40 2011-03-10 Thermozone AD 300 A/E/W 0.0 m 1.5 m 2.5 m 3.5 m 5.8 m/s 4.0 m/s 3.3 m/s 12 m/s AD 300 A/E/W Thermozone ® AD 300 A/E/W Air curtains for entry doors with heights of up to 3,5 metres AD300 is an air curtain with a modern design intented for permanent installation above doorways with heights of up to 3,5 meters. By separating zones of different temperature with a jet of air, AD300 effectively prevents cold draughts through open doorways and provides good heating comfort and the opportunity to make use of the floor space close to the opening. AD300 can also be used for heating and drying at the opening. A significantly reduced energy loss gives large savings. An adjustable air blower grille makes it possible to direct the air for an optimal air curtain effect. With AD300A without heat it is possible to significantly reduce energy losses through openings to refrigerated rooms, or openings to air conditioned rooms. AD300 can be built into false ceilings. For wide doorways it is possible to mount several units beside each other and control them with a single thermostat and control panel. The three different product lengths make it possible to cover openings of different widths. Air velocity profile Lengths: 1, 1,5 and 2 metres Ambient, no heat • Low sound level. • Corrosion proof housing made of hot zinc-plated and powder enamelled steel panels. Colour: RAL 9016. • Adjustable c/c distance between mounting brackets. • Easy to mount. • Compact and easily positioned. • The front panel is easy to remove, which facilitates installation and maintenance. • Optimized airflow with Thermozone technology. Electrical heat 9-18 kW Water heat Design and specifications are subject to change without notice.

Thermozone AD 300 A/E/W - Планета Климата€¦ · Control kit CK03: - ADEA, regulator (complete with outdoor sensor, built-in room sensor and door contact) - ADEAIS,

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Thermozone AD 300 A/E/W - Планета Климата€¦ · Control kit CK03: - ADEA, regulator (complete with outdoor sensor, built-in room sensor and door contact) - ADEAIS,

40

2011-03-10Thermozone AD 300 A/E/W

0.0 m

1.5 m

2.5 m

3.5 m

5.8 m/s

4.0 m/s

3.3 m/s

12 m/s

AD 300 A/E/W

R

Thermozone® AD 300 A/E/WAir curtains for entry doors with heights of up to 3,5 metres

AD300 is an air curtain with a modern design intented for permanent installation above doorways with heights of up to 3,5 meters. By separating zones of different temperature with a jet of air, AD300 effectively prevents cold draughts through open doorways and provides good heating comfort and the opportunity to make use of the floor space close to the opening. AD300 can also be used for heating and drying at the opening.

A significantly reduced energy loss gives large savings. An adjustable air blower grille makes it possible to direct the air for an optimal air curtain effect.

With AD300A without heat it is possible to significantly reduce energy losses through openings to refrigerated rooms, or openings to air conditioned rooms.

AD300 can be built into false ceilings. For wide doorways it is possible to mount several units beside each other and control them with a single thermostat and control panel. The three different product lengths make it possible to cover openings of different widths.

Air velocity profile

Lengths: 1, 1,5 and 2 metresAmbient, no heat

• Lowsoundlevel.

• Corrosionproofhousingmadeofhotzinc-platedandpowderenamelledsteelpanels.Colour:RAL9016.

• Adjustablec/cdistancebetweenmountingbrackets.

• Easytomount.

• Compactandeasilypositioned.

• Thefrontpaneliseasytoremove,whichfacilitatesinstallation and maintenance.

• OptimizedairflowwithThermozonetechnology.

Electrical heat 9-18 kW

Water heat

Design and specifications are subject to change without notice.

Page 2: Thermozone AD 300 A/E/W - Планета Климата€¦ · Control kit CK03: - ADEA, regulator (complete with outdoor sensor, built-in room sensor and door contact) - ADEAIS,

41

Thermozone AD 300 A/E/W

Technical specifications | Thermozone AD 300 A without heat 1

Technical specifications | Thermozone AD 300 W with water heat 2

Technical specifications | Thermozone AD 300 E with electrical heat 3

*1) Conditions: Distance to the unit 5 metres. Directional factor: 2. Equivalent absorption area: 200 m2. *2) ∆t = temperature rise of passing air at maximum heat output and lowest/highest airflow. *3) Power supply 2x9 kW (2x13A), separate feedings. *4) Applicable at water temperature 80/60 °C, air temperature +15 °C.

ProtectionclassAD300A/E/W(IP20)

ApprovedbySEMKOandCEcompliant.

