Power Network Telecommunication FWT 2000iSystem for Telecontrol and Data Transmission

7 VR 56Power

to the

Siemens AGPower Transmission andDistribution GroupPower Systems andEnergy Management DivisionHofmannstrasse 51D-81359 Munich

www.ev.siemens.de

Siemens Aktiengesellschaft Order No.: E50001-U336-A18-X-7600Printed in GermanyDispo-Stelle 0640161U1279 WÜ 336502 PA 06972.5

Subject to change without prior notice

Page 2: Power Network Telecommunication FWT 2000i€¦ ·  · 2009-09-09Power Network Telecommunication FWT 2000i System for Telecontrol and Data Transmission ... railway companies and refineries,

32

FWT 2000i –a modular, flexible system for telecontroland data transmission

In all areas related to the telemonitor-ing of systems, automation technologyand the control of decentralizedequipment, it is necessary to transmitsignals and measured values economi-cally and reliably.

The new FWT 2000i System for Tele-control and Data Transmission can beflexibly used to perform the varioustransmission tasks involved in systemmanagement not only in public utilitycompanies, railway companies andrefineries, but also in the areas ofenvironmental protection and civildefense, as well as in hydrographic andmeteorological services.

The following characteristics of theFWT 2000i System make it suitable formeeting users‘ special requirements:

• Safe operating method around high-voltage systems;

• High degree of reliability and security;

• Short process cycle times;

• Easy handling;

• Economical use.

Page 3: Power Network Telecommunication FWT 2000i€¦ ·  · 2009-09-09Power Network Telecommunication FWT 2000i System for Telecontrol and Data Transmission ... railway companies and refineries,

32

FWT 2000i –a modular, flexible system for telecontroland data transmission

In all areas related to the telemonitor-ing of systems, automation technologyand the control of decentralizedequipment, it is necessary to transmitsignals and measured values economi-cally and reliably.

The new FWT 2000i System for Tele-control and Data Transmission can beflexibly used to perform the varioustransmission tasks involved in systemmanagement not only in public utilitycompanies, railway companies andrefineries, but also in the areas ofenvironmental protection and civildefense, as well as in hydrographic andmeteorological services.

The following characteristics of theFWT 2000i System make it suitable formeeting users‘ special requirements:

• Safe operating method around high-voltage systems;

• High degree of reliability and security;

• Short process cycle times;

• Easy handling;

• Economical use.

Page 4: Power Network Telecommunication FWT 2000i€¦ ·  · 2009-09-09Power Network Telecommunication FWT 2000i System for Telecontrol and Data Transmission ... railway companies and refineries,

FWT 2000i frequency raster

2400 Bd+/– 800 Hz

300 Hz 7200 Hz

1200 Bd+/– 400 Hz

600 Bd+/– 200 Hz

200 Bd+/– 120 Hz

200 Bd+/– 90 Hz

100 Bd+/– 60 Hz

100 Bd+/– 45 Hz

50 Bd+/– 30 Hz

50 Bd+/– 22,5 Hz

Adjustable in 30 Hz raster from300-7200 Hz = n adjustment options

n = 108n = 108

n = 168

n = 190

n = 201

n = 204

n = 209

n = 210

n = 212

n = 213

Example:

max. number of channels in thefrequency range 0.3–3.4 kHz basedon the 30-Hz frequency raster

50 Bd SB 33 channels

50 Bd FM 120 25 channels

100 Bd SB 12 (13) channels

100 Bd FM 240 17 channels

200 Bd SB 8 channels

200 Bd FM 480 6 channels

600 Bd 2 channels

1200 Bd 1 channel

54

System characteristics:

Flexibility

The FWT 2000i System offers a varietyof modules for the widest possiblerange of transmission tasks. Thanks tothe unlimited equipping options of theframe, virtually all system variantsnecessary for operation can be imple-mented on a customer-specific basis.

Integration in other systems

The modularity of the KS 2000i ChannelUnit is typified by its integration invarious other systems, i.e. its use is notlimited to the FWT 2000i System.

For instance, the channel unit can beintegrated in:

• The PLC-System ESB 2000i;

• The Teleprotection Signaling System SWT 2000 F6;

• Telecontrol systems.

