Ovation Controller OCR 400

Embed Size (px)

Citation preview

  • 7/22/2019 Ovation Controller OCR 400

    1/14

    Emerson Process Management Confidential 1

    Model OCR400 Controller.ControllerController

  • 7/22/2019 Ovation Controller OCR 400

    2/14

    2Emerson Process Management Confidential

    What do you get vs the OCR161What do you getWhat do you get vsvs the OCR161the OCR161z 50% speed improvement

    z 50mS Copy to Backup

    z Double RAM, Quadruple Flash

    z More integrated NIC ports

    z 60% Smaller Overall Package and Power Usage

    All without using fans

    z Greater Hardware I/O connectivity concurrently

    Local Ovation, Local Q Line and Remote Q or Ovation I/Oconcurrently

    z Same config tools, Same controls, Same database

  • 7/22/2019 Ovation Controller OCR 400

    3/14

    3Emerson Process Management Confidential

    Ovation Redundant ControllerOvation Redundant ControllerOvation Redundant Controllerz 1:1 functional replacement

    of existing controller 60% smaller DIN rail

    mountable package

    Same I/O interfacesz Same Control Builder and

    Developer Studioconfiguration Minimal controller

    configuration changes onlyz Control schemes, database,

    etc remain the same

    z Same Environmentalrequirements

    But without Fansz Same 24V Power scheme

    Processor

    Modules

    I/O Interface

    Modules

  • 7/22/2019 Ovation Controller OCR 400

    4/14

    4Emerson Process Management Confidential

    Processor ModuleProcessor ModuleProcessor Modulez Control Processor & Highway Interface

    400MHz Processor

    64MB expandable to 128MB DRAM

    128Mb Flash memory accessible undercap

    z 4 On Board Fast Ethernet Ports

    Network connections

    Fieldbus and 3rd Party virtual I/O devicecapability

    z Fits in an I/O module housing with newcap

    z Uses PCI to interconnect with the I/OInterface Module

    z LEDs for Power and 4 NICs

  • 7/22/2019 Ovation Controller OCR 400

    5/14

    5Emerson Process Management Confidential

    OCR400 Network ConnectionsOCR400 Network ConnectionsOCR400 Network Connections

    Ethernet 3rd Party Link #1 (Foundation Fieldbus*, Modbus/TCP,Profibus*, GE Mk V/VI, A-B DF1, etc)

    Ovation Network Connection #1

    Ovation Network #2 Connection or

    Ethernet 3rd Party Link #3

    50mS Copy to Backup or

    Ethernet 3rd Party Link #2

    * Not supported on Solaris 1.7

    Single Dual

    Attach

  • 7/22/2019 Ovation Controller OCR 400

    6/14

    6Emerson Process Management Confidential

    Hardwired and Virtual I/O DevicesHardwired and Virtual I/O DevicesHardwired and Virtual I/O Devicesz Controller supports 5 I/O Devices

    1 Hardwired I/O which includes redundancy

    All 5 can be virtual I/O devices

    z Hardwired I/O Device

    Single Device to handle all Hardwired I/O

    Connections made via Backplane and I/OInterface Module

    z Virtual I/O Device

    Up to 5 Devices used to handle each of theVirtual (3rd party) I/O Device types

    GE MkV/VI, Modbus, Ff, A-B, etc

    Connections made via Ethernet Ports

    z The same controller limits apply

    Approximately 2000 maximum field I/O pointsper Controller

    Virtual

    I/O

    Hardwired

    I/O

  • 7/22/2019 Ovation Controller OCR 400

    7/14

    7Emerson Process Management Confidential

    I/O Interface ModuleI/O Interface ModuleI/O Interface Modulez Provides internal power

    internal 12V, 5VDC from 24VDC

    z Interfaces to all hardwired I/O types

    Local Ovation I/O

    Remote Ovation I/O

    Local Q Line I/O

    Remote Q Line I/O

    z Local Ovation I/O connections arethe same as the current controller

    z Q Line and Remote I/O connectionsare via RJ45 ports on top of the

    module

    z Fits in an I/O module housing withnew cap

  • 7/22/2019 Ovation Controller OCR 400

    8/14

  • 7/22/2019 Ovation Controller OCR 400

    9/14

    9Emerson Process Management Confidential

    OCR400 Controller I/O ArchitecturesOCR400 Controller I/O ArchitecturesOCR400 Controller I/O ArchitecturesThe IO interface only deals with two types of interfacesLocal Ovation I/O andAUI connected I/O

