TS-KS-W1019-0 To: Specification Document Single-circuit Water Leakage Detector AD–AS–1AM (RoHS-directive-compatible) Date( ) <Manufacturer > System Equipment Division Electronic Materials & System Equipment Group TATSUTA Electric Wire & Cable Co., Ltd. System Equipment Division Approved by: Checked by: Prepared by:

Specification Document Single-circuit Water Leakage ...€¦ · facilities, warehouses, valuable documents, and similar objects from unforeseeable water leakage. 2. Overview of the

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Specification Document Single-circuit Water Leakage ...€¦ · facilities, warehouses, valuable documents, and similar objects from unforeseeable water leakage. 2. Overview of the

TS-KS-W1019-0 To:

Specification Document

Single-circuit Water Leakage Detector AD–AS–1AM

(RoHS-directive-compatible)

Date:( ) <Manufacturer > System Equipment Division Electronic Materials & System Equipment Group TATSUTA Electric Wire & Cable Co., Ltd.

System Equipment Division Approved by: Checked by: Prepared by:

Page 2: Specification Document Single-circuit Water Leakage ...€¦ · facilities, warehouses, valuable documents, and similar objects from unforeseeable water leakage. 2. Overview of the

Warnings

<<<Important safety instructions>>>

Warning

Erroneous operation of this water leakage detector not complying with the warning labels or the following warnings may lead to fatal accident, serious injury, electric shock, fire, or detector failure.

Never modify or disassemble the detector.

Allow only persons responsible for handling this product to perform installation work on it or to adjust or inspect it with the outer cover opened.

Observe ratings of power supply voltage and contact capacity. * Application of AC 200 V to the AC 100 V terminal will destroy the detector.

After the detector is installed, do not leave it with the cover open, except for inspection and maintenance purposes.

Do not touch any internal component with wet hands.

When performing maintenance on the product, avoid using organic solvent. Use dry wiping rags or a small amount of diluted neutral detergent.

Check detector supply voltage and rated voltage before installing.

When installing and electrically connecting the detector, follow the instructions in the instruction manual.

When inspecting and maintaining the detector, follow the instructions in the instruction manual.

When using control output contacts, check the contact rated load in the instruction manual.

Locations easily accessible to the general public

Locations close to sources of vibration, organic gas or strong electromagnetic induction.

Locations with much waste and dust

Locations where there is possibility of water leakage and temperature and humidity are high

Strict Prohibitions

Checkpoints

Do not install the detector in the following locations!

Page 3: Specification Document Single-circuit Water Leakage ...€¦ · facilities, warehouses, valuable documents, and similar objects from unforeseeable water leakage. 2. Overview of the

Table of contents

Page

1. Scope ................................................................................................................ 1 2. Overview of Detector ......................................................................................... 1

2–1 Internal Configuration of Detector ................................................................. 1 2–2 Typical Configuration of Detecting System .................................................... 1

3. Specifications ..................................................................................................... 1

3–1 Ratings ......................................................................................................... 1 3–2 Performance ................................................................................................. 2 3–3 Control Output Contact Specifications ............................................................ 3

4. Operation Chart ................................................................................................. 3 Attached Drawing 1: Outside Dimensions of Water Leakage Detector (AD–AS–1AM(U)) Attached Drawing 2: Parts Layout of Water Leakage Detector (AD–AS–1AM(U)) Attached Drawing 3: Dimensional drawing for wall-embedded type detector of Water Leakage Detector (AD–AS–1AM(U))

Page 4: Specification Document Single-circuit Water Leakage ...€¦ · facilities, warehouses, valuable documents, and similar objects from unforeseeable water leakage. 2. Overview of the

- 1 -

1. Scope This specification document is applicable to the single-circuit-use water-leakage detector, model AD–AS–1AM(RoHS-directive-compatible), developed to protect computer rooms, important facilities, warehouses, valuable documents, and similar objects from unforeseeable water leakage.

