Upload
vishalgohel12195
View
284
Download
7
Embed Size (px)
Citation preview
TOPIC:- UNSYMMETRICAL FAULT
introduction
• Generator, transformer , and transmission line
• The fault which gives rise to unsymmetrical fault current are known as unsymmetrical fault.
• It makes system unbalanced.
How can fault occur
• Falling of tree on line
• Wind and ice loading on transmission line
• Vehicle colliding with supporting structures
• Birds shorting on lines
• Insulation failure
Unsymmetrical fault
• Single line to ground fault
• Line to line fault
• Double line to ground fault
Analysis of unsymmetrical faults using the bus impedance matrix
• we use the positive sequence bus impedance matrix for calculation of current and voltage during balanced three phase faults.
• This method is extended here to unsymmetrical fault by representing each sequence network as a bus impedance equivalent circuit.
• A bus impedance matrix can be computed for each sequence network by inverting the corresponding bus admittance network.
• ForSimplicity,resistance,shuntadmittance,non-rotating impedance load and pre fault load current are neglected.
• Show in the fig. the connection of sequence of equivalents for both symmetrical and unsymmetrical fault at bus n of N- bus three phase power system each bus impedance element are show subscrip = 0,1 and 2 that identified the sequence equivalent in which it is located.
• The prefault voltage Vf is included in the positive-sequence equivalent.
• show in the fig..the sequence components of the fault current for each type of fault at bus n are aa follows:
Balanced three phase faults :
Ia1 = Vf / Znn – 1
Ia0 = Ia2 = 0
Single line to ground fault : Ia0 = Ia1 = Ia2 = Vf / (Znn-0 + Znn-1 + Znn-2 +3Zf)
Line to line ground fault:
Ia1 = -Ia2 = Vf / Znn-1 + Znn-2 + Zf
Ia = 0
Double line to ground fault :
Ia1=Vf / Znn-1 [Znn-2 ( Znn-0 + 3Zf ) / Znn-2+Znn-0 + 3Zf ]
Ia2 = -Ia1 [Znn-0 + 3Zf / Znn-0 + 3Zf +Znn-2]
Ia0 = -Ia1 [Znn-2 / Znn-0 + 3Zf +Znn-2]