FWT 2000i –a modular, flexible system for telecontroland data transmission
In all areas related to the telemonitor-ing of systems, automation technologyand the control of decentralizedequipment, it is necessary to transmitsignals and measured values economi-cally and reliably.
The new FWT 2000i System for Tele-control and Data Transmission can beflexibly used to perform the varioustransmission tasks involved in systemmanagement not only in public utilitycompanies, railway companies andrefineries, but also in the areas ofenvironmental protection and civildefense, as well as in hydrographic andmeteorological services.
The following characteristics of theFWT 2000i System make it suitable formeeting users‘ special requirements:
• Safe operating method around high-voltage systems;
• High degree of reliability and security;
• Short process cycle times;
• Easy handling;
• Economical use.
32
FWT 2000i –a modular, flexible system for telecontroland data transmission
In all areas related to the telemonitor-ing of systems, automation technologyand the control of decentralizedequipment, it is necessary to transmitsignals and measured values economi-cally and reliably.
The new FWT 2000i System for Tele-control and Data Transmission can beflexibly used to perform the varioustransmission tasks involved in systemmanagement not only in public utilitycompanies, railway companies andrefineries, but also in the areas ofenvironmental protection and civildefense, as well as in hydrographic andmeteorological services.
The following characteristics of theFWT 2000i System make it suitable formeeting users‘ special requirements:
• Safe operating method around high-voltage systems;
• High degree of reliability and security;
• Short process cycle times;
• Easy handling;
• Economical use.
FWT 2000i frequency raster
2400 Bd+/– 800 Hz
300 Hz 7200 Hz
1200 Bd+/– 400 Hz
600 Bd+/– 200 Hz
200 Bd+/– 120 Hz
200 Bd+/– 90 Hz
100 Bd+/– 60 Hz
100 Bd+/– 45 Hz
50 Bd+/– 30 Hz
50 Bd+/– 22,5 Hz
Adjustable in 30 Hz raster from300-7200 Hz = n adjustment options
n = 108n = 108
n = 168
n = 190
n = 201
n = 204
n = 209
n = 210
n = 212
n = 213
Example:
max. number of channels in thefrequency range 0.3–3.4 kHz basedon the 30-Hz frequency raster
50 Bd SB 33 channels
50 Bd FM 120 25 channels
100 Bd SB 12 (13) channels
100 Bd FM 240 17 channels
200 Bd SB 8 channels
200 Bd FM 480 6 channels
600 Bd 2 channels
1200 Bd 1 channel
54
System characteristics:
Flexibility
The FWT 2000i System offers a varietyof modules for the widest possiblerange of transmission tasks. Thanks tothe unlimited equipping options of theframe, virtually all system variantsnecessary for operation can be imple-mented on a customer-specific basis.
Integration in other systems
The modularity of the KS 2000i ChannelUnit is typified by its integration invarious other systems, i.e. its use is notlimited to the FWT 2000i System.
For instance, the channel unit can beintegrated in:
• The PLC-System ESB 2000i;
• The Teleprotection Signaling System SWT 2000 F6;
• Telecontrol systems.
This modularity is possible only becauseall functions have been integrated onone module and a number of differentsupply voltages are possible.
Quick and easy fault location
Fault location is guaranteed to be quickand easy thanks to facilities such as the:
• Local circuit monitors for transmitter and receiver;
• Level monitor for transmitter andreceiver;
• Useful signal level monitor;
• Test code generator;
• Mode selector switch.
Transmitter and receiver as separatemodules
In many cases, users simply require atransmitter in Station A and a receiverin Station B for unidirectional connec-tions. Separate modules that functiononly as a receiver or only as a transmitterare available for this operating method.
Universal for all frequencies andtransmission rates of up to 2400 baud
The basic module of the FWT 2000iSystem is the KS 2000i Channel Unit.It accommodates a complete trans-mitter and receiver assembly.
The KS 2000i Channel Unit is of univer-sal application. All transmission ratesfrom 50 to 2400 baud can be set in allfrequencies within the 30-Hz raster,including in the frequency raster toITU-T.
Transmission in the superimposedfrequency band
The FWT 2000i System permits trans-mission in the frequency range from300 to 7200 Hz.
A second band can thus be used oncable runs along with the normal voiceband from 300 to 3400 Hz. The samechannel assignment is possible in thissuperimposed frequency band as in thebasic frequency band.
