Upload
amar-ridhwan
View
251
Download
3
Embed Size (px)
Citation preview
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
1/74
CHAPTER 5
UNSYMMETRICALFAULT
REVISED BY : PN ZETTY NURAZLINDA ZAKARIAPREPARED BY: EN NASRUL HELMEI BIN HALIM
SCHOOL OF ELECTRICAL SYSTEM ENGINEERINGUniMAP
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
2/74
IntroductionMost of the faults occurs on power systems areunsymmetrical faults, which may consist of unsymmetrical short circuits, unsymmetrical faultsthrough impedance, or open conductors.
Unsymmetrical faults occur as:Single line-to-ground faultsLine-to-line-faultsDouble line-to-ground faults
The path of the fault current from line to line or line toground may or may not contain impedance.
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
3/74
Introduction (cont..)
One or two open conductors result inunsymmetrical fault, through either the breakingof one or two conductors e.g. the breaking of fuse
Since unsymmetrical fault causes unbalancedcurrents to flow in the system, the method of
symmetrical components is very useful in ananalysis to determine the currents and voltagesin the system after the occurrence of the fault.
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
4/74
Unsymmetrical Faults in Power
SystemsConsider a general power network in Fig. 1.
It is assumed that a faultoccurs at point F in thesystem, as a result of which currents I a , I b , I c
flow out of the system.V a , V b , V c are voltages of line a, b, c with respect toground. Fig. 1
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
5/74
Unsymmetrical Faults in Power
Systems (cont..)
Thevenin equivalents circuit : (a) zero, (b) positive and(c) negative sequence.
+
-
E a V a1
Z 1 I a1 +
-
V a2
Z 2 I a2 +
-
V a0
Z 0 I a0
Fig. 2
(a) (b) (c)
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
6/74
Unsymmetrical Faults in Power
Systems (cont..)The positive sequence voltages of
synchronous machines will be identicaland will equal the pre-fault voltage at faultpoint, F .
This voltage labeled as E a (refer Fig 2(b)).
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
7/74
Unsymmetrical Faults in Power
Systems (cont..)The sequence/symmetrical components of voltages at faultpoint can be expressed in terms of sequence currents andThevenin sequence impedance as (refer Fig 2):
2
1
0
2
1
0
2
1
0
0000
00
0
0
a
a
a
a
a
a
a
I I
I
Z Z
Z
E V V
V
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
8/74
And the phase voltages during fault;
2
1
0
2
2
1
1
111
a
a
a
c
b
a
V
V
V
aa
aa
V
V
V
Unsymmetrical Faults in Power
Systems (cont..)
1201
1201
;where
2a
a
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
9/74
Unsymmetrical Faults in Power
Systems (cont..)The sequence/symmetrical components of currents can beexpressed in terms of phase currents:-
c
b
a
a
a
a
I
I
I
aa
aa
I
I
I
2
2
2
1
0
1
1
111
31
1201
1201
;where
2a
a
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
10/74
Unsymmetrical Faults in Power
Systems (cont..)The phase currents are;
2
1
0
2
2
1
1111
a
a
a
c
b
a
I
I I
aa
aa
I
I I
1201
1201
;where
2
a
a
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
11/74
How to do fault analysis???Single-line-Ground Fault
Line-Line FaultDouble-Line-Ground Fault
What should we analyse???Component currents & voltagesPhase currents & voltages during fault
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
12/74
Single Line-to-Ground Faults
Caused by lightning or by conductorsmaking contact with grounded structures.
Fig. 3 shows a line-to-ground fault at F ina power system through a fault impedanceZ F .
The phases are so labeled that the faultoccurs on phase a .
