8
® ® Job Name: Job Number: Model Numbers: Page SPECIFICATION SUBMITTAL 369355 Rev B 1 09.02.11 Power Modules 3-Wire Fluorescent Power Module Model Number PHPM-3F-DV-WH PHPM-3F-120-WH Capacity 16 A 16 A Control Power 120 V~ 120 V~ 3-Wire Fluorescent Power Module Description • Provides capability for a zone on a GRAFIK EyeR control unit (or other product) to dim fluorescent lights that have Lutron Hi-lumeR and Eco-10R (Eco Series) line-voltage control electronic dimming ballasts. • Utilizes SoftswitchR arcless switching technology. • Up to 3 power modules may be wired on a single GRAFIK EyeR zone. • Models available for 120 V~ control power. • Models available for 120 V~ or 120 - 277 V~ load power. Works with 120 V~ versions of: • Lutron 3-wire fluorescent dimmers (consult Lutron for ViertiR); see approved list in the dimmers & switches specification guide at www.lutron.com • GRAFIK EyeR QS control units • GRAFIK EyeR 3000 Series control units • LP, LCP, and GP dimming panels • HomeWorksR and HomeWorksR QS remote power panels Models and Capacities Load Power 120 - 277 V~ 120 V~ ®

3-Wire Fluorescent Power Module Spec · 3-Wire Fluorescent Power Module PHPM-3F-DV-WH PHPM-3F-120-WH 369355 369-355 GRAFIK Eye Eco-10 Eco QS 3000 LP LCP GP HomeWorks Created Date

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: 3-Wire Fluorescent Power Module Spec · 3-Wire Fluorescent Power Module PHPM-3F-DV-WH PHPM-3F-120-WH 369355 369-355 GRAFIK Eye Eco-10 Eco QS 3000 LP LCP GP HomeWorks Created Date

®

®

Job Name:

Job Number:

Model Numbers:

PageSPECIFICATION SUBMITTAL

369355 Rev B 1 09.02.11

Power Modules3-Wire Fluorescent Power Module

Model Number

PHPM-3F-DV-WH

PHPM-3F-120-WH

Capacity

16 A

16 A

Control Power

120 V~

120 V~

3-Wire Fluorescent Power Module

Description

•ProvidescapabilityforazoneonaGRAFIKEyeR controlunit(orotherproduct)todimfluorescentlightsthathaveLutronHi-lumeRand Eco-10R(EcoSeries)line-voltagecontrolelectronicdimmingballasts.

•UtilizesSoftswitchRarclessswitchingtechnology.•Upto3powermodulesmaybewiredonasingleGRAFIKEyeRzone.

•Modelsavailablefor120V~controlpower.•Modelsavailablefor120V~or120-277V~ loadpower.

Works with 120 V~ versions of:

•Lutron3-wirefluorescentdimmers(consultLutronforViertiR);seeapprovedlistinthedimmers&switchesspecificationguideatwww.lutron.com

•GRAFIKEyeRQScontrolunits•GRAFIKEyeR3000Seriescontrolunits•LP,LCP,andGPdimmingpanels•HomeWorksRandHomeWorksRQSremotepowerpanels

Models and Capacities

Load Power

120-277V~

120 V~

®

Page 2: 3-Wire Fluorescent Power Module Spec · 3-Wire Fluorescent Power Module PHPM-3F-DV-WH PHPM-3F-120-WH 369355 369-355 GRAFIK Eye Eco-10 Eco QS 3000 LP LCP GP HomeWorks Created Date

®

®

Job Name:

Job Number:

Model Numbers:

PageSPECIFICATION SUBMITTAL

369355 Rev B 2 09.02.11

Power

•Controlvoltage:120V~•Loadvoltage:120V~onlyforPHPM-3F-120-WH

120–277V~forPHPM-3F-DV-WH•Capacity:Full16A

120 V~:1920W 120–277V~:1920–4432W

•Frequency:50/60Hz,phase-to-neutral.•Load(output)power:Phaseindependentofcontroldevice/controlvoltage.

Sources/Load Types

•OperatesLutronRHi-lumeR,Eco-10R(EcoSeries),CompactSET,EcoSystemR,andEcoSystemRCompactline-voltagecontrolelectronicdimmingballastswithasmoothcontinuousSquareLawdimmingcurve.

Key Design Features

•PatentedRTISSTcircuitrycompensatesinrealtimeforincominglinevoltagevariations:Compensatesfor+/-2%changeinRMSvoltage/cycleand +/-2%Hzchangeinfrequency/second.