Type Output*4 [kW]

Airflow [m3/h]

∆t*2,4 [°C]

Water volume [l]

Sound level*1 [dB(A)]

Voltage [V]

Amperage [A]

Length [mm]

Weight [kg]

AD310W 22 1150/1800 41/35 2,1 44/57 230V~ 1,2 1025 28

AD315W 37 1700/3000 43/36 3,2 46/59 230V~ 1,7 1565 40

AD320W 45 2300/3600 43/37 4,1 47/60 230V~ 2,4 2028 54

Type Output steps [kW]

Airflow [m3/h]

∆t*2 [°C]

Sound level*1 [dB(A)]

Voltage [V] Amperage [A] (control)

Voltage [V] Amperage [A] (heat)

Length [mm]

Weight [kg]

AD310E09 0/4,5/9 1200/1900 22/14 46/57 230V~/1,4A 400V3~/13A 1025 25

AD315E14 0/7/13,5 1800/3200 22/13 47/60 230V~/1,8A 400V3~/19,5A 1565 37

AD320E18 0/9/18 2400/3800 22/14 50/61 230V~/2,4A 400V3~/26A*3 2028 49

Type Output [kW]

Airflow [m3/h]

Sound level*1 [dB(A)]

Voltage [V]

Amperage [A]

Length [mm]

Weight [kg]

AD310A 0 1200/1900 46/57 230V~ 1,4 1025 22

AD315A 0 1800/3200 47/60 230V~ 1,8 1565 32

AD320A 0 2400/3800 50/61 230V~ 2,4 2028 42

Page 3: Thermozone AD 300 A/E/W - Планета Климата€¦ · Control kit CK03: - ADEA, regulator (complete with outdoor sensor, built-in room sensor and door contact) - ADEAIS,

42

Thermozone AD 300 A/E/W

500-900 (AD310) 700-1400 (AD315)

Ø23 (x4)

Ø38 (x2)

Ø23 (x4)

Ø38 (x2)

Ø38 (x2)

AD320

1400-1900

Ø7

Ø14

124

9090

490

34028

540

1025 / 1565 / 2028

AD310 / 315

80

AD310/315A/E

AD300A/E

AD320A/E

Dimensions

Ambient/Electrical

To open

Page 4: Thermozone AD 300 A/E/W - Планета Климата€¦ · Control kit CK03: - ADEA, regulator (complete with outdoor sensor, built-in room sensor and door contact) - ADEAIS,

43

Thermozone AD 300 A/E/W

Connection DN20 (3/4”) Outside thread

Water

To open

Dimensions

Page 5: Thermozone AD 300 A/E/W - Планета Климата€¦ · Control kit CK03: - ADEA, regulator (complete with outdoor sensor, built-in room sensor and door contact) - ADEAIS,

44

Thermozone AD 300 A/E/W

Min 120 mm

524

Min 50 mm

Positioning, mounting and installation

MountingThermozone AD300 can be permanently mounted on the wall or on the ceiling using threaded drop rods and a suspension kit, see next page. The air curtain unit canalsobebuiltintofalseceilings,seeFig.2.Theunitcan only be mounted horizontally, with the air outlet pointingdownwards.Minimumdistancefromoutlettoflammable material is 50 mm.

The distance between the mounting brackets is adjustable, which simplifies mounting. Brackets suitable foreachunitareincludedondelivery.The2metreunits should be fitted using three fixing points.

For maximum performance the units should cover the whole width of the opening and be fitted as close to the opening as possible. Several units can be mounted next to each other to form a continuous air curtain. The units should then be positioned as close together as possible.

Connection AD 300E 3The appliance should be preceded by a triple pole switch with at least 3 mm breaking gap. The connection should be made through knock outs on the top side oftheunitØ29mm.Forconnectiontothesupplyterminalblock,acableofmaximum16mm2 is used. For connection to the control terminal block, a cable of maximum 4 mm² is used. For units with electrical heating, power and control should normally be supplied separately.

ForAD320Eheatingelementsaredividedandpowered by two separate supplies. See wiring diagrams and dimension drawings.

Connection AD 300W 2The control cable is connected via a knock out on the topsidetotheleft(seenfrominsidethebuilding).Connections(DN20(3/4”),outsidethread)tothewaterheating coil are located on the top of the unit to the left (seenfrominsidethebuilding).Seewiringdiagrams.

SeepageforcontrolkitsandthechapteronControlsand accessories for further information.