This modularity is possible only becauseall functions have been integrated onone module and a number of differentsupply voltages are possible.

Quick and easy fault location

Fault location is guaranteed to be quickand easy thanks to facilities such as the:

• Local circuit monitors for transmitter and receiver;

• Level monitor for transmitter andreceiver;

• Useful signal level monitor;

• Test code generator;

• Mode selector switch.

Transmitter and receiver as separatemodules

In many cases, users simply require atransmitter in Station A and a receiverin Station B for unidirectional connec-tions. Separate modules that functiononly as a receiver or only as a transmitterare available for this operating method.

Universal for all frequencies andtransmission rates of up to 2400 baud

The basic module of the FWT 2000iSystem is the KS 2000i Channel Unit.It accommodates a complete trans-mitter and receiver assembly.

The KS 2000i Channel Unit is of univer-sal application. All transmission ratesfrom 50 to 2400 baud can be set in allfrequencies within the 30-Hz raster,including in the frequency raster toITU-T.

Transmission in the superimposedfrequency band

The FWT 2000i System permits trans-mission in the frequency range from300 to 7200 Hz.

A second band can thus be used oncable runs along with the normal voiceband from 300 to 3400 Hz. The samechannel assignment is possible in thissuperimposed frequency band as in thebasic frequency band.

Optimization of transmissioncapacity

The transmission capacity of the FWT2000i System can be further increasedby setting up narrow-band channels.

The improved transmission character-istics result in distortion values fornarrow-band channels that are lowerthan the distortion values for broad-bandchannels in older systems, thusachieving optimal transmission quality.

Page 5: Power Network Telecommunication FWT 2000i€¦ ·  · 2009-09-09Power Network Telecommunication FWT 2000i System for Telecontrol and Data Transmission ... railway companies and refineries,

FWT 2000i frequency raster

2400 Bd+/– 800 Hz

300 Hz 7200 Hz

1200 Bd+/– 400 Hz

600 Bd+/– 200 Hz

200 Bd+/– 120 Hz

200 Bd+/– 90 Hz

100 Bd+/– 60 Hz

100 Bd+/– 45 Hz

50 Bd+/– 30 Hz

50 Bd+/– 22,5 Hz

Adjustable in 30 Hz raster from300-7200 Hz = n adjustment options

n = 108n = 108

n = 168

n = 190

n = 201

n = 204

n = 209

n = 210

n = 212

n = 213

Example:

max. number of channels in thefrequency range 0.3–3.4 kHz basedon the 30-Hz frequency raster

50 Bd SB 33 channels

50 Bd FM 120 25 channels

100 Bd SB 12 (13) channels

100 Bd FM 240 17 channels

200 Bd SB 8 channels

200 Bd FM 480 6 channels

600 Bd 2 channels

1200 Bd 1 channel

54

System characteristics:

Flexibility

The FWT 2000i System offers a varietyof modules for the widest possiblerange of transmission tasks. Thanks tothe unlimited equipping options of theframe, virtually all system variantsnecessary for operation can be imple-mented on a customer-specific basis.

Integration in other systems

The modularity of the KS 2000i ChannelUnit is typified by its integration invarious other systems, i.e. its use is notlimited to the FWT 2000i System.

For instance, the channel unit can beintegrated in:

• The PLC-System ESB 2000i;

• The Teleprotection Signaling System SWT 2000 F6;

• Telecontrol systems.

This modularity is possible only becauseall functions have been integrated onone module and a number of differentsupply voltages are possible.

Quick and easy fault location

Fault location is guaranteed to be quickand easy thanks to facilities such as the:

• Local circuit monitors for transmitter and receiver;

• Level monitor for transmitter andreceiver;

• Useful signal level monitor;

• Test code generator;

• Mode selector switch.

Transmitter and receiver as separatemodules

In many cases, users simply require atransmitter in Station A and a receiverin Station B for unidirectional connec-tions. Separate modules that functiononly as a receiver or only as a transmitterare available for this operating method.

Universal for all frequencies andtransmission rates of up to 2400 baud

The basic module of the FWT 2000iSystem is the KS 2000i Channel Unit.It accommodates a complete trans-mitter and receiver assembly.

