2
Main Features The DTI can collect information from up to 10 of each of the following Autoflame products: • Mk7 MM Controller, Mini Mk8 MM Controller, Mini Mk7 MM Controller, or any combination to a total of 10 units • Autoflame Exhaust Gas Analyser, either used in conjunction with an MM Controller for trim, or linked directly to the DTI for monitoring purposes only • Up to 10 Input/Output modules with both analogue and digital connections There are up to 150 items of information that are viewable via the DTI from each MM Controller & EGA. Overview The DTI (Data Transfer Interface) lets users know in real time how the boilers are performing, either on-site through its built-in touch screen, via a local PC, or via a BMS system. It stores data history of all boilers for 2 years. The DTI is a gateway for communicating with the Autoflame MM Controller/EGA range of products. The DTI can collect and store information from a maximum of 10 Autoflame Systems in one location. The information gathered is later available for transmission to an external source such as a BMS via RS422 or Ethernet links. The data gathered by the Autoflame DTI can be synchronised and viewed using the included CEMS (Continuous Emissions Monitoring) software, which allows data collection over a local network or over the internet. The Mk7 DTI also supports the Modbus protocol over ethernet and RS422 as standard. Touchscreen Mk7 DTI Monitor up to 10 Boilers Remotely Modbus/LAN/Remote Connectivity • Save Data for 2 Years BMS Local PC Up to 10 MM Controllers Up to 10 EGA’s Up to 10 I/O’s Typical Configuration DTI Mk7: Data Transfer Interface

Monitor up to 10 Boilers Remotely · 2018. 8. 8. · Main Features The DTI can collect information from up to 10 of each of the following Autoflame products: • Mk7 MM Controller,

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Monitor up to 10 Boilers Remotely · 2018. 8. 8. · Main Features The DTI can collect information from up to 10 of each of the following Autoflame products: • Mk7 MM Controller,

Main FeaturesThe DTI can collect information from up to 10 of each of the following Autoflame products:

•Mk7MMController,MiniMk8MMController,MiniMk7MMController,oranycombinationtoatotal of 10 units

•AutoflameExhaustGasAnalyser,eitherusedinconjunctionwithanMMControllerfortrim,orlinkeddirectlytotheDTIformonitoringpurposesonly

•Upto10Input/Outputmoduleswithbothanalogue and digital connections

There are up to 150 items of information that are viewableviatheDTIfromeachMMController&EGA.

OverviewTheDTI(DataTransferInterface)letsusersknowinrealtimehowtheboilersareperforming,eitheron-sitethroughitsbuilt-intouchscreen,viaalocalPC,orviaaBMSsystem.Itstoresdatahistoryofallboilersfor2years.

TheDTIisagatewayforcommunicatingwiththeAutoflameMMController/EGArangeofproducts.The DTI can collect and store information from a maximumof10AutoflameSystemsinonelocation.TheinformationgatheredislateravailablefortransmissiontoanexternalsourcesuchasaBMSviaRS422orEthernetlinks.ThedatagatheredbytheAutoflameDTIcanbesynchronisedandviewedusingtheincludedCEMS(ContinuousEmissionsMonitoring)software,whichallowsdatacollectionoveralocalnetworkorovertheinternet.TheMk7DTIalsosupportstheModbusprotocoloverethernetandRS422asstandard.

TouchscreenMk7DTI

Monitor up to 10 Boilers RemotelyModbus/LAN/RemoteConnectivity•SaveDatafor2Years

BMS LocalPC

Upto10MMControllers

Upto10EGA’s

Upto10I/O’s

TypicalConfiguration

DTIMk7:DataTransferInterface

Page 2: Monitor up to 10 Boilers Remotely · 2018. 8. 8. · Main Features The DTI can collect information from up to 10 of each of the following Autoflame products: • Mk7 MM Controller,

AutoflameEngineeringLtd.Autoflame.com

EGAInformation(Viewable&StoredwithintheDTIfor2Years)•O2,CO2,CO,NO,SO2&NO2percentile&ppmvalues

•Exhausttemperature,combustionefficiency,fuelconsumption&emissionsauditingdata

•EGAerrorconditions

•Flow-metering&on-lineExhaustGasAnalysisdata,bothinstantaneous&totalisedfor:O2,CO2,H2O,NO,CO,SO2,N2,totalemissionsasaweight,&correspondingvolumeatexhaustexittemperature&pressure

•Heatinput,heatloss&netusefulheat

•Netefficiency,grossefficiency&temperaturechange

•Fuelflowperhour&fuelflowtotalised

•Calculatedcostoffuelused(costpertonne)

DTI Input ValuesThefollowingsettingsmaybemodifiedinindividualMMControllersviatheDTI:

•Altersetpoint(individual&global)

•Enable/disableburner

•Re-orderboilersequencing&selectleadboiler

•Input/Outputlabelling&control

•Remoteloadindexcontrol

ConnectivityTheAutoflamenetworkoperatesusingatwo-corescreenedcable.TheDTIassesseseachitemonthenetworkperiodically,storingup-to-dateinformationontheDTI&outputstodefinedModbusaddresses.Thesearethenavailabletothirdpartysystems.TheDTIfeaturesdedicateddataportsforRS422&Ethernetconnections.The10.4”touch-screendisplaystheoperationalstatusoftheDTI’scommunications,withcorrespondingerrorconditionsintheeventofacommunicationfailure.

AutoflameCEMSAuditSoftwareManager/Supervisor•Customizablesitelayouts,boilerimages,sitenaming, ancillaries,mechanical&electricaldrawings

•AbilitytoviewlivestreameddatathroughaMk7MMControllerscreen&EGAscreen

•Remoteorlocalcontrol

•RemoteconnectiontoDTIoverinternetorLAN

Thedataissampledat1minuteintervals&storedonanSDCardwithintheMk7DTIandwithintheEGA.

Avarietyofconfigurationsareavailable,includingtheabilitytomonitormultipleDTI’sfromasinglePC(requiresadditionalproducts).ContactAutoflameoryourlocaltechnologycentreformoreinformation.

MMControllerData(Viewable&Stored within the DTI for Two Years):•Requiredandactualboilertemperatureorpressure

•Burnerfiringrate(%)

•Fuelselected&flowmeteringvalues

•Auto/Hand/Lowflameholdoperation

•Numberofcontrolchannelsoptionedshowingbothactual&commissionedpositions

•Maximum/minimumsetpointacceptedfromDTI

•Sequencestatus(on,stand-by,warm,off)&leadboilerstatus

•Enable/disabledstatus&errorconditions

•Alarmstatus

•Firstoutannunciation*

•Draftcontrol*

FlameSafeguardFunctions•Burnerfiringstatus(off,firing,purge,ignition,offline)

•Hoursrun&numberofstart-ups

•Lockoutstatus

•Gaspressure(online&commissioned)

•Oilpressure(online&commissioned)

•Airpressure(online&commissioned)

WaterLevelControlFunctions•Operationalinformation:steamandfeedwater*

•Temperature,pumpstatusandvalveposition*

•Probeinformation:temperature,signalvalue*

•Steamflowmeteringdata*

*RequiresMk7MMControllerwithExpansionBoard

DTIMk7:DataTransferInterface