    GRAVINERMk 7 OIL MIST DETECTOR

    INSTALLATION,OPERATION AND

    MAINTENANCEMANUAL59812-K007

    PROPRIETY RIGHTS NOTICE

    The information contained in this manual is the property of Kidde Products Limited and may not be reproduced ortransmitted in any form or by any means, electronic, mechanical, photocopying, recording or otherwise, nor storedin any retrieval system or any nature without the express written authority of Kidde Products Limited.

    © Copyright 2011 Kidde Products Ltd

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    2/88

    January 2012 Page ii of viii 59812-K007 Rev 3

    TABLE OF CONTENTS

    Chapter Page

    OIL MIST DETECTOR WARRANTIES .................................................................................. 7 

    1  DESCRIPTION AND OPERATION ................................................................................ 9 

    1.1  INTRODUCTION 9 1.2

     

    DESCRIPTION 10 

    1.3  TECHNICAL SPECIFICATION 12 1.4  SYSTEM OVERVIEW 14 1.5  SYSTEM CONTROLS AND DISPLAYS 15 

    2  INSTALLATION AND COMMISSIONING .....................................................................16 

    2.1  CONTROL UNIT MOUNTING 16 2.2  DETECTOR MOUNTING 17 2.3

     

    DETECTOR CABLES 20 

    2.4 

    REMOTE DISPLAY UNIT 23 

    2.5  CONTROL UNIT 26 2.6  REMOTE DISPLAY UNIT. 29 2.7  CONNECTING THE SYSTEM 32 2.8  SYSTEM CHECKS PRIOR TO SWITCHING ON 34 2.9

     

    SYSTEM SETUP / CONFIGURATION – WITH A REMOTE DISPLAY UNIT. 35 

    2.10  ISOLATION – USING THE REMOTE DISPLAY UNIT 47 2.11

     

    TEST MENU & EVENT LOG 55 

    3  MAINTENANCE ...........................................................................................................62 

    3.1 

    ROUTINE MAINTENANCE 62 3.2  DETECTOR HEAD REPLACEMENT 62 

    3.3 

    DETECTOR HEAD REFURBISHMENT 63 

    3.4  FAN REPLACEMENT 67 3.5

     

    CABLE REPLACEMENT 67 

    3.6  CONTROL UNIT MEMBRANE 68 3.7  CONTROL UNIT PCB REPLACEMENT 68 3.8  DECOMMISSIONING 68 

    4  FAULT FINDING ..........................................................................................................69 

    4.1  GENERAL 69 

    5  SPARE PARTS ............................................................................................................84 

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    3/88

    January 2012 Page iii of viii 59812-K007 Rev 3

    LIST OF ILLUSTRATIONS

    Figure Title Page

    Figure 1   Areas of Failure – 2 Stroke Engine ...................................................................... 9 Figure 2

     

     Areas of Failure – 4 Stroke Engine ...................................................................... 9 

    Figure 3 

    Graviner Mk7 OMD Components ........................................................................10 

    Figure 4  Typical System Configuration .............................................................................11 Figure 5  Relay Function Modes ........................................................................................15 Figure 6  Control Unit 53836-K270 ....................................................................................16 Figure 7

     

    Ideal Mounting Position.......................................................................................17 

    Figure 8  Detector Head Installation ...................................................................................18 Figure 9  Detector Head Installation (Short Sample Pipe) ..................................................19 Figure 10  Detector Cable ................................................................................................20 Figure 11  Detector Cable Assembly (Straight Connector) ...............................................21 Figure 12  Detector Cable Assembly (Right Angle Connector) .........................................22 Figure 13  Flush Mounting Cut-out for Remote Display Unit .............................................23 

    Figure 14 

    Flush Mounting for Remote Display Unit .........................................................24 

    Figure 15 

    Bulk Head Mounting for Remote Display Unit ..................................................25 

    Figure 16 

    Control Unit PCB .............................................................................................27 

    Figure 17  Wiring Drawing ................................................................................................28 Figure 18

     

    24v DC Socket Wiring Drawing .......................................................................29 

    Figure 19  Modbus Connector Wiring Drawing .................................................................30 Figure 20  Remote Display Unit 53836-K271 ...................................................................30 Figure 21

     

    Intentionally Left Blank ....................................................................................31 

    Figure 22  Power cable ....................................................................................................32 Figure 23

     

    Power cable through EMC gland .....................................................................32 

    Figure 24  Control unit relay cable assembly ....................................................................33 Figure 25  Detector cable assembly .................................................................................33 

    Figure 26 

    Control unit - Detector cable assembly ............................................................34 Figure 27  Screen Shot 1 .................................................................................................35 

    Figure 28  Screen Shot 2 .................................................................................................35 Figure 29  Screen Shot 3 .................................................................................................35 Figure 30

     

    Screen Shot 4 .................................................................................................36 

    Figure 31  Screen Shot 5 .................................................................................................36 Figure 32  Screen Shot 6 .................................................................................................36 Figure 33  Screen Shot 7 .................................................................................................36 Engine Selection List ............................................................................................................37 Figure 34

     

    Screen Shot 8 .................................................................................................37 

    Figure 35  Screen Shot 9 .................................................................................................37 Figure 36

     

    Screen Shot 10 ...............................................................................................37 

    Figure 37 

    Screen Shot 11 ...............................................................................................38 Figure 38  Screen Shot 12 ...............................................................................................38 

    Figure 39  Screen Shot 13 ...............................................................................................38 Figure 40  Screen Shot 14 ...............................................................................................38 Figure 41  Screen Shot 15 ...............................................................................................39 Figure 42  Screen Shot 16 ...............................................................................................39 Figure 43

     

    Screen Shot 17 ...............................................................................................39 

    Figure 44  Screen Shot 18 ...............................................................................................39 Figure 45

     

    Screen Shot 19 ...............................................................................................40 

    Detector Selection List..........................................................................................................40 Figure 46  Screen Shot 20 ...............................................................................................40 Figure 47  Screen Shot 21 ...............................................................................................41 

    Figure 48 

    Screen Shot 22 ...............................................................................................41 

    Figure 49 

    Screen Shot 23 ...............................................................................................41 

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    4/88

    January 2012 Page iv of viii 59812-K007 Rev 3

    Figure 50 

    Screen Shot 24 ...............................................................................................41 

    Figure 51  Control Unit – USB Connector .........................................................................42 Figure 52

     

    Computer Connection – USB Connector .........................................................42 

    Figure 53  USB Screen Shot 1 .........................................................................................43 Figure 54  USB Screen Shot 2 .........................................................................................43 Figure 55  USB Screen Shot 3 .........................................................................................43 Figure 56

     

    Smoke Tester ..................................................................................................44 

    Figure 57 

    Smoke Test .....................................................................................................45 

    Figure 58  Screen Shot 25 ...............................................................................................47 Figure 59  Screen Shot 26 ...............................................................................................47 Figure 60  Screen Shot 27 ...............................................................................................47 Figure 61  Screen Shot 28 ...............................................................................................48 Figure 62

     

    Screen Shot 29 ...............................................................................................48 

    Figure 63  Screen Shot 30 ...............................................................................................48 Figure 64

     

    Screen Shot 31 ...............................................................................................48 

    Figure 65  Screen Shot 32 ...............................................................................................49 Figure 66

     

    Screen Shot 33 ...............................................................................................49 

    Figure 67 

    Screen Shot 34 ...............................................................................................49 

    Figure 68 

    Screen Shot 35 ...............................................................................................49 

    Figure 69  Screen Shot 36 ...............................................................................................50 Figure 70  Screen Shot 37 ...............................................................................................50 Figure 71

     

    Screen Shot 38 ...............................................................................................50 

    Figure 72  Screen Shot 39 ...............................................................................................50 Figure 73

     

    Screen Shot 40 ...............................................................................................51 

    Figure 74  Screen Shot 41 ...............................................................................................51 Figure 75  Screen Shot 42 ...............................................................................................51 Figure 76  Screen Shot 43 ...............................................................................................51 Figure 77  Screen Shot 44 ...............................................................................................52 Figure 78

     

    Screen Shot 45 ...............................................................................................52 

    Figure 79 

    Screen Shot 46 ...............................................................................................52 Figure 80

     

    Screen Shot 47 ...............................................................................................52 

    Figure 81  Screen Shot 48 ...............................................................................................53 Figure 82  Screen Shot 49 ...............................................................................................53 Figure 83  Screen Shot 50 ...............................................................................................53 Figure 84  Screen Shot 51 ...............................................................................................53 Figure 85

     

    Control Unit Membrane ...................................................................................54 

    Figure 86  Screen Shot 52 ...............................................................................................55 Figure 87

     

    Screen Shot 53 ...............................................................................................55 

    Figure 88  Screen Shot 54 ...............................................................................................55 Figure 89  Screen Shot 55 ...............................................................................................56 Figure 90  Screen Shot 56 ...............................................................................................56 

    Figure 91 

    Screen Shot 57 ...............................................................................................56 

    Figure 92 

    Screen Shot 58 ...............................................................................................56 

    Figure 93  Screen Shot 59 ...............................................................................................57 Figure 94

     

    Screen Shot 60 ...............................................................................................57 

    Figure 95  Screen Shot 61 ...............................................................................................57 Figure 96

     

    Screen Shot 62 ...............................................................................................57 

    Figure 97  Screen Shot 63 ...............................................................................................58 Figure 98  Screen Shot 64 ...............................................................................................58 Figure 99  Screen Shot 65 ...............................................................................................58 Figure 100  Screen Shot 66 ...............................................................................................58 Figure 101