REMEMBER : ZF Zn
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
13/74
Single Line-to-Ground Faults
At the fault point F , the currents out of the power systemand the line to ground voltages are constrained as follows:
Fig. 3
I b = 0 I c = 0 V a = I a Z f
i f Z f = 0; V a = 0
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
14/74
Single Line-to-Ground Faults
The symmetrical components of the fault currents are:
00
11
111
31
2
2
2
1
0 a
a
a
a I
aaaa
I I
I
From which it is easy to see that
aaaa I I I I 31
021
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
15/74
Single Line-to-Ground Faults
Fig 4: Connection of sequence network for a single line-to-ground fault
V a = 3I a1 Z F = I a Z F
3 Z F
aaaa I I I I 31
021
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
16/74
Single Line-to-Ground Faults
Phase a voltage in terms of symmetrical components is
1210
210
)( aa
aaaa
I Z Z Z E
V V V V
From the Thevenin equivalent sequence network;
f
aa Z Z Z Z
E I
30211 or
0021
1
f
aa
Z if
Z Z Z E
I
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
17/74
Single Line-to-Ground Faults
2
1
0
2
2
1
1
111
a
a
a
c
b
a
I
I
I
aa
aa
I
I
I
The fault currents is
1
021
3 a
aaa
a F
I
I I I
I I
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
18/74
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
19/74
Single Line-to-Ground Faults
case: syn. generator
Fig. 6
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
20/74
Exercise 1 A 100 MVA, 13. 8 kV, wye connected synchronousgenerator has a subtransient reactance X of 0.2 pu, anegative reactance X 2 of 0.25 pu, a zero sequencereactance of 0.1 pu and negligible resistance as in Fig. 6.
The neutral of generator is solidly grounded. Assume thatthe generator is initially unloaded and operating at ratedvoltage, and that a single line-to-ground fault occurs onphase a at the terminals of generator.
Evaluate the voltages and currents in each phase duringthe subtransient period immediately after the fault occurs.
Also, determine the line-to-line voltages at that time.Base : 100 MVA, 13.8 kV
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
21/74
Exercise 1: ANSWERS
Line currentsIa = 5.45590 o = 22.82 kA
Ib = 0Ic = 0
Line VoltagesVa = 0Vb = 0.983 -106 o
Vc = 0.983+106 o
Line-to-line voltagesVab = Va Vb = 0.98674 o
Vbc = Vb Vc = 1.890 -90o
Vca = Vc Va = 0.986 106 o
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
22/74
Example 5.1The one-line diagram of a simple power system is shown in Fig. 5.1. Theneutral of each generator is grounded through a current-limiting reactor of 0.25/3 per-unit on a 100 MVA base. The system data expressed in per-unit ona common 100 MVA base is tabulated below. The generators are running onno-load at their rated voltage and rated frequency with their rated e.m.f. inphase.
Fig. 5.1
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
23/74
Example 5.1 (cont..)
Item BaseMVA
VoltageRating
X 1 X 2 X 0
G 1 100 20kV 0.15 0.15 0.05G 2 100 20kV 0.15 0.15 0.05T 1 100 20/220kV 0.10 0.10 0.10
T 2 100 20/220kV 0.10 0.10 0.10L12 100 220kV 0.125 0.125 0.30L13 100 220kV 0.15 0.15 0.35
L23 100 220kV 0.25 0.25 0.7125
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
24/74
Example 5.1 (cont..)
Determine:a) The fault current when a single line-to-
ground fault occurs at bus 3 through afault impedance Z F = j0.1p.u.b) Phase Voltages at all buses during fault
at bus 3
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
25/74
Solution:
Step 1:Draw the positive, negative and zero sequence
networks of the system.