Optimization of transmissioncapacity
The transmission capacity of the FWT2000i System can be further increasedby setting up narrow-band channels.
The improved transmission character-istics result in distortion values fornarrow-band channels that are lowerthan the distortion values for broad-bandchannels in older systems, thusachieving optimal transmission quality.
FWT 2000i frequency raster
2400 Bd+/– 800 Hz
300 Hz 7200 Hz
1200 Bd+/– 400 Hz
600 Bd+/– 200 Hz
200 Bd+/– 120 Hz
200 Bd+/– 90 Hz
100 Bd+/– 60 Hz
100 Bd+/– 45 Hz
50 Bd+/– 30 Hz
50 Bd+/– 22,5 Hz
Adjustable in 30 Hz raster from300-7200 Hz = n adjustment options
n = 108n = 108
n = 168
n = 190
n = 201
n = 204
n = 209
n = 210
n = 212
n = 213
Example:
max. number of channels in thefrequency range 0.3–3.4 kHz basedon the 30-Hz frequency raster
50 Bd SB 33 channels
50 Bd FM 120 25 channels
100 Bd SB 12 (13) channels
100 Bd FM 240 17 channels
200 Bd SB 8 channels
200 Bd FM 480 6 channels
600 Bd 2 channels
1200 Bd 1 channel
54
System characteristics:
Flexibility
The FWT 2000i System offers a varietyof modules for the widest possiblerange of transmission tasks. Thanks tothe unlimited equipping options of theframe, virtually all system variantsnecessary for operation can be imple-mented on a customer-specific basis.
Integration in other systems
The modularity of the KS 2000i ChannelUnit is typified by its integration invarious other systems, i.e. its use is notlimited to the FWT 2000i System.
For instance, the channel unit can beintegrated in:
• The PLC-System ESB 2000i;
• The Teleprotection Signaling System SWT 2000 F6;
• Telecontrol systems.
This modularity is possible only becauseall functions have been integrated onone module and a number of differentsupply voltages are possible.
Quick and easy fault location
Fault location is guaranteed to be quickand easy thanks to facilities such as the:
• Local circuit monitors for transmitter and receiver;
• Level monitor for transmitter andreceiver;
• Useful signal level monitor;
• Test code generator;
• Mode selector switch.
Transmitter and receiver as separatemodules
In many cases, users simply require atransmitter in Station A and a receiverin Station B for unidirectional connec-tions. Separate modules that functiononly as a receiver or only as a transmitterare available for this operating method.
Universal for all frequencies andtransmission rates of up to 2400 baud
The basic module of the FWT 2000iSystem is the KS 2000i Channel Unit.It accommodates a complete trans-mitter and receiver assembly.
The KS 2000i Channel Unit is of univer-sal application. All transmission ratesfrom 50 to 2400 baud can be set in allfrequencies within the 30-Hz raster,including in the frequency raster toITU-T.
Transmission in the superimposedfrequency band
The FWT 2000i System permits trans-mission in the frequency range from300 to 7200 Hz.
A second band can thus be used oncable runs along with the normal voiceband from 300 to 3400 Hz. The samechannel assignment is possible in thissuperimposed frequency band as in thebasic frequency band.
Optimization of transmissioncapacity
The transmission capacity of the FWT2000i System can be further increasedby setting up narrow-band channels.
The improved transmission character-istics result in distortion values fornarrow-band channels that are lowerthan the distortion values for broad-bandchannels in older systems, thusachieving optimal transmission quality.
76
( ) ( )
I
II
I
II
I
II
I
II
Alternative path switching
For the transmission of important data,transmission paths are frequently dupli-cated. On the send side, the signal isapplied to two paths. On the receiveside, switchover from the main path tothe standby path takes place in theevent of a fault. This function is per-formed by the alternative path switchingmodule (ZWU).
The system’s internal switchover criteriaare the:
• Receive level;
• Signal-to-noise ratio.
Either of these criteria alone or the twotogether can result in switchover.Users can determine the switchoverthreshold within a wide range.In addition to the system’s internalswitchover criteria, switchover can alsobe controlled externally, e.g. by thetelecontrol unit.
The alternative path switching modulepermits the selection of line (LU) orchannel (KU) switchover. Transmissionpath priority is determined by means ofa front connector.
Control frequency transmission formulti-station control systems
The audio-frequency multi-stationcontrol system is a special type of tele-control system. It is used, for example,for changing meter rates and for con-trolling street and traffic lights.