     

    Screen Shot 67 ...............................................................................................59 

    Figure 102  Screen Shot 68 ...............................................................................................59 Figure 103

     

    Screen Shot 70 ...............................................................................................60 

    Figure 104  Screen Shot 71 ...............................................................................................60 

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    5/88

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    6/88

    January 2012 Page vi of viii 59812-K007 Rev 3

    REVISION HISTORY

    Issue  Date Of Issue  Revision History  Amended by  Approved by

    1  Oct 2011  Draft – For Approval M Daley A Willis

    2  Nov 2011   Approved for Distribution M Daley A Willis

    3 Jan 2012 Changes to Back Alarmoperating philosophy andSmoke Test procedure.  M Daley A Willis

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    7/88

    January 2012 Page vii of viii 59812-K007 Rev 3

    Oil Mist Detector Warranties

    1. Kidde Products Ltd (KPL) warrants, for a period of 3 years from the handover of the Oil MistDetector (OMD) system to the system owner, that any component forming part of the original

    OMD system manufactured by or supplied by KPL shall be free from defects in workmanship ormaterials during normal usage (the “OMD System Warranty”). If any such component does notconform to this warranty KPL will, at its sole discretion and its cost, either repair or replace suchcomponent. Installation of the repaired / replacement parts is not covered under the OMD SystemWarranty. Components replaced or repaired under the terms of the OMD System Warranty shallcontinue to have the benefit of the unexpired portion of the OMD System Warranty, unless thatunexpired portion is less than 12 months, in which case the repaired / replacement parts shallhave the benefit of a 12 month warranty against defects in workmanship or materials duringnormal usage starting on the date of delivery. OMD ‟s supplied as spares shall be warranted inaccordance with paragraph 2 below only.

    2. KPL warrants for a period of 12 months from delivery that individual OMD‟s supplied as spares

    shall be free from defects in workmanship or materials during normal usage.

    3. Performance of KPL‟s repair or replacement obligations shall constitute an entire discharge ofKPL's liability under the warranties set out in paragraphs 1 and 2 above (“Warranties”). 

    4. The Warranties shall not apply to the following:

    a. defects reasonably judged by KPL as being caused by the improper installation of theOMD‟s and/or OMD system;

    b. defects reasonably judged by KPL as being caused by the failure to follow therecommendations contained in KPL‟s product manuals and/or other documentation

    regarding the frequency of routine maintenance and testing of the OMD ‟s and/or OMDsystem and/or the failure to have such routine maintenance performed;

    c. defects which are attributable to careless handling or storage, accident, improper use ofthe OMD‟s and/or OMD system, or incorrectly completed repairs or routine maintenanceservices;

    d. damages or losses occurring as a result of any act or omission which is wilfully unlawful ornegligent;

    e. defects arising from the use of non-genuine KPL parts or accessories, or the use ofmaterials not approved for use by KPL;

    f. any modifications to or installations performed on the OMD‟s and/or OMD system outside

    the scope of normal routine maintenance or running repairs without the express priorwritten approval of KPL;

    g. deterioration, staining or corrosion of parts which will occur due to normal exposure andusage;

    h. alleged defects not materially affecting the quality or proper functioning of the OMDsystem.

    5. In addition the Warranties shall be limited as follows:

    a. KPL shall be under no liability in respect of any defect in the OMD‟s and/or OMD Systemarising from any drawing, design or specification supplied by or at the request of the buyeror system owner (not being a drawing, design or specification of KPL);

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    8/88

    January 2012 Page viii of viii 59812-K007 Rev 3

    b. KPL shall be under no liability in respect of any defect or failure of the OMD‟s and/or OMDSystem to operate in accordance with specifications, illustrations, descriptions or otherparticulars due to their combination or use with any incompatible equipment or product.

    6. The Warranties are conditional upon:

    a. the buyer or OMD system owner giving written notice to KPL of the alleged defect, such

    notice to be given immediately when the buyer or OMD system owner discovers or oughtto have discovered the defect;

    b. the buyer or OMD system owner affording KPL a reasonable opportunity to inspect theOMD‟s and/or OMD system;

    c. the buyer or OMD system owner not altering or attempting to repair the OMD‟s and/orOMD system without the written consent of KPL.

    7. The Warranties can be transferred to any new owner of the OMD system provided KPL isinformed in writing within 30 days of the transfer. The OMD System Warranty cannot betransferred to another KPL OMD system.

    8. Save to the extent amended by the provisions set out above, KPL‟s standard terms and conditions

    of sale shall apply.

    OMD Service Life

    Oil Mist Detectors (OMD‟s) are an integral part of critical safety systems designed to detect

    certain conditions that could lead to crankcase explosions on large Diesel engines. They aretypically installed in harsh operating conditions - particularly with respect to temperature andvibration - and are expected to provide continuous service over extended periods. They aretherefore subject to considerable wear and tear.

    In order to ensure reliable performance, it is particularly important that OMD‟s are properlyinstalled, operated and maintained in accordance with the manufacturer‟s instructions andguidelines. Given that they are components within key safety systems, as precautionary advicethe manufacturer recommends replacing or refurbishing OMD‟s which are more than 10 yearsold, even if they are functioning correctly at that time.

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    9/88

    January 2012 Page 9 of 88  59812-K007 Rev 3

    1 DESCRIPTION AND OPERATION

    1.1 INTRODUCTION

    High temperatures, in excess of 200ºC that occur on bearing surfaces under initial failureconditions, can lead to a rapid generation of oil vapour When the hot vapour contacts therelatively cooler atmosphere of the crankcase it condenses into a fine mist, with typical particlesizes of around 0.5 to 5 microns in diameter. When the density of these particles reachesbetween 30 to 50 mg/I (Milligrams per litre), depending upon the type of oil, an explosivecondition exists.

    Piston Rod Seal

    Cross Head Slides

    Cross Head Bearing

    Top End Bearing

    Bottom End Bearing

    Main Bearing

     

    Figure 1 Areas of Failure – 2 Stroke Engine 

    Piston Seizure

    Cam Shaft Bearings

    Bottom End

    Bearing

    Top End Bearing

    Piston Blow By

    Main Bearing

     

    Figure 2 Areas of Failure – 4 Stroke Engine

     A fire or explosion needs three constituents: fuel, oxygen and an ignition source. Remove one ofthese and no explosion will occur. Similarly, within the crankcase, the three constituents whichcould cause an explosion are air, oil mist and an ignition source, the “hot spot‟. Using opticalmeasuring techniques, oil mist density can be measured at levels as low as 0.05 mg/I and giveearly warning of a rise in oil mist density.

    Oil Mist Detection (OMD) techniques have been used to monitor diesel engine crankcases forpotential explosive conditions and early detection of bearing failures. The systems available relymainly on analysing the optical density of oil mist samples drawn from the crankcasecompartments, through pipes to the detector. While these systems proved successful in the past,engine design has improved significantly over the years and oil mist detection techniques haveimproved substantially to maintain adequate protection.

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    10/88

    January 2012 Page 10 of 88  59812-K007 Rev 3

    The Graviner Mk 7 OMD provides the following benefits:

     Auto addressed system monitoring up to 10 detector heads per control unit

    Up to 10 control units per single system.

    Suitable for both 2 stroke and 4 stroke engines.

    Elimination of sample pipes - reduced installation costs.Engine mounted Control Unit.

    Optional Remote Display Unit mounted in a safe area, typically the Engine Control Room(ECR).

    Figure 3 Graviner Mk7 OMD Components

    1.2 DESCRIPTION

    The system comprises three main components (refer to Figure 3):

    Detectors 53836-K269 (with base) / 53836-K272 (replacement head)

    53836-269-01 (Short sample pipe)

    Control Unit 53836-K270 (With Membrane)53836-K276 (Without Membrane)

    Remote Display Unit 53836-K271

     And connecting cables

    Control Unit to Detector cable (Straight) 43682-K286-XX

    Control Unit to Detector cable (Right Angle) 43682-K285-XX

    The Graviner Mk 7 OMD system can comprise up to 100 detectors directly mounted on thecrankcases of up to 10 engines, allowing both main propulsion and auxiliary generators to bemonitored at the same time.

    Each detector communicates electronically over a serial data link via the engine mountedControl Unit with the optional Remote Display Unit designed to be mounted within the EngineControl Room. This eliminates the need to enter the machinery space in alarm conditions.

