Upload
tufan-maity
View
701
Download
35
Embed Size (px)
Citation preview
7/22/2019 Ovation Controller OCR 400
1/14
Emerson Process Management Confidential 1
Model OCR400 Controller.ControllerController
7/22/2019 Ovation Controller OCR 400
2/14
2Emerson Process Management Confidential
What do you get vs the OCR161What do you getWhat do you get vsvs the OCR161the OCR161z 50% speed improvement
z 50mS Copy to Backup
z Double RAM, Quadruple Flash
z More integrated NIC ports
z 60% Smaller Overall Package and Power Usage
All without using fans
z Greater Hardware I/O connectivity concurrently
Local Ovation, Local Q Line and Remote Q or Ovation I/Oconcurrently
z Same config tools, Same controls, Same database
7/22/2019 Ovation Controller OCR 400
3/14
3Emerson Process Management Confidential
Ovation Redundant ControllerOvation Redundant ControllerOvation Redundant Controllerz 1:1 functional replacement
of existing controller 60% smaller DIN rail
mountable package
Same I/O interfacesz Same Control Builder and
Developer Studioconfiguration Minimal controller
configuration changes onlyz Control schemes, database,
etc remain the same
z Same Environmentalrequirements
But without Fansz Same 24V Power scheme
Processor
Modules
I/O Interface
Modules
7/22/2019 Ovation Controller OCR 400
4/14
4Emerson Process Management Confidential
Processor ModuleProcessor ModuleProcessor Modulez Control Processor & Highway Interface
400MHz Processor
64MB expandable to 128MB DRAM
128Mb Flash memory accessible undercap
z 4 On Board Fast Ethernet Ports
Network connections
Fieldbus and 3rd Party virtual I/O devicecapability
z Fits in an I/O module housing with newcap
z Uses PCI to interconnect with the I/OInterface Module
z LEDs for Power and 4 NICs
7/22/2019 Ovation Controller OCR 400
5/14
5Emerson Process Management Confidential
OCR400 Network ConnectionsOCR400 Network ConnectionsOCR400 Network Connections
Ethernet 3rd Party Link #1 (Foundation Fieldbus*, Modbus/TCP,Profibus*, GE Mk V/VI, A-B DF1, etc)
Ovation Network Connection #1
Ovation Network #2 Connection or
Ethernet 3rd Party Link #3
50mS Copy to Backup or
Ethernet 3rd Party Link #2
* Not supported on Solaris 1.7
Single Dual
Attach
7/22/2019 Ovation Controller OCR 400
6/14
6Emerson Process Management Confidential
Hardwired and Virtual I/O DevicesHardwired and Virtual I/O DevicesHardwired and Virtual I/O Devicesz Controller supports 5 I/O Devices
1 Hardwired I/O which includes redundancy
All 5 can be virtual I/O devices
z Hardwired I/O Device
Single Device to handle all Hardwired I/O
Connections made via Backplane and I/OInterface Module
z Virtual I/O Device
Up to 5 Devices used to handle each of theVirtual (3rd party) I/O Device types
GE MkV/VI, Modbus, Ff, A-B, etc
Connections made via Ethernet Ports
z The same controller limits apply
Approximately 2000 maximum field I/O pointsper Controller
Virtual
I/O
Hardwired
I/O
7/22/2019 Ovation Controller OCR 400
7/14
7Emerson Process Management Confidential
I/O Interface ModuleI/O Interface ModuleI/O Interface Modulez Provides internal power
internal 12V, 5VDC from 24VDC
z Interfaces to all hardwired I/O types
Local Ovation I/O
Remote Ovation I/O
Local Q Line I/O
Remote Q Line I/O
z Local Ovation I/O connections arethe same as the current controller
z Q Line and Remote I/O connectionsare via RJ45 ports on top of the
module
z Fits in an I/O module housing withnew cap
7/22/2019 Ovation Controller OCR 400
8/14
7/22/2019 Ovation Controller OCR 400
9/14
9Emerson Process Management Confidential
OCR400 Controller I/O ArchitecturesOCR400 Controller I/O ArchitecturesOCR400 Controller I/O ArchitecturesThe IO interface only deals with two types of interfacesLocal Ovation I/O andAUI connected I/O