Step 2:
Reduce the networks to their Thevenin equivalentcircuit viewed from the faulted bus (bus 3)
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
26/74
Solution (cont..):
Positive sequence network
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
27/74
Solution (cont..):
Using to Y conversion
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
28/74
Solution (cont..):
0357.0
25.015.0125.0)15.0)(125.0(
1
j
j j j j j
Z s
0595.0
25.015.0125.0)25.0)(125.0(
2
j
j j j j j
Z s
0714.0
25.015.0125.0)25.0)(15.0(
3
j
j j j j j
Z s
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
29/74
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
30/74
Solution (cont..):
Negative sequence network
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
31/74
Solution (cont..):
Negative sequence network
22.0
0714.03095.02857.0
)3095.0)(2857.0(2
j
j j j j j
Z
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
32/74
Solution (cont..):
Zero sequence network
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
33/74
Solution (cont..):
0771.0
7125.035.03.0)35.0)(3.0(
1
j
j j j j j
Z s
183.0
25.015.0125.0)7125.0)(35.0(
3
j
j j j j j
Z s
1569.0
7125.035.03.0)7125.0)(3.0(
2
j
j j j j j
Z s
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
34/74
Solution (cont..):
Zero sequence network
35.0
183.02569.04771.0
)2569.0)(4771.0(0
j
j j j j j
Z
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
35/74
Solution (cont..):
The symmetrical components of the faultcurrents are:
p.u.9174.0)1.0(335.022.022.0
0.1
3021021
j j j j j
Z Z Z Z E
I I I f
aaaa
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
36/74
Solution (cont..):The fault current,
0
0
7523.2
9174.0
9174.0
9174.0
1
1
1111
1
111
2
2
2
1
0
2
2
j
j
j
j
aa
aa
I
I
I
aa
aa
I
I
I
a
a
a
c
b
a
..7523.2 u p j I I a F
A
kV
MVA I F
29.722
7523.243.262
7523.22203
100
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
37/74
Solution (cont..):
The symmetrical components of bus voltageduring fault are
2018.0
7982.0
3211.0
)9174.0(22.000
0)9174.0(22.00
00)9174.0(35.0
0
0.1
0
00
0000
0
0
2
1
0
2
1
0
2
1
0
j j
j j
j j
I
I
I
Z
Z Z
E
V
V
V
a
a
a
a
a
a
a
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
38/74
Solution (cont..):Voltage at bus 3 during fault
56.1250647.1
56.1250647.1
02752.02018.0
7982.0
3211.0
1
1
111
1
1
111
2
2
2
1
0
2
2
aa
aa
V
V
V
aa
aa
V
V
V
a
a
a
c
b
a
kV234.234
kV2200647.1
p.u.56.1250647.1
kV234.234
kV2200647.1
p.u.56.1250647.1
60.544kVkV2202752.0
p.u.02752.0
c
c
b
b
a
a
V
V
V
V
V
V
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
39/74
Line-to-Line FaultsFig. 7 shows a line-to-linefault at F in a power systemthrough a fault impedanceZ F . The phases can alwaysbe relabeled, such that thefault is on phases b and c.
The currents and the voltages at the fault can be expressed
as
I a = 0 I b = - I c V b - V c = I b Z F
i f Z F = 0; V b = V c
Fig. 7Z F
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
40/74
Line-to-Line Faults
The symmetrical components of the fault currents are:
b
b
a
a
a
I I
aaaa
I I
I 0
11
111
31 22
2
1
0
From which it is easy to see that
120 ;0 aaa I I I
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
41/74
Line-to-Line Faults
Fig. 8: Connection of sequence networks for a line-to-line faults
Z F
12 aa I I V a = I a1 Z F = -I a2 Z F
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
42/74
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
43/74
Line-to-Line Faults
Phase a voltage in terms of symmetrical components is
2111
21
Z I Z I E
V V V
aaa
aaa
From the Thevenin equivalent sequence network;
f
aa Z Z Z
E I
211 or
021
1
f
aa
Z if
Z Z E
I
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
44/74
Line-to-Line Faults
2
1
2
2
0
1
1
111
a
a
c
b
a
I
I
aa
aa
I
I
I
Hence, the fault currents is;
Since the phase currents are as follows;
since I a0 = 0
cb F I I I
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
45/74
Line-to-Line FaultsTherefore, phase voltages during fault are;
2
12
2
0
11
111
a
a
c
b
a
V V
aaaa
V V
V
since V a0 = 0
2
2
1
21
2
21
aac
aab
aaa
V aaV V
aV V aV
V V V Hence;
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
46/74
Line-Line Faults
case: syn. generator
Fig 9
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
47/74
Exercise 2 A 100 MVA, 13. 8 kV, wye connected synchronousgenerator has a subtransient reactance X of 0.2 pu, anegative reactance X 2 of 0.25 pu, a zero sequencereactance of 0.1 pu and negligible resistance as in Fig. 9.
