Upload
others
View
25
Download
2
Embed Size (px)
Citation preview
2014 INTERNATIONAL CONFERENCE ON COMPUTATION OF POWER, ENERGY, INFORMATION AND COMMUNICATION (ICCPEIC)
978-1-4799-3826-1/14/$31.00©2014 IEEE
Analysis of Unsymmetrical Fault using Symmetrical
Components for the Improvement of
Overcurrent Relay
Akshay V.APG Scholar
K.S.Rangasamy College of Technology,
Tiruchengode, Tamilnadu, India.
Abstract-Transient currents are quite common in power
systems. Transients can occur for both faults and switching
events. In order to reduce hazardous effects of overcurrent
caused by faults, the faster operation of overcurrent protection
is desirable which means maximum sensitivity of the
overcurrent relays. The high sensitivity sometimes causes mal-
trip of relay protection when there is no fault in the system.
This undesirable operation is due to transient events, such as
transformer energizing and induction motors. Therefore,
proper methods must be used to discriminate overcurrent due
to fault from the inrush current due to transformer energizing
and induction motor starting. The main protection system for
a given zone of protection is primary protection. Due to many
factors, in the event of fault a primary protection may fail to
operate and clear the fault gives the importance of backup
protection in the 13 bus radial system. The proposed method
using the concept of symmetrical components for analyzing the
improvement of overcurrent protection in radial system during
the fault and inrush current flowing. This extensive simulation
will be carrying out by using MATLAB/Simulink environment
power system block set toolboxes. The result shows using the
algorithm the new set value of 0.40 could help the overcurrent
relay to discriminate fault from no-fault.
Keywords- Unsymmetrical Faults, Overcurrent relay, Switching
Transients, Symmetrical component.
1. INTRODUCTION
In a power system consisting of generators,
transformers, transmission and distribution circuits, it is
inevitable that eventually some failure will occur
somewhere in the system. When a failure occurs on any part
of the system, it must be quickly detect and disconnect from
the system. There are two principle reasons for it. Firstly, if
the fault is not cleared quickly, it may cause unnecessary
interruption of service to the customers. Secondly, rapid
disconnection of faulted apparatus limits the amount of
damage to it and prevents the effects of fault from spreading
in to the other part of the system.
The detection of a fault and disconnection of a faulty
section or apparatus can be achieved by using fuses or
relays in conjunction with circuit breakers. A fuse performs
both detection and interruption functions automatically but
its use is limited for the protection of low-voltage circuits
only. For high voltage circuits relays and circuit breaker,
Dr. N LoganathanAssociate Professor
K.S.Rangasamy College of Technology,
Tiruchengode, Tamilnadu, India.
which performs the function of circuit interruption. The
protective relay is a device that detects the fault and initiates
the operation of the circuit breaker to isolate the defective
element from the rest of the system.
Overcurrent relay is one of the most important part
of the radial distribution networks[1].In [2] the sensitivity
improvement of overcurrent relay has been studied. The
high sensitivity sometimes causes mal-trip of relay
protection when there is no fault in the system. This
undesirable operation is due to transient events, such as
transformer energizing and induction motors. In [3], effects
of overcurrent on the operation of overcurrent relays due to
these switching have been studied. Therefore, proper
methods must be used to discriminate overcurrent due to
fault from the inrush current due to transformer energizing
and induction motor starting. In [4], the concept of
symmetrical components has been used and a method for
preventing the undesirable relay operations due to over
currents has been presented.
In order to avoid the mal-operation of the relay, the
proposed method based on variation of fundamental
component amplitude of current signal which describes a
criterion function using the concept of symmetrical
components is used for analyzing the improvement of
overcurrent protection in radial system during the inrush
current.
II. STUDY OF DIFFERENT CASES
In this part, the main features of over current due to
different cases (fault, transformer energizing and induction
motor starting) are described.
A. Induction Motor Starting
The starting of a large induction motors leads to a
current typically 5–6 times the rated current. Generally, the
starting current has a very high initial peak, which is
damped out after a few cycles, normally no more than two
cycles depending on the circuit time constant [5], and after
that drops rapidly to a multiple value of its nominal level,
and is maintained during most of the acceleration period.
The current is then smoothly reduced to the nominal value
that depends on the steady-state mechanical load of motor.
8
AKSHAY V.A, et.al.: ANALYSIS OF UNSYMMETRICAL FAULT USING SYMMETRICAL COMPONENTS FOR THE IMPROVEMENT
Solid-state starters and variable-frequency drives
(VFD) can keep line current during starting at any preset
value and obviate difficulties of direct across the line
starting [6]. If the utility power system is quite stiff then
direct on line starting will likely be the preferred, which
provides the highest possible starting torque without the use
of a drive, and the shortest acceleration times and most
economical solution for a typical variable-torque load, such
as a pump [7].The high amount of current due to this kind of
starting may cause a trip in a sensitive over-current relays.
The star-delta starting can roughly reduce the starting
currents to 3–4 times the motor full-load current. The
transient inrush current due to the temporary disconnection
of the motor from the supply line in so-called “open circuit
transition” switching procedure, which because of lower
cost is the most common method of star-delta starting,
should be considered. Current surges can typically attain
peak values of up to 20 times the motor full load current
rating and generally last for 10 to about 40 ms . The same
happens in the case of the auto-transformer motor starting.
These transient currents can influence the operation
of highly sensitive over-current relay, particularly when
many switching happen simultaneously. This may be
occurred during energizing a feeder that has not been used
over a long time, which may lead to high starting current
that affects the operation of relays. Therefore, fault current
must be diagnosed from these transient currents.
B. Transformer Energizing
When a transformer is energized, magnetizing inrush
current is expected. The magnitude of this current depends
on the factors such as switching instant, source impedance,
residual flux in the core, transformer size, and design. This
inrush current could reach values as high as 25 times full-
load current and will decay with time until a normal exciting
current value is reached [8]. The decay of the inrush current
may vary from times as short as 20–40 cycles to as long as
minutes for highly inductive circuits, which might have,
hazardous effect on the locally installed over-current relays.
According to one main characteristic of magnetizing current
is that its fundamental component amplitude varies with
time.
C. Faults
The fault analysis of a power system is required to
provide information for the selection of switchgear, setting
of relays and stability of system operation. Faults usually
occur in a power system due to
Insulation failure of equipment
Flashover of lines initiated by a lighting stroke
Permanent damage to conductors and towers or
accidental faulty operations
Faults may either be three – phases in nature
involving all three – phases in a symmetrical manner, or
may be asymmetrical where usually only one or two phases
may be involved. Faults may also caused either by short –
circuits to earth, between live conductors, or by broken
conductors in one or more phases. Sometimes simultaneous
faults may occur involving both both short – circuit and
broken conductor faults (also known as open – circuit fault).
1) Types of Faults
(i) Series fault or open circuit fault
One open conductor fault
Two open conductor fault
(ii) Shunt fault or Short circuit fault
Symmetrical fault or balanced fault
Three phase fault
(iii) Unsymmetrical fault or unbalanced fault
Line to ground (L-G) fault
Line to line (L-L) fault
Double line to ground (L-L-G) fault
A three phase fault is a condition where either all the
three phases of the system are short circuited to each other,
or all the three phases of the system are earthed. This type
of fault is defined as the simultaneous short circuit fault
which occurs at all the three phases and give rise to
symmetrical current. It occurs infrequently, but it is the
most severe type [9].
Thus in general, is a balanced condition and we just
needed to know the positive sequence network to analyze
faults. Typically, only 5% of the initial faults in a power
system are three phase faults with or without earth. Of the
unbalanced faults, 80% are the line – earth and 15% are
double line faults with or without earth and which can often
deteriorate to three – phase fault. Broken conductor faults
account for the rest.
III. PROPOSED METHOD
For any unbalanced or nonsymmetrical network, such
as unsymmetrical fault occurs or having unbalanced load,
symmetrical component conversion can decouple three-
phase system into three independent sequence equivalent
networks, namely positive, negative and zero sequence
network. Therefore these three sequence networks can be
analyzed separately. Then we can convert the sequence
value back into phase variables. This analysis procedure is
commonly used in analyzing the unbalanced system
network, including fault [10]. Symmetrical components can
be viewed as a mathematical tool on which we can entirely
based for analysis of system without converting back to
phase variable. For example, the amplitude of zero sequence
signifies the degree of unbalance, and therefore can be used
to detect the unbalanced fault.
A. Theoretical Background
The symmetrical component transformation for an
arbitrary three-phase set of variables (balanced or
unbalanced), for example, the three-phase current and
inverse transformation is given in (1)
9
2014 INTERNATIONAL CONFERENCE ON COMPUTATION OF POWER, ENERGY, INFORMATION AND COMMUNICATION (ICCPEIC)
Here I1, I2 and Io denote the positive, negative and zero
sequence respectively.
