Galaxy 7000

250–500 kVA 380/400/415 V UPS

Technical Specifications

03/2018

www.schneider-electric.com

Page 2: Galaxy 7000 - download.schneider-electric.com

Legal InformationThe Schneider Electric brand and any registered trademarks of Schneider ElectricIndustries SAS referred to in this guide are the sole property of Schneider ElectricSA and its subsidiaries. They may not be used for any purpose without the owner'spermission, given in writing. This guide and its content are protected, within themeaning of the French intellectual property code (Code de la propriétéintellectuelle français, referred to hereafter as "the Code"), under the laws ofcopyright covering texts, drawings and models, as well as by trademark law. Youagree not to reproduce, other than for your own personal, noncommercial use asdefined in the Code, all or part of this guide on any medium whatsoever withoutSchneider Electric's permission, given in writing. You also agree not to establishany hypertext links to this guide or its content. Schneider Electric does not grantany right or license for the personal and noncommercial use of the guide or itscontent, except for a non-exclusive license to consult it on an "as is" basis, at yourown risk. All other rights are reserved.

Electrical equipment should be installed, operated, serviced, and maintained onlyby qualified personnel. No responsibility is assumed by Schneider Electric for anyconsequences arising out of the use of this material.

As standards, specifications, and designs change from time to time, please ask forconfirmation of the information given in this publication.

Page 3: Galaxy 7000 - download.schneider-electric.com

250–500 kVA 380/400/415 V UPS

Table of Contents

Important Safety Instructions — SAVE THESEINSTRUCTIONS.........................................................................................5

Safety Precautions .....................................................................................6

Technical Data.............................................................................................8Model list ...................................................................................................8Input Power Factor .....................................................................................8Efficiency ...................................................................................................8

Efficiency Curves ..................................................................................9Derating due to Load Power Factor ............................................................10Batteries ..................................................................................................10

Efficiency DC to AC.............................................................................10End of Discharge Voltage .................................................................... 11

Compliance.............................................................................................. 11

Facility Planning ........................................................................................12Input Specifications ..................................................................................12Bypass Specifications ...............................................................................12Output Specifications................................................................................12Battery Specifications ...............................................................................13

End of Discharge Current ....................................................................13Recommended Cable Sizes ......................................................................13

Power Cables for Single UPS ..............................................................13Power Cables for Parallel UPSs...........................................................14Connection Terminals..........................................................................16

Recommended Overcurrent Protection ......................................................16Recommended Upstream and Downstream Protection ..........................16Recommended Residual Current Protection .........................................18Battery Breaker Box Configurations......................................................18

Environmental ..........................................................................................20Heat Dissipation .................................................................................20

Weights and Dimensions...........................................................................20Shipping Weights and Dimensions.............................................................20Clearance ................................................................................................21Default settings ........................................................................................22

Drawings ....................................................................................................23Galaxy 7000 Single System.......................................................................24Galaxy 7000 Single System with Transformer .............................................25

Options .......................................................................................................26Hardware Options.....................................................................................26Configuration Options ...............................................................................27Parallel Capabilities ..................................................................................27

Limited Factory Warranty.........................................................................30

990–3887C-001 3

Page 4: Galaxy 7000 - download.schneider-electric.com
Page 5: Galaxy 7000 - download.schneider-electric.com

Important Safety Instructions — SAVE THESEINSTRUCTIONS 250–500 kVA 380/400/415 V UPS

Important Safety Instructions — SAVE THESEINSTRUCTIONS

Read these instructions carefully and look at the equipment to become familiar withit before trying to install, operate, service or maintain it. The following safetymessages may appear throughout this manual or on the equipment to warn ofpotential hazards or to call attention to information that clarifies or simplifies aprocedure.

The addition of this symbol to a “Danger” or “Warning” safetymessage indicates that an electrical hazard exists which will result inpersonal injury if the instructions are not followed.

This is the safety alert symbol. It is used to alert you to potentialpersonal injury hazards. Obey all safety messages with this symbolto avoid possible injury or death.

DANGERDANGER indicates a hazardous situation which, if not avoided, will result indeath or serious injury.

Failure to follow these instructions will result in death or serious injury.

WARNINGWARNING indicates a hazardous situation which, if not avoided, could result indeath or serious injury.

Failure to follow these instructions can result in death, serious injury, orequipment damage.

CAUTIONCAUTION indicates a hazardous situation which, if not avoided, could result inminor or moderate injury.

Failure to follow these instructions can result in injury or equipmentdamage.

NOTICENOTICE is used to address practices not related to physical injury. The safetyalert symbol shall not be used with this type of safety message.

Failure to follow these instructions can result in equipment damage.

Please NoteElectrical equipment should only be installed, operated, serviced, and maintainedby qualified personnel. No responsibility is assumed by Schneider Electric for anyconsequences arising out of the use of this material.

A qualified person is one who has skills and knowledge related to the construction,installation, and operation of electrical equipment and has received safety trainingto recognize and avoid the hazards involved.