The neutral of generator is solidly grounded. Assume thatthe generator is initially unloaded and operating at ratedvoltage, and that a line-to-line fault occurs between phaseb an d c at the terminals of generator.
Evaluate the voltages and currents in each phase duringthe subtransient period immediately after the fault occurs. Also, determine the line-to-line voltages at that time.Base : 100 MVA, 13.8 kV
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
48/74
Exercise 2: ANSWERS
Line currentsIa = 0
Ib= 3.849180 o
Ic = 3.8490 = 16.1 kA
Line VoltagesVa = 1.1120 o
Vb = 0.556180 o
Vc = 0.556180 o
Line-to-line voltagesVab = Va Vb = 1.6680 o
Vbc = Vb
Vc= 00 o
Vca = Vc Va = 1.668180 o
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
49/74
Example 5.2
Repeat Example 5.1 when a line-to-line fault occur at bus 3 through a fault impedance Z F = j0.1 p.u.
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
50/74
Solution:zero sequence impedance, Z 0 = j0.35 p.u.positive sequence impedance, Z 1 = j0.22 p.u.negative sequence impedance, Z 2 = j0.22 p.u.
The symmetrical components of fault currents
00a I
p.u.8519.1
1.022.022.01
21
21
j
j j j
Z Z Z
E I I
F
aaa
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
51/74
Solution (cont..)
The phase currents
2075.3
2075.3
0
8519.1
8519.1
0
1
1
111
11
111
2
2
2
1
0
2
2
j
j
aa
aa
I I
I
aaaa
I I
I
a
a
a
c
b
a
The fault current,
..2075.3 u p j I I I cb F
A
kV
MVA I F
74.8412075.343.262
2075.32203
100
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
52/74
Solution (cont..):
The symmetrical components of bus voltageduring fault are
4074.0
5926.0
0
)8519.1(22.000
0)8519.1(22.00
00)0(35.0
0
0.1
0
00
00
00
0
0
2
1
0
2
1
0
2
1
0
j j
j j
j
I
I
I
Z
Z
Z
E
V
V
V
a
a
a
a
a
a
a
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
53/74
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
54/74
Double Line-to-Ground FaultsFig. 10 shows a doubleline-to-ground fault at F in a power system. The
fault may in generalhave an impedance Z F as shown.
Fig. 10
The currents and the voltages conditions at the fault areexpressed as
I a = 0or
I a0 +I a1 +I a2 = 0
V b = V c = (I b + I c )Z F
i f Z F = 0; V b = V c = 0
Z F
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
55/74
Double Line-to-Ground FaultsThe symmetrical components of voltages at F are:
b
b
a
a
a
a
V
V
V
aa
aa
V
V
V
2
2
2
1
0
1
1
111
3
1
))((31 2
21 baaa V aaV V V
Where V c = V b
Therefore;
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
56/74
Double Line-to-Ground Faults
f a0
f a2a1a0
f a2a12
a0a22
a1a0
f c b b
Z3I
]ZII[2I)]ZaIIa(I)IaaI[(I
)ZI(IV
a2a1
a1a12
a0 b
VVwhere
aVVaVV
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
57/74
Double Line-to-Ground Faults
;ISolve
VVZ3I
a)V(aVZ3I
a0
a1a0f a0
a12
a0f a0
F
aaa Z Z Z I E
I 32110
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
58/74
Double Line-to-Ground Faults
;ISolve
ZIZIE
VV
a2
2a21a1a
a2a1
2
112 Z
Z I E I
aaa
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
59/74
Double Line-to-Ground Faults
;ISolve
)II(I
0III
a1
a0a2a1
a0a2a1
)3()3(
))3//((
02
021
021
1
F
F
a
F
aa
Z Z Z Z Z Z
Z
E Z Z Z Z
E I
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
60/74
Double Line-to-Ground Faults
Fig. 11: Connection of sequence network for a double line-to-groundfault