2. Overview of the detector

2–1 Internal Configuration of Detector

Fig. 1 Detector configuration

2-2 Typical configuration of detecting system

Fig.2 Typical detecting system configuration * Make a secure connection from the water leakage sensor to the instrumentation line and to the

break detection terminal; insulate connections with vinyl tape or similar material. It is recommended that the connections and the break detection terminal be housed in a joint box to be installed in a location safe from submersion in water.

3. Specifications

3-1. Ratings See Table 1 for the ratings.

Table 1 Ratings Item Specification

Rated voltage AC 100 V/200 V (common to 50 Hz and 60 Hz) Supply voltage fluctuation ±10% of the rated voltage

Power consumption 3 VA or less Control output contact Check Subsection 3-3, Control Output Contact Specifications. Sensor applied voltage AC 2.8 V or less

Working ambient temperature -10˚C to 50˚C (no icing) Working ambient humidity 35%RH to 85%RH (no condensation)

L1

Pow

er s

uppl

y ci

rcui

t

Transformer

AC100V

Signal amplification circuit

A-D conversion

input

Control circuit microcomputer

Pro

tect

ion

circ

uit

Sensors

AC200V

○Ground

COM

NC

NO

Wat

er le

akag

e al

arm

ou

tput

con

tact

s

L2 L3

Pulse output

B-SW

Fail-safe setting switchAlarm hold setting switchBreak detection setting switch

TF

TF: Temperature fuse, 250 V 2.0 A, 127°C to 133°CPS1: Polymer PTC (Poliswitch) PS2: Polymer PTC (Poliswitch) L1: Power indicator LED (stays lit yellow)L2: Water leakage indicator LED (flashes red)L3: Break indicator LED (flashes green)B: BuzzerB-SW: Buzzer sounding setting switch

Power supply

COM

NC

NO

○Brea

k al

arm

out

put

cont

act

Buzzer stop button

Reset button

Buzzer volume adjuster

Test circuit

PS1

PS2

Detection level setting adjuster

AC power supply

Instrumentation line forcontrol output contacts

Instrumentation line for sensors:0.3 SQ or more, within 100 m

Water leakage sensor: within 100 m

Break detectionterminal

AD-AS-1AM

P O W E R

WATER LEAKAGE

CUT-OFF SENCOR

BUZZER STOP

R E S E T

WATER-LEAKAGEDETECTOR

Connected to thecentral monitorpanel and others

Tatsuta Electric Wire & Cable Co., Ltd.

Page 5: Specification Document Single-circuit Water Leakage ...€¦ · facilities, warehouses, valuable documents, and similar objects from unforeseeable water leakage. 2. Overview of the

- 2 -

3-2. Performance See Table 2 for the performance.

Table 2 Performance Items Specification

Number of sensor circuits One Water leakage detection/recovery

level ±20% With the break detection setting “activated”:

(Factory default setting) With the break detection setting “not activated”

Adjuster position Detection level Recovery level Detection level Recovery level Adjuster at the minimum

setting 2.0 kW 2.8 kW 2.2 kW 3.3 kW

3.0 kW 4.2 kW 3.5 kW 5.3 kW 4.0 kW 5.5 kW 5.0 kW 7.5 kW

Adjuster at the middle setting

(Factory default setting)

5.0 kW 6.7 kW 6.7 kW 10.1 kW

6.0 kW 7.8 kW 8.6 kW 12.9 kW 7.0 kW 9.0 kW 10.8 kW 16.2 kW 8.0 kW 10.0 kW 13.3 kW 20.0 kW 9.0 kW 11.0 kW 16.4 kW 24.6 kW

Adjuster at the maximum setting 14.0 kW 15.6 kW 46.7 kW 70.0 kW

* The factory default setting is the value at which our water leakage sensor*1 can properly detect the presence of common city water. *1: Line sensors (AD, AD-R, AD-H, and FR-AD): within 100 m; point sensor (AD-PA)

* Our suggestions: When seeking to detect a low conductivity liquid or when using a low-sensitivity water leakage sensor (such as AD-F), raise the detection level; conversely, when seeking to detect a high conductivity liquid or when installing the detector in a high-temperature, high-humidity environment, lower the detection level.