    Remote DisplayUnit

    Detector

    DetectorCable

    Control Unit

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    11/88

    January 2012 Page 11 of 88  59812-K007 Rev 3

    Figure 4 Typical System Configuration

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    12/88

    January 2012 Page 12 of 88  59812-K007 Rev 3

    1.3 TECHNICAL SPECIFICATION

    Detector

    Mounting ¾ inch BSP

    Enclosure Rating IP65

    Indicators Green Detector On

    Red Alarm

     Amber Detector Fault

    Power Consumption 1.5W

    Temperature Rating 0 – 70oC

    Height 153mm

    Width 90mm

    Length 205mm

    Weight 0.5kg

    Control Unit 

    Enclosure Rating IP65

    Max detector inputs 10

    Output Relays Volt-free change over contacts rated at 30Vdc 1A

    Back-up Alarm 1 set (de-energised during normal operation)

    Pre Alarm 1 set (de-energised during normal operation)

    Fault Alarm 1 set (energised during normal operation)

    Engine Slowdown / Shutdown 1 set (de-energised during normal operation)

     Alarm Ranges Pre Alarm 0.5mg/l to 1.2mg/l (adjustable)

     Alarm 1.3mg/l to 2.4mg/l (adjustable)

    Backup 3.0mg/l (fixed)

    Power Consumption 3.9W

    Temperature Rating 0 – 70oC

    Dimensions

    Height 186mm (110mm mounting centres)

    Width 318mm (240mm mounting centres)

    Depth 90mm

    Weight 2.8kg

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    13/88

    January 2012 Page 13 of 88  59812-K007 Rev 3

    Remote Display Unit

    Enclosure Rating IP32

    Max No. of detectors 100

    Max No. of engines monitored 10

    Power Supply 24Vdc (+30% -25%)

    Power Consumption 6.0W

    Temp Rating 0 – 70oC

    Humidity level 95%

    Dimensions

    Bulkhead Mounted: Height 225mm (202mm mounting centres)

    Width 240mm (217mm mounting centres)

    Depth 58mm

    Panel Mounted: Height 225mm (202mm mounting centres)

    Width 240mm (217mm mounting centres)

    Depth 55mm

    Weight 1.0kg

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    14/88

    January 2012 Page 14 of 88  59812-K007 Rev 3

    1.4 SYSTEM OVERVIEW

    The Graviner Mk7 OMD is an auto addressed oil mist detection system capable of monitoringup to 10 Control Units per system with each Control Unit having up to 10 detectors connectedto it. This is achieved without external sample pipes and with minimum cabling. Each detectorhead monitors a single crank space and is a stand-alone device. On power up the detectorsgather oil mist density data and convert it to a digital signal for transmission via the data lines

    in the detector cable to the Control Unit which is also mounted on the side of the engine. Alarm levels and Alarm output requirements are all set from either the optional RemoteIndicator Display or a PC connected directly to the control unit.

    The Remote Display Unit houses a 7.5” LCD Touch Screen display that shows, on demand,the signal from each detector and indicates the oil mist level for each engine and whenrequired each detector as well as the status of the system. In the event of an alarm, the displayimmediately shows the oil mist levels for the relevant engine. It also enables the individualreadings of each detector on the engine to be displayed on demand and automatically underalarm conditions.

    In the event of a detector fault, that detector can be isolated without affecting the function ofthe other detectors on the engine. The system will continue to operate while the faulty detectoris replaced, repaired or maintenance is carried out.

    The Mk7 detectors still use optical sensing, (light scatter) as it‟s detection method andcontinually monitors the oil mist density in the crank space to which it is connected. In addition,it self checks for any internal faults. The Control Unit interrogates each detector in turn,identifies the position connected at the Control Unit, the oil mist density value and determinesthe status of the detector.

    Each detector is fitted with 3 LED indicator lights:

    Green - Power onRed - Alarm

     Amber - Fault

     As all detectors operate independently, the loss of one detector through a fault does not affectthe operation of the rest of the system. Individual detectors, or engine groups, can be isolated

    from the rest of the system for maintenance while the rest of the system remains in operation.

    The Control Unit can be supplied with or without a control membrane. The control membranehas LED indication for detectors connected, push buttons for isolation and de-isolation ofdetectors, as well as pushbuttons for Accepting and Resetting Alarms.

     Alarm Philosophy

    The system has 3 separate alarm levels as detailed below

    1. Pre Alarm - This indicates that the oil mist levels are increasing in a particularcrank space and that investigation should be undertaken. This alarm will not operatethe slowdown or shutdown relays.

    2. High Alarm - When any detector reaches this threshold then the slowdown orshutdown relays will be operated if they are connected.

    3. Back Up Alarm - In the event of a failure of either the Pre Alarm or High Alarm, thenthe Back Up Alarm will operate, but it will not operate the slowdown or shutdown relay.This is an additional functional precaution added by Kidde Products Ltd which can beconnected in any way the customer requires. This is usually connected to a warningbeacon or siren, however the customer may choose to connect the relay to anotherdevice or the engine slow down circuitry.

    On receipt of either a Pre Alarm or High Alarm the engine should, unless connected to aslowdown / shutdown relay, be stopped if safe to do so and allowed to cool down so that thebackground oil mist levels reduce before entering the engine room.

    When the oil mist levels have returned to normal then the Accept and Reset buttons can be

    operated from the Control Unit membrane if fitted or alternatively form the Remote Display Unitand the system will then return to normal operation.

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    15/88

    January 2012 Page 15 of 88  59812-K007 Rev 3

    Fault Diagnosis

    When a system fault is received, the information on the display should be noted and then theappropriate Fault Finding procedure in Chapter 4 of the manual should be checked to enablethe fault to be rectified.

    When the faults have been rectified the Accept and Reset buttons can be operated and thesystem will return to normal

    Event Log

     All alarms, faults and events are recorded in an Event Log which is date and time stamped andwill indicate the type of event which enables analysis of the events at a later time. The EventLog has a capacity of 1024 events and is a rolling buffer.

    1.5 SYSTEM CONTROLS AND DISPLAYS

    The Remote Display Unit and PC software is menu driven and provides a logical route to allfunctions. It has three operating levels:

    UserEngineerService

    The User level is essentially for read only interrogation and does not allow any adjustments tobe made to alarm settings or system configuration.

    The Engineer level is password protected and allows access to most functions and the fullrange of programmable settings. When selected, a prompt for a password will appear Enter012345, when programming is completed the Password should be changed by an authorisedperson to prevent unauthorised access in the future. This process can be followed in Chapter2.9 of this manual

    The Service level is also password protected (different from the Engineer Menu) and allows

    access to all functions. This is only available to authorised Kidde Fire Protection personnel andauthorised service agents.

    RelayDescription

    Unit off Unit on Pre-Alarm SlowdownBackup Alarm

    Fault

    Pre-Alarm

     Alarm

    Backup-alarm

    Fault

    Figure 5 Relay Function Modes

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    16/88

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    17/88

    January 2012 Page 17 of 88  59812-K007 Rev 3

    2.2 DETECTOR MOUNTING

    Each detector is mounted to an individual crankcase via a ¾ inch BSP threaded hole.

    Ensure all detectors fitted to the engine are locked tightly in place by means of the lock nutsupplied.

    It is recommended that the detector be located at the upper part of the crankcase wall not inthe direct line of the oil throw. On smaller engines it is permissible to mount the detector on thecrankcase door if desired or as installation dictates, subject to vibration levels.

    Figure 7 Ideal Mounting Position

    The detector must be fitted at a maximum of plus or minus 20 degrees from the vertical.Horizontally the detector must be mounted level or with the detector body inclined towards the

    engine to ensure oil drainage. Refer to Figure 8. 

    Please ensure that Detector 1 is connected to position 1 on the Control Unit, Detector 2 toposition 2. Repeat for all Detectors fitted.

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    18/88

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    19/88

    January 2012 Page 19 of 88  59812-K007 Rev 3

    Figure 9 Detector Head Installation (Short Sample Pipe)

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    20/88

    January 2012 Page 20 of 88  59812-K007 Rev 3

    2.3 DETECTOR CABLES

    Each detector must be connected to the Control Unit by way of a supplied detector cable,see Figure 10Ensure that the cables are run in a suitable cable tray and clipped at regular intervals toensure they cannot be subjected to mechanical damage caused by vibration.

    Cable Lengthm

    90o ConnectorPart No.

    Straight ConnectorPart No.

    1.0 43682-K285-1.0 43682-K286-1.01.5 43682-K285-1.5 43682-K286-1.52.0 43682-K285-2.0 43682-K286-2.02.5 43682-K285-2.5 43682-K286-2.53.0 43682-K285-3.0 43682-K286-3.03.5 43682-K285-3.5 43682-K286-3.54.0 43682-K285-4.0 43682-K286-4.04.5 43682-K285-4.5 43682-K286-4.55.0 43682-K285-5.0 43682-K286-5.0

    5.5 43682-K285-5.5 43682-K286-5.56.0 43682-K285-6.0 43682-K286-6.06.5 43682-K285-6.5 43682-K286-6.57.0 43682-K285-7.0 43682-K286-7.07.5 43682-K285-7.5 43682-K286-7.58.0 43682-K285-8.0 43682-K286-8.08.5 43682-K285-8.5 43682-K286-8.59.0 43682-K285-9.0 43682-K286-9.09.5 43682-K285-9.5 43682-K286-9.510.0 43682-K285-10.0 43682-K286-10.010.5 43682-K285-10.5 43682-K286-10.511.0 43682-K285-11.0 43682-K286-11.0

    11.5 43682-K285-11.5 43682-K286-11.512.0 43682-K285-12.0 43682-K286-12.012.5 43682-K285-12.5 43682-K286-12.515.0 43682-K285-15.0 43682-K286-15.017.5 43682-K285-17.5 43682-K286-17.520.0 43682-K285-20.0 43682-K286-20.022.5 43682-K285-22.5 43682-K286-22.525.0 43682-K285-25.0 43682-K286-25.0

    Figure 10 Detector Cable

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    21/88

    January 2012 Page 21 of 88  59812-K007 Rev 3

    Figure 11 Detector Cable Assembly (Straight Connector)

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    22/88

    January 2012 Page 22 of 88  59812-K007 Rev 3

    Figure 12 Detector Cable Assembly (Right Angle Connector)

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    23/88

    January 2012 Page 23 of 88  59812-K007 Rev 3

    2.4 REMOTE DISPLAY UNIT

    The Remote Display Unit part number 53836-K271 must be mounted in the Engine ControlRoom (ECR) or similar safe environment, do not mount in an Engine Room as it is notdesigned to be mounted in this type of environment. Additionally Class Society rules state thatany display must be mounted in a safe area away from the Engine Room.