Fig. 1: Minimum distance

Fig. 2: False ceiling mounting

Space for service/inspection hatch

Inlet air grille 22003/22004

Min 600mm

Page 6: Thermozone AD 300 A/E/W - Планета Климата€¦ · Control kit CK03: - ADEA, regulator (complete with outdoor sensor, built-in room sensor and door contact) - ADEAIS,

45

Thermozone AD 300 A/E/W

36

175

30

9

20

7

113

161

Ø9

40

40

4 x

1 m

2 x

ADPF1

ADPK1

Mounting with suspension kit (extra)

Threaded bars and M8 nuts are not included on delivery

Page 7: Thermozone AD 300 A/E/W - Планета Климата€¦ · Control kit CK03: - ADEA, regulator (complete with outdoor sensor, built-in room sensor and door contact) - ADEAIS,

46

Thermozone AD 300 A/E/W

Ambient 1

Level 1Airflow is controlled manually.Completecontrolkit:

- CB30N,controlbox,controlstheairflowin3steps

Level 2Desired airflow is set manually and the unit starts automatically, according to the setting, when the door opens. When the door closes the fan will continue to runforthedesiredtime(2s–10min.)setonMDC.Completecontrolkit:

- CB30N,controlbox,controlstheairflowin3stages

- MDC,doorcontactwithtimerelay

Electric 3

Level 1Airflowiscontrolledmanually.Roomthermostatcontrolstheheatoutputin2steps.ControlkitCK01E:

- CB32N,controlbox,controlstheairflowin3stepsandheatoutputin2steps

- RTI2,2-steproomthermostat

Level 2Airflow and heat output are controlled automatically based on the opening of the door and the room temperature.

When the door is open the fan runs on high speed, when the door closes the fan will continue to run for the desiredtime(2s–10min.)setonMDC.Whenthedooris closed the fan runs on low speed if there is a need for heating, if not the fan is switched off.

The room thermostat controls the heat output. E.g.thethermostatisseton23°Candthedifferencebetweenthesteps4°C.Thethermostatwillactivatebelow19°Cwhenthedoorisclosed.Whenthedooropens,thethermostatwillactivatebelow23°Candnormally the heat is switched on.ControlkitCK02E:

- CB32N,controlbox,controlstheairflowin3stepsandheatoutputin2steps

- MDC,magneticdoorcontactwithtimedelay

- RTI2,2-steproomthermostat

Level 3Airflow and heat output are controlled automatically based on the opening of the door, outdoor temperature and the room temperature.

The system is based on an advanced microprocessing regulator in an attractive design.

Allparametersarepre-programmedforeasyandquick installation.ControlkitCK03:

-ADEA,regulator(completewithoutdoorsensor,built-inroomsensoranddoorcontact)

- ADEAIS,indoorsensor

- ADEAEB,controlboard,forexternalmounting

Optionalcontrolkitlevel3:

- ADEA,regulator(completewithoutdoorsensor,builtinroomsensoranddoorcontact)

- ADEAIS,indoorsensor

- ADEAIB,controlboard,forinternalmounting

ReadmoreaboutoperationandusageofADEAinchapteronControlsandaccessories.

Control kits

Page 8: Thermozone AD 300 A/E/W - Планета Климата€¦ · Control kit CK03: - ADEA, regulator (complete with outdoor sensor, built-in room sensor and door contact) - ADEAIS,

47

Thermozone AD 300 A/E/W

SeealsochapteronControlsandaccessoriesorcontactFricoformoreoptions.

Water 2

Level 1Airflowiscontrolledmanually.Roomthermostatcontrolstheheatoutputviaactuator/valve.

ControlkitCK01W:

- CB30N,controlbox,controlstheairflowin3steps

- T10,roomthermostatIP30Note!AsetofvalvesVR20orVR25oractuator+valveSD20+TVV20orTVV25shouldbeaddedforacompletecontrol kit.

Level 2Airflow and heat output are controlled automatically based on the opening of the door and the room temperature.

When the door is open the fan runs on high speed, when the door closes the fan will continue to run for the desiredtime(2s–10min.)setonMDC.Whenthedooris closed the fan runs on low speed if there is a need for heating, if not the fan is switched off.

The room thermostat controls the heat output. E.g.thethermostatisseton23°Candthedifferencebetweenthesteps4°C.Thethermostatwillactivatebelow19°Cwhenthedoorisclosed.Whenthedooropens,thethermostatwillactivatebelow23°Candnormally the heat is switched on.