In general application in power system analysis, we
typically begin with information in “phase variables”
denoted by subscripts a, b, and c. Note that phase variables
corresponds to actual physical quantities. The value of
converting physical quantities to symmetrical components is
in visualizing and quantization the degree of unbalanced
system network. For a balanced three-phase system, it won’t
be difficult to calculate that the zero and negative sequence
components are zero, and the positive sequence component
is equal to phase a, no matter current or voltage.
Symmetrical components consist of three quantities
[11]: positive sequence (exists during all system conditions,
but is prevalent for balanced conditions on a power system
including three phase faults); negative-sequence (exist
during unbalanced conditions); zero-sequence (exist when
ground is involved in an unbalanced condition). Negative
and zero-sequence components have relatively large values
during unbalanced fault conditions on a power system and
can be used to determine when these fault conditions occur.
Negative sequence components indicate phase-to-phase,
phase-to ground, and phase-to-phase-to-ground faults. Zero
sequence components indicate phase-to-ground and phase -
to-phase-to ground faults.
Also 1+α+α2=0 if currents Ia , Ib and Ic are balanced
(i.e., Ia = I < 0, Ib = I <-1200 and Ic = I <120
0 ). Therefore,
existence of the negative components means that the system
is unbalanced except over a transient period that may be
because of different switching method or non-identical
saturated case of three-phase transformers, three phases are
almost affected simultaneously during switching event.
Consequently, [12] the negative component is not
considerably changed in this case. On the other hand, faults
are classified into symmetrical and asymmetrical parts. The
major feature of these faults is the large value of the
negative component. Therefore, the negative component in
the asymmetrical faults is considerable. For symmetrical
faults the negative component tends to zero. The criterion
function for discriminating fault from non-fault switching is
defined as follows. The criterion function for discriminating
fault from non fault switching is defined as follows:
Since there is a considerable negative component in the
asymmetrical fault case, according to criterion function the
value of R is close to zero. In the switching case, the
negative component is very small and R is close to 1.
In the switching case, the negative component is
very small and R is close to 1. The threshold value of R is
set as R<0.35 indicates the fault; otherwise, over current is
the result of switching. The suggested criterion is based on
the different behavior of the current components during
fault and non fault conditions and is independent of the
amplitude of the current which is advantageous. The reason
is that it operates based on the relative difference between
the negative and positive component of the current. The
suggested criterion function in the asymmetrical distribution
networks also operates properly. During the asymmetrical
fault, the negative component of current increases and the
value of R is much smaller than that before fault event.
Fig.1 Proposed Model
The improvement of overcurrent protection is shown
in Fig1. First, the analog input signal is converted to the
digital signal by a data acquisition unit and entered to the
relay characteristic and detector. If amplitude of the current
becomes larger than the relay setting, the detector unit
operates, if the value of R is smaller than the setting value, it
means that the fault occurs and the output of the AND gate
becomes 1. Now, if in 1 of the AND gate, considering the
relay characteristic, becomes 1, then the relay sends the trip
signal to the circuit breaker.
IV. SIMULATION RESULTS
To show the advantage of the proposed algorithm, the
network parameter of the 13-bus distribution system is
modeled using the MATLAB/Simulink in the Fig.2. In this
13 bus radial system 11kV is the generated voltage and is
stepped up to 11/33kV using step-up transformer for the
transmission and stepped down to 33/11 kV for distribution.
Several non fault events are applied to this system along
with some short circuit events at different times. The
simulation results show that how the proposed algorithm
could help the overcurrent relay to discriminate fault from
non-fault events. The following cases are presented here:
10
AKSHAY V.A, et.al.: ANALYSIS OF UNSYMMETRICAL FAULT USING SYMMETRICAL COMPONENTS FOR THE IMPROVEMENT
A. Normal Operation
In order to study different cases, the step down voltage
of 33/11kV is given to the resistive load. The Fig.3 shows the
voltage and current in bus bar 13 during normal operation.
Fig.3 Three Phase Voltage and Current in 13-Bus during
Normal Operation
B. Induction Motor Starting
In order to study an Induction Motor starting, Induction
motor starting is simulated on 13 Bus Distribution System. A
detailed study of a typical case is presented below. In this case
Induction Motor at busbar 13 is switched on at instant t =
2.50sec and three-phase currents are measured. Fig.4 shows
these three-phase currents. As shown in Fig.5, except over a
transient period, R is close to 1 and is larger than setting (0.40)
that shows nonfault case. In this case tripping signal is
prevented.
Fig.4 Three Phase Current due to Induction Motor
Starting
Fig.5 Value of R due to Induction Motor Starting
Fig.2 Simulated 13-Bus Radial System
11
2014 INTERNATIONAL CONFERENCE ON COMPUTATION OF POWER, ENERGY, INFORMATION AND COMMUNICATION (ICCPEIC)
C. Fault
i. Phase - Ground Fault
In this case a phase-ground fault occurs at busbar 13
at instant t = 2.5sec and three-phase currents are measured.
Fig.6 shows these three-phase currents. As shown in Fig.9, R
is close to zero (less than 0.40) that shows a fault case in
which the tripping signal is issued.
Fig.6 Three Phase Current due to Phase - Ground Fault
ii. Phase – Phase – Ground Fault
In this case a phase-phase-ground fault occurs at
busbar 13 at instant t = 0.2sec and three-phase currents are
measured. Fig.7 shows these three-phase currents. As shown
in Fig.9, R is close to zero (less than 0.40) that shows a fault
case in which the tripping signal is issued.
Fig.7 Three Phase Current due to Phase – Phase
Ground Fault
iii. Phase - Phase Fault
In this case a phase-phase fault occurs at busbar 13 at
instant t = 2.5sec and three-phase currents are measured. Fig.8
shows these three-phase currents. As shown in Fig.9, R is
close to zero (less than 0.40) that shows a fault case in which
the tripping signal is issued.
Fig.8 Three Phase Current due to Phase - Phase Fault
Fig.9 Value of R due to Fault
C. Simultaneous Induction Motor Starting and Fault
Occurrence
In this case a simultaneous motor starting and phase-
phase fault occurs at busbar 13 at instant t = 2.5sec and three-
phase currents are measured. Fig.10 shows these three-phase
currents. As shown in Fig.11, R is close to zero(less than 0.40)
that shows a fault case in which the tripping signal is issued.
Fig.10Three Phase Current Due to Simultaneous
Induction Motor Starting and Three Phase Fault
12
AKSHAY V.A, et.al.: ANALYSIS OF UNSYMMETRICAL FAULT USING SYMMETRICAL COMPONENTS FOR THE IMPROVEMENT
Fig.11 Value of R Due to Simultaneous Induction
Motor Switching and Phase – Ground Fault
In fact, one more advantage of the suggested algorithm
is that, in addition to the diagnosis of the fault in the
individual occurrence from the nonfault case, it enables to
discriminate a fault from simultaneous switching properly.
This is necessary because, if in the case of fault, the operation
of the relay is prevented and it is assumed switching case, it
may lead to a serious damage.
D. Primary and Backup Protection
In the case if unsymmetrical fault occur at bus bar 13 at
instant 2.5sec, the three-phase currents are measured at fault
cases and it shows that these currents are less than 0.40 which
indicates that there is a fault and the relay, R1 trips at instant
2.8sec. If primary protection R1 fails to trip the backup
protection R2 will trip at instant 3.1s and if R1 and R2 fail
Relay R3 will trip at instant 3.4sec is shown in Fig.12, which
gives zones of protection to the complete radial system.
V. CONCLUSION
In this paper, a simple method for improving
overcurrent relays operation has been introduced. The
suggested algorithm is based on the different behavior of the
positive and negative sequence current components during
fault and no-fault conditions and is independent of the current
amplitudes. Based on these differences, a criterion function
has been introduced. The case study was performed using the
simulation software MATLAB and several simulations were
performed in the 13 bus radial system.
The Induction Motor at bus bar 13 is switched on at
instant t = 2.50 seconds the inrush current produced at the
instant except over a transient period, the criterion function R
is close to 1 and is larger than setting (0.40) . During the
unsymmetrical faults injected at instant t = 2.50 seconds, the
criterion function R is close to zero and is less than setting
(0.40). Also simultaneously when induction motor starts and
fault occurs at instant 2.50 seconds, the criterion function R is
close to zero and is less than setting (0.40).
It was concluded that using the algorithm the new set
value of 0.40 could help the overcurrent relay to discriminate
fault from no-fault, considering that undesirable operation of
the overcurrent relays due to the switching is prevented. If
primary protection of relay fails in the 13 bus radial system
the importance of back up protection has been demonstrated
with the new method by simulating various cases during
unsymmetrical faults and induction motor starting.
REFERENCES
[1] A. Conde and E. Vazquez, (2011) “Application of a
Proposed Overcurrent Relay in Radial Distribution
Networks” Electric Power Systems Research Vol.81, pp.