    For flush mounting details see below and Figure 13 and Figure 14. For bulk head mounting details see Figure 15. 

    Figure 13 Flush Mounting Cut-out for Remote Display Unit

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    24/88

    January 2012 Page 24 of 88  59812-K007 Rev 3

    Figure 14 Flush Mounting for Remote Display Unit

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    25/88

    January 2012 Page 25 of 88  59812-K007 Rev 3

    Figure 15 Bulk Head Mounting for Remote Display Unit

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    26/88

    January 2012 Page 26 of 88  59812-K007 Rev 3

    2.5 CONTROL UNIT

    24v DC Input supply

    The supply should be 24v DC +30% -25% rated at 1.2 amps.

    Cables should be segregated from high voltage cables and follow good installationpractice

    Cable type-2 Cores + Earth, CSA 2.5mm2  (50/0.25mm), flexible stranded bare copperconductors, low smoke halogen free insulation, cores laid up, braided screen, low smokehalogen free sheath – grey, outside diameter 9.8mm, operating temperature 0ºC + 80ºC.

    Suggested cablesLapp Kabel CY cable 3 core 2.5mm2 Prysmian LSM-HF 3 core 2.5mm2 Helkama LKAM-HF 3 core 2.5mm2 

    Refer  Figure 16 for connector location.Refer  Figure 16 for wiring drawing.

    Modbus

    Cable type – Individually screened 2 pair data cable, 24AWG, low capacitance, low smokehalogen free. Outer diameter 7mm (max)

    Cables should be segregated from high voltage cables and follow good installationpractice

    Suggested cablesFS Cables 2402PIFFHBeldon 9729Helkama RFE-HF(i) 2x2x0.75Jinro 60V RCOP(IS)

    The above cable should be used to connect between the Control Unit and either the ships AMS system or the Remote Display Unit.

    Refer  Figure 16 for connector location.Refer  Figure 16 for wiring drawing.

    Relay Outputs

    The relay outputs are rated at 30v DC at 1amps.

    2 Cores + Earth, CSA 2.5mm2  (50/0.25mm), flexible stranded bare copper conductors, lowsmoke halogen free insulation, cores laid up, braided screen, low smoke halogen free sheath

     – grey, outside diameter 9.8mm, operating temperature 0oC + 80oC.

    Cables should be segregated from high voltage cables and follow good installationpractice

     Approved cablesLapp Kabel CY cable 3 core 2.5mm2 Prysmian LSM-HF 3 core 2.5mm2 Helkama LKAM-HF 3 core 2.5mm2 

    Refer  Figure 16 for connector location.Refer  Figure 16 for wiring drawing.

    USB Connection

    Refer  Figure 16 for connection location. 

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    27/88

    January 2012 Page 27 of 88  59812-K007 Rev 3

    Figure 16 Control Unit PCB

     All Detector connectors are prewired.

    24v DC inputConnector

    ModbusConnector

    Relay OutputConnectors

    USB

    Connection

    End of LineJumper

    End of LineJumper

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    28/88

    January 2012 Page 28 of 88  59812-K007 Rev 3

    Figure 17 Wiring Drawing

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    29/88

    January 2012 Page 29 of 88  59812-K007 Rev 3

    2.6 REMOTE DISPLAY UNIT.

    24v DC Input supply

     A 24v DC supply rated 1.5 amps should be connected via an Hirschmann GM216 NJ.

    Cable type – 2 Cores + Earth, CSA 1.5mm2, fine stranded bare copper wires, braided screen,low smoke halogen free sheath, outside diameter 10mm (max), operating temperature 0ºC +80ºC.

    Cables should be segregated from high voltage cables and follow good installationpractice

    Suggested cablesLapp Kabel 1.5mm2 Ölflex Classic 110CH - 10035068Prysmian LSM-HF 3 core 1.5mm2 Helkama LKAM-HF 3 core 1.5mm2 

    Refer Figure 18 for 24vDC Socket wiring drawing.Refer  Figure 20 for connection location.

    Figure 18 24v DC Socket Wiring Drawing

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    30/88

    January 2012 Page 30 of 88  59812-K007 Rev 3

    Modbus

    Cable type – Individually screened 2 pair data cable, 24AWG, low capacitance, low smokehalogen free. Outer diameter 7mm (max)

    Cables should be segregated from high voltage cables and follow good installationpractice

    Suggested cablesFS Cables 2402PIFFHBeldon 9729Helkama RFE-HF(i) 2x2x0.75Jinro 60V RCOP(IS)

    The above cable should be used to connect between the control unit and either the ships AMSsystem or the Remote Display Unit

    Refer Figure 19 for Modbus Connector Wiring Drawing.Refer  Figure 20 for connector location.

    Figure 19 Modbus Connector Wiring Drawing

    Figure 20 Remote Display Unit 53836-K271

    24v DCConnector Modbus

    Connector

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    31/88

    January 2012 Page 31 of 88  59812-K007 Rev 3

    Intentionally Left Blank

    Figure 21 Intentionally Left Blank

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    32/88

    January 2012 Page 32 of 88  59812-K007 Rev 3

    2.7 CONNECTING THE SYSTEM

    2.7.1 Input power

    +24 V dc and 0 V dc power input cables for the Control Unit should be terminated onto SupplyInput (terminal block TB1).

    Cables should be segregated from high voltage cables and follow good installation

    practice

    Note all terminations should be made using crimped wires.

    For each of the power connections strip the power cable to the required length to connect tothe terminals in the control unit. Then remove approximately 1cm of the outer sheath toexpose the cable screen as shown below.

    Figure 22 Power cable

    Feed the cable into the control unit via a metal IP65 EMC gland supplied, ensuring that themetal prongs make contact with the exposed cable screen as shown below.

    Figure 23 Power cable through EMC gland

    Exposed screen

    Earthing Prongs

    Cable gland

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    33/88

    January 2012 Page 33 of 88  59812-K007 Rev 3

    2.7.2 Relay Cables

    The connection to the slowdown relay, pre-alarm relay, backup alarm relay and fault relay and24Vdc supply cables at the Control Unit should be made using screened cable. For each of therelay connection strip the cable to the required length to connect to the terminals in the controlunit. Then remove approximately 1cm of the outer sheath to expose the cable screen asshown below see Figure 24. 

    Cables should be segregated from high voltage cables and follow good installationpractice

    Figure 24 Control unit relay cable assembly

    Feed the cable into the control unit via a metal IP65 EMC gland supplied, ensuring that themetal prongs make contact with the exposed cable screen as shown.

    2.7.3 Control Unit to Detector Connections

     At the detector, screw the connector to the top of the detector.

    Figure 25 Detector cable assembly

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    34/88

    January 2012 Page 34 of 88  59812-K007 Rev 3

     At the control unit, screw the connector to the input required.

    Figure 26 Control unit - Detector cable assembly

    2.8 SYSTEM CHECKS PRIOR TO SWITCHING ON

    2.8.1 Ensure that the 24v DC input power supply cable is connected correctly at each Control Unit (ifmore than one installed).

    2.8.2 Ensure that the Modbus Communication (if required) is terminated correctly at each ControlUnit (if more than one installed and/or Remote Indication Display installed or connected to

     AMS).

    2.8.2.1 If more than one control unit is installed, please ensure the End of Line (EOL) jumpers areremoved from all Control Units (refer Figure 15) except for the highest Modbus addressedControl Unit.

    2.8.2.2 Make sure that the Modbus address‟s are set as required, refer section 2.9.1 for procedure.

    2.8.3 Ensure that the Backup Alarm, Pre Alarm, Fault and Slowdown relays are connected correctlyat each Control Unit (if more than one installed).

    2.8.4 Ensure the detectors are connected to each Control Unit in the correct number sequence.

    2.8.5 Check the cable run of all Modbus Communication cables between all installed Control Unitsto each other and to the Remote Indication Display (If Installed) or AMS to ensure that it is notdamaged.

    2.8.6 Ensure that the Modbus Communication and power supply cables are connected correctly atthe Remote Display Unit (If installed).

    2.8.7 Ensure that the input voltage at the Control Unit(s) and the Remote Display Unit (If installed) isa clean 24 V dc +30%, - 25%

    2.8.8 When all of the above have been checked and are satisfactory the system is ready to switchon.

    2.8.9  Allow 20 minutes for the system to reach it‟s normal operating temperature before continuingto system configuration and commissioning.

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    35/88

    January 2012 Page 35 of 88  59812-K007 Rev 3

     After a few seconds the following willbe seen on the Remote Display Unit,this shows one engine connected butmay show up to ten.

    Press „OK‟ 

    Press the „Engineer‟ button to log inas an Engineer.

    Note – To setup Engine andDetectors and Save Logs, youmust be logged in as Engineer.

    2.9 SYSTEM SETUP / CONFIGURATION – WITH A REMOTE DISPLAY UNIT.

    When all of the connections have been completed and checked, power up the Control Unit andRemote Display Unit, the following power up screen will show for a few seconds on the emoteDisplay Unit.

    If there is more than one Control Unit connected to the display the Modbus address needs tobe set up via the USB connection on the control unit before it can talk to the display unit.Please refer to section 2.9.1.1 for the Modbus setup

    Figure 27 Screen Shot 1

    Figure 28 Screen Shot 2

    Figure 29 Screen Shot 3

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    36/88

    January 2012 Page 36 of 88  59812-K007 Rev 3

    Enter password 012345.