Break judgment level 30 kΩ ±20% or more Break recovery level 25 kΩ ±20% or less

Function of the outer cover operating button

Function Buzzer stop button

Reset button Action

Buzzer stop ¾ Pressing this button when the alarm is on stops the buzzer temporarily. * A new alarm causes the buzzer to sound again.

Alarm hold cancel ¾ This button cancels the alarm contact output and buzzer when alarm is being held as a result of activation of the alarm hold setting.

Lamp test ¾ Pressing this button causes all indicator lamps to light and the buzzer to sound when the alarm hold setting is not activated and under normal condition.

Water leakage/ break simulation test

Pressing this button for three seconds or longer outputs the alarm for a simulated water leakage detection state; three seconds later, the alarm for a simulated break is output.

Outer cover LED indication Power indicator lamp, yellow: One (stays lit) Water leakage indicator lamp, red: One (flashes) Break indicator lamp, green: One (flashes)

Alarm buzzer Water leakage: sound varies in frequency between 4 kHz and 2 kHz (repeated howling); break: sound alternates between 4 kHz and 2 kHz (repeated pee-poh sound)

Function setting and adjustment With the outer cover open, the following settings can be input using the internal switches and knobs:

Setting/adjustment item Setting/adjustment range Factory default setting

Break detection setting Break detection setting activated/not activated

Break detection setting activated DIP-SW-4 ON

Alarm hold setting Alarm hold setting activated/not activated

Alarm hold setting not activated DIP-SW-3 OFF

Fail-safe setting Fail-safe output activated/not activated Fail-safe output not activated DIP-SW-2 OFF

Buzzer sounding setting Buzzer sounding activated/not activated Buzzer sounding activated DIP-SW-1 ON

Buzzer volume adjustment Buzzer volume “low” to “high” Buzzer volume “high” VR-1 Clockwise to maximum

Detection level adjustment ±20% of 2 kΩ, 5 kΩ, and 14 kΩ 5.0 kΩ ± 20% VR-2 Middle position

Control output contacts Contact configuration

Control output contacts (See Subsection 3-3 under 3.Specifications.) Water leakage: 1c; break: 1c

Withstand voltage Between all power supply terminals bundled and main body enclosure: AC 1,500 V (50/60 Hz) for 1 min. Between all power supply terminals bundled and all control output contact terminals bundled: AC 1,500 V (50/60 Hz) for 1 min.

Insulation resistance Between all power supply terminals bundled and main body enclosure: 10 MΩ or more (with a DC 500 V megger) Between all power supply terminals bundled and all control output contact terminals bundled: 10 MΩ or more (with a DC 500 V megger)

Noiseproof property

Power supply noise: ±1,000 V with a pulse width of 1 msec. (with noise simulator) (between each phase and the ground) Static charge: ±10 kV applied through a series combination of a 150-pF capacitor and a 330-Ω resistor, with results of no breakdown and no malfunction (Contact discharge to sensor terminals)

Outside dimensions W120 x H124 x D55 (in mm; see Attached Drawing 1.) Weight, enclosure material and

color 300 g ± 20 g; ABS; ivory white

Page 6: Specification Document Single-circuit Water Leakage ...€¦ · facilities, warehouses, valuable documents, and similar objects from unforeseeable water leakage. 2. Overview of the

- 3 -

3-3. Control Output Contact Specifications Refer to Table 3 for control output contacts.

Table 3 Control output contact specifications Item Resistive load Inductive load

Rated load AC250 V 6.0 A DC24 V 6.0 A

AC250 V 3.0 A DC24 V 3.0 A

(Relay contacts: FTR-LYCA005 according to a catalog of Fujitsu Component Limited) 4. Operation Chart

Refer to Fig. 3 for the operation chart.

Fig. 3 Operation Chart

Water leakage

Power-on

Water leakage alarm indication LED

Water leakage control output contacts (COM-NO)

Sensor state Break

OpenClosed

Open

ONOFF OFF

Power indicator LED Switched off

Switched on

Break alarm indicator LED

Normal

Flashing

Buzzer stop button* To perform a simulation test, push and hold the button together with the reset button.