The audio-frequency multi-stationcontrol converter (TRU) converts thecontrol frequency signals for transmit-ting the multi-station control frequency.The signal is output on a VFT transmittervia a V.28 interface. In this way, thecontrol frequency is routed to the cor-responding station using a minimum offrequency space. A VFT receiver routesthe control frequency signal to the TRUreceiver unit, which contains a controlfrequency filter. This filter greatlyreduces the jittering that interfereswith multi-station control. Thus, acontrol frequency of the best possiblequality is supplied to the multi-stationcontrol command unit in the substation.
ZWU, lineswitchover
ZWU, channel switchover
Data transmission in the voice bandwith SEU 2000i
The SEU 2000i module comprises atransmitter and receiver for transmittinga data channel via a 2-wire or 4-wire linein the voice band from 300 to 3400 Hz.Due to the fact that signal processingis less complex, this module offers aneconomical alternative in cases whereflexibility is limited.
The SEU 2000i module is identical tothe KS 2000i Channel Unit.Since the pin assignment is the same,the SEU 2000i can be installedwherever a KS 2000i can be installed(e.g. adapter module in telecontrolunits).
In contrast to the KS 2000i, only 4 fre-quencies can be set on the SEU 2000i.The first two frequencies are identicalto those of the earlier SEU A,B/STmodules. The second frequency pairmakes it possible to transmit a1200 baud duplex channel via a two-wire cable connection.
The SEU 2000i was designed with aview to possible advantages for users,including economical system manage-ment, transmission security andreliability and short process cycletimes, as well as easy handling.
Compatibility
The FWT 2000i System is fully com-patible with the predecessor systemFWT 2000 and can be operated withother VFT systems.
• The FWT 2000i modules also operatein the module frames of theFWT 2000 System.
• The modules of the old FWT 2000 System also operate in the module frames of the new FWT 2000iSystem.
• The KS 2000i Channel Unit can be installed in any module adapter in which the KS 2000 can be installed.
• The SEU 2000i can be installed in anymodule adapter in which the KS 2000ior KS 2000 can be installed.
• Due to its flexible setting options, theKS 2000i Channel Unit operates in conjunction with all VFT systems.
V
KU1
KU1
K1
K2
KU2
KU2W II
SP
UM
SÜ II
PÜ II
SÜ I
PÜ I
Eü
E
SZWU/LU
KS
Controlfrequency
TRU S
S
E
Data
Data
TRUE
S
E
Schematic scheme of control frequency transmission
Integrated controlfrequency filter
KU1
KU1
W II
SP
UM
SÜ II
PÜ II
SÜ I
PÜ I
ZWU/LU
E
S
KS
E
S
KS
K1
K2
KU2
KU2
76
( ) ( )
I
II
I
II
I
II
I
II
Alternative path switching
For the transmission of important data,transmission paths are frequently dupli-cated. On the send side, the signal isapplied to two paths. On the receiveside, switchover from the main path tothe standby path takes place in theevent of a fault. This function is per-formed by the alternative path switchingmodule (ZWU).
The system’s internal switchover criteriaare the:
• Receive level;
• Signal-to-noise ratio.
Either of these criteria alone or the twotogether can result in switchover.Users can determine the switchoverthreshold within a wide range.In addition to the system’s internalswitchover criteria, switchover can alsobe controlled externally, e.g. by thetelecontrol unit.
The alternative path switching modulepermits the selection of line (LU) orchannel (KU) switchover. Transmissionpath priority is determined by means ofa front connector.
Control frequency transmission formulti-station control systems
The audio-frequency multi-stationcontrol system is a special type of tele-control system. It is used, for example,for changing meter rates and for con-trolling street and traffic lights.
The audio-frequency multi-stationcontrol converter (TRU) converts thecontrol frequency signals for transmit-ting the multi-station control frequency.The signal is output on a VFT transmittervia a V.28 interface. In this way, thecontrol frequency is routed to the cor-responding station using a minimum offrequency space. A VFT receiver routesthe control frequency signal to the TRUreceiver unit, which contains a controlfrequency filter. This filter greatlyreduces the jittering that interfereswith multi-station control. Thus, acontrol frequency of the best possiblequality is supplied to the multi-stationcontrol command unit in the substation.