    Press „Menu‟ Button to display theEngineers menu.

    To set or change Engine Namespress „Engine Names‟. 

    Press the up and down arrows tocycle through possible Engine

    Names, this figure shows one engineconnected but may show up to ten.

    Please see below for the full list ofEngine Names.

    Press „Save‟ once your desired nameis selected for Engines.

    Figure 30 Screen Shot 4

    Figure 31 Screen Shot 5

    Figure 32 Screen Shot 6

    Figure 33 Screen Shot 7

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    37/88

    January 2012 Page 37 of 88  59812-K007 Rev 3

    Use numeric keys to set the Timeand Date. Press „OK‟ when complete 

    Note – Time and Date must beentered even if the correct Timeand Date is displayed.

    Press „OK‟, Figure 32 will then be

    displayed.To change the Engineer PIN press„Change Engineer PIN‟. 

    Press „OK‟. 

    Figure 32 will then be displayed.

    To change the Time & Date press

    „Set Time / Date 

    Engine Selection List

    ME 1 – Main Engine 1 ME 2 – Main Engine 2 FSU – Fuel Supply UnitG/E 1 – Generator 1 GEN 1 – Generator 1 AUX 1 – Auxiliary Engine 1G/E 2 – Generator 2 GEN 2 – Generator 2 AUX 2 – Auxiliary Engine 2G/E 3 – Generator 3 GEN 3 – Generator 3 AUX 3 – Auxiliary Engine 3G/E 4 – Generator 4 GEN 4 – Generator 4 AUX 4 – Auxiliary Engine 4

    G/E 5 – Generator 5 GEN 5 – Generator 5 AUX 5 – Auxiliary Engine 5G/E 6 – Generator 6 GEN 6 – Generator 6 AUX 6 – Auxiliary Engine 6G/E 7 – Generator 7 GEN 7 – Generator 7 AUX 7 – Auxiliary Engine 7G/E 8 – Generator 8 GEN 8 – Generator 8 AUX 8 – Auxiliary Engine 8G/E 9 – Generator 9 GEN 9 – Generator 9 AUX 9 – Auxiliary Engine 9

    Figure 34 Screen Shot 8

    Figure 35 Screen Shot 9

    Figure 36 Screen Shot 10

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    38/88

    January 2012 Page 38 of 88  59812-K007 Rev 3

    Use numeric keys to enter new pin of6 digits and then store in a safe placewhere only authorised users canaccess it

    If the PIN number is lost, please referto Kidde Fire Protection

    Use numeric keys to re enter new pinof 6 digits.

    Press „OK‟. 

    Figure 32 will then be displayed.

    To save the event Log press „SaveLogs‟ 

    Figure 37 Screen Shot 11

    Figure 38 Screen Shot 12

    Figure 39 Screen Shot 13

    Figure 40 Screen Shot 14

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    39/88

    January 2012 Page 39 of 88  59812-K007 Rev 3

    Press „Menu‟ to display the EngineMenu.

    To set or change Detector Namespress „Detector Names‟. 

    To setup the Detectors on eachEngine, press the button under themg/l display for the Engine beingsetup.

    Press „OK‟ to return to Figure 32. 

    Note – Once the Logs are saved,only Kidde Authorised ServiceAgents can download them.

    Press „Exit‟ to return to Engines

    Overview screen (Figure 31)

    Figure 41 Screen Shot 15

    Figure 42 Screen Shot 16

    Figure 43 Screen Shot 17

    Figure 44 Screen Shot 18

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    40/88

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    41/88

    January 2012 Page 41 of 88  59812-K007 Rev 3

    To set the individual Detectorparameters, press the button underthe mg/l display for the requireddetector.

    Press „Menu‟ to display the DetectorMenu.

    Press „OK‟. 

    Figure 48 will then be displayed.Press „Back‟ to return to Figure 47. 

    Repeat setting Detector settings forthe number of Detectors connected.

    Press the up and down arrows toselect the desired Alarm and Pre

     Alarm Levels.

    Alarm Limits 1.3 – 2.4mg/l

    Pre-Alarm Limits 0.5 – 1.2mg/l

    Press „Save‟ once complete. 

    Figure 47 Screen Shot 21

    Figure 48 Screen Shot 22

    Figure 49 Screen Shot 23

    Figure 50 Screen Shot 24

    Once Detectors on Engine 1 have been set, Press „Back‟ to return to Engine Overview screen.

    Repeat setting Engine Names & Detector settings for the number of Engines connected.

    The OMD Mk7 System should now be setup.

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    42/88

    January 2012 Page 42 of 88  59812-K007 Rev 3

    2.9.1 Control Unit Addressing

    When more than one Control Unit is connected on 1 system, the Modbus address needs to beset up via the USB connection on the PCB in each Control Unit (refer Figure 51) before thesystem will work properly.

    NOTE – For multiple Control Units per system, each Control Unit must have its ownControl Unit Address and they must be sequential, i.e. 01. 02. 03 …..10 

     All Control Units will come shipped as Modbus address 01 (1st Control Unit)

    2.9.1.1 To change the Modbus address

    a. Connect the 24Vdc power supply to the Control Unit to be changed.b. Connect the USB-B end to the USB socket located on the PCB inside the Control Unit (refer

    Figure 51)

    Figure 51 Control Unit – USB Connectorc. Connect the other end of the USB Lead to a USB socket on your computer (refer

    Figure 53)

    Figure 52 Computer Connection – USB Connector

    USBConnection

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    43/88

    January 2012 Page 43 of 88  59812-K007 Rev 3

    Click „Login‟, then „Engineer‟ 

    Enter 012345 and press „Login‟ 

    Select the required Control Unit Address (this is the Modbus address)

    2.9.1.2 With the above cables connected, open the „Mk7 Oil Mist Engine Manger‟ software on thecomputer.

    Figure 53 USB Screen Shot 1

    Figure 54 USB Screen Shot 2

    Figure 55 USB Screen Shot 3

    Repeat the above for the number of Control Units installed per system.

     After the address‟s have been changed, please ensure that the EOL jumpers are fitted to the lastControl Unit, all other Control Units need to have the EOL jumpers removed.

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    44/88

    January 2012 Page 44 of 88  59812-K007 Rev 3

    2.9.2 Detector Smoke Alarm Test

    Commence the smoke alarm test as follows: with the detector(s) fitted, electrically connected,functioning and configured as described in the instruction manual.

    Note: Isolation of the output relays (Pre Alarm and Slow-Down Relays) is

    required before commencing the smoke alarm test. If the Back-up Alarm Relayis connected to the engine shut/slow down system this should bedisconnected.

    Warning: Carrying out this test without isolation or disconnection of the outputrelays will cause the engine shut/slow down system to operate if connected.

    a. Cut a length of wick approximately 30 mm long. Assemble the smoke tester by pushingthe wick into the wick holder fitted with the pipette bulb. Press the nylon pipe into the pipeconnector (refer to Figure 566).

    Figure 56 Smoke Tester

    b. Push the nylon pipe of the smoke tester into the connector on the side of the detectorbase body (refer to Figure 57).

    Wick

    Pipette Bulb

    Wick Holder

    Nylon Pipe

    Pipe Connector

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    45/88

    January 2012 Page 45 of 88  59812-K007 Rev 3

    Figure 57 Smoke Test

    c. Dip the wick into the bottle of smoke oil and reseal the bottle firmly

    Note: Only a small quantity of oil is required.

    d. Ignite the wick of the smoke tester and blow out the flame. Squeeze the pipette bulb tokeep the wick smoking.

    Note: Care to be taken with this activity at all times .

    e. While the wick is still smouldering, insert it into the pipe connector and squeeze thepipette bulb.

    f. Observe the wick is still smouldering, insert nylon pipe into the pipe connector of thedetector and squeeze the pipette bulb.

    g. After tests are completed the Detector Peak Level readings should be erased. This can bedone via the Engine Menu using Clear Peak. (refer Figure 44)

    h. To release the pipe from the connector, press in the metal collar on the end of theconnector at the same time as pulling the pipe out

    i. Remove the nylon pipe from the pipe connector for stowage purposes.

     j. The wick is reusable and can be left in the wick holder. Fully extinguish the wick after useat all times.

    k. Refer to the Material Safety Data Sheet in the event of health or safety issues.

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    46/88

    January 2012 Page 46 of 88  59812-K007 Rev 3

    2.9.3 Back Up Alarm

    The backup alarm is a hard wired link from each Detector installed on the system. This facilitywill allow any detector which is in a fault condition and sees an oil mist level of 3.0mg/I orgreater to produce a „Back Up Alarm. This will produce operation of the Backup Alarm Relay inthe Control Unit, the Backup Alarm will also override any detector or detectors that areisolated.

    Whilst any detectors are in a Backup Alarm condition the accept key is inoperative untilthe oil mist level drops below 3.0mg/l.

    It is possible for a healthy detector to produce a back up alarm if the level of oil rises veryrapidly.

    NOTE - The Backup Alarm will not operate the Slow-Down Relay

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    47/88

    January 2012 Page 47 of 88  59812-K007 Rev 3

    Press the „Isolate‟ button. 

    Press the „Menu‟ button. 

