    TESTING OF H.T.

    MOTORS

  • 7/31/2019 Testing of Ht Motors

    2/16

    RANGE OF MOTORS & TYPE OF

    M/Cs.

    RANGE : 140 KW TO 40 MW

    TYPE OF M/Cs

    INDUCTION : SLIP RING INDUCTION MOTORS: SQ. CAGE INDUCTION MOTORS

    SYNCHRONOUS : MOTORS & GENERATORS

    VFD MACHINES ( VARIABLE FREQUENCY DRIVE )

    FLAME PROOF , PRESSURISED MACHINES.

  • 7/31/2019 Testing of Ht Motors

    3/16

    TYPES OF TESTS

    1.0 IN PROCESS OR STAGE TESTS :

    MEASUREMENT OF

    RESISTANCE, IMPEDANCE, IR , PI, TAN DELTA

    AND HV

    TEST . MAGNETIC CENTRING .

    2.0ROUTINE TESTS : TO CHECK GENERAL

    PERFORMANCE

    OF ASSEMBLED MOTOR ON TEST BED.

  • 7/31/2019 Testing of Ht Motors

    4/16

    LIST OF ROUTINE TESTS.

    1.0 COLD RESISTANCE.

    2.0 PHASE SEQUENCE / DOR

    3.0 MECHANICAL RUN OF MOTOR AT NO

    LOAD.

    4.0 NO LOAD CURVE , SHAFT VOLTAGE &

    VIBRATIONS.5.0 LOCK ROTOR TEST.

    6.0 POLARISATION INDEX ( >1.5).

    7.0 AC H. V. TEST AT (2XU+1) FOR 1

    MINUTE.

  • 7/31/2019 Testing of Ht Motors

    5/16

    TYPETESTS1.0NO LOAD SATURATION CURVE( FROM 125 %RATED

    VOLTAGE TO 25% RATED VOLTAGE.)

    2.0 DETERMINATION OF STARTING CURRENT &

    STARTING

    TORQUE BY LOCK ROTOR TEST.

    3.0 LOAD POINTS AT 100 %, 75% & 50 %.

    4.0 OVER LOAD AT 160% RATED CURRENT.

    (SUBJECT TO

    TEST PLANT LIMITATION.

  • 7/31/2019 Testing of Ht Motors

    6/16

  • 7/31/2019 Testing of Ht Motors

    7/16

    1.0IP 55 (IInd NUMERAL)

    2.0TAN DELTA TEST ON MACHINES ABOVE 3.3 KV

    3.0IMPULSE TEST AT (4 U+5) KV . U=LINE VOLTAGE

    4.0RETARDATION TEST.

    5.0 PRESSURISATION TEST.

    6.0 VOLTAGE DECAY

    7.0 WORKING OF BACKSTOP

    8.0 EXTENDED NO LOAD RUN

  • 7/31/2019 Testing of Ht Motors

    8/16

    .

    -FRICTION & WINDAGE LOSSES FROM NO LOAD CURVE-IRON LOSS FROM NO LOAD CURVE

    -STATOR Cu LOSS ( 3X Isq.R )

    -ROTOR Cu LOSS (Slip X AIR GAP POWER)

    AIR GAP POWER= INPUT-St. Cu LOSS-IRON LOSS-STRAY LOAD LOSS = 0.5 % OF OUTPUT

    -OUTPUT=INPUT-LOSSES

    -EFFICIENCY= (OUTPUT/INPUT)X100

  • 7/31/2019 Testing of Ht Motors

    9/16

    TOTAL LOSSES : +10%

    POWER FACTOR (Min 0.02 & Max 0.07) : 1/6(1-Pf)

    STARTING CURRENT : +20%

    STARTING TORQUE : -15%,+25%

    PULL OUT TORQUE : -10%

    RESISTANCE VARIATION(M/C TO M/C) : +/-10%

    RESISTANCE VARIATION(PH TO PH) : +/-2%

    PHASE CURRENT : +/-2%

    VIBRATION AS PER IS 12075 OR VDE

    NOISE AS PER IS 12005

  • 7/31/2019 Testing of Ht Motors

    10/16

    M/C VOLTAGE (KV) IR(AMBIENT) IR(75 C)

    UP TO 1.0 KV 30 M OHMS 1 M OHMS

    UP TO 3.3 KV 120 M OHMS 4 M OHMS

    UP TO 6.6 KV 250 M OHMS 7 M OHMS

    UP TO 11.0 KV 500 M OHMS 15 M OHMS

  • 7/31/2019 Testing of Ht Motors

    11/16

    -15 MVA MG SET-10 MVA MG SET-5 MVA MG SET

    -2 MVA MG SET-1750 KVA MG SET-650 KVA MG SET-2000 KVA MG SET

    -HIGH ACCURACY DIGITAL INSTRUMENTATIONS-POWER ANALYSERS-NOISE , VIBRATION , TEMPERATUREMEASURING DIGITAL INSTRUMENTS.-DIGITAL CONTROL OF MG SETS& M/c U/TEST.

  • 7/31/2019 Testing of Ht Motors

    12/16

  • 7/31/2019 Testing of Ht Motors

    13/16

  • 7/31/2019 Testing of Ht Motors

    14/16

    1. Geometrical center of stator and rotor,is not the magnetic center of machine

    due to asymmetry of core & other components.

    2. Magnetic force pulls the rotor to-ward centerof the stator axially.

    3. Motor bearing thrust shoulders are notdesigned to carry any axial thrust exerted fromdriven equipment side.

    4. Motor may hunt if it is coupled off center, and

    specially w/o Limited End Float coupling .