ZWU, lineswitchover
ZWU, channel switchover
Data transmission in the voice bandwith SEU 2000i
The SEU 2000i module comprises atransmitter and receiver for transmittinga data channel via a 2-wire or 4-wire linein the voice band from 300 to 3400 Hz.Due to the fact that signal processingis less complex, this module offers aneconomical alternative in cases whereflexibility is limited.
The SEU 2000i module is identical tothe KS 2000i Channel Unit.Since the pin assignment is the same,the SEU 2000i can be installedwherever a KS 2000i can be installed(e.g. adapter module in telecontrolunits).
In contrast to the KS 2000i, only 4 fre-quencies can be set on the SEU 2000i.The first two frequencies are identicalto those of the earlier SEU A,B/STmodules. The second frequency pairmakes it possible to transmit a1200 baud duplex channel via a two-wire cable connection.
The SEU 2000i was designed with aview to possible advantages for users,including economical system manage-ment, transmission security andreliability and short process cycletimes, as well as easy handling.
Compatibility
The FWT 2000i System is fully com-patible with the predecessor systemFWT 2000 and can be operated withother VFT systems.
• The FWT 2000i modules also operatein the module frames of theFWT 2000 System.
• The modules of the old FWT 2000 System also operate in the module frames of the new FWT 2000iSystem.
• The KS 2000i Channel Unit can be installed in any module adapter in which the KS 2000 can be installed.
• The SEU 2000i can be installed in anymodule adapter in which the KS 2000ior KS 2000 can be installed.
• Due to its flexible setting options, theKS 2000i Channel Unit operates in conjunction with all VFT systems.
V
KU1
KU1
K1
K2
KU2
KU2W II
SP
UM
SÜ II
PÜ II
SÜ I
PÜ I
Eü
E
SZWU/LU
KS
Controlfrequency
TRU S
S
E
Data
Data
TRUE
S
E
Schematic scheme of control frequency transmission
Integrated controlfrequency filter
KU1
KU1
W II
SP
UM
SÜ II
PÜ II
SÜ I
PÜ I
ZWU/LU
E
S
KS
E
S
KS
K1
K2
KU2
KU2
98
+/– 12 V24 V DC48 / 60 V DC
KS 2000i
S
E
Optimal security and reliability
Users’ demands for operationalsecurity and reliability are met by thefollowing special features of theFWT 2000i System:
• The effects of temperature and aging are practically eliminated by the use ofdigital signal processors.
• The power supply concept permits secondary voltages of ± 12 V from twopower supply units to be connectedin parallel.
• The power supply units can also be fedwith different primary voltages.
• The receiver unit monitors the level and the signal-to-noise ratio.When transmission ratios worsen,a prealarm is activated.
• When there is no guarantee of data security, the output is applied tocontinuous potential, thus preventingthe system from outputting incorrect data.
• The local circuit to the VFT transmitteris monitored for interruptions. In the event of an interruption, the receiver isset to continuous polarity in order to prevent the output of incorrect data.
• Voltage-carrying modules can beinserted and removed, thus permittingall the other modules to remainin operation.
• The secondary voltage can be suppliedto the alternative path switchingmodule from two power supply units.
50 Bd 50 Bd 100 Bd 100 Bd 200 Bd 200 Bd 600 Bd 1200Bd 2400BdSB FM 120 SB FM 240 SB FM 480
Nominal signaling speed Bd 50 50 100 100 200 200 600 1200 2400
Maximum signaling speed Bd 50 75 100 150 200 300 600 1200 2400
Frequency shift Hz ± 22.5 ± 30 ± 45 ± 60 ± 90 ± 120 ± 200 ± 400 ± 800
Send/receive level, nominal, value per channel dBm – 24.5 – 22.5 – 21.5 – 19.5 – 18.5 – 16.5 – 13.5 – 10.5 – 7.5
Minimum frequency band width Hz 90 120 180 240 360 480 1100 1700 3100
Inherent distortion (text)for nominal % < 4 < 3 < 4 < 3 < 4 < 3 < 3 < 4 < 12signaling speed
Approx. signal transfer delay **) ms 48 35 26 20 15 10 4,5 3,5 2,5
Approx. operate delays of level monitor (PÜ)**)ms 30 23 15 12 7.5 6.5 2.5 2.0 1.5
Number ofchannels in a frequencyband of 0.3 bis 7.2 76 57 38 28 19 14 8 4 2
KS 2000i direct supply
Technical data
Maximum deviation of VFT frequencies Hz ± 0.1
Frequency range kHz 0.3...7.2
Raster of adjustable channelmid-frequencies Hz 30
Maximum deviation of send level dB ± 0.5referred to set value
Operating range of receiver,referred to nominal channel level dBr –20...+ 10
Send level adjustment in 2 dB steps referred dBr –22...+ 18to nominal level
Display of receive level referred, to nominal channel level 8 V at RL socket, in accordance with 0 dBr
Threshold value of receiverlevel monitor dBr adjustable from –25…–10 in steps of 1 dBreferred to nominal level
Threshold value of signalmonitor (SÜ), adjustable in steps,in accordance with telegraphic distortion of % ca. 20, 30
Neutral setting automaticallysets 1:1 signaling, initializedvia pushbutton in range % ± 25
The relevant ITU-T recommendations apply to FM 120, FM 240,and FM 480 systems
*) Please observe level control for multi-channel operation**) Receive filter without increased suppression loss
Power supply for the entire inputvoltage range
Only two power supply modules arerequired for the entire input voltagerange of 24–60 V DC or 110–220 V DCand 110–230 V AC.
One power supply module is requiredfor the following input voltage range:24/48/60 V DC.
The second power supply module isused for the following input voltagerange: 110–220 DC and 110–230 V AC.
KS 2000i Channel Unit for batteryconnection
On request, the KS 2000i Channel Unitcan be equipped with a voltage regula-tor for connection to a 24–60 V battery.In order to prevent interference withadjacent system components, thevoltage regulator is radio-interference-suppressed to Class B.
In addition to the system featuresdescribed above, the FWT 2000iSystem provides all users with thecost-effective and technical benefitsexpected and required when thissystem is used.
• An economical stocking of spare partsis possible since only one module is needed for all rates and frequencies.
• The system can be placed in servicequickly and easily thanks to automaticlevel adjustment and automatic com-pensation of distortion.
• The use of the latest digital processorsand components ensures that thesystem will have a long service life and a high rate of availability.
98
+/– 12 V24 V DC48 / 60 V DC
KS 2000i
S
E
Optimal security and reliability
Users’ demands for operationalsecurity and reliability are met by thefollowing special features of theFWT 2000i System:
• The effects of temperature and aging are practically eliminated by the use ofdigital signal processors.
• The power supply concept permits secondary voltages of ± 12 V from twopower supply units to be connectedin parallel.
• The power supply units can also be fedwith different primary voltages.
• The receiver unit monitors the level and the signal-to-noise ratio.When transmission ratios worsen,a prealarm is activated.
• When there is no guarantee of data security, the output is applied tocontinuous potential, thus preventingthe system from outputting incorrect data.
• The local circuit to the VFT transmitteris monitored for interruptions. In the event of an interruption, the receiver isset to continuous polarity in order to prevent the output of incorrect data.
• Voltage-carrying modules can beinserted and removed, thus permittingall the other modules to remainin operation.
• The secondary voltage can be suppliedto the alternative path switchingmodule from two power supply units.
50 Bd 50 Bd 100 Bd 100 Bd 200 Bd 200 Bd 600 Bd 1200Bd 2400BdSB FM 120 SB FM 240 SB FM 480
Nominal signaling speed Bd 50 50 100 100 200 200 600 1200 2400
Maximum signaling speed Bd 50 75 100 150 200 300 600 1200 2400
Frequency shift Hz ± 22.5 ± 30 ± 45 ± 60 ± 90 ± 120 ± 200 ± 400 ± 800
Send/receive level, nominal, value per channel dBm – 24.5 – 22.5 – 21.5 – 19.5 – 18.5 – 16.5 – 13.5 – 10.5 – 7.5
Minimum frequency band width Hz 90 120 180 240 360 480 1100 1700 3100
Inherent distortion (text)for nominal % < 4 < 3 < 4 < 3 < 4 < 3 < 3 < 4 < 12signaling speed
Approx. signal transfer delay **) ms 48 35 26 20 15 10 4,5 3,5 2,5
Approx. operate delays of level monitor (PÜ)**)ms 30 23 15 12 7.5 6.5 2.5 2.0 1.5
Number ofchannels in a frequencyband of 0.3 bis 7.2 76 57 38 28 19 14 8 4 2
KS 2000i direct supply
Technical data
Maximum deviation of VFT frequencies Hz ± 0.1
Frequency range kHz 0.3...7.2
Raster of adjustable channelmid-frequencies Hz 30
Maximum deviation of send level dB ± 0.5referred to set value
Operating range of receiver,referred to nominal channel level dBr –20...+ 10
Send level adjustment in 2 dB steps referred dBr –22...+ 18to nominal level
Display of receive level referred, to nominal channel level 8 V at RL socket, in accordance with 0 dBr
Threshold value of receiverlevel monitor dBr adjustable from –25…–10 in steps of 1 dBreferred to nominal level
Threshold value of signalmonitor (SÜ), adjustable in steps,in accordance with telegraphic distortion of % ca. 20, 30
Neutral setting automaticallysets 1:1 signaling, initializedvia pushbutton in range % ± 25
The relevant ITU-T recommendations apply to FM 120, FM 240,and FM 480 systems
*) Please observe level control for multi-channel operation**) Receive filter without increased suppression loss
Power supply for the entire inputvoltage range
Only two power supply modules arerequired for the entire input voltagerange of 24–60 V DC or 110–220 V DCand 110–230 V AC.