The KS 2000i Channel Unit is of univer-sal application. All transmission ratesfrom 50 to 2400 baud can be set in allfrequencies within the 30-Hz raster,including in the frequency raster toITU-T.

Transmission in the superimposedfrequency band

The FWT 2000i System permits trans-mission in the frequency range from300 to 7200 Hz.

A second band can thus be used oncable runs along with the normal voiceband from 300 to 3400 Hz. The samechannel assignment is possible in thissuperimposed frequency band as in thebasic frequency band.

Optimization of transmissioncapacity

The transmission capacity of the FWT2000i System can be further increasedby setting up narrow-band channels.

The improved transmission character-istics result in distortion values fornarrow-band channels that are lowerthan the distortion values for broad-bandchannels in older systems, thusachieving optimal transmission quality.

Page 6: Power Network Telecommunication FWT 2000i€¦ ·  · 2009-09-09Power Network Telecommunication FWT 2000i System for Telecontrol and Data Transmission ... railway companies and refineries,

76

( ) ( )

I

II

I

II

I

II

I

II

Alternative path switching

For the transmission of important data,transmission paths are frequently dupli-cated. On the send side, the signal isapplied to two paths. On the receiveside, switchover from the main path tothe standby path takes place in theevent of a fault. This function is per-formed by the alternative path switchingmodule (ZWU).

The system’s internal switchover criteriaare the:

• Receive level;

• Signal-to-noise ratio.

Either of these criteria alone or the twotogether can result in switchover.Users can determine the switchoverthreshold within a wide range.In addition to the system’s internalswitchover criteria, switchover can alsobe controlled externally, e.g. by thetelecontrol unit.

The alternative path switching modulepermits the selection of line (LU) orchannel (KU) switchover. Transmissionpath priority is determined by means ofa front connector.

Control frequency transmission formulti-station control systems

The audio-frequency multi-stationcontrol system is a special type of tele-control system. It is used, for example,for changing meter rates and for con-trolling street and traffic lights.

The audio-frequency multi-stationcontrol converter (TRU) converts thecontrol frequency signals for transmit-ting the multi-station control frequency.The signal is output on a VFT transmittervia a V.28 interface. In this way, thecontrol frequency is routed to the cor-responding station using a minimum offrequency space. A VFT receiver routesthe control frequency signal to the TRUreceiver unit, which contains a controlfrequency filter. This filter greatlyreduces the jittering that interfereswith multi-station control. Thus, acontrol frequency of the best possiblequality is supplied to the multi-stationcontrol command unit in the substation.

ZWU, lineswitchover

ZWU, channel switchover

Data transmission in the voice bandwith SEU 2000i

The SEU 2000i module comprises atransmitter and receiver for transmittinga data channel via a 2-wire or 4-wire linein the voice band from 300 to 3400 Hz.Due to the fact that signal processingis less complex, this module offers aneconomical alternative in cases whereflexibility is limited.

The SEU 2000i module is identical tothe KS 2000i Channel Unit.Since the pin assignment is the same,the SEU 2000i can be installedwherever a KS 2000i can be installed(e.g. adapter module in telecontrolunits).

In contrast to the KS 2000i, only 4 fre-quencies can be set on the SEU 2000i.The first two frequencies are identicalto those of the earlier SEU A,B/STmodules. The second frequency pairmakes it possible to transmit a1200 baud duplex channel via a two-wire cable connection.

The SEU 2000i was designed with aview to possible advantages for users,including economical system manage-ment, transmission security andreliability and short process cycletimes, as well as easy handling.

Compatibility

The FWT 2000i System is fully com-patible with the predecessor systemFWT 2000 and can be operated withother VFT systems.

• The FWT 2000i modules also operatein the module frames of theFWT 2000 System.

• The modules of the old FWT 2000 System also operate in the module frames of the new FWT 2000iSystem.

• The KS 2000i Channel Unit can be installed in any module adapter in which the KS 2000 can be installed.

• The SEU 2000i can be installed in anymodule adapter in which the KS 2000ior KS 2000 can be installed.