    To Isolate Engine or detectors on theengine, press the button under themg/l display for the Engine to beisolated. You must be in the Engineerlevel to carry out this function

    2.10 ISOLATION – USING THE REMOTE DISPLAY UNIT

    If required, it is possible to isolate any individual detector, a complete engine, engine Pre- Alarm or Slow Down relays. This allows maintenance to be carried out without affecting theremaining system. Isolation inhibits all alarms and faults for the isolated item except theBackup Alarm, which is a fixed level.

    To prevent the possible activation of the Back-up Alarm Relay disconnect the cable from thetop of the detector unit.

    2.10.1 Engine Isolation

    Figure 58 Screen Shot 25

    Figure 59 Screen Shot 26

    Figure 60 Screen Shot 27

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    48/88

    January 2012 Page 48 of 88  59812-K007 Rev 3

    To Isolate All Detectors, press the„Isolate‟ button. 

    Press „Yes‟ to Isolate All Detectors. 

    Press „OK‟ 

    To De-Isolate All Detectors, press the„De-Isolate‟ button. 

    Figure 61 Screen Shot 28

    Figure 62 Screen Shot 29

    Figure 63 Screen Shot 30

    Figure 64 Screen Shot 31

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    49/88

    January 2012 Page 49 of 88  59812-K007 Rev 3

    Press „Yes‟ to De-Isolate AllDetectors.

    Press „OK‟ 

    You will be returned to Figure 64. 

    To Isolate the Pre-Alarm Relay, press„Isolate‟ 

    Press „Yes‟ to Isolate the Pre-Alarmrelay.

    Press „OK‟ 

    Figure 65 Screen Shot 32

    Figure 66 Screen Shot 33

    Figure 67 Screen Shot 34

    Figure 68 Screen Shot 35

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    50/88

    January 2012 Page 50 of 88  59812-K007 Rev 3

    To De-Isolate the Pre-Alarm relay,press the „De-Isolate‟ button. 

    Press „Yes‟ to De-Isolate the Pre- Alarm relay.

    Press „OK‟ 

    You will be returned to Figure 69. 

    To Isolate the Slow Down Relay,press „Isolate‟ 

    Press „Yes‟ to Isolate the Slow Downrelay.

    Figure 69 Screen Shot 36

    Figure 70 Screen Shot 37

    Figure 71 Screen Shot 38

    Figure 72 Screen Shot 39

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    51/88

    January 2012 Page 51 of 88  59812-K007 Rev 3

    Press „OK‟ 

    To De-Isolate the Slow Down relay,press the „De-Isolate‟ button. 

    Press „Yes‟ to De-Isolate the SlowDown relay.

    Press „OK‟ 

    You will be returned to Figure 74. 

    Press „Exit‟ to return to Figure 59. Press „Exit‟ to return to Engine 1overview.

    Figure 73 Screen Shot 40

    Figure 74 Screen Shot 41

    Figure 75 Screen Shot 42

    Figure 76 Screen Shot 43

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    52/88

    January 2012 Page 52 of 88  59812-K007 Rev 3

    Press „Isolate‟ 

    Press „Yes‟ to Isolate the Detector. 

    Press „Menu‟ 

    To Isolate single Detectors, press thebutton under the mg/l display for therequired detector.

    2.10.2 Detector Isolation

    Figure 77 Screen Shot 44

    Figure 78 Screen Shot 45

    Figure 79 Screen Shot 46

    Figure 80 Screen Shot 47

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    53/88

    January 2012 Page 53 of 88  59812-K007 Rev 3

    Press „OK‟ 

    To De-Isolate the selected Detector,press „De-Isolate‟ 

    Press „Yes‟ to De-Isolate theDetector.

    Press „OK‟ 

    You will be returned to Figure 82. 

    Press „Back‟ button to return to Figure 78. 

    Press „Back‟ button to return to Engine 1overview screen (Figure 77).

    Press „Back‟ button to return to Enginesoverview screen.

    Figure 81 Screen Shot 48

    Figure 82 Screen Shot 49

    Figure 83 Screen Shot 50

    Figure 84 Screen Shot 51

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    54/88

    January 2012 Page 54 of 88  59812-K007 Rev 3

    2.10.3 Detector Isolation – Using the Membrane

    To isolate a detector at the Control Unit fitted with a Membrane, press the detector numberbutton for 2 seconds until the amber LED is steady. (Refer Figure 85)

    Note: with the detector isolated the Back-up Alarm Relay may be activated if the oil mist levelincreases above 3mg/l or light is introduced in to the detector. To prevent the possible

    activation of the Back-up Alarm Relay disconnect the cable from the top of the detector unit.

    Figure 85 Control Unit Membrane

    Repeat the above to de-isolate a detector.

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    55/88

    January 2012 Page 55 of 88  59812-K007 Rev 3

    To test the Slow Down Relay, pressthe „1‟ button.

    Press the „Test‟ button. 

    Select the desired Engine for testing.

    2.11 TEST MENU & EVENT LOG

    This section will show how to Test the components in the OMD Mk7 system, and how to viewthe Event Log. The Test and Event Log instructions are the same for User Level and EngineerLevel with the exception that the User Level cannot Test the Slow Down Relay.

    2.11.1 Test Menu.

    Warning: Carrying out this test with the engine operating will cause the engine shut/slow downsystem to operate if connected.

    Figure 86 Screen Shot 52

    Figure 87 Screen Shot 53

    Figure 88 Screen Shot 54

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    56/88

    January 2012 Page 56 of 88  59812-K007 Rev 3

    Press „OK‟ 

    You will be returned to Figure 88

    To Test the Pre-Alarm Relay, pressthe „1‟ button. 

    Press „OK‟ 

    You will be returned to Figure 88.

    To Test the Fault Relay, press the „0‟button.

    Press „OK‟ 

    You will be returned to Figure 88.

    To Test the Backup Alarm, press the„Test‟ button. 

    Note – This is a software test only.

    Press „OK‟ 

    You will be returned to Figure 88.

    To Test the Optics, press the „Test‟button.

    Figure 89 Screen Shot 55

    Figure 90 Screen Shot 56

    Figure 91 Screen Shot 57

    Figure 92 Screen Shot 58

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    57/88

    January 2012 Page 57 of 88  59812-K007 Rev 3

    For Testing of detectors per engine,press the button under the mg/ldisplay for the required detector.

    Press „OK‟ 

    You will be returned to Figure 88.

    To Test the Front Panel, press the„Test‟ button. 

    Press „OK‟ 

    You will be returned to Figure 88.

    Press „Exit‟ to return to Engine 1overview.

    Note - This will also reset all Tests.

    Press „Alarm Test‟ 

    Figure 93 Screen Shot 59

    Figure 94 Screen Shot 60

    Figure 95 Screen Shot 61

    Figure 96 Screen Shot 62

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    58/88

    January 2012 Page 58 of 88  59812-K007 Rev 3

    Press „Test‟ 

    Press the button under the mg/ldisplay for the required engine.

    Press „ Accept‟ 

    Press „OK‟ 

    Figure 97 Screen Shot 63

    Figure 98 Screen Shot 64

    Figure 99 Screen Shot 65

    Figure 100 Screen Shot 66

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    59/88

    January 2012 Page 59 of 88  59812-K007 Rev 3

    Press „Reset‟ 

    Press „OK‟ 

    You will now return to Figure 87.

    Press the „Back‟ button to return toEngine Overview, Figure 86.

    Figure 101 Screen Shot 67

    Figure 102 Screen Shot 68

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    60/88

    January 2012 Page 60 of 88  59812-K007 Rev 3

    Use the Up and Down arrows toscroll through the events in thisscreen.

    Press „By Date‟ tab to view event logby date.

    Use the number buttons to select thedate to view events.

    Press „Search‟ once the correct dateis entered.

    Use the Up and Down arrows toscroll through the events in thisscreen.

    Press „By Event‟ tab to view event logby Event.

    2.11.2 Event Log.

    The Event Log enables the user to interrogate the past 1024 events and can be accessed viathe menus below. The Event Log is a rolling buffer and when the events exceed 1024 thenNumber 1 is dropped off and replaced by the latest Event

    To access the Event Log from Figure 87, press „Event Log‟ button.

    Figure 103 Screen Shot 70

    Figure 104 Screen Shot 71

    Figure 105 Screen Shot 72

    Note - If there are no Events matching your search then this screen will be blank.

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    61/88

    January 2012 Page 61 of 88  59812-K007 Rev 3

    Use the Up and Down arrows toselect the event to search.

    Press „Search‟ to view event log byselected event.

    Use the Up and Down arrows toscroll through the events in thisscreen.

    Press „By Detector‟ tab to view eventlog by Detector.

    Use the Up and Down arrows toselect the detector to search.

    Press „Search‟ to view event log by

    selected detector.

    Use the Up and Down arrows toscroll through the events in this

    screen.Press „Exit‟ to return to Engine 1overview, Figure 87. 

    Press „Back‟ to return to EnginesOverview screen.

    Figure 106 Screen Shot 73

    Figure 107 Screen Shot 74

    Figure 108 Screen Shot 75

    Figure 109 Screen Shot 76

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    62/88

    January 2012 Page 62 of 88  59812-K007 Rev 3

    3 MAINTENANCE

    3.1 ROUTINE MAINTENANCE

    Warning: Do not work on the system unless the power isswitched off or isolated.

    Caution: Ensure that anti static handling procedures areobserved applied when working on the system, i.e. Anti- StaticWrist Straps

    The following checks are recommended to be carried out every 6 months , with thesystem switched off. The checks should be carried out by competent personnel withsuitable skill levels.