One power supply module is requiredfor the following input voltage range:24/48/60 V DC.
The second power supply module isused for the following input voltagerange: 110–220 DC and 110–230 V AC.
KS 2000i Channel Unit for batteryconnection
On request, the KS 2000i Channel Unitcan be equipped with a voltage regula-tor for connection to a 24–60 V battery.In order to prevent interference withadjacent system components, thevoltage regulator is radio-interference-suppressed to Class B.
In addition to the system featuresdescribed above, the FWT 2000iSystem provides all users with thecost-effective and technical benefitsexpected and required when thissystem is used.
• An economical stocking of spare partsis possible since only one module is needed for all rates and frequencies.
• The system can be placed in servicequickly and easily thanks to automaticlevel adjustment and automatic com-pensation of distortion.
• The use of the latest digital processorsand components ensures that thesystem will have a long service life and a high rate of availability.
1110
Order specifications for FWT 2000i to MLFBAll sections of the order specificationform must be filled out to orderan assembled FWT 2000i System
Power supply
Alarms
Design
Environmental conditions
Permissible ambient temperature – 5 °C to +55 °CRelative humidity 5 to 95 %Maximum absolute humidity 29 g/m
3
Formation of condensation not permissibleClimatogram as per IEC 721-3-3Permissible ambient temperatureduring transport and storage as per IEC 721-3-1 –40 °C to +70 °C
General alarmLocal circuit monitor for transmitter and recieverLevel monitor for transmitter and receiverSignal monitor (S/N) in receiverOperating voltages monitorAlarms displayed via LED, alarms rerouted viaV.28 interface or floating contact
Plug-in module for regulatedoperating voltages (± 12 V)Primary voltage for type N 90 to 370 V DC
85 to 260 V ACPrimary voltage for type B 14 to 70 V DCMaximum power consumptionon the primary side 60 VAPlug-in module for interfacevoltages (± 26 V)Supply from operating voltages, secondary voltages (± 26 V) isolatedThe plug-in modules for operating voltages can beduplicated (redundancy)
Data interfaces
Long-distance line connection
Connection to 2- or 4-wire linesConnection impedance (Z) balanced 600 Ω at 1 kHz
> 100 kΩ (waystation operation mode)at 1 kHz
Termination hybridCable frequency can be compensatedUnbalance loss (0,3...3.4 kHz) > 45 dBReturn loss (0,3...3.4 kHz) > 30 dBTransient protection
Incoming data Isolated data sink with -V.28 or20 V/20 mA interface
Outgoing data Data source V.28 or20 V/20 mA interface
Isolation possible
Order number: 7VR60
6 7 8 109 11 12 13 14 15 16 17
Without power supply module 024–60 V DC without module +/–26 V 1110–220VDC, 115–230VAC without module +/–26V 2red. power supply module 24–60 VDC without module +/– 26 V 3red. power supply module 110–220VDC, 115–230VAC without module. +/–26V 424-60 V DC with module +/–26 V 5110–220VDC, 115–230VAC with module +/–26V 6wiring no / test unit no 0wiring no / test unit yes 1wiring yes / test unit no 2wiring yes / test unit yes 3
–Without alternative path switching 01xZWU 12xZWU 23xZWU 34xZWU 45xZWU 5Without channel unit A1xKS B2xKS C3xKS D4xKS E5xKS F6xKS G7xKS H8xKS J9xKS K10xKS LWithout SEU A X1xSEU B2xSEU C3xSEU D4xSEU E5xSEU F6xSEU G7xSEU H8xSEU J9xSEU K10xSEU LWithout amplifier 0 X1xV 12xV 23xV 34xV 45xV 5For future use 0 X