ON

OFF

Switched off

Buzzer soundingON

OFFON ON

OFF OFF OFF

Closed

Water leakage control output contacts with the fail-safe setting activated * (COM-NC) Open

Closed ClosedOpenOpen

Closed Closed

Normal Normal

OFF

Break control output contacts (COM-NO)

OpenClosed

Open

Break control output contacts with the fail-safe setting activated * (COM-NC) Open

ClosedOpen

Closed Closed

Reset button* To perform a lamp test, push this button when the system is in normal state.

ResetON

OFF OFF

Open

Extended when alarm hold setting is activated.

Extended when alarm hold setting is activated.

ON

Switched on

Switched on

Push and hold both for three seconds or longer.

Extended when alarm hold setting is activated.

Flashing (for three seconds)

Flashing

Closed

Closed

Open

Open

ON

Flashing

Extended when alarm hold setting is activated.

Extended when alarm hold setting is activated.

Extended when alarm hold setting is activated.

Switched off

OFF

Open

Open

ON

OFF OFF

Simulated water leakage/

break test

Simulated water leakage/

break test

* To perform a simulated water leakage/break test, push and hold the buzzer stop button together with the reset button .

OFFOFF

Normal

Lamp test

ON

ON

Switched off

Switched off

Switched off

Switched off

Switched off

Switched off

Switched off

Page 7: Specification Document Single-circuit Water Leakage ...€¦ · facilities, warehouses, valuable documents, and similar objects from unforeseeable water leakage. 2. Overview of the

DrawingNumber

Desig-nation

Drawn byCheckedby

Approvedby

H

G

F

E

D

C

B

A

8 7 6 5 4 3 2 1

H

G

F

E

D

C

B

A

8 7 6 5 4 3 2 1Attached Drawing 1

55

124

120

Outside Dimension ofWater Leakage Detector

(AD-AS-1AM)

TTS-KS-W3062-0

mm

-/-Scale

Unit

Drawnon

TATSUTA Electric Wire & Cable Co., Ltd.

September14, 2009

AD-AS-1AM

P O W E R

WATER LEAKAGE

CUT-OFF SENCOR

BUZZER STOP

R E S E T

WATER-LEAKAGEDETECTOR

70

70

27

27

2525

13

20 18 206 6

12 wire entry holes

Four 5-mm-diametermounting holes

Two 6x1.5-mm notches to permit outer cover removal

Tatsuta Electric Wire & Cable Co.,Ltd.

Page 8: Specification Document Single-circuit Water Leakage ...€¦ · facilities, warehouses, valuable documents, and similar objects from unforeseeable water leakage. 2. Overview of the

ON 1

23

AD-AS-1AM-1

H

G

F

E

D

C

B

A

8 7 6 5 4 3 2 1

H

G

F

E

D

C

B

A

8 7 6 5 4 3 2 1Attached Drawing 2

Parts layout ofWater Leakage Detector

(AD-AS-1AM)

TTS-KS-W3063-0

mm

-/-

September14, 2009

AD-AS-1AM

P O W E R

WATER LEAKAGE

CUT-OFF SENCOR

BUZZER STOP

R E S E T

WATER-LEAKAGEDETECTOR

Break indicator LED(green)

Buzzer stop button

Reset button Reset button

Buzzer stop button

Break indicator LED(green)

Buzzer

VR-1:Buzzer volume adjustingknob

VR-2: Detection leveladjusting knob

DIP-SW:Function-setting switches

Output terminal blockPower supply andsensor terminal block

Outer cover (front view) Internal layout

Insulating sheet

Detector construction

Outer cover Insulatingsheet

Circuitboard

EnclosureIntermediateboard

Dustproof cover

ON 1

23

AD-AS-1AM-1

Terminal blockdescription

Water leakage alarm contact NC1

Water leakage alarm contact COM1

Water leakage alarm contact NO1

Break alarm contact NC2

Break alