Synchrophasors and Next Generation Energy Management Systems (EMS) Celebrating the Visions of Synchrophasor Pioneers: Arun Phadke and Jim Thorp May 9 th , 2013 Manu Parashar

Synchrophasors and Next Generation Energy …shukla/tps/Session1/... · Synchrophasors and Next Generation Energy Management Systems (EMS) Celebrating the Visions of Synchrophasor

Embed Size (px)

Citation preview

Page 1: Synchrophasors and Next Generation Energy …shukla/tps/Session1/... · Synchrophasors and Next Generation Energy Management Systems (EMS) Celebrating the Visions of Synchrophasor

Synchrophasors and Next Generation Energy

Management Systems (EMS)

Celebrating the Visions of Synchrophasor

Pioneers: Arun Phadke and Jim Thorp

May 9th, 2013

Manu Parashar

Page 2: Synchrophasors and Next Generation Energy …shukla/tps/Session1/... · Synchrophasors and Next Generation Energy Management Systems (EMS) Celebrating the Visions of Synchrophasor

Changing Landscape

Analog Computer

SCADA & Load

Frequency Control

An

alo

g

Operator Terminal Operating System – Digital Computer

Database & Development Environment

SCADA

Generation

Applications

Operator Console

Transmission

Applications D

ata

Ac

qu

isit

ion

Training

Simulator

Real-Time Applications

60’s & 70’s Analog / Hardwired

80’s & 90’s Digital /Study Mode / Modeling

Economics Reliability

Late 90’s Energy Markets

Vertically Integrated Industry Deregulation

Offers “predictive” capabilities… Centralized systems… Adds uncertainty…

Power System

(Generators & Tielines)

p2

Page 3: Synchrophasors and Next Generation Energy …shukla/tps/Session1/... · Synchrophasors and Next Generation Energy Management Systems (EMS) Celebrating the Visions of Synchrophasor

PMU Deployment within North America North American SynchroPhasor Initiative (NASPI)

Currently 200+

PMUs Installed.

Expected to exceed

800+ PMUs by 2013

(under SGIG Investments)

Source: NASPI Website (www.naspi.org)

Page 4: Synchrophasors and Next Generation Energy …shukla/tps/Session1/... · Synchrophasors and Next Generation Energy Management Systems (EMS) Celebrating the Visions of Synchrophasor

Energy Management Systems of the Future

» Control Center -PDC

PMU MEASUREMENT-BASED

Analysis

Traditional MODEL-BASED

Analysis

(EMS)

SCADA & Alarms WAMS

State Estimator

State Measurement

Other EMS Applications

New Applications

Small Signal Stability

Oscillation Monitoring

Transient & Voltage Stability

Stability Monitoring & Control

Island

Management

Island Detection,

Resync,&

Blackstart

p4

Page 5: Synchrophasors and Next Generation Energy …shukla/tps/Session1/... · Synchrophasors and Next Generation Energy Management Systems (EMS) Celebrating the Visions of Synchrophasor

Integrated “measurement-based” & “model-based” Analysis…. A nice marriage, indeed!

PMU Measurement-based analysis

PhasorPoint

»PREDICT & MITIGATE

TRUE

LIMIT

GRID

OPERATING POINT

Model-based analysis:

Corrective actions based on „what-if‟ analysis

EMS

Limit

NEW

Limit

Page 6: Synchrophasors and Next Generation Energy …shukla/tps/Session1/... · Synchrophasors and Next Generation Energy Management Systems (EMS) Celebrating the Visions of Synchrophasor

Wide Area Visualisation

RTUs

Alstom Solution Architecture

PhasorPoint Workbench

Synchrophasor Framework

PMU & RTU Aggregation Applications

e-terrabrowser

e-terravision

PMUs

Energy Management System

Dynamic Security

Assessment

»Copyright ALSTOM Grid

Page 7: Synchrophasors and Next Generation Energy …shukla/tps/Session1/... · Synchrophasors and Next Generation Energy Management Systems (EMS) Celebrating the Visions of Synchrophasor

SynchroPhasor Applications for the Control Center

High Voltage

e-terravision Displays PG&E SynchroPhasor Project Vahid Madani – Project Technical Leader

Page 8: Synchrophasors and Next Generation Energy …shukla/tps/Session1/... · Synchrophasors and Next Generation Energy Management Systems (EMS) Celebrating the Visions of Synchrophasor

PG&E Proof of Concept (PoC) Laboratory Vahid Madani – Project Technical Leader

PG&E POC facility has been instrumental in gathering the expertise to provide the industry with direction and a fast track process for maturing the standards such as the IEEE C37.118.2, C37.238, 242,244, and IEC-61850-90-5

-- "Going Beyond the Abstract"

Copyright ALSTOM Grid

Page 9: Synchrophasors and Next Generation Energy …shukla/tps/Session1/... · Synchrophasors and Next Generation Energy Management Systems (EMS) Celebrating the Visions of Synchrophasor

Generalized Security Assessment

Wide Area Visibility

Situation Awareness Visualization

Steady State

Security

Dynamic Stability

Synchrophasor

Applications

EMS

Applications

DSA

Applications

“Measurement-based” Applications

Network Model-based Apps

Correlation

Non-operational

Data

Condition

Monitoring

RT & Look-ahead trends

Production

Forecast

Weather

conditions

Improving Situational Awareness in the Control Room

»Copyright ALSTOM Grid

Page 10: Synchrophasors and Next Generation Energy …shukla/tps/Session1/... · Synchrophasors and Next Generation Energy Management Systems (EMS) Celebrating the Visions of Synchrophasor