•Providesair-gapoff.•Moduleprotectsitselfduringtemporaryover-currentconditionsondimmedoutput.•TwoLEDsonfrontofunitprovidediagnosticinformation (visiblewhenfaceplateisremoved).

Terminals

•Acceptuptotwo12AWG(2.5mm2)wires.

Environment

•32to104°F(0to40°C).Relativehumiditylessthan90%non-condensing.•Indooruseonly.•Maximumheatoutputofmodule:15BTU/hour.

Mounting

•Surfaceorrecessmount.•PowermoduleisULtestedandapprovedforuseinspacesdesignedforenvironmentalairhandling.

Specifications

Power Modules3-Wire Fluorescent Power Module®

Page 3: 3-Wire Fluorescent Power Module Spec · 3-Wire Fluorescent Power Module PHPM-3F-DV-WH PHPM-3F-120-WH 369355 369-355 GRAFIK Eye Eco-10 Eco QS 3000 LP LCP GP HomeWorks Created Date

®

®

Job Name:

Job Number:

Model Numbers:

PageSPECIFICATION SUBMITTAL

369355 Rev B 3 09.02.11

•Mountin2-gangU.S.wallbox3.5in (89mm)deepor4x4in(102x102mm) junctionbox2.1indeep(53mm).

•Indoorsonly.•Thisdevicegeneratesheat;mountonlywhereambienttemperatureis32to104°F(0to40°C).

•Mountwitharrowsfacinguptoensureadequatecooling.

•Allow4.5in(114mm)aboveandbelowunitandbetweenfaceplateswhenmountingseveralinaverticallayout.

•Mountsoline(mains)voltagewiringisatleast6ft(1.8m)fromsoundorelectronicequipmentandwiring.

•Mountwithin7°oftruevertical.

Mountto4x4in(102x102mm),2.1in(53mm)deep U.S.junctionbox

Mountto2-gangU.S.wallboxDimensions and Mounting

6.3in (160mm)

1.0in(25mm)

Mountto4x4in(102x102mm),2.1in(53mm)deep U.S.junctionboxwithbarrier (for277V~modelifrequiredbylocalelectricalcode)

1.2in(30.5mm)

5.1in (129.5mm)

Barrier

Power Modules3-Wire Fluorescent Power Module®

Page 4: 3-Wire Fluorescent Power Module Spec · 3-Wire Fluorescent Power Module PHPM-3F-DV-WH PHPM-3F-120-WH 369355 369-355 GRAFIK Eye Eco-10 Eco QS 3000 LP LCP GP HomeWorks Created Date

®

®

Job Name:

Job Number:

Model Numbers:

PageSPECIFICATION SUBMITTAL

369355RevB409.02.11

•Pull12AWG(2.5mm2)copper(Cu)wires(75°C/167°Fminimum)forinputpowerandloadcircuit.•Strip1/2in(12mm)insulationfromwiresbeforeconnecting.•Runseparateneutralforloadcircuit-nocommonneutrals.

Wiring

Note: Thepowermodulemaybeonthesamecircuitasthecontrolunitonlyifthetotalloaddoesnotexceedtheratingofthebreaker.

Single Power Feed

1 2 3 4 5 6 L N

H/L

N

SH

DH

H/LN

LutronR Ballast

GRAFIKEyeR QS

Zonein

ControlNeutral

Wiretoappropriatezone

LegendH/L Hot/LiveN NeutralSH SwitchedHotDH DimmedHot Ground

NotUsed

Circuitbreaker

120 V~ {

Power Modules3-Wire Fluorescent Power Module®

Page 5: 3-Wire Fluorescent Power Module Spec · 3-Wire Fluorescent Power Module PHPM-3F-DV-WH PHPM-3F-120-WH 369355 369-355 GRAFIK Eye Eco-10 Eco QS 3000 LP LCP GP HomeWorks Created Date

®

®

Job Name:

Job Number:

Model Numbers:

PageSPECIFICATION SUBMITTAL

369355 Rev B 5 09.02.11

Multiple Power Feeds

Wiring

Theloadbreakermaybeonadifferentphasethanthecontrolbreaker.