570–579.
[2] Arturo Conde Enriquez and Ernesto Vazquez Martinez
(2007) “Sensitivity Improvement of Time Overcurrent
Relays” Electric Power Systems Research Vol.77, pp.
119–124.
[3] F. Wang and M.H.J. Bollen (2003) “Classification of
Component Switching Transients in the Viewpoint of
Protective Relays” Electric Power Systems Research
Vol. 64, pp. 197-207.
[4] S. Lotfi-fard, J. Faiz, M.R. Iravani, Improved over-
current protection using symmetrical components, IEEE
Trans. Power Deliv. 22 (2) (2007) 843–850.
[5] G.J. Rogers, D. Shirmohammadi, Induction machine
modeling for electromagnetic transient program, IEEE
Trans. Energy Convers. 2 (4) (1987) 622–628.
[6] G. Zenginobuz, I. Cadirci, M. Ermis, C. Barlak, Soft
starting of large induction motors at constant current
with minimized starting torque pulsations, IEEE Trans.
Ind. Appl. 37 (5) (2001) 1334–1347.
[7] J.A. Kay, R.H. Paes, J.G. Seggewiss, R.G. Ellis,
Methods for the control of large medium-voltage motors: Fig.12 Primary and Backup Protection during Fault
13
2014 INTERNATIONAL CONFERENCE ON COMPUTATION OF POWER, ENERGY, INFORMATION AND COMMUNICATION (ICCPEIC)
application considerations and guidelines, IEEE Trans.
Ind. Appl. 36 (6) (2000) 1688–1696.
[8] J. F. Witte, F. P. Decesaro, and S. R. Mendis,
“Damaging long-term over voltages on industrial
capacitor banks due to transformer energization inrush
currents,” IEEE Trans. Ind. Appl., vol. 30, no. 4,
pp.1107–1115, Jul./Aug. 1994.
[9] P.Venkatesh, B.V.Manikandan, S.Charles Raja,
A.Srinivasan “Electrical Power Systems Analysis,
Security and Deregulation”
[10] Mohsen Mohammadi Alamuti, Hassan Nouri, Rade M.
Ciric, and Vladimir Terzija (2012) “Intermittent Fault
Location in Distribution Feeders” IEEE Transactions on
Power Delivery, Vol. 27, No. 1, pp.96-103.
[11] K.M. EI-Naggar (2001) “A Fast Method for
Identification of Symmetrical Components for Power
System Protection” Electrical Power and Energy
Systems Vol. 23, pp. 813-817.
[12] A.F. Elneweihi, E.O. Schweitzer, M.W. Feltis (1993)
“Negative-Sequence Overcurrent Element Application
and Coordination in Distribution Protection” IEEE
Transactions on Power Delivery, Vol.8, No.3, pp. 915-
924.
[13] Javad Sadeh, Ehsan Bakhshizadeh, Rasoul Kazemzadeh
(2013) “A New Fault Location Algorithm for Radial
Distribution Systems Using Modal Analysis” Electrical
Power and Energy Systems Vol. 45, pp. 271–278.
[14] Mamdouh Abdel-Akher and Khalid Mohamed Nor
(2010) “Fault Analysis Of Multiphase Distribution
Systems Using Symmetrical Components” IEEE
Transactions On Power Delivery, Vol. 25, No. 4, pp.
2931- 2939.
[15] Bhuvanesh A. Oza and Sukumar M. Brahma (2005)
“Development of Power System Protection Laboratory
through Senior Design Projects” IEEE Transactions on
Power Delivery, Vol. 20, No. 2, pp. 532-537.
Akshay V.A was born in India in 1986. He
received his B.Tech degree in Electrical
and Electronics Engineering from
Mahatma Gandhi University, Kerala in
2009. He has three years experience in
Industries. He currently pursues Master
Degree in Power Systems Engineering at K.S.Rangasamy
College of Technology, Tamilnadu. His research interests
include Power system Protection, power quality.
Dr.N. Loganathan He was born in India, in
1970. He received B.E. degree in Electrical
and Electronics Engineering in Government
College of Engineering Salem in 1999 and
M.E degree in Power and Energy System
Engineering in University Vishveshwarya
College of Engineering, Bangalore, India and Ph.D. degree in
Anna University,Chennai, India in 2013. Currently he is
working as an Associate Professor at K.S.Rangasamy College
of Technology in the Department of Electrical and Electronics
Engineering, Tamilnadu, India. His research interest include in
High voltage insulation, and power system Engineering.
14