ControlkitCK02W:

- CB30N,controlbox,controlstheairflowin3steps

- MDC,magneticdoorcontactwithtimedelay

- RTI2,2-steproomthermostatNote!AsetofvalvesVR20orVR25oractuator+valveSD20+TVV20orTVV25shouldbeaddedforacompletecontrol kit.

Level 3Airflow and heat output are controlled automatically based on the opening of the door, outdoor temperature and the room temperature.

The system is based on an advanced microprocessing regulator in an attractive design.

Allparametersarepre-programmedforeasyandquick installation. ControlkitCK03:

-ADEA,regulator(completewithoutdoorsensor,built-inroomsensoranddoorcontact)

- ADEAIS,indoorsensor

- ADEAEB,controlboard,forexternalmountingNote!AsetofvalvesVR20orVR25oractuator+valveSD20+TVV20orTVV25shouldbeaddedforacompletecontrol kit.

Optionalcontrolkitlevel3:

- ADEA,regulator(completewithoutdoorsensor,builtinroomsensoranddoorcontact)

- ADEAIS,indoorsensor

- ADEAIB,controlboard,forinternalmountingNote!AsetofvalvesVR20orVR25oractuator+valveSD20+TVV20orTVV25shouldbeaddedforacompletecontrol kit.

ReadmoreaboutoperationandusageofADEAinchapteronControlsandaccessories.

Page 9: Thermozone AD 300 A/E/W - Планета Климата€¦ · Control kit CK03: - ADEA, regulator (complete with outdoor sensor, built-in room sensor and door contact) - ADEAIS,

48

Thermozone AD 300 A/E/W

Output charts water

Incoming / outgoing water temperature 90/70 °C

Incoming air temp.= +15 °C Incoming air temp. = +20 °C

Type Fan position

Airflow [m3/h]

Output [kW]

Outgoing air temp. [°C]

Water flow [l/s]

Output [kW]

Outgoing air temp. [°C]

Water flow [l/s]

Incoming / outgoing water temperature 80/60 °C

Incoming air temp.= +15 °C Incoming air temp. = +20 °C

Type Fan position

Airflow [m3/h]

Output [kW]

Outgoing air temp. [°C]

Water flow [l/s]

Output [kW]

Outgoing air temp. [°C]

Water flow [l/s]

Incoming / outgoing water temperature 60/50 °C

Incoming air temp.= +15 °C Incoming air temp. = +20 °C

Type Fan position

Airflow [m3/h]

Output [kW]

Outgoing air temp. [°C]

Water flow [l/s]

Output [kW]

Outgoing air temp. [°C]

Water flow [l/s]

Incoming / outgoing water temperature 60/40 °C

Incoming air temp.= +15 °C Incoming air temp. = +20 °C

Type Fan position

Airflow [m3/h]

Output [kW]

Outgoing air temp. [°C]

Water flow [l/s]

Output [kW]

Outgoing air temp. [°C]

Water flow [l/s]

AD310W max 1800 26,1 57 0,31 24,1 59 0,28

min 1150 19,2 64 0,22 17,7 65 0,21

AD315W max 3000 44,4 58 0,52 40,9 60 0,48

min 1700 29,9 66 0,35 27,6 67 0,32

AD320W max 3600 55,6 60 0,66 51,3 62 0,61

min 2300 40,6 67 0,48 37,5 68 0,44

AD310W max 1800 21,9 50 0,26 19,8 52 0,23

min 1150 16,1 56 0,19 14,6 57 0,17

AD315W max 3000 37,3 51 0,44 33,8 53 0,40

min 1700 25,2 58 0,30 22,9 59 0,27

AD320W max 3600 45,7 52 0,54 41,4 54 0,49

min 2300 32,6 58 0,38 29,5 59 0,35

AD310W max 1800 16,0 41 0,38 13,9 42 0,33

min 1150 11,7 45 0,28 10,2 46 0,24

AD315W max 3000 27,1 41 0,64 23,7 43 0,56

min 1700 18,2 46 0,43 16,0 47 0,38

AD320W max 3600 34,0 42 0,81 29,7 44 0,71

min 2300 24,7 46 0,59 21,7 47 0,51

AD310W max 1800 13,1 36 0,15 11,0 38 0,13

min 1150 9,8 40 0,11 8,3 41 0,09

AD315W max 3000 23,0 37 0,27 19,4 39 0,23

min 1700 15,8 42 0,18 13,4 43 0,15

AD320W max 3600 28,1 38 0,33 23,7 39 0,28

min 2300 20,9 41 0,24 17,7 42 0,21

Page 10: Thermozone AD 300 A/E/W - Планета Климата€¦ · Control kit CK03: - ADEA, regulator (complete with outdoor sensor, built-in room sensor and door contact) - ADEAIS,