• Due to its flexible setting options, theKS 2000i Channel Unit operates in conjunction with all VFT systems.

V

KU1

KU1

K1

K2

KU2

KU2W II

SP

UM

SÜ II

PÜ II

SÜ I

PÜ I

E

SZWU/LU

KS

Controlfrequency

TRU S

S

E

Data

Data

TRUE

S

E

Schematic scheme of control frequency transmission

Integrated controlfrequency filter

KU1

KU1

W II

SP

UM

SÜ II

PÜ II

SÜ I

PÜ I

ZWU/LU

E

S

KS

E

S

KS

K1

K2

KU2

KU2

Page 7: Power Network Telecommunication FWT 2000i€¦ ·  · 2009-09-09Power Network Telecommunication FWT 2000i System for Telecontrol and Data Transmission ... railway companies and refineries,

76

( ) ( )

I

II

I

II

I

II

I

II

Alternative path switching

For the transmission of important data,transmission paths are frequently dupli-cated. On the send side, the signal isapplied to two paths. On the receiveside, switchover from the main path tothe standby path takes place in theevent of a fault. This function is per-formed by the alternative path switchingmodule (ZWU).

The system’s internal switchover criteriaare the:

• Receive level;

• Signal-to-noise ratio.

Either of these criteria alone or the twotogether can result in switchover.Users can determine the switchoverthreshold within a wide range.In addition to the system’s internalswitchover criteria, switchover can alsobe controlled externally, e.g. by thetelecontrol unit.

The alternative path switching modulepermits the selection of line (LU) orchannel (KU) switchover. Transmissionpath priority is determined by means ofa front connector.

Control frequency transmission formulti-station control systems

The audio-frequency multi-stationcontrol system is a special type of tele-control system. It is used, for example,for changing meter rates and for con-trolling street and traffic lights.

The audio-frequency multi-stationcontrol converter (TRU) converts thecontrol frequency signals for transmit-ting the multi-station control frequency.The signal is output on a VFT transmittervia a V.28 interface. In this way, thecontrol frequency is routed to the cor-responding station using a minimum offrequency space. A VFT receiver routesthe control frequency signal to the TRUreceiver unit, which contains a controlfrequency filter. This filter greatlyreduces the jittering that interfereswith multi-station control. Thus, acontrol frequency of the best possiblequality is supplied to the multi-stationcontrol command unit in the substation.

ZWU, lineswitchover

ZWU, channel switchover

Data transmission in the voice bandwith SEU 2000i

The SEU 2000i module comprises atransmitter and receiver for transmittinga data channel via a 2-wire or 4-wire linein the voice band from 300 to 3400 Hz.Due to the fact that signal processingis less complex, this module offers aneconomical alternative in cases whereflexibility is limited.

The SEU 2000i module is identical tothe KS 2000i Channel Unit.Since the pin assignment is the same,the SEU 2000i can be installedwherever a KS 2000i can be installed(e.g. adapter module in telecontrolunits).

In contrast to the KS 2000i, only 4 fre-quencies can be set on the SEU 2000i.The first two frequencies are identicalto those of the earlier SEU A,B/STmodules. The second frequency pairmakes it possible to transmit a1200 baud duplex channel via a two-wire cable connection.

The SEU 2000i was designed with aview to possible advantages for users,including economical system manage-ment, transmission security andreliability and short process cycletimes, as well as easy handling.

Compatibility

The FWT 2000i System is fully com-patible with the predecessor systemFWT 2000 and can be operated withother VFT systems.

• The FWT 2000i modules also operatein the module frames of theFWT 2000 System.

• The modules of the old FWT 2000 System also operate in the module frames of the new FWT 2000iSystem.

• The KS 2000i Channel Unit can be installed in any module adapter in which the KS 2000 can be installed.

• The SEU 2000i can be installed in anymodule adapter in which the KS 2000ior KS 2000 can be installed.

• Due to its flexible setting options, theKS 2000i Channel Unit operates in conjunction with all VFT systems.

V

KU1

KU1

K1

K2

KU2

KU2W II

SP

UM

SÜ II

PÜ II

SÜ I

PÜ I

E

SZWU/LU

KS

Controlfrequency

TRU S

S

E

Data

Data

TRUE

S

E

Schematic scheme of control frequency transmission

Integrated controlfrequency filter

KU1

KU1

W II

SP

UM

SÜ II

PÜ II

SÜ I

PÜ I

ZWU/LU

E

S

KS

E

S

KS

K1

K2

KU2

KU2

Page 8: Power Network Telecommunication FWT 2000i€¦ ·  · 2009-09-09Power Network Telecommunication FWT 2000i System for Telecontrol and Data Transmission ... railway companies and refineries,

98

+/– 12 V24 V DC48 / 60 V DC

KS 2000i

S

E

Optimal security and reliability

Users’ demands for operationalsecurity and reliability are met by thefollowing special features of theFWT 2000i System:

• The effects of temperature and aging are practically eliminated by the use ofdigital signal processors.

• The power supply concept permits secondary voltages of ± 12 V from twopower supply units to be connectedin parallel.

• The power supply units can also be fedwith different primary voltages.

• The receiver unit monitors the level and the signal-to-noise ratio.When transmission ratios worsen,a prealarm is activated.

• When there is no guarantee of data security, the output is applied tocontinuous potential, thus preventingthe system from outputting incorrect data.

• The local circuit to the VFT transmitteris monitored for interruptions. In the event of an interruption, the receiver isset to continuous polarity in order to prevent the output of incorrect data.

• Voltage-carrying modules can beinserted and removed, thus permittingall the other modules to remainin operation.

• The secondary voltage can be suppliedto the alternative path switchingmodule from two power supply units.

50 Bd 50 Bd 100 Bd 100 Bd 200 Bd 200 Bd 600 Bd 1200Bd 2400BdSB FM 120 SB FM 240 SB FM 480

Nominal signaling speed Bd 50 50 100 100 200 200 600 1200 2400

Maximum signaling speed Bd 50 75 100 150 200 300 600 1200 2400

Frequency shift Hz ± 22.5 ± 30 ± 45 ± 60 ± 90 ± 120 ± 200 ± 400 ± 800

Send/receive level, nominal, value per channel dBm – 24.5 – 22.5 – 21.5 – 19.5 – 18.5 – 16.5 – 13.5 – 10.5 – 7.5

Minimum frequency band width Hz 90 120 180 240 360 480 1100 1700 3100

Inherent distortion (text)for nominal % < 4 < 3 < 4 < 3 < 4 < 3 < 3 < 4 < 12signaling speed

Approx. signal transfer delay **) ms 48 35 26 20 15 10 4,5 3,5 2,5

Approx. operate delays of level monitor (PÜ)**)ms 30 23 15 12 7.5 6.5 2.5 2.0 1.5

Number ofchannels in a frequencyband of 0.3 bis 7.2 76 57 38 28 19 14 8 4 2

KS 2000i direct supply

Technical data

Maximum deviation of VFT frequencies Hz ± 0.1

Frequency range kHz 0.3...7.2

Raster of adjustable channelmid-frequencies Hz 30

Maximum deviation of send level dB ± 0.5referred to set value

Operating range of receiver,referred to nominal channel level dBr –20...+ 10

Send level adjustment in 2 dB steps referred dBr –22...+ 18to nominal level

Display of receive level referred, to nominal channel level 8 V at RL socket, in accordance with 0 dBr

Threshold value of receiverlevel monitor dBr adjustable from –25…–10 in steps of 1 dBreferred to nominal level

Threshold value of signalmonitor (SÜ), adjustable in steps,in accordance with telegraphic distortion of % ca. 20, 30

Neutral setting automaticallysets 1:1 signaling, initializedvia pushbutton in range % ± 25

The relevant ITU-T recommendations apply to FM 120, FM 240,and FM 480 systems

*) Please observe level control for multi-channel operation**) Receive filter without increased suppression loss

Power supply for the entire inputvoltage range

Only two power supply modules arerequired for the entire input voltagerange of 24–60 V DC or 110–220 V DCand 110–230 V AC.

One power supply module is requiredfor the following input voltage range:24/48/60 V DC.

The second power supply module isused for the following input voltagerange: 110–220 DC and 110–230 V AC.

KS 2000i Channel Unit for batteryconnection

On request, the KS 2000i Channel Unitcan be equipped with a voltage regula-tor for connection to a 24–60 V battery.In order to prevent interference withadjacent system components, thevoltage regulator is radio-interference-suppressed to Class B.

In addition to the system featuresdescribed above, the FWT 2000iSystem provides all users with thecost-effective and technical benefitsexpected and required when thissystem is used.

• An economical stocking of spare partsis possible since only one module is needed for all rates and frequencies.

• The system can be placed in servicequickly and easily thanks to automaticlevel adjustment and automatic com-pensation of distortion.

• The use of the latest digital processorsand components ensures that thesystem will have a long service life and a high rate of availability.

Page 9: Power Network Telecommunication FWT 2000i€¦ ·  · 2009-09-09Power Network Telecommunication FWT 2000i System for Telecontrol and Data Transmission ... railway companies and refineries,

98

+/– 12 V24 V DC48 / 60 V DC

KS 2000i

S

E

Optimal security and reliability

Users’ demands for operationalsecurity and reliability are met by thefollowing special features of theFWT 2000i System:

• The effects of temperature and aging are practically eliminated by the use ofdigital signal processors.

• The power supply concept permits secondary voltages of ± 12 V from twopower supply units to be connectedin parallel.

• The power supply units can also be fedwith different primary voltages.

• The receiver unit monitors the level and the signal-to-noise ratio.When transmission ratios worsen,a prealarm is activated.

• When there is no guarantee of data security, the output is applied tocontinuous potential, thus preventingthe system from outputting incorrect data.

• The local circuit to the VFT transmitteris monitored for interruptions. In the event of an interruption, the receiver isset to continuous polarity in order to prevent the output of incorrect data.

• Voltage-carrying modules can beinserted and removed, thus permittingall the other modules to remainin operation.

• The secondary voltage can be suppliedto the alternative path switchingmodule from two power supply units.

50 Bd 50 Bd 100 Bd 100 Bd 200 Bd 200 Bd 600 Bd 1200Bd 2400BdSB FM 120 SB FM 240 SB FM 480

Nominal signaling speed Bd 50 50 100 100 200 200 600 1200 2400

Maximum signaling speed Bd 50 75 100 150 200 300 600 1200 2400

Frequency shift Hz ± 22.5 ± 30 ± 45 ± 60 ± 90 ± 120 ± 200 ± 400 ± 800

Send/receive level, nominal, value per channel dBm – 24.5 – 22.5 – 21.5 – 19.5 – 18.5 – 16.5 – 13.5 – 10.5 – 7.5

Minimum frequency band width Hz 90 120 180 240 360 480 1100 1700 3100

Inherent distortion (text)for nominal % < 4 < 3 < 4 < 3 < 4 < 3 < 3 < 4 < 12signaling speed

Approx. signal transfer delay **) ms 48 35 26 20 15 10 4,5 3,5 2,5

Approx. operate delays of level monitor (PÜ)**)ms 30 23 15 12 7.5 6.5 2.5 2.0 1.5

Number ofchannels in a frequencyband of 0.3 bis 7.2 76 57 38 28 19 14 8 4 2

KS 2000i direct supply

Technical data

Maximum deviation of VFT frequencies Hz ± 0.1

Frequency range kHz 0.3...7.2

Raster of adjustable channelmid-frequencies Hz 30

Maximum deviation of send level dB ± 0.5referred to set value

Operating range of receiver,referred to nominal channel level dBr –20...+ 10

Send level adjustment in 2 dB steps referred dBr –22...+ 18to nominal level

Display of receive level referred, to nominal channel level 8 V at RL socket, in accordance with 0 dBr

Threshold value of receiverlevel monitor dBr adjustable from –25…–10 in steps of 1 dBreferred to nominal level

Threshold value of signalmonitor (SÜ), adjustable in steps,in accordance with telegraphic distortion of % ca. 20, 30

Neutral setting automaticallysets 1:1 signaling, initializedvia pushbutton in range % ± 25

The relevant ITU-T recommendations apply to FM 120, FM 240,and FM 480 systems

*) Please observe level control for multi-channel operation**) Receive filter without increased suppression loss

Power supply for the entire inputvoltage range

Only two power supply modules arerequired for the entire input voltagerange of 24–60 V DC or 110–220 V DCand 110–230 V AC.