990–3887C-001 5

Page 6: Galaxy 7000 - download.schneider-electric.com

250–500 kVA 380/400/415 V UPSImportant Safety Instructions — SAVE THESE

INSTRUCTIONS

Safety Precautions

DANGERHAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH• The product must be installed according to the specifications and

requirements as defined by Schneider Electric. It concerns in particular theexternal and internal protections (upstream circuit breakers, battery circuitbreakers, cabling, etc.) and environmental requirements. No responsibility isassumed by Schneider Electric if these requirements are not respected.

• After the UPS system has been electrically wired, do not start up the system.Start-up must only be performed by Schneider Electric.

Failure to follow these instructions will result in death or serious injury.

DANGERHAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

The UPS System must be installed according to local and national regulations.Install the UPS according to:• IEC 60364 (including 60364–4–41- protection against electric shock, 60364–

4–42 - protection against thermal effect, and 60364–4–43 - protection againstovercurrent), or

• NEC NFPA 70depending on which one of the standards apply in your local area.

Failure to follow these instructions will result in death or serious injury.

DANGERHAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH• Install the UPS system in a temperature controlled area free of conductive

contaminants and humidity.• Install the UPS system on a non-inflammable, level, and solid surface (e.g.

concrete) that can support the weight of the system.Failure to follow these instructions will result in death or serious injury.

DANGERHAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

The UPS is not designed for and must therefore not be installed in the followingunusual operating environments:• Damaging fumes• Explosive mixtures of dust or gases, corrosive gases, or conductive or radiant

heat from other sources• Moisture, abrasive dust, steam or in an excessively damp environment• Fungus, insects, vermin• Salt-laden air or contaminated cooling refrigerant• Pollution degree higher than 2 according to IEC 60664-1• Exposure to abnormal vibrations, shocks, and tilting• Exposure to direct sunlight, heat sources, or strong electromagnetic fieldsFailure to follow these instructions will result in death or serious injury.

6 990–3887C-001

Page 7: Galaxy 7000 - download.schneider-electric.com

Important Safety Instructions — SAVE THESEINSTRUCTIONS 250–500 kVA 380/400/415 V UPS

NOTICERISK OF OVERHEATING

Respect the clearance requirements around the UPS system and do not coverthe product’s ventilation openings when the UPS system is in operation.

Failure to follow these instructions can result in equipment damage.

NOTICERISK OF EQUIPMENT DAMAGE

Do not connect the UPS output to regenerative load systems includingphotovoltaic systems and speed drives.

Failure to follow these instructions can result in equipment damage.

990–3887C-001 7

Page 8: Galaxy 7000 - download.schneider-electric.com

250–500 kVA 380/400/415 V UPS Technical Data

Technical Data

Model listThe Galaxy 7000 UPS is available in the following models:• Galaxy 7000 250 kVA 380/400/415 V• Galaxy 7000 300 kVA 380/400/415 V• Galaxy 7000 400 kVA 380/400/415 V• Galaxy 7000 500 kVA 380/400/415 V

Input Power Factor

For linear and non-linear load

Load 25% 50% 75% 100%

Power Factor ≥ 0.95 > 0.99 > 0.99 > 0.99

EfficiencyThe table below provides average system efficiencies on a double conversionsingle unit with a balanced linear load, PF 0.9, AC input voltage 400 V / AC outputvoltage 400 V.

Efficiency on load PF 0.8 or for other input or output AC voltages is very close tothe values given below for PF 0.9, voltage input / 400 V output. Difference is lessthan + / -0.2%.

Minimum system efficiency is very close to average system efficiency. Thedifference is 0.2% maximum.

All these measures are coming from the production line ATE statistics performedon over 200 units.

System 25% load 50% load 75% load 100% load

250 kVA 89.7 93.2 93.8 93.8

300 kVA 90.5 93.5 93.9 93.6

400 kVA 92.2 94.1 94.3 94.1

500 kVA 91.4 94.3 94.5 94.3

8 990–3887C-001

Page 9: Galaxy 7000 - download.schneider-electric.com

Technical Data 250–500 kVA 380/400/415 V UPS

Efficiency Curves

250 kVA 400 V

300 kVA 400 V

400 kVA 400 V

990–3887C-001 9

Page 10: Galaxy 7000 - download.schneider-electric.com

250–500 kVA 380/400/415 V UPS Technical Data

500 kVA 400 V

Derating due to Load Power Factor

Batteries

Efficiency DC to AC

Efficiency in Battery Mode

Efficiency during discharge (output voltage 380 V or 400 V, inductive load PF 0.8 or0.9 )

% load 250 kVA 300 kVA 400 kVA 500 kVA

25 90.2 91.0 92.7 91.9

50 93.7 94.0 94.6 94.8

75 94.3 94.4 94.8 95.0

100 94.3 94.1 94.6 94.8

10 990–3887C-001

Page 11: Galaxy 7000 - download.schneider-electric.com

Technical Data 250–500 kVA 380/400/415 V UPS

DC Power in kW— PF 0.8

% load 250 kVA 300 kVA 400 kVA 500 kVA

25 55.4 65.9 86.3 108.8

50 106.7 127.6 169.1 211.0

75 159.1 190.7 253.2 315.8

100 212.1 255.0 338.3 422.0

DC Power in kW— PF 0.9

% load 250 kVA 300 kVA 400 kVA 500 kVA

25 62.3 74.1 97.1 122.4

50 120.0 143.6 190.2 237.4

75 179.0 214.5 284.9 355.3

100 238.6 286.9 380.6 474.8

End of Discharge Voltage

I batt(A) = battery current at the beginning of discharge. C10(Ah)= battery capacityin 10 hours