1 2 3 4 5 6 L N

H/L

N

SH

DH

H/L

N

NH/L

LutronR Ballast

GRAFIKEyeR QS

Zonein

ControlNeutral

Wiretoappropriatezone

LegendH/L Hot/LiveN NeutralSH SwitchedHotDH DimmedHot Ground

NotUsed

Loadbreaker

Controlbreaker

120 V~}

Loadwiring1{

1Loadfeed:120V~forPHPM-3F-120-WH; 120–277 V~forPHPM-3F-DV-WH

Power Modules3-Wire Fluorescent Power Module®

Page 6: 3-Wire Fluorescent Power Module Spec · 3-Wire Fluorescent Power Module PHPM-3F-DV-WH PHPM-3F-120-WH 369355 369-355 GRAFIK Eye Eco-10 Eco QS 3000 LP LCP GP HomeWorks Created Date

®

®

Job Name:

Job Number:

Model Numbers:

PageSPECIFICATION SUBMITTAL

369355 Rev B 6 09.02.11

Wiring Multiple Power Modules to a Single GRAFIK EyeR Zone

Shownwithseparatefeedsforcontrolandloads.Allbreakersmustbeturnedoffpriortoinstallingorservicingthemodules.Upto3powermodulesmaybewiredtoasinglezone.

1 2 3 4 5 6 L N

H/L

N

DH

H/L

N

DH

H/L

N

DH

H/L

N

H/L

N

H/L

N

N

H/L

SH

SH

SH

LutronR Ballast

GRAFIKEyeR QS

ZoneinControlNeutral

Wiretoappropriatezone

Loadbreaker

LutronR Ballast

ZoneinControlNeutral

Loadbreaker

LutronR Ballast

ZoneinControlNeutral

Loadbreaker

Controlbreaker

Loadwiring1 forPowerModule#1 {Loadwiring1 forPowerModule#2 {Loadwiring1 forPowerModule#3 {

1Loadfeed:120V~forPHPM-3F-120-WH;120–277 V~forPHPM-3F-DV-WH

120 V~}

Power Modules3-Wire Fluorescent Power Module®

Page 7: 3-Wire Fluorescent Power Module Spec · 3-Wire Fluorescent Power Module PHPM-3F-DV-WH PHPM-3F-120-WH 369355 369-355 GRAFIK Eye Eco-10 Eco QS 3000 LP LCP GP HomeWorks Created Date

®

Job Name:

Job Number:

Model Numbers:

PageSPECIFICATION SUBMITTAL

369355RevB709.02.11

Power Modules3-Wire Fluorescent Power Module®

Note: Thepowermodulemaybeonthesamecircuit/controlzoneasthecontroldeviceonlyifthetotalloaddoesnotexceedtheratingofthebreaker(120V~only).

Multi-location Wiring

H/L

N

SH

DH

H/L

N

LutronR Ballast

LegendH/L Hot/LiveN NeutralSH SwitchedHotDH DimmedHot Ground NotUsed

Circuitbreaker

{

3-wirefluorescentdimmer 120 V~(maindimmer)

3-wirefluorescentdimmer 120 V~(accessory/companiondimmeror 3-wayswitch)

H/L120 V~

N

Loadwiring(seeNotebelow)

Note: Loadfeed:120V~forPHPM-3F-120-WH; 120–277 V~forPHPM-3F-DV-WH

SH(redwire)Capoff

DH (yellow

ororangewire)

ZoneinControlNeutral

Forspecificwirecolors,seethewallboxlightingcontrolscatalogatwww.lutron.com/wallboxcatalog

Page 8: 3-Wire Fluorescent Power Module Spec · 3-Wire Fluorescent Power Module PHPM-3F-DV-WH PHPM-3F-120-WH 369355 369-355 GRAFIK Eye Eco-10 Eco QS 3000 LP LCP GP HomeWorks Created Date

®

DHDHDHDH H N N N N N

H/L

N

SH

H/L

N

DH

®

Job Name:

Job Number:

Model Numbers:

PageSPECIFICATION SUBMITTAL

369355RevB809.02.11

Wiring a Power Module to an LP, LCP, GP, or HomeWorksR Panel

Uptothree3-wirefluorescentpowermodulesmaybewiredtoanoutputofa120 V~LPorLCPpanel.TheloadtypefortheoutputmustbesetasEco-10RorHi-lumeRfluorescentloadtypeonthepanel’scircuitselector(foranLPorGPpanel),controller(foranLCPpanel),orHomeWorksRsoftware(foraHomeWorksR panel).

LutronR Ballast

(1)14to10AWG (2.0to4.0mm2)

(1)14to10AWG (2.0to4.0mm2)

ZoneIn

ControlNeutral

DimmedHot

Neutral

120 V~BranchCircuitBreakers

NeutralLug

Neutral(1)14to2/0AWG (2.0to70mm2)

Power(Hot/Live) (3)14to2/0AWG(2.0to70mm2)

1Loadfeed: 120 V~ifusedwithPHPM-3F-120-WHpowermodule 120–277 V~ifusedwithPHPM-3F-DV-WHpowermodule

Wiretoappropriateoutput

Loadwiring1{

Power Modules3-Wire Fluorescent Power Module®