–For future use 0 XWithout transmitter A X1xS B2xS C3xS D4xS E5xS F6xS G7xS H8xS J9xS K10xS LWithout receiver A X1xE B2xE C3xE D4xE E5xE F6xE G7xE H8xE J9xE K10xE LWithout TRU 0 X1xTRU 12xTRU 23xTRU 3
Order dataX– –
84TE=426.72
14482.6
1
7
465.1
240
132
132
37.4
57.1
5
1110
Order specifications for FWT 2000i to MLFBAll sections of the order specificationform must be filled out to orderan assembled FWT 2000i System
Power supply
Alarms
Design
Environmental conditions
Permissible ambient temperature – 5 °C to +55 °CRelative humidity 5 to 95 %Maximum absolute humidity 29 g/m
3
Formation of condensation not permissibleClimatogram as per IEC 721-3-3Permissible ambient temperatureduring transport and storage as per IEC 721-3-1 –40 °C to +70 °C
General alarmLocal circuit monitor for transmitter and recieverLevel monitor for transmitter and receiverSignal monitor (S/N) in receiverOperating voltages monitorAlarms displayed via LED, alarms rerouted viaV.28 interface or floating contact
Plug-in module for regulatedoperating voltages (± 12 V)Primary voltage for type N 90 to 370 V DC
85 to 260 V ACPrimary voltage for type B 14 to 70 V DCMaximum power consumptionon the primary side 60 VAPlug-in module for interfacevoltages (± 26 V)Supply from operating voltages, secondary voltages (± 26 V) isolatedThe plug-in modules for operating voltages can beduplicated (redundancy)
Data interfaces
Long-distance line connection
Connection to 2- or 4-wire linesConnection impedance (Z) balanced 600 Ω at 1 kHz
> 100 kΩ (waystation operation mode)at 1 kHz
Termination hybridCable frequency can be compensatedUnbalance loss (0,3...3.4 kHz) > 45 dBReturn loss (0,3...3.4 kHz) > 30 dBTransient protection
Incoming data Isolated data sink with -V.28 or20 V/20 mA interface
Outgoing data Data source V.28 or20 V/20 mA interface
Isolation possible
Order number: 7VR60
6 7 8 109 11 12 13 14 15 16 17
Without power supply module 024–60 V DC without module +/–26 V 1110–220VDC, 115–230VAC without module +/–26V 2red. power supply module 24–60 VDC without module +/– 26 V 3red. power supply module 110–220VDC, 115–230VAC without module. +/–26V 424-60 V DC with module +/–26 V 5110–220VDC, 115–230VAC with module +/–26V 6wiring no / test unit no 0wiring no / test unit yes 1wiring yes / test unit no 2wiring yes / test unit yes 3
–Without alternative path switching 01xZWU 12xZWU 23xZWU 34xZWU 45xZWU 5Without channel unit A1xKS B2xKS C3xKS D4xKS E5xKS F6xKS G7xKS H8xKS J9xKS K10xKS LWithout SEU A X1xSEU B2xSEU C3xSEU D4xSEU E5xSEU F6xSEU G7xSEU H8xSEU J9xSEU K10xSEU LWithout amplifier 0 X1xV 12xV 23xV 34xV 45xV 5For future use 0 X
–For future use 0 XWithout transmitter A X1xS B2xS C3xS D4xS E5xS F6xS G7xS H8xS J9xS K10xS LWithout receiver A X1xE B2xE C3xE D4xE E5xE F6xE G7xE H8xE J9xE K10xE LWithout TRU 0 X1xTRU 12xTRU 23xTRU 3
Order dataX– –
84TE=426.72
14482.6
1
7
465.1
240
132
132
37.4
57.1
5
Power Network TelecommunicationFWT 2000i – System for Telecontrol and Data Transmission
7 VR 56Power
to the
Siemens AGPower Transmission andDistribution GroupPower Systems andEnergy Management DivisionHofmannstrasse 51D-81359 Munich
www.ev.siemens.de
Siemens Aktiengesellschaft Order No.: E50001-U336-A18-X-7600Printed in GermanyDispo-Stelle 0640161U1279 WÜ 336502 PA 06972.5
Subject to change without prior notice