    3.1.2 Control Unit

    1. Ensure that all connectors are tight to prevent ingress of oil and moisture and the srewson the Control Unit are correctly tightened

    3.1.3 Cables

    1. Ensure all connections on the Control Unit are tight.

    2. Check all cables. Replace any that are found to be damaged.

    3.1.4 Detectors

    1. Ensure that the detector base is screwed tight into the crankcase,

    2. Remove the cable connector from the detector and check for damage.

    3.2 DETECTOR HEAD REPLACEMENT

    Warning: Do not remove the detector base from the crankcase whilst the engine is in

    operation. This operation should be carried out while the engine is stoppedto avoid the possibility of hot oil coming out of the base fixing hole.

    If an in-service detector head is removed for any reason, the detector optics must be cleanedbefore reassembling and replacing it.

    3.2.1 To replace the detector:

    1. Switch off the system (if safe to do so) or isolate the detector

    2. Remove the cable connector fitted to the top of the detector

    3. Using a 4mm hexagonal key, loosen the two fixing screws in the assembly base.

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    63/88

    January 2012 Page 63 of 88  59812-K007 Rev 3

    Figure 110 Base Fixing Screw Removal

    4. Lift out the faulty detector head

    5. Fit the new detector head onto its base and tighten up the fixing screws. re-fit the cable tothe detector head.

    6. If the system was switched off, switch back on and allow the system to initialise.

    7. If isolated, then de-isolate, Press OK on the Remote Display Unit, display will then returnto normal

    3.3 DETECTOR HEAD REFURBISHMENT

    1. Isolate the detectors as described in section 2.10 of the instruction manual.

    2. Disconnect the cable from the top of the detector unit and remove the unit from the enginecasing (refer to Figure 111).

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    64/88

    January 2012 Page 64 of 88  59812-K007 Rev 3

    Figure 111 Cable Disconnect

    3. Using a 4mm hexagon key, unscrew 2 off screws from the underside of the detector head(refer to Figure 110). The screws are self-retaining.

    4. Remove and invert the top part of the detector head. Examine the base moulding seal and

    replace if damaged or perished (refer to Figure 112).

    Screw Removal

    Figure 112 Base Moulding Seal

    Caution: Do not press the fan, only handle the outer housing.

    Fan Retaining Plug

    Fan Socket FixingScrew

    Base Moulding Seal

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    65/88

    January 2012 Page 65 of 88  59812-K007 Rev 3

    5. Using the Pulling Tool (refer to Figure 113), remove the Fan Retaining Plug by capturingthe shoulder and pulling. Carefully remove the Fan from its mountings (refer to Figure114).

    Figure 113 Pulling Tool

    Figure 114 Fan Removal

    Fan

    CompressionSpring

    Fan RetainingPlug

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    66/88

    January 2012 Page 66 of 88  59812-K007 Rev 3

    6. Examine the 4 off compression springs and the fan retainer plug; replace any bent ordamaged items from the spares.

    7. Examine the fan for free running and clogging due to oil residues. If damaged, refer toparagraph 3.4 in the instruction manual. Although not necessary for service cleaning,spares of the M3 screw and the fan connector seal are included in the kit.

    8. Using a foam bud with glass cleaner applied, wipe carefully around the inside of thesmoke detecting orifice (refer to Figure 115).

    Figure 115 Cleaning Light Guide

    9. Dry the inside of the unit.

    10. Examine the base body cavity and sampling tube, and wipe clean where necessary.

    11. Reassemble the fan to the detector using a fan retaining plug.

    Caution: Do not press the fan, only handle the outer housing.

    12. Reassemble the detector head and base body. Replace the detector and then de-isolate.

    13. Repeat the procedure for all detectors to be cleaned.

    Refer to the Materials Safety Data Sheet in the event of health or safety issues.

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    67/88

    January 2012 Page 67 of 88  59812-K007 Rev 3

    3.4 FAN REPLACEMENT

    Warning: Do not remove the detector base from the crankcasewhilst the engine is in operation. This operation shouldbe carried out while the engine is stopped to avoid thepossibility of hot oil coming out of the base fixing hole.

    3.4.1 To replace the fan:

    1. Switch off the system (if safe to do so), or isolate the associated detector.

    2. Remove the cable connector from the top of the detector.

    3. Using a 4mm Allen key, loosen the detector fixing screws on the base.

    4. Remove the detector from its base and turn it upside down to reveal the fan.

    5. Remove the fixing screw holding the fan socket to the mounting plate.

    6. Using a pulling tool (Part Number D9131-002 available with service kit Part No.D9221-027), remove the fan retaining plug holding the fan onto its mounting legs.

    7. Lift the fan off of its mounting legs, ensuring the springs under the fan are not lost.

    8. Discard the failed fan and fit a replacement fan in reverse order of disassembly.

    3.5 CABLE REPLACEMENT

    If changing a detector cable, isolating that detector will be sufficient (see section 2.10)

    3.5.1 Detector Cable

    1. Isolate the detector with the damaged cable.

    2. Remove the cable connector on top of the detector.

    3. Identify the cable to be removed at the Control Unit

    4. Unscrew the cable connector at the Detector and discard the damaged cable.

    5. Connect the replacement cable to the connector on the Control Unit ensuring it is screwedin place.

    6. Connect the cable connector to the detector

    7. De-isolate the detector

    8. Press OK on The Remote Display Unit

    3.5.2 Power Supply Cable Replacement (Supplied by Others)

    1. Switch off the system.

    2. Disconnect the damaged power supply cable from the Control Unit or Remote Display

    Unit.

    3. Connect the replacement power supply cable to the Control Unit or Remote Indictor Unitensuring wires and cable screen are correctly fitted in the terminals.

    4. Switch the system on and allow to initialise.

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    68/88

    January 2012 Page 68 of 88  59812-K007 Rev 3

    3.5.3 Communications Cable Replacement (Supplied by Others)

    1. Switch off the system.

    2. Disconnect the damaged communications cable from the Control Unit.

    3. Disconnect the damaged communications cable from the Remote Display Unit or AMS.

    4. Connect the replacement communications cable to the Control Unit ensuring it is screwedin place.

    5. The replacement communications cable must be connected to the terminals in the ControlUnit and the Remote Display Unit or AMS.

    6. Switch the system on and allow it to initialise.

    3.5.4 Control Unit (Pre-Alarm, Slowdown/Shutdown and Back Up Alarm or Fault Relay CableReplacement (Supplied by Others)

    1. Switch off the system.

    2. Remove the Control Unit Lid by removing the 4 screws

    3. Disconnect the damaged relay cable from the Control Unit.

    4. Disconnect the damaged relay cable from the monitoring equipment.

    5. Connect the replacement relay cable to the control unit ensuring it is screwed in place.

    6. Connect the replacement relay cable to the monitoring equipment.

    7. Switch the system on and allow it to initialise.

    3.6 CONTROL UNIT MEMBRANE

     A new Control Unit Lid will be supplied fitted with the Membrane.

    1. Unscrew the 4 screws to remove the Control Unit Lid

    2. Disconnect the 2 ribbon cables connecting the Control Unit Lid to the main PCB.3. Fit new lid in reverse

    3.7 CONTROL UNIT PCB REPLACEMENT

    1. Power down the system

    2. Remove the 4 screws from the lid

    3. Disconnect the ribbon cables

    4. Remove the top half of the terminal blocks for the Communications Cables, Pre Alarm andHigh Alarm Cables and Fault Cables

    5. Disconnect the detector connectors (1 through to 10) – Push sides to release.

    6. Remove the 4 screws at the corners of the PCB

    7. Remove PCB

    8. Fit new PCB in reverse order to the above

    3.8 DECOMMISSIONING

     All the components of the Graviner Mk7 OMD system must be disposed of aselectrical/electronic equipment waste. i.e. using waste disposal methods in accordance withcurrent local waste disposal regulations.

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    69/88

    January 2012 Page 69 of 88  59812-K007 Rev 3

    4 FAULT FINDING

    4.1 GENERAL

    The table below lists a series of failure modes and the likely faults that would be indicatedshould that failure mode appear. Also listed are Actions, numbered 1 to 19, which should befollowed if the associated fault appears. On the following pages, Actions 1 to 19 are shown asflow charts which will assist with fault finding on the Graviner Mk7 OMD system

    Control Unit without a Remote Display

    Failure Mode Fault Indication Fault Action

    Control Unit Power indicator is off  All Control Unit LED‟s off  Supply Failure

    Membrane failure1.

    Control Unit fault Control Unit fault LED on. Control Unit fault 2.

     All detector Power On (Green)indicators are off.

    No indication on thedetectors.

    Control Unit fault LED on, alldetector fault LED‟s flashing

    1sec on 1sec off

    Control Unit fuse.

    Detectors disconnected.3.

     A detector indicatingcommunications fault

    Detector fault LED on

    Control Unit fault LED on, alldetector fault LED flashing

    1sec on 1sec off

    Damaged detector cable

    Detector failure.

    Damaged Control Unit PCB

    4.

    Detector fault other thancommunications fault.

    Detector fault LED on

    Control Unit fault LED on, alldetector fault LED flashing

    0.5sec on 0.5sec off

    Fan fault

    LED contamination fault

    Detector failure

    5.

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    70/88

    January 2012 Page 70 of 88  59812-K007 Rev 3

    Control Unit with Remote Display

    Failure Mode Fault Indication Fault Action

    Control Unit Power indicator is off

     All Control Unit LED‟s off  

    Communications fault withthe engine indicated on the

    Remote Display

    Supply Failure 6.

    Control Unit membrane fault

    Control Unit fault LED on.