One power supply module is requiredfor the following input voltage range:24/48/60 V DC.

The second power supply module isused for the following input voltagerange: 110–220 DC and 110–230 V AC.

KS 2000i Channel Unit for batteryconnection

On request, the KS 2000i Channel Unitcan be equipped with a voltage regula-tor for connection to a 24–60 V battery.In order to prevent interference withadjacent system components, thevoltage regulator is radio-interference-suppressed to Class B.

In addition to the system featuresdescribed above, the FWT 2000iSystem provides all users with thecost-effective and technical benefitsexpected and required when thissystem is used.

• An economical stocking of spare partsis possible since only one module is needed for all rates and frequencies.

• The system can be placed in servicequickly and easily thanks to automaticlevel adjustment and automatic com-pensation of distortion.

• The use of the latest digital processorsand components ensures that thesystem will have a long service life and a high rate of availability.

Page 10: Power Network Telecommunication FWT 2000i€¦ ·  · 2009-09-09Power Network Telecommunication FWT 2000i System for Telecontrol and Data Transmission ... railway companies and refineries,

1110

Order specifications for FWT 2000i to MLFBAll sections of the order specificationform must be filled out to orderan assembled FWT 2000i System

Power supply

Alarms

Design

Environmental conditions

Permissible ambient temperature – 5 °C to +55 °CRelative humidity 5 to 95 %Maximum absolute humidity 29 g/m

3

Formation of condensation not permissibleClimatogram as per IEC 721-3-3Permissible ambient temperatureduring transport and storage as per IEC 721-3-1 –40 °C to +70 °C

General alarmLocal circuit monitor for transmitter and recieverLevel monitor for transmitter and receiverSignal monitor (S/N) in receiverOperating voltages monitorAlarms displayed via LED, alarms rerouted viaV.28 interface or floating contact

Plug-in module for regulatedoperating voltages (± 12 V)Primary voltage for type N 90 to 370 V DC

85 to 260 V ACPrimary voltage for type B 14 to 70 V DCMaximum power consumptionon the primary side 60 VAPlug-in module for interfacevoltages (± 26 V)Supply from operating voltages, secondary voltages (± 26 V) isolatedThe plug-in modules for operating voltages can beduplicated (redundancy)

Data interfaces

Long-distance line connection

Connection to 2- or 4-wire linesConnection impedance (Z) balanced 600 Ω at 1 kHz

> 100 kΩ (waystation operation mode)at 1 kHz

Termination hybridCable frequency can be compensatedUnbalance loss (0,3...3.4 kHz) > 45 dBReturn loss (0,3...3.4 kHz) > 30 dBTransient protection

Incoming data Isolated data sink with -V.28 or20 V/20 mA interface

Outgoing data Data source V.28 or20 V/20 mA interface

Isolation possible

Order number: 7VR60

6 7 8 109 11 12 13 14 15 16 17

Without power supply module 024–60 V DC without module +/–26 V 1110–220VDC, 115–230VAC without module +/–26V 2red. power supply module 24–60 VDC without module +/– 26 V 3red. power supply module 110–220VDC, 115–230VAC without module. +/–26V 424-60 V DC with module +/–26 V 5110–220VDC, 115–230VAC with module +/–26V 6wiring no / test unit no 0wiring no / test unit yes 1wiring yes / test unit no 2wiring yes / test unit yes 3

–Without alternative path switching 01xZWU 12xZWU 23xZWU 34xZWU 45xZWU 5Without channel unit A1xKS B2xKS C3xKS D4xKS E5xKS F6xKS G7xKS H8xKS J9xKS K10xKS LWithout SEU A X1xSEU B2xSEU C3xSEU D4xSEU E5xSEU F6xSEU G7xSEU H8xSEU J9xSEU K10xSEU LWithout amplifier 0 X1xV 12xV 23xV 34xV 45xV 5For future use 0 X