    Ovation I/O Bus

    IOIC QOLQline

    I/OCTRL

    Local

    Q Line I/O

    DIOBAUI

    Remote

    Q Line I/OIOIC MAU QOR

    Qline

    I/OCTRL

    DIOBAUI FO

    IOIC MAU RNCOvation

    I/OCTRL

    Remote

    Ovation I/O

    AUI FO Ovation

    OvationI/O

    IOICCTRL LocalOvation I/O

    Ovation

    New OCR400 Migration Kit 5X00251

    New OCR400 Controller Kit 5X00247

    All other components are existing drawing numbers

    FO cable is supplied by the project

    Existing AUI & RNC components

    Ovation OCR400 I/O has the same

    drawing numbers and is

    fully interchangeable

    5X00230

    Existing AUI & RNC components

    5X00238

    5X00238

    5X00238

  • 7/22/2019 Ovation Controller OCR 400

    10/14

    10Emerson Process Management Confidential

    I/O Driver Types & I/O Device TypesI/O Driver Types & I/O Device TypesI/O Driver Types & I/O Device Typesz Hardwired I/O

    OVATION (I/O Driver) - Local Ovation, Remote Ovation, Local QLine, Remote Q Line (I/O Device)

    z 3rd Party I/O ALLEN BRADLEY - Allen Bradley PLC

    MODBUS - Modbus Master

    RTP IO - RTP IOBC6700

    GE MARK V/VI - GE Mark V, GE Mark VI

    EXTERNAL OVATION NETWORK - External Ovation Network

    MHI - MHI

    TOSHIBA - Toshiba

    FIELDBUS - Foundation Fieldbus

    GE Genius - GE Genius

    PROFIBUS - Profibus

  • 7/22/2019 Ovation Controller OCR 400

    11/14

    11Emerson Process Management Confidential

    I/O Driver Types & Simulator Driver TypesI/O Driver Types & Simulator Driver TypesI/O Driver Types & Simulator Driver Typesz Some valid combinations of an I/O Driver, and a Sim Driver

    z OVATION, NO ENTRY Ovation I/O used with no simulation points

    Standard configuration for controller

    z OVATION, OVATION Ovation I/O used with Ovation Points from Simulator Model

    Allows Mix and Match of Ovation Real I/O and Simulated I/O

    Controller expects to interface with a SimServer

    z NO ENTRY, FAKE Ovation I/O used with Ovation Points from same controller

    Model implemented in additional control sheets

    No SimServer involvement

    z MODBUS, OVATION (One of many unexpected combinations) Modbus I/O used with Ovation Points from Simulator Model

    Allows Mix and Match of Modbus I/O and Simulated I/O

    Controller expects to interface with a SimServer

  • 7/22/2019 Ovation Controller OCR 400

    12/14

    12Emerson Process Management Confidential

    Virtual I/O Device CapabilitiesVirtual I/O Device CapabilitiesVirtual I/O Device Capabilities

    881Profibus (Future)

    881GE Genius

    1616 (64

    segments)1Foundation Fieldbus

    111External Ovation Network

    221GE Mark V or GE Mark VI

    551RTP IOBC6700I/O

    515Toshiba

    515MHI

    2555Modbus Master

    2555Allen Bradley PLCSystems

    Max perController*

    Max AddressesPer Device

    Max DevicesDevice TypeType

    z Remember 1 Hardwired I/O Device is required for redundancy

    *This reduces the above Max per Controller numbers.

  • 7/22/2019 Ovation Controller OCR 400

    13/14

    13Emerson Process Management Confidential

    LED IndicationsLED IndicationsLED IndicationsPower OK

    Single Attach

    Backup Controller Primary Controller

    Power OK

    N1

    P

    N2

    N3

    N4

    Communication

    Qline I/ORemote I/O #2Remote I/O #1Local I/O 9-16Local I/O 1-8

    Error (Red)

    AliveBackup (Fl)

    PCmCtA

    EO1O2R3R4Q5

    Remote I/O #1Local I/O 9-16

    AlivePrimary (Solid)

    Power OKCommunication

    z 1 Red Error LED instead of 4 Char display

    z 5 Lowest LEDs cyclically indicate error code

  • 7/22/2019 Ovation Controller OCR 400

    14/14

    14Emerson Process Management Confidential

    Controller CapabilitiesController CapabilitiesController Capabilitiesz Lots of Hardwired I/O

    4778 Max

    z

    And Lots of Virtual I/O capability 2048 x 4 = 8192 Max

    z Plus Lots of ports & connections

    z

    Plus Lots of control sheets Multiplies Field I/O x 6, 8, or 10

    z However the maximum overalloriginated I/O point limit per

    controller is still

    16,000 points16,000 points