3 Z F
3 Z F
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
61/74
Double Line-to-Ground Faults
The symmetrical components of fault currents isgiven by;
)3()3(
))3//((
02
021
0211
F
F
a
F
aa
Z Z Z Z Z Z Z
E
Z Z Z Z E
I 2
112 Z
Z I E I aaa
F
aaa Z Z
Z I E I 32
110
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
62/74
Double Line-to-Ground Faults
The fault currents is
0
210
212
022
10
3
2
)()(
a
aaa
aaaaaa
cb F
I
I I I
aI I a I I aaI I I I I
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
63/74
Double Line-to-Ground FaultsPhase currents during fault ;
Phase voltages during fault ;
2
2
10
21
2
0
210
aaac
aaab
aaaa
V aaV V V
aV V aV V
V V V V
22
10
21
2
0
210
aaac
aaab
aaaa
I aaI I I aI I a I I
I I I I
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
64/74
Double Line-to-Ground Faults
case:syn. generator
Fig 12
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
65/74
Exercise 3 A 100 MVA, 13. 8 kV, wye connected synchronousgenerator has a subtransient reactance X of 0.2 pu, anegative reactance X 2 of 0.25 pu, a zero sequencereactance of 0.1 pu and negligible resistance as in Fig. 12.
The neutral of generator is solidly grounded. Assume thatthe generator is initially unloaded and operating at ratedvoltage, and that a double line to ground fault occursbetween phase b an d c to g ro u n d at the terminals of generator.Evaluate the voltages and currents in each phase duringthe subtransient period immediately after the fault occurs.
Also, determine the line-to-line voltages at that time.Base : 100 MVA, 13.8 kV
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
66/74
Exercise 3: ANSWERS
Line currentsIa = ?Ib = ?Ic = ?
Line VoltagesVa = ?Vb = ?Vc = ?
Line-to-line voltagesVab = Va Vb = ?Vbc = Vb Vc = ?Vca = Vc Va = ?
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
67/74
Example 5.3
Repeat Example 5.1 when a double line-to-ground faultoccur at bus 3 through a fault impedance Z F = j0.1 p.u.
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
68/74
Solution:
zero sequence impedance, Z 0 = j0.35 p.u.positive sequence impedance, Z 1 = j0.22 p.u.negative sequence impedance, Z 2 = j0.22 p.u.
The symmetrical components of fault currents
..6017.2
))1.0(335.0(22.0))1.0(335.0(22.0
22.0
1
))3//(( 0211
u p j
j j j j j
j
Z Z Z Z E
I F
aa
..9438.1
22.0)22.0)(6017.2(1
2
112
u p j
j j j
Z Z I E
I aaa
6579.0
3.035.0)22.0)(6017.2(1
3211
0
j
j j j j
Z Z Z I E
I F
aaa
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
69/74
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
70/74
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
71/74
Solution (cont..):Voltage at bus 3 during fault
1801974.0
1801974.0
00855.14276.0
4276.0
2303.0
1
1
111
1
1
111
2
2
2
1
0
2
2
aa
aa
V
V
V
aa
aa
V
V
V
a
a
a
c
b
a
kV43.43
kV2201974.0
p.u.1801974.0
kV43.43
kV2201974.0
p.u.1801974.0
8.81kV32kV2200855.1
p.u.00855.1
c
c
b
b
a
a
V
V
V
V
V
V
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
72/74
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
73/74
Exercise 4
Item MVA Voltage X X1 X2 X0Generator (Y-grounded)
25 11 kV 15% 15% 10%
Transformer T1 &T2( -Ygrounded)
25 11/66 kV 10% 10% 5%
Motor (Y grounded)
25 11 kV 15% 15% 10%
Line 25 66 kV 10% 10% 5%
Figure 13
7/30/2019 3 Unsymmetrical Faults Eet308 Updated Sv
74/74