Between 0.1 <alpha<0.97, equation of battery shutdown voltage level is : U battmini(V/ cell) = (- 0.3x alpha) + 1.93

Example alpha = 0.5 Ubatt mini = 1.78V/ cell

Compliance

Directives for CE marking

Low voltage directive 2006/95/CEE

EMC directive 2004/108/CEE

Safety standard of UPS CEI/EN 62040-1 edition 2008/2008

EMC standard of UPS CEI/EN 62040–2 edition 2005/2006

Declaration of conformity with UPS harmonised standards and directives IEC62040-1 (Safety) and IEC 62040-2 (EMC) are available on demand.

990–3887C-001 11

Page 12: Galaxy 7000 - download.schneider-electric.com

250–500 kVA 380/400/415 V UPS Facility Planning

Facility Planning

Input Specifications

250 kVA 300 kVA 400 kVA 500 kVA

Voltage (V) 380 400 415 440 380 400 415 440 380 400 415 440 380 400 415 440

Nominal inputcurrent (A)1

369 351 337 319 441 420 403 382 586 558 536 507 735 700 672 636

Connections L1, L2, L3

Frequency (Hz) 45 to 66

Total HarmonicDistortion (THDI)

< 5% at full load

Input power factorcorrection

> 0.99 at load > 50%

Bypass Specifications

250 kVA 300 kVA 400 kVA 500 kVA

380 400 415 440 380 400 415 440 380 400 415 440 380 400 415 440

Nominal inputcurrent (A)

379 361 347 328 455 433 417 393 607 577 556 524 759 722 695 656

Connections 4-wire (L1, L2, L3 + N + PE)

Frequency (Hz) 45 to 66

Output Specifications

250 kVA 300 kVA 400 kVA 500 kVA

Voltage (V) 380 400 415 440 380 400 415 440 380 400 415 440 380 400 415 440

Nominal outputcurrent (A)

379 361 347 328 455 433 417 393 607 577 556 524 759 722 695 656

Connections 4-wire (L1, L2, L3 + N + PE)

Output capacity 150% for 30 seconds (normal operation)125% for 10 minutes (normal operation)

Output frequency(sync to mains)(Hz)

50/60 ± 0.1

Slew rate (Hz/Sec)

2

Total HarmonicDistortion (THDU)

< 2% ph/ph

Output powerfactor

0.9

Dynamic loadresponse

± 1%

Output voltageregulation

± 1%

Crest factor 2.7 2.9 3.0 3.3 2.3 2.4 2.5 2.8 2.3 2.4 2.5 2.8 2.6 2.7 2.8 3.0

12 990–3887C-001

1. For 400 V interphase voltages and a load with a power factor of 0.9.

Page 13: Galaxy 7000 - download.schneider-electric.com

Facility Planning 250–500 kVA 380/400/415 V UPS

Battery Specifications

Type Sealed lead-acid Vented lead-acid Ni-Cad

Min./Max. number of cells 264 / 288 264 / 288 422 / 468

Floating voltage per cell (V) 2.27 2.2 1.4

Min./Max. floating voltage (V) 600 / 654 581 / 634 600 / 655

Equalising voltage per cell (V) Not applicable 2.4 1.5

Boost voltage per cell (V) Not applicable 2.25 1.45

Min. voltage per cell (V) 1.65 to 1.9 1.65 to 1.9 1

Recharge current 0.1 x C10 0.1 x C10 0.2 C5

End of Discharge Current

Sealed lead-acid Vented lead-acid Ni-Cad

250 kVA 548/502 548/502 566/509

300 kVA 659/604 659/604 680/612

400 kVA 874/801 874/801 902/812

500 kVA 1090/999 1090/999 1125/1012

NOTE: The battery current is an average current Pn with a power factor of 0.9

Recommended Cable Sizes

Power Cables for Single UPS

AC cable sizes are determined for the TNS system and for the following cablecharacteristics:• copper single-core cables, type U1000 R02V• maximum length 100 m with a line voltage drop <3%• installation on perforated cable trays• XLPE-type insulation, single-layer trefoil formation• THDI between 15% and 33%• 35°C, at 400 V• grouped by four cables.Battery cable sizes are determined for:• installation on perforated metallic grounded cable trays,• copper, single-core cables, type U1000 R02V,• maximum length 25 m with a line voltage drop <1%.

UPS rating Minimum size (mm²)

Normal AC line Bypass AC line Load Battery

250 kVA 1 x 150 1 x 150 1 x 150 1 x 150

300 kVA 1 x 240 1 x 240 1 x 240 1 x 185

400 kVA 2 x 150 2 x 150 2 x 150 1 x 240

500 kVA 2 x 240 2 x 240 2 x 240 2 x 1502

990–3887C-001 13

2. Per battery cabinet.

Page 14: Galaxy 7000 - download.schneider-electric.com

250–500 kVA 380/400/415 V UPS Facility Planning

Power Cables for Parallel UPSs

Normal AC Line and Battery

AC cable sizes are determined for the TNS system and for the following cablecharacteristics:• copper single-core cables, type U1000 R02V• maximum length 100 m with a line voltage drop <3%• installation on perforated cable trays• XLPE-type insulation, single-layer trefoil formation• THDI between 15% and 33%• 35°C, at 400 V• grouped by four cables.Battery cable sizes are determined for:• installation on perforated metallic grounded cable trays,• copper, single-core cables, type U1000 R02V,• maximum length 25 m with a line voltage drop <1%.NOTE: Important: For > 200 kVA UPS, the output cables must be at least 6metres long (L ≥ 6 m).

UPS rating Minimum size (mm²)

Normal AC line Battery

250 kVA 1 x 150 1 x 150

300 kVA 1 x 240 1 x 185

400 kVA 2 x 150 1 x 240

500 kVA 2 x 240 2 x 1503

Bypass AC Line and Load

UPS rating Number of UPSs Total power rating(kVA)

Current on AC bypassor load (A)

Minimum size for ACbypass or load (mm²)

250 kVA 2 250 361 1 x 150

300 kVA 2 300 433 1 x 240

400 kVA 2 400 577 2 x 150

500 kVA 2 500 722 2 x 240

Frequency Converters

UPS rating Number of UPSs Total power rating(kVA)

Current on AC bypassor load (A)

Minimum size for load(mm²)

250 kVA 2 250 361 1 x 150

300 kVA 2 300 433 1 x 240

400 kVA 2 400 577 2 x 150

500 kVA 2 500 722 2 x 240

NOTE: The power cables between the UPS units and the upstream protectivedevices must be of the same size and length.NOTE: The power cables between the UPS units and the load must be of thesame size and length.

14 990–3887C-001

3. Per battery cabinet.

Page 15: Galaxy 7000 - download.schneider-electric.com

Facility Planning 250–500 kVA 380/400/415 V UPS

Integrated Parallel UPS Units with External Bypass Cabinet

UPS rating Number ofUPSs

Total powerrating (kVA)4

Current on AC bypass or load (A) Minimum size for load (mm²)

250 kVA 2 500 722 2 x 185

3 750 1083 3 x 300

4 1000 1443 4 x 240

300 kVA 2 600 866 2 x 240

3 900 1300 4 x 240

4 1200 1732 4 x 300

400 kVA 2 400 1154 4 x 185

3 1200 1732 4 x 300

4 1600 2308 4 x 500

500 kVA 2 500 1433 4 x 240

3 1500 2165 4 x 500

4 2000 2886 Consult us5

NOTE: The power cables between the UPS units and the upstream protectivedevices must be of the same size and length.NOTE: The power cables between the UPS units and the load must be of thesame size and length.

Parallel UPS Units with Static-Switch Cabinet (SSC)

UPS rating Numberof UPS

Total powerrating4 (kVA)

Current on AC bypass or load (A) Minimum size for load (mm²)

250 kVA 2 500 722 2 x 185

3 750 1083 3 x 300

4 1000 1443 4 x 240

300 kVA 2 600 866 2 x 240

3 900 1300 4 x 240

4 1200 1732 4 x 300

400 kVA 2 400 1154 4 x 185

3 1200 1732 4 x 300

4 1600 2308 4 x 500

500 kVA 2 500 1433 4 x 240

3 1500 2165 4 x 500

4 2000 2886 Consult us5

NOTE: The power cables between the UPS units and the upstream protectivedevices must be of the same size and length.NOTE: The power cables between the UPS units and the load must be of thesame size and length.

990–3887C-001 15

4. Not including redundant UPS units.5. Standard NFC15–100 limits the number of cables to four.

Page 16: Galaxy 7000 - download.schneider-electric.com

250–500 kVA 380/400/415 V UPS Facility Planning

Connection Terminals

UPS Cabinets

UPS rating

Phase terminal Earth terminal Battery terminal

Type of stud Number of holes x diameter (mm)

250 — 400 kVA 2 x M106 1 x 10 5 x 13 3 x 13

500 kVA N/A 4 x 13 5 x 13 3 x 13

SSC, SSC Maintenance, External Bypass Cabinets

Cabinets Phase terminal Earth terminal

Hole diameter (mm)

800 kVA 13 13

1200 kVA 13 13

2000 kVA 13 and 17 13

Recommended Overcurrent Protection

Recommended Upstream and Downstream Protection

Selection of Protection Devices

Time/current Curves for UPS input and Output Fuses

16 990–3887C-001

6. Maximum tightening torque 25 Nm.

Page 17: Galaxy 7000 - download.schneider-electric.com

Facility Planning 250–500 kVA 380/400/415 V UPS

UPS Output Current

UPS 250 kVA 300 kVA 400 kVA 500 kVA

In at 400 V (A) 361 433 577 722

Ioutput maximum7 (A) 1030 1030 1374 1975

Ioutput minimum7 (A) 793 793 1140 1470

Line-current Values

UPS 250 kVA 300 kVA 400 kVA 500 kVA

Continuous input current (A) 368 442 587 735

Input current at 1.25 In overload limited to 10 minutes(A)

441 530 706 881

Input current at 1.5 In overload limited to 30 seconds(A)

530 636 848 1058

Input / output fuse ratings (A) 630 630 800 1000

For U=400V and power factor=0.9.

Power Circuit Protection

UPS 250 kVA 300 kVA 400 kVA 500 kVA

CB Trip Unit CB Trip Unit CB Trip Unit CB Trip Unit

Normal ACsource

NSX 630N3P

Micrologic2.3

NSX 630N3P

Micrologic2.3

NS 800N 3P Micrologic2.0

NS 800N 3P Micrologic5.0

Bypass ACsource

NSX 630N4P

Micrologic2.3

NSX 630N4P

Micrologic2.3

NS 800N 4P Micrologic2.0

NS 800N 4P Micrologic5.0

Output NSX 100 N TM D 80 NSX 100 N TM D 80 NSX 100 N TM D 100 C125N D 125

C120N C80 C120N C80 NG 125N C 125 NSX 160N TM 160D

C120N B 125 C120N B 125 C125H C 125 NG125N D125

Icw 8(kA) 26.7 22

NOTE: If these downstream protection recommendations are not followed, ashort-circuit on an output circuit can result in a break in power longer than 20ms on all the other output circuits.

Permissible UPS overloads as a Function of Time

Normal Mode Operation

990–3887C-001 17

7. RMS current limit when inverter is coupled and bypass AC source is out of tolerances8. RMS shortime current value that can be carried without damage under condition defined by the standard IEC 62040-1.

Page 18: Galaxy 7000 - download.schneider-electric.com

250–500 kVA 380/400/415 V UPS Facility Planning

Bypass AC Mode or Static Switch Operation

Recommended Residual Current Protection

Requirements for residual current protection:

For single mains:• The same residual current protection can be used for input and bypass.For dual mains:• A transformer is required upstream of either the input or bypass.• Equip each source with a circuit breaker or switch with residual current

protection.The recommended minimum residual current protection is 3 A, provided theconditions defined in IEC60364-4-61 are complied with.

Battery Breaker Box Configurations

DANGERHAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

The battery breaker box must only be used with the Galaxy 7000 UPS.

Failure to follow these instructions will result in death or serious injury.

WARNINGHAZARD OF FIRE OR ARC FLASH• The battery breaker box must be connected as described in this manual.• The undervoltage coil must be wired to the UPS as shown on the diagrams.Failure to follow these instructions can result in death, serious injury, orequipment damage.

The below battery solutions can be made of several strings in parallel. All stringsmust be identical: same element block and the same number of blocks.

The below battery configurations and settings are based on nominal power at apower factor of 0.9 and 264 lead battery cells. For other battery configurationsplease contact Schneider Electric.

18 990–3887C-001

Page 19: Galaxy 7000 - download.schneider-electric.com

Facility Planning 250–500 kVA 380/400/415 V UPS

Battery Configurations with One Battery Breaker (QF1)

UPS Battery Backup Time Minutes

QF1 (NSX500S TM-DC)

BatteryStrings

Thermal/MagneticSetting (A)

250 kVA < 90 1 500/1250

300 kVA < 10 1 500/1250

Battery Configurations with Two Battery Breakers (QF1)

UPSBattery Backup TimeMinutes

Total Number ofBattery Strings

QF1-1(NSX500S TM-DC)

QF1-2(NSX500S TM-DC)

BatteryStrings

Thermal/MagneticSetting (A)

BatteryStrings

Thermal/MagneticSetting (A)

250 kVA Any 2 1 500/1250 1 500/1250

3 2 500/1250 1 500/1250

4 2 500/1250 2 500/1250

5 3 500/1250 2 500/1250

6 3 500/1250 3 500/1250

300 kVA Any 2 1 500/1250 1 500/1250

3 2 500/1250 1 500/1250

4 2 500/1250 2 500/1250

5 3 500/1250 2 500/1250

6 3 500/1250 3 500/1250

400 kVA < 90 2 1 500/1250 1 500/1250

4 2 500/1250 2 500/1250

6 3 500/1250 3 500/1250

500 kVA < 20 2 1 500/1250 1 500/1250

4 2 500/1250 2 500/1250

6 3 500/1250 3 500/1250

Battery Configurations with Three Battery Breakers (QF1)

UPS

BatteryBackupTimeMinutes

TotalNumber ofBatteryStrings

QF1-1(NSX500S TM-DC)

QF1-2(NSX500S TM-DC)

QF1-3(NSX500S TM-DC)

BatteryStrings

Thermal/MagneticSetting (A)

BatteryStrings

Thermal/MagneticSetting (A)

BatteryStrings

Thermal/MagneticSetting (A)

400 kVA Any 3 1 500/1250 1 500/1250 1 500/1250

5 2 500/1250 2 500/1250 1 500/1250

500 kVA Any 3 1 500/1250 1 500/1250 1 500/1250

5 2 500/1250 2 500/1250 1 500/1250

6 2 500/1250 2 500/1250 2 500/1250

990–3887C-001 19

Page 20: Galaxy 7000 - download.schneider-electric.com

250–500 kVA 380/400/415 V UPS Facility Planning

EnvironmentalOperating temperature 0 - 40 °C

Storage temperature with or without batteries -25 - 45 °C dry heat

Operating relative humidity 20- 95%, non-condensing

Storage relative humidity 20- 95%, non-condensing

Operating elevation 0–1500 m: 85% load1500–2000 m: 79% load2000–2300 m: 75% load2300–3000 m: 69% load3000–4000 m: 59% load

Storage elevation 0-10000 meters

Audible noise according to ISO 3746 (NFS 31 027)250-400 kVA 380/400/415/440 V500 kVA 380/400/415/440 V

75 dBA75 dBA

Protection class From IP20 to IP32

Colour Pearl dark grey (RAL 9023)

Heat Dissipation

250 kVA 300 kVA 400 kVA 500 kVA

Batteriesfullycharged

Batteriescharging

Batteriesfullycharged

Batteriescharging

Batteriesfullycharged

Batteriescharging

Batteriesfullycharged

Batteriescharging

Active power(kW)

112 225 135 270 180 360 225 450

Efficiency 93.2 93.8 93.5 93.6 94.1 94.1 94.3 94.3

Heat losses (kW) 8.2 14.9 9.4 18.6 11.3 22.6 13.6 27.2

Heat losses(calories/s)

1962 3554 2243 4449 2697 5395 3250 6501

Weights and Dimensions

UPS rating Weight (kg) Height (mm) Width (mm) Depth (mm)

250 kVA 990 1900 1412 855

300 kVA 990 1900 1412 855

400 kVA 1140 1900 1412 855

500 kVA 1500 1900 1812 855

Shipping Weights and Dimensions

UPS Weight (kg) Height (mm) Width (mm) Depth (mm)

160 kVA 860 2030 1525 970

200 kVA 860 2030 1525 970

250 kVA 1010 2030 1525 970

300 kVA 1010 2030 1525 970

400 kVA 1160 2030 1525 970

500 kVA 1520 2030 1925 970

20 990–3887C-001

Page 21: Galaxy 7000 - download.schneider-electric.com

Facility Planning 250–500 kVA 380/400/415 V UPS

ClearanceNOTE: Clearance dimensions are published for airflow and service accessonly. Consult with the local safety codes and standards for additionalrequirements in your local area.NOTE: The UPS system can be placed up against the wall. It is preferable toleave some space for easier maintenance.

NOTICEHAZARD OF OVERHEATING• Leave nothing on top of the UPS.• Maintain 500 mm of free space above the UPS.• Ensure that the UPS cabinet rests on its four cylindrical feet, (six feet for 500

kVA UPS).• Ensure that the distance between the UPS rear panel and the floor is less

than 10 mm.Failure to follow these instructions can result in equipment damage.

NOTE: Leave one meter of free space in front of the UPS for door opening.

990–3887C-001 21

Page 22: Galaxy 7000 - download.schneider-electric.com

250–500 kVA 380/400/415 V UPS Facility Planning

Default settings

System Settings (only updated when in load disconnect) Default setting

Nominal output rated voltage (ph-ph) 400 V (380, 400, or 415)

Frequency 50 Hz (50 or 60 Hz)

Frequency range 45 Hz to 66 Hz

Automatic start Forbidden

Rate of synchronization with AC Bypass source 1 Hz/s

Transfer to Bypass AC Allowed

AC bypass overload control active

AC Bypass frequency threshold tolerance 8 %

AC Bypass Static Switch operation when EPO Close

Shutdown mode (can only be set from service port) Never

PFC current ramp enable Yes

Break duration 100 ms

Remote command enabled No

Shutdown setting

Shutdown mode (can only be set from service port) Never

Other settings

Battery present No

Battery-test interval 1 month

Low battery warning voltage threshold 20 %

Low battery warning time threshold 1 minute

Deep battery discharge Forbidden

Display settings

Display language English

Date format mm/dd/yyyy

Temperature unit °C

Main screen Welcome screen

Password OOO

22 990–3887C-001

Page 23: Galaxy 7000 - download.schneider-electric.com

Drawings 250–500 kVA 380/400/415 V UPS

DrawingsNOTE: A comprehensive set of drawings is available on the engineeringwebsite at engineer.apc.com.NOTE: These drawings are for reference ONLY — subject to change withoutnotice.

990–3887C-001 23

Page 24: Galaxy 7000 - download.schneider-electric.com

250–500 kVA 380/400/415 V UPS Drawings

Galaxy 7000 Single System

24 990–3887C-001

Page 25: Galaxy 7000 - download.schneider-electric.com

Drawings 250–500 kVA 380/400/415 V UPS

Galaxy 7000 Single System with Transformer

990–3887C-001 25

Page 26: Galaxy 7000 - download.schneider-electric.com

250–500 kVA 380/400/415 V UPS Options

Options

Hardware Options

Battery Cabinets

• Galaxy 7000 Empty Battery Cabinet 700 mm

Auxiliary Cabinets

• Galaxy 7000 Empty Auxiliary Cabinet• Galaxy 7000 Empty Auxiliary Cabinet 700 mm• Galaxy 7000 400 V Top Connection

External Bypass

• Galaxy 7000 External Bypass

Battery Circuit Breaker Boxes

• Galaxy 7000 Battery Circuit Breaker Box 200 kVA 400 V• Galaxy 7000 Auxiliaries 250 kVA• Galaxy 7000 Auxiliaries 300 kVA• Galaxy 7000 Auxiliaries 400 kVA• Galaxy 7000 Auxiliaries 500 kVA

Protection and Cover Features

• Galaxy 7000 Transversal Auxiliaries• Galaxy 7000 400 V IP Cover

Static Switch Cabinets

• Galaxy 7000 Static Bypass Switch

Management Cards

• Network management card with ModBus/Jbus• Network management teleservice card• Environment sensor for network management cable

26 990–3887C-001

Page 27: Galaxy 7000 - download.schneider-electric.com

Options 250–500 kVA 380/400/415 V UPS

Configuration Options• Connection through the top• Isolation/Voltage matching transformer• Synchronisation module• B2000 or Cellwatch battery-monitoring system for block by block management• Lightning arrestor (built into the UPS cabinet)• Backfeed protection• Jbus/Modbus + Ethernet 10/100• Multi-standard communication cards• Jbus/Modbus + Ethernet 10/100 + Modem• Two ports with dry contacts and/or remote shutdown• Battery circuit breaker unit• Supervision and shutdown software• Enterprise Power Manager V.2

Parallel Capabilities

Integrated Parallel UPSs

Q1 Q5N

1

A BNormal AC

+�

QF1

2

Q4S

Q3BP

DByp ass AC

C

Q1 Q5N

1

A BNormal AC

+�

QF1

2

Q4S

Q3BP

DByp ass AC

C

UPS cabinet (1)PFC rectifier module (A)Inverter module (B)Battery chopper (C)Static-switch on AC bypassline (D)Batteries (2)

990–3887C-001 27

Page 28: Galaxy 7000 - download.schneider-electric.com

250–500 kVA 380/400/415 V UPS Options

Integrated Parallel UPSs with external bypass cabinet

Q3BP e xt

Q5Ne xt

3Byp ass AC

Q1 Q5N

1

A BNormal AC

+�

QF12

Q4S

Q3BP

DByp ass AC

C

Q1 Q5N

1

A BNormal AC

+�

QF12

Q4S

Q3BP

DByp ass AC

C

UPS cabinet (1)PFC rectifier module (A)Inverter module (B)Battery chopper (C)Static-switch on AC bypassline (D)Batteries (2)External bypass cabinet (3)

Parallel UPSs with SSC (Static-Switch Cabinet)

Up to eight UPS units can be connected in parallel with a Static-Switch Cabinet.

Normal AC

Byp ass AC

Normal AC

Q 5 N

Q3BP

Q4S

Q 1 Q 5 N

+ -Q F 1

Q 1 Q 5 N

1

3

1

A B

D

A B

C

C

+�

QF1

+�

QF1

2

2

UPS 1 cabinet (1)PFC rectifier module (A)Inverter module (B)Battery chopper (C)Batteries (2)SSC (3)Static-switch on AC bypassline (D)

28 990–3887C-001

Page 29: Galaxy 7000 - download.schneider-electric.com

Options 250–500 kVA 380/400/415 V UPS

Parallel UPSs with SSC and SSC maintenance cabinet

Normal AC

Byp ass AC

Normal AC

Q 5 N

Q3BP

Q4S

Q 1 Q 5 N

+ -Q F 1

Q 1 Q 5 N

1

3

1

A B

D

A B

C

C

+�

QF1

+�

QF1

2

2

QN

4

QM

UPS 1 cabinet (1)PFC rectifier module (A)Inverter module (B)Battery chopper (C)Batteries (2)SSC (3)Static-switch on AC bypassline (D)SSC maintenance cabinet(4)

Parallel UPSs set up as frequency converters

+�

QF1

2

+�

QF1

2

Q1 Q5N

Q1 Q5N

1

1

A B

A B

C

C

Normal AC

Normal AC

UPS cabinet (1)PFC rectifier module (A)Inverter module (B)Battery chopper (C)Batteries (2)

990–3887C-001 29

Page 30: Galaxy 7000 - download.schneider-electric.com

250–500 kVA 380/400/415 V UPS Limited Factory Warranty

Limited Factory Warranty

One-Year Factory WarrantyThe limited warranty provided by Schneider Electric in this Statement of LimitedFactory Warranty applies only to products you purchase for your commercial orindustrial use in the ordinary course of your business.

Terms of WarrantySchneider Electric warrants that the product shall be free from defects in materialsand workmanship for a period of one year from the date of product start-up whenstart-up is performed by Schneider Electric-authorized service personnel andoccurs within six months of the Schneider Electric shipment date. This warrantycovers repairing or replacing any defective parts including on-site labor and travel.In the event that the product fails to meet the foregoing warranty criteria, thewarranty covers repairing or replacing defective parts at the sole discretion ofSchneider Electric for a period of one year from the shipment date. For SchneiderElectric cooling solutions, this warranty does not cover circuit breaker resetting,loss of refrigerant, consumables, or preventive maintenance items. Repair orreplacement of a defective product or part thereof does not extend the originalwarranty period. Any parts furnished under this warranty may be new or factory-remanufactured.

Non-transferable WarrantyThis warranty is extended to the first person, firm, association or corporation(herein referred to by “You” or “Your”) for whom the Schneider Electric productspecified herein has been purchased. This warranty is not transferable orassignable without the prior written permission of Schneider Electric.