Ovation I/O Bus
IOIC QOLQline
I/OCTRL
Local
Q Line I/O
DIOBAUI
Remote
Q Line I/OIOIC MAU QOR
Qline
I/OCTRL
DIOBAUI FO
IOIC MAU RNCOvation
I/OCTRL
Remote
Ovation I/O
AUI FO Ovation
OvationI/O
IOICCTRL LocalOvation I/O
Ovation
New OCR400 Migration Kit 5X00251
New OCR400 Controller Kit 5X00247
All other components are existing drawing numbers
FO cable is supplied by the project
Existing AUI & RNC components
Ovation OCR400 I/O has the same
drawing numbers and is
fully interchangeable
5X00230
Existing AUI & RNC components
5X00238
5X00238
5X00238
7/22/2019 Ovation Controller OCR 400
10/14
10Emerson Process Management Confidential
I/O Driver Types & I/O Device TypesI/O Driver Types & I/O Device TypesI/O Driver Types & I/O Device Typesz Hardwired I/O
OVATION (I/O Driver) - Local Ovation, Remote Ovation, Local QLine, Remote Q Line (I/O Device)
z 3rd Party I/O ALLEN BRADLEY - Allen Bradley PLC
MODBUS - Modbus Master
RTP IO - RTP IOBC6700
GE MARK V/VI - GE Mark V, GE Mark VI
EXTERNAL OVATION NETWORK - External Ovation Network
MHI - MHI
TOSHIBA - Toshiba
FIELDBUS - Foundation Fieldbus
GE Genius - GE Genius
PROFIBUS - Profibus
7/22/2019 Ovation Controller OCR 400
11/14
11Emerson Process Management Confidential
I/O Driver Types & Simulator Driver TypesI/O Driver Types & Simulator Driver TypesI/O Driver Types & Simulator Driver Typesz Some valid combinations of an I/O Driver, and a Sim Driver
z OVATION, NO ENTRY Ovation I/O used with no simulation points
Standard configuration for controller
z OVATION, OVATION Ovation I/O used with Ovation Points from Simulator Model
Allows Mix and Match of Ovation Real I/O and Simulated I/O
Controller expects to interface with a SimServer
z NO ENTRY, FAKE Ovation I/O used with Ovation Points from same controller
Model implemented in additional control sheets
No SimServer involvement
z MODBUS, OVATION (One of many unexpected combinations) Modbus I/O used with Ovation Points from Simulator Model
Allows Mix and Match of Modbus I/O and Simulated I/O
Controller expects to interface with a SimServer
7/22/2019 Ovation Controller OCR 400
12/14
12Emerson Process Management Confidential
Virtual I/O Device CapabilitiesVirtual I/O Device CapabilitiesVirtual I/O Device Capabilities
881Profibus (Future)
881GE Genius
1616 (64
segments)1Foundation Fieldbus
111External Ovation Network
221GE Mark V or GE Mark VI
551RTP IOBC6700I/O
515Toshiba
515MHI
2555Modbus Master
2555Allen Bradley PLCSystems
Max perController*
Max AddressesPer Device
Max DevicesDevice TypeType
z Remember 1 Hardwired I/O Device is required for redundancy
*This reduces the above Max per Controller numbers.
7/22/2019 Ovation Controller OCR 400
13/14
13Emerson Process Management Confidential
LED IndicationsLED IndicationsLED IndicationsPower OK
Single Attach
Backup Controller Primary Controller
Power OK
N1
P
N2
N3
N4
Communication
Qline I/ORemote I/O #2Remote I/O #1Local I/O 9-16Local I/O 1-8
Error (Red)
AliveBackup (Fl)
PCmCtA
EO1O2R3R4Q5
Remote I/O #1Local I/O 9-16
AlivePrimary (Solid)
Power OKCommunication
z 1 Red Error LED instead of 4 Char display
z 5 Lowest LEDs cyclically indicate error code
7/22/2019 Ovation Controller OCR 400
14/14
14Emerson Process Management Confidential
Controller CapabilitiesController CapabilitiesController Capabilitiesz Lots of Hardwired I/O
4778 Max
z
And Lots of Virtual I/O capability 2048 x 4 = 8192 Max
z Plus Lots of ports & connections
z
Plus Lots of control sheets Multiplies Field I/O x 6, 8, or 10
z However the maximum overalloriginated I/O point limit per
controller is still
16,000 points16,000 points