–For future use 0 XWithout transmitter A X1xS B2xS C3xS D4xS E5xS F6xS G7xS H8xS J9xS K10xS LWithout receiver A X1xE B2xE C3xE D4xE E5xE F6xE G7xE H8xE J9xE K10xE LWithout TRU 0 X1xTRU 12xTRU 23xTRU 3

Order dataX– –

84TE=426.72

14482.6

1

7

465.1

240

132

132

37.4

57.1

5

Page 11: Power Network Telecommunication FWT 2000i€¦ ·  · 2009-09-09Power Network Telecommunication FWT 2000i System for Telecontrol and Data Transmission ... railway companies and refineries,

1110

Order specifications for FWT 2000i to MLFBAll sections of the order specificationform must be filled out to orderan assembled FWT 2000i System

Power supply

Alarms

Design

Environmental conditions

Permissible ambient temperature – 5 °C to +55 °CRelative humidity 5 to 95 %Maximum absolute humidity 29 g/m

3

Formation of condensation not permissibleClimatogram as per IEC 721-3-3Permissible ambient temperatureduring transport and storage as per IEC 721-3-1 –40 °C to +70 °C

General alarmLocal circuit monitor for transmitter and recieverLevel monitor for transmitter and receiverSignal monitor (S/N) in receiverOperating voltages monitorAlarms displayed via LED, alarms rerouted viaV.28 interface or floating contact

Plug-in module for regulatedoperating voltages (± 12 V)Primary voltage for type N 90 to 370 V DC

85 to 260 V ACPrimary voltage for type B 14 to 70 V DCMaximum power consumptionon the primary side 60 VAPlug-in module for interfacevoltages (± 26 V)Supply from operating voltages, secondary voltages (± 26 V) isolatedThe plug-in modules for operating voltages can beduplicated (redundancy)

Data interfaces

Long-distance line connection

Connection to 2- or 4-wire linesConnection impedance (Z) balanced 600 Ω at 1 kHz

> 100 kΩ (waystation operation mode)at 1 kHz

Termination hybridCable frequency can be compensatedUnbalance loss (0,3...3.4 kHz) > 45 dBReturn loss (0,3...3.4 kHz) > 30 dBTransient protection

Incoming data Isolated data sink with -V.28 or20 V/20 mA interface

Outgoing data Data source V.28 or20 V/20 mA interface

Isolation possible

Order number: 7VR60

6 7 8 109 11 12 13 14 15 16 17

Without power supply module 024–60 V DC without module +/–26 V 1110–220VDC, 115–230VAC without module +/–26V 2red. power supply module 24–60 VDC without module +/– 26 V 3red. power supply module 110–220VDC, 115–230VAC without module. +/–26V 424-60 V DC with module +/–26 V 5110–220VDC, 115–230VAC with module +/–26V 6wiring no / test unit no 0wiring no / test unit yes 1wiring yes / test unit no 2wiring yes / test unit yes 3

–Without alternative path switching 01xZWU 12xZWU 23xZWU 34xZWU 45xZWU 5Without channel unit A1xKS B2xKS C3xKS D4xKS E5xKS F6xKS G7xKS H8xKS J9xKS K10xKS LWithout SEU A X1xSEU B2xSEU C3xSEU D4xSEU E5xSEU F6xSEU G7xSEU H8xSEU J9xSEU K10xSEU LWithout amplifier 0 X1xV 12xV 23xV 34xV 45xV 5For future use 0 X

–For future use 0 XWithout transmitter A X1xS B2xS C3xS D4xS E5xS F6xS G7xS H8xS J9xS K10xS LWithout receiver A X1xE B2xE C3xE D4xE E5xE F6xE G7xE H8xE J9xE K10xE LWithout TRU 0 X1xTRU 12xTRU 23xTRU 3

Order dataX– –

84TE=426.72

14482.6

1

7

465.1

240

132

132

37.4

57.1

5

Page 12: Power Network Telecommunication FWT 2000i€¦ ·  · 2009-09-09Power Network Telecommunication FWT 2000i System for Telecontrol and Data Transmission ... railway companies and refineries,

Power Network TelecommunicationFWT 2000i – System for Telecontrol and Data Transmission