SynchroPhasor Wide Area Visualization (e-terravision)

Angle Difference monitoring to assess “wide-area” grid stress

Node Pair definitions and associated alert/alarm thresholds

»Copyright ALSTOM Grid

Page 11: Synchrophasors and Next Generation Energy …shukla/tps/Session1/... · Synchrophasors and Next Generation Energy Management Systems (EMS) Celebrating the Visions of Synchrophasor

Dynamic (Oscillatory) Stability Management

“The interconnected electric power grid is one of the largest dynamic system of today”

p11

• Numeric SCADA displays today

• With synchro-phasors – high resolution trend display

Rapidly changing digits on a numeric display

-5 0 5 10 15 20 2559.98

59.99

60

60.01

60.02

60.03

60.04

60.05

60.06

Time (sec)

Freq

uenc

y (H

z)

Western Interconnection Frequencies - August 4 2000 Oscillation

Grand Coulee

Malin

Devers

Oscillations seen by SCADA and PMU data

-5 0 5 10 15 20 2559.98

59.99

60

60.01

60.02

60.03

60.04

60.05

60.06

Time (sec)

Freq

uenc

y (H

z)

Western Interconnection Frequencies - August 4 2000 Oscillation

Grand Coulee

Malin

Devers

Page 12: Synchrophasors and Next Generation Energy …shukla/tps/Session1/... · Synchrophasors and Next Generation Energy Management Systems (EMS) Celebrating the Visions of Synchrophasor

Oscillatory Modes Observed in Colombia (2009)

Inter-area mode at 0.49Hz

(Colombia-Ecuador). Opposing

phase in South

p12

1/F MODE FREQUENCY

MODE AMPLITUDE

A

MODE DECAY TIME

EXP(-t/ )

MODE PHASE

Mode Frequency

Mode Amplitude

Mode decay time

Mode Phase

Exp(-t/ )

Measured P / f /

Operations

Planning Dynamic model validation / plant performance

Early warning alarms of poor damping

Page 13: Synchrophasors and Next Generation Energy …shukla/tps/Session1/... · Synchrophasors and Next Generation Energy Management Systems (EMS) Celebrating the Visions of Synchrophasor

Australia

Queensland – NSW

Interconnector

Great Britain

Scotland – England

Interconnector

Transmission Corridor

Net Transfer Capacity

+300MW

+300MW

Model limitwith margin

Limit withmeasureddamping

Thermallimit

AREA 1

AREA 2

Congestion Relief Dynamic Stability

p13

Page 14: Synchrophasors and Next Generation Energy …shukla/tps/Session1/... · Synchrophasors and Next Generation Energy Management Systems (EMS) Celebrating the Visions of Synchrophasor

In distribution network, increase connection capacity by constraining by angle

»Marginal reduction of capacity factor

More capacity

More energy

Renewables Integration – Scotland (2012)

Page 15: Synchrophasors and Next Generation Energy …shukla/tps/Session1/... · Synchrophasors and Next Generation Energy Management Systems (EMS) Celebrating the Visions of Synchrophasor

A single phase to ground fault with resistance of 100 ohm on Line ID#37768062

p15

Distribution Fault Location using Synchrophasors

Page 16: Synchrophasors and Next Generation Energy …shukla/tps/Session1/... · Synchrophasors and Next Generation Energy Management Systems (EMS) Celebrating the Visions of Synchrophasor

Wide Area Protection Scheme – Iceland (2012)

SW FREQ

E FREQ

Smelter load

Main generation area

Loss of Large Smelter in SW

Frequency rises rapidly

Nearby generators change speed/angle

quickly

Frequency rises more

slowly

Trip Gen proportionally in correct zone

Angle difference increase

Smart Grid in the Future:

Protective control schemes that dynamically adapt to current power system conditions, to preserve the “integrity of the grid” as an entity.

Tightly integrate fast sub-second measurements with fast sub-second controls (FACTS, HVDC, etc)

p16

Page 17: Synchrophasors and Next Generation Energy …shukla/tps/Session1/... · Synchrophasors and Next Generation Energy Management Systems (EMS) Celebrating the Visions of Synchrophasor

Islanding, Resynchronization and Blackstart

System split »Vectors:

Voltage Phasors

Identify islanding quickly

Alarm raised

Islands clearly visualized

Reduce time to resynchronize

Improve system visibility in blackstart

Ice slide destroys 2 transmission towers, IRB used to monitor system to maintain synchronisation for 2 weeks

Page 18: Synchrophasors and Next Generation Energy …shukla/tps/Session1/... · Synchrophasors and Next Generation Energy Management Systems (EMS) Celebrating the Visions of Synchrophasor

Synchrophasors: The New Heartbeat of the Grid! Enabling Intelligent Decentralized Grid Monitoring & Control

EMS

Dynamic Security

Assessment

State Estimation

Contingency

Analysis

Offline

Analysis

Modelling

Root Cause

Analysis

Wide Area

Controls

Post-Event

Generator & ISO

Compliance

New Smart Grid

Applications

Distribution

DMS

Distributed

Generation

Demand

Response

SynchroPhasors:

„the new heartbeat of the grid‟

Local

Controls

Synchrophasor

Analytics