    Front panel test failedindicated on the Remote

    Display

    Control Unit membranefault

    Control Unit PCB fault

    7.

    Control Unit memory fault

    Control Unit fault LED on.

    External RAM indicated onthe Remote Display

    Control Unit PCB fault 8.

    Control Unit watchdog fault

    Control Unit fault LED on.

    Watchdog fault indicated onthe Remote Display

    Control Unit PCB fault 8.

     All detector Power On (Green)indicators are off.

    No indication on thedetectors.

    Control Unit fault LED on, alldetector fault LED‟s flashing

    1sec on 1sec off

    Remote Display indicates

    communications fault on alldetectors for that engine.

    Detectors disconnected.

    Power Supply failure3.

     A detector indicatingcommunications fault

    Detector fault LED on

    Control Unit fault LED on, alldetector fault LED flashing

    1sec on 1sec off

    Remote Display indicatescommunications fault on one

    detector

    Damaged detector cable

    Detector failure.

    Damaged Control Unit PCB

    4.

    Detector fan fault.

    Detector fault LED on

    Control Unit fault LED on, alldetector fault LED flashing

    0.5sec on 0.5sec off

    Remote Display indicates fanfault on a detector

    Fan fault 9.

    Detector LED fault.

    Detector fault LED on

    Control Unit fault LED on, alldetector fault LED flashing

    0.5sec on 0.5sec off

    Remote Display indicates anLED fault on a detector

    Detector sample arearequires cleaning.

     An LED has failed.

    Detector failure.

    10.

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    71/88

    January 2012 Page 71 of 88  59812-K007 Rev 3

    Control Unit with Remote Display

    Failure Mode Fault Indication Fault Action

    Detector LED fault.

    Detector fault LED on

    Control Unit fault LED on, all

    detector fault LED flashing0.5sec on 0.5sec off

    Remote Display indicates aphotodiode fault on a

    detector

    Detector sample arearequires cleaning.

    Detector failure.

    10.

    Detector watchdog fault.

    Detector fault LED on

    Control Unit fault LED on, alldetector fault LED flashing

    0.5sec on 0.5sec off

    Remote Display indicates a

    watchdog fault on a detector

    Detector software has reset 11

    Remote Display communicationswith all engines fault.

    Remote Display indicates acommunications fault on all

    engines

    Modbus communicationscable fault

    End of line terminationincorrect.

    Remote Display failure

    12

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    72/88

    January 2012 Page 72 of 88  59812-K007 Rev 3

     Action 1

    Is 24v present

    at the supply

    input terminals

    (TB1)

    Is the 24v input

    power supplycable connected

    correctly

    Correctly connect the 24v

    supply to the Control UnitReplace the Control

    Unit

    No

    No

    Yes

    Yes

     

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    73/88

    January 2012 Page 73 of 88  59812-K007 Rev 3

     Action 2

    Is 24v supply

    between 18  –

    31.2v

    Reconnect the input

    supply to the correct

    voltage

    Replace the Control Unit

    PCB

    Cycle the power supply to

    the Control Unit off then on.

    Do all of the

    membrane LED‟s

    operate correctly

    Replace the Control

    Unit lid and membrane

    No

    No

    Yes

    Yes

     

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    74/88

    January 2012 Page 74 of 88  59812-K007 Rev 3

     Action 3

     Are all

    connections

    made correctly

    Correct the

    connections

    Replace the Control

    Unit PCB

    Check the connections from the Control

    Unit PCB to the Detector connectors.

    Check all detector cables are connectedcorrectly.

    On power up arethe detector

    power LED‟s on

    No

    Yes

    Yes

    Remove the power from the

    Control Unit for a period of 15

    minutes

    End

    No

     

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    75/88

    January 2012 Page 75 of 88  59812-K007 Rev 3

     Action 4

    Does the

    communications

    fault move with

    the detector 

    Replace the faulty

    detector.

    Replace the faulty

    detector cable

    Swap the detector with an adjacent

    working detector.

    Does the

    communications

    fault move with

    the cable

    Yes

    No

    No

     At the Control Unit swap the

    detector cable with an adjacent

    working connection.

    Replace the Control

    Unit PCB

    Yes

     

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    76/88

    January 2012 Page 76 of 88  59812-K007 Rev 3

     Action 5

    Is the fan

    operating

    correctly

    Replace the detector

    fan.

    Replace the

    detector 

    Remove the detector head andcheck the operation of the fan.

    Has the faultbeen cleared

    No

    Yes

    Yes

    Clean the detector sample

    chamber and replace the

    detector head and reset the

    Control Unit.

    End

    No

     

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    77/88

    January 2012 Page 77 of 88  59812-K007 Rev 3

     Action 6

    Is 24v present

    at the supply

    input terminals

    (TB1)

    Is the 24vinput power

    supply cable

    connected

    correctly

    Correctly connect the

    24v supply to the

    Control UnitReplace the

    Control Unit

    No

    No

    Yes

    Yes

     

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    78/88

    January 2012 Page 78 of 88  59812-K007 Rev 3

     Action 7

    Do all of the

    LED‟s operate

    correctly?

    Replace the Control Unit

    lid and membraneReplace the Control

    Unit PCB

    No

    Yes

    Switch the Control Unit power

    off and on.

    Observe the LED test

    performed at power up

     

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    79/88

    January 2012 Page 79 of 88  59812-K007 Rev 3

     Action 8

    Replace the

    Control UnitPCB

     

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    80/88

    January 2012 Page 80 of 88  59812-K007 Rev 3

     Action 9

    Replace the

    Detector 

    Replace the Detector fan

    Reset the fault on the

    Control Unit

     After 30 seconds

    does the fan fault

    remain cleared.

    End

    Yes

    No

     

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    81/88

    January 2012 Page 81 of 88  59812-K007 Rev 3

     Action 10

    Replace the

    Detector 

    Remove the detector head

    and clean the sample

    chamber 

    Optics testpassed?

    End

    Yes

    No

    (Repeat once)

    Replace the detector head

    and perform an optics test

    No

     

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    82/88

    January 2012 Page 82 of 88  59812-K007 Rev 3

     Action 11

    Replace the

    Detector 

    Clear the fault on the

    Control Unit

    Does the

    watchdog fault

    reoccur?

    End

    No

    Yes

     

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    83/88

    January 2012 Page 83 of 88  59812-K007 Rev 3

     Action 12

     Are all

    connectionsmade correctly

    Correct the connections

    Correctly set the

    Control Unit Modbus

    addresses

    Check the Modbus connections fromthe Remote Display Unit to each of the

    Control Units.

     Are all of the

    Control Units

    addressed

    correctly?

    No

    Yes

    Yes

    Replace the RemoteDisplay Unit

    No

     Are the end of

    line jumpers set

    correctly in each

    Control Unit

    Correct the jumper

    links Yes

    No

     

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    84/88

    January 2012 Page 84 of 88  59812-K007 Rev 3

    5 SPARE PARTS

    Figure 116 Control Unit Spares

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    85/88

    January 2012 Page 85 of 88  59812-K007 Rev 3

    Control Unit Spares

    Item Description Part No.

    1. Printed Circuit Board c/w Ribbon Cables 43782-K172-00

    1. Printed Circuit Board w/out Ribbon Cables 43782-K172-01

    2. 25mm Blanking Plug 22540-K029

    3. Metal Gland 22540-K028

    4. Detector Connection Cap 27400-K303

    Detector Harness Kit 53569-K003

    5. 6 Way Detector Connection – Qty 1

    Wrench Tool – Qty 1

    Control Unit Connector Kit 53569-K004

    6. Relay & Power Plugs – Qty 3

    7. Modbus Plug – Qty 1

    8. EOL Jumpers – Qty 2

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    86/88

    January 2012 Page 86 of 88  59812-K007 Rev 3

    Remote Display Unit Spares

    Item Description Part No.

    1. 24VDC Power Socket (no Cable) 27400-K304

    2. Modbus Connector (no Cable) 27400-K305

    3. Modbus Connector c/w 5m Cable 43682-K297

    4. 24VDC Power Socket c/w 5m Cable 43682-K296

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    87/88

    January 2012 Page 87 of 88  59812-K007 Rev 3

    Figure 117 Detector Spares

    Item Description Part No.

    1 Detector Head Assembly 53836-K272

    2 Fan Assembly D5622-005-02

    3 Base Unit sub-Assembly D5622-101

    4 Connector Push In B5465-307

    5 Base moulding O Ring C1513-802

  • 8/18/2019 59812-K007 Mk7 Manual Rev3

    88/88

    Commissioning Kit D9221-026 consists of:

    Description Part No. Qty Category

    Wipes, Wet & Dry A7311-001 2 Consumables

    Smoke Test Oil -30 ml D9221-028 1 Bottle ConsumablesWick - 150 mm 17100-H06 3 Consumables

    Smoke Tester D9221-029 1 Tools

    Materials Safety Data Sheet - 2 Information

    Service Kit D9221-027

    Description Part No Qty Category

    Fan Retainer B3741-902 5 Spares

    Compression Spring B3721-006 5 Spares

    Base Moulding Seal C1513-802 5 Spares

    Fan Connector Seal C1413-801 5 Spares

    M3 Screw 21833-H01 5 Spares

    Glass Cleaner 500ml A7311-002 1 Consumables

    Foam Buds Pkts B6910-217 2 Consumables

    4mm Hexagon Key B691 0-219 2 Tools

    Pulling Tool D9131-002 1 Tools

    Materials Saf