setting.

C6097A

FLAME SAFEGUARDCONTROL (RM78XX)

C NO

NCPOSITIONINDICATIONLAMP

L1

L2 M16524

C6097B FLAME SAFEGUARDCONTROL (RM78XX)

C NO

NC

POSITIONINDICATIONLAMP

L1

L2

M16525

Page 7: 65-0237 06 - C6097A,B Pressure Switches · C6097A,B Pressure Switches APPLICATION The C6097 Pressure Switches are safety devices used in positive-pressure or differential-pressure

C6097A,B PRESSURE SWITCHES

7 65-0237—06

Fig. 9. C6097 schematic.

OPERATION AND CHECKOUT

OperationThe manual reset C6097A diaphragm actuates the snap-acting switch to break a control circuit and lock out when pressure falls to the scale setting. The recycle C6097A models recycle automatically when the control circuit returns to scale setting plus differential.

The manual reset C6097B diaphragm actuates the snap-acting switch that breaks a control circuit and locks out when the pressure rises to the scale setting. The recycle C6097B models recycle automatically when the control pressure falls to the scale setting minus differential.

Manual ResettingThe C6097A manual reset models lock out when pressure falls to the scale setting and require manual resetting after the pressure rises to scale setting plus differential to resume normal operation.

The C6097B manual reset models lock out when pressure rises to the scale setting and require manual resetting after the pressure falls to scale setting minus the differential to resume normal operation.

To reset, once normal operating pressure is restored, push the reset button in as far as it goes, then release.

IMPORTANTLockout models cannot be made to recycle automatically by permanently holding in the reset lever.

Checkout

C6097 Gas Fuel Application1. Set cutoff pressure.2. Open main supply line. Depress reset lever on lockout

models until switch makes control circuit.3. Set controller and limit switch to call for heat.4. For C6097A: Close the manual gas shutoff valve. C6097

should open control circuit when pressure reaches cutoff point.For C6097B: Open the manual gas shutoff valve, wait a few minutes for the pressure to rise; then lower the scale setting until the switch breaks control circuit and locks out.

5. For C6097A: Open the shutoff valve, return the pressure switch to its original setting and press the reset button (if necessary).For C6097B: raise setting to normal and press reset button (if necessary).

6. Allow system to operate through at least one complete cycle to make sure all components are functioning properly.

C6097A Air Application1. Set cutoff pressure.2. Turn on fan.3. Block fan inlet or filter area. Switch should break control

circuit when pressure drops to cutoff point. Manual reset models lock out.

4. Remove obstruction. Press reset lever (manual reset models) and allow system to operate through at least one complete cycle to be sure all components are functioning properly.

1

1

2

2

NO

NC

C

C6097A BREAKS C-NO, MAKES C-NC ON PRESSURE FALL. MANUAL RESET MODELS LOCK OUT.

C6097B BREAKS C-NC, MAKES C-NO ON PRESSURE RISE AND LOCKS OUT. M17123

Page 8: 65-0237 06 - C6097A,B Pressure Switches · C6097A,B Pressure Switches APPLICATION The C6097 Pressure Switches are safety devices used in positive-pressure or differential-pressure

C6097A,B PRESSURE SWITCHES

Automation and Control Solutions

Honeywell International Inc.

1985 Douglas Drive North

Golden Valley, MN 55422

Honeywell Limited-Honeywell Limitée

35 Dynamic Drive

Toronto, Ontario M1V 4Z9

customer.honeywell.com

® U.S. Registered Trademark© 2009 Honeywell International Inc.65-0237—06 M.S. Rev. 12-09 Printed in U.S.A.