49

Thermozone AD 300 A/E/W

V V

0,01 0,1 1,0

0,01

0,1

0,7

101,00,1

70

10

1

0,01 0,1 1,0

0,01

0,1

0,7

101,00,1

70

10

1

Pressure drop water

Water pressure drop over AD 300 W water coil

Water pressure drop over regulations and valves

Pres

sure

dro

p [

kPa]

Pres

sure

dro

p [

bar

]Water flow [m3/h]

Water flow [l/s]

Water flow [m3/h]

Pres

sure

dro

p [

kPa]

Pres

sure

dro

p [

bar

]

Water flow [l/s]

Thepressuredropiscalculatedforanaveragetemperatureof70°C(PVV80/60).Forotherwatertemperatures,thepressuredropismultipliedbythefactorK.

Average temp. water °C 40 50 60 70 80 90

K 1,10 1,06 1,03 1,00 0,97 0,93

Page 11: Thermozone AD 300 A/E/W - Планета Климата€¦ · Control kit CK03: - ADEA, regulator (complete with outdoor sensor, built-in room sensor and door contact) - ADEAIS,

50

Thermozone AD 300 A/E/W

AD300A

AD300A AD300A

Wiring diagrams AD 300 A

Ambient control options

Ambient - Level 1

Ambient - Level 2

CB30N, control box

CB30N, control box

MDC, magnetic door contact with time relay

Design and specifications are subject to change without notice.

Page 12: Thermozone AD 300 A/E/W - Планета Климата€¦ · Control kit CK03: - ADEA, regulator (complete with outdoor sensor, built-in room sensor and door contact) - ADEAIS,

51

Thermozone AD 300 A/E/W

2 3 4 5 61 8 9107

CB32N

11

L

21

5

34

67

N

RTI2

400V 3~, Heat230V ~, Motor and control

AD310/315E

CB32N

7

400V 3~, Heat6+PE

6

RTI2

AD310/315E

6+PE

400V 3~, Heat230V ~, Motor and control

AD320E

CB32N

7

400V 3~, Heat6+PE

6

RTI2

AD320E

6+PE400V 3~, Heat 400V 3~, Heat

400V3~

AD310/315E

Gre

en Y

ello

w

N LTk Tk 0

Ora

nge

Blu

e

Whi

teW

hite

Bro

wn

21 4 5 6 7

M~

118 910 L1L2L3

k2k1

kW kW

C

C

230V~

k1k2

400V3~

L1L2L3

k2k1

kW kW

AD320EB

lack

CK01E

Wiring diagrams AD 300 E

Electrical control options

Electrical - Level 1

CB32N,control box

RTI2, electronic 2-step thermostat

Page 13: Thermozone AD 300 A/E/W - Планета Климата€¦ · Control kit CK03: - ADEA, regulator (complete with outdoor sensor, built-in room sensor and door contact) - ADEAIS,

52

Thermozone AD 300 A/E/W

400V3~

AD310/315E

Gre

en Y

ello

w

N LTk Tk 0O

rang

eB

lue

Whi

teW

hite

Bro

wn

21 4 5 6 7

M~

118 910 L1L2L3

k2k1

kW kW

C

C

230V~

k1k2

400V3~

L1L2L3

k2k1

kW kW

AD320E

Bla

ck

AD320E AD320E

AD310/315E AD310/315E

DC

DC

CB32N

CB32N

MDCRTI2

MDCRTI2

CK02E

Electrical - Level 2

CB32N,control box

RTI2, electronic 2-step thermostat

MDC, magnetic door contact with time delay

Page 14: Thermozone AD 300 A/E/W - Планета Климата€¦ · Control kit CK03: - ADEA, regulator (complete with outdoor sensor, built-in room sensor and door contact) - ADEAIS,