Assignment of WarrantiesSchneider Electric will assign you any warranties which are made bymanufacturers and suppliers of components of the Schneider Electric product andwhich are assignable. Any such warranties are assigned “AS IS” and SchneiderElectric makes no representation as to the effectiveness or extent of suchwarranties, assumes no responsibility for any matters which may be warranted bysuch manufacturers or suppliers and extends no coverage under this Warranty tosuch components.

Drawings, DescriptionsSchneider Electric warrants for the warranty period and on the terms of thewarranty set forth herein that the Schneider Electric product will substantiallyconform to the descriptions contained in the Schneider Electric Official PublishedSpecifications or any of the drawings certified and agreed to by contract withSchneider Electric if applicable thereto (“Specifications”). It is understood that theSpecifications are not warranties of performance and not warranties of fitness for aparticular purpose.

ExclusionsSchneider Electric shall not be liable under the warranty if its testing andexamination disclose that the alleged defect in the product does not exist or was

30 990–3887C-001

Page 31: Galaxy 7000 - download.schneider-electric.com

Limited Factory Warranty 250–500 kVA 380/400/415 V UPS

caused by end user or any third person misuse, negligence, improper installationor testing. Further, Schneider Electric shall not be liable under the warranty forunauthorized attempts to repair or modify wrong or inadequate electrical voltage orconnection, inappropriate on-site operation conditions, corrosive atmosphere,repair, installation, start-up by non-Schneider Electric designated personnel, achange in location or operating use, exposure to the elements, Acts of God, fire,theft, or installation contrary to Schneider Electric recommendations orspecifications or in any event if the Schneider Electric serial number has beenaltered, defaced, or removed, or any other cause beyond the range of the intendeduse.

THERE ARE NOWARRANTIES, EXPRESS OR IMPLIED, BY OPERATION OFLAW OR OTHERWISE, OF PRODUCTS SOLD, SERVICED OR FURNISHEDUNDER THIS AGREEMENT OR IN CONNECTION HEREWITH. SCHNEIDERELECTRIC DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY,SATISFACTION AND FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDERELECTRIC EXPRESS WARRANTIES WILL NOT BE ENLARGED, DIMINISHED,OR AFFECTED BYAND NO OBLIGATION OR LIABILITY WILL ARISE OUT OF,SCHNEIDER ELECTRIC RENDERING OF TECHNICAL OR OTHER ADVICE ORSERVICE IN CONNECTION WITH THE PRODUCTS. THE FOREGOINGWARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OFALL OTHERWARRANTIES AND REMEDIES. THE WARRANTIES SET FORTH ABOVECONSTITUTE SCHNEIDER ELECTRIC SOLE LIABILITYAND PURCHASER’SEXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES.SCHNEIDER ELECTRIC WARRANTIES RUN ONLY TO PURCHASER AND ARENOT EXTENDED TO ANY THIRD PARTIES.

IN NO EVENT SHALL SCHNEIDER ELECTRIC, ITS OFFICERS, DIRECTORS,AFFILIATES OR EMPLOYEES BE LIABLE FOR ANY FORM OF INDIRECT,SPECIAL, CONSEQUENTIAL OR PUNITIVE DAMAGES, ARISING OUT OF THEUSE, SERVICE OR INSTALLATION, OF THE PRODUCTS, WHETHER SUCHDAMAGES ARISE IN CONTRACT OR TORT, IRRESPECTIVE OF FAULT,NEGLIGENCE OR STRICT LIABILITY ORWHETHER SCHNEIDER ELECTRICHAS BEEN ADVISED IN ADVANCE OF THE POSSIBILITY OF SUCHDAMAGES, SPECIFICALLY, SCHNEIDER ELECTRIC IS NOT LIABLE FOR ANYCOSTS, SUCH AS LOST PROFITS OR REVENUE, LOSS OF EQUIPMENT,LOSS OF USE OF EQUIPMENT, LOSS OF SOFTWARE, LOSS OF DATA,COSTS OF SUBSTITUANTS, CLAIMS BY THIRD PARTIES, OR OTHERWISE.

NO SALESMAN, EMPLOYEE OR AGENT OF SCHNEIDER ELECTRIC ISAUTHORIZED TO ADD TO OR VARY THE TERMS OF THIS WARRANTY.WARRANTY TERMS MAY BE MODIFIED, IF ATALL, ONLY IN WRITING SIGNEDBYAN SCHNEIDER ELECTRIC OFFICER AND LEGAL DEPARTMENT.

Warranty ClaimsCustomers with warranty claims issues may access the SCHNEIDER ELECTRICworldwide customer support network through the SCHNEIDER ELECTRIC website: http://www.schneider-electric.com. Select your country from the countryselection pull-down menu. Open the Support tab at the top of the web page toobtain contact information for customer support in your region.

990–3887C-001 31

Page 32: Galaxy 7000 - download.schneider-electric.com

Printed in.Schneider Electric

Schneider Electric35 rue Joseph Monier92500 Rueil MalmaisonFrance

+ 33 (0) 1 41 29 70 00

www.schneider-electric.com

As standards, specifications, and design change from time to time,please ask for confirmation of the information given in this publication.

© 2011 – 2018 Schneider Electric. All rights reserved.

990–3887C-001