53

Thermozone AD 300 A/E/W

400V3~

AD310/315E

Gre

en Y

ello

w

N LTk Tk 0

Ora

nge

Blu

e

Whi

teW

hite

Bro

wn

21 4 5 6 7

M~

118 910 L1L2L3

k2k1

kW kW

C

C

230V~

k1k2

400V3~

L1L2L3

k2k1

kW kW

AD320E

Bla

ck

9L 54 6 8N

ADEAEB/ADEAIB

5020 31 5130 4041 8680 83 8782 848521 81

104 7 116 8 95

ADEARADEAOS

MDCDC

ADEAIS

230V ~, Motor and control

AD310/315E

8+PE

AD310/315E

8+PE

400V 3~, Heat230V ~, Motor and control

AD320E

400V 3~, Heat2+PE

AD320E

2+PE400V 3~, Heat 400V 3~, Heat

400V 3~, Heat 400V 3~, Heat

ADEAEB

9+PE

ADEAR

8x0,5mm2

ADEAOSMDCDC

ADEAIS

(ADEAIB)

8x0,5mm2

ADEAR

2x0,5mm2

ADEAOSMDCDC

ADEAIS

ADEAEB

9+PE5 5

2x0,5mm22x0,5mm2

2x0,5mm2

2x0,5mm22x0,5mm2

10 11 121314 1516 17)(ADEAIB

CK03

Electrical - Level 3

ADEAIB, internal control board for AD300/400

ADEAIS, external room sensor

MDCDC, magnetic door contact

ADEAR, regulator with display unit and built-in room sensor

ADEAOS, outdoor sensor

ADEAEB, external control board

Page 15: Thermozone AD 300 A/E/W - Планета Климата€¦ · Control kit CK03: - ADEA, regulator (complete with outdoor sensor, built-in room sensor and door contact) - ADEAIS,

54

Thermozone AD 300 A/E/W

230V~

2 4 5 6N

Bro

wn

Blu

eO

rang

e

L 1

Whi

teW

hite

30TkTk

M~

AD300W/AD400W

0

CB30N

1 2 3 4 5 6 7

SD20

TVV20/25

230V ~, Motor and control

AD300W/AD400W

CB30N

5+PE

4+PE

2+PE

AD300W/AD400W

4+PE

2+PE

T10SD20

A/B

2

44

>t°C

62

7

T10

Bla

ck

0

CB30N

1 2 3 4 5 6 7

SD20

TVV20/25

L21 53 4 6 7 N

c °

RTI2

24L

DC DC

MDC

Doorcontact

21 22N

230V ~, Motor and control

AD300/400W

CB30N

4+PE

4+PE

5+PE

AD300/400W

4+PE

2+PE

RTI2SD20 MDC

Doorcontact

3+PE

2

2+PE2 4 5 6N

Bro

wn

Blu

eO

rang

e

L 1

Whi

teW

hite

30TkTk

M~

AD300W/AD400W

Bla

ck

CK02W

CK01W

Wiring diagrams AD 300 W

Water regulation options

Water - Level 1

Water - Level 2

SD20, actuator

RTI2, electronic 2-step thermostat

CB30N,control box

MDC, magnetic door contact with time delay

T10, room thermostat

CB30N,control box

TVV20/25, 2-way valve

Page 16: Thermozone AD 300 A/E/W - Планета Климата€¦ · Control kit CK03: - ADEA, regulator (complete with outdoor sensor, built-in room sensor and door contact) - ADEAIS,

55

Thermozone AD 300 A/E/W

9L 54 6 8N

ADEAEB / ADEAIB

5020 31 5130 4041 8680 83 8782 848521 81

104 7 116 8 95

ADEAR

230V~

SD20 TVV20/25

ADEAOS

MDCDC

ADEAIS

230V ~, Motor and control

AD300/400W

ADEAEB

7+PE

2+PE

AD300/400W

2+PE

2+PE SD20

ADEAR

8x0,5mm2

ADEAOSMDCDC

ADEAIS

3

ADEAEB

7+PE

230V ~, Motor and control

AD300/400W (ADEAIB)

8x0,5mm2

2+PE

AD300/400W

2+PE

2+PESD20

ADEAR

3

2x0,5mm2

ADEAOSMDCDC

ADEAIS

5

(ADEAIB)

3

2x0,5mm22x0,5mm2

2x0,5mm2

2x0,5mm22x0,5mm2

1610 13 17)12 141511(ADEAIB

2 4 5 6N

Bro

wn

Blu

eO

rang

e

L 1

Whi

teW

hite

30TkTk

M~

AD300W/AD400WB

lack

CK03

Water - Level 3

SD20, actuator

TVV20/25 2-way regulation valve

ADEAIB, internal control board for AD300/400

ADEAIS, external room sensor

MDCDC, magnetic door contact

ADEAR, regulator with display unit and built-in room sensor

ADEAOS, outdoor sensor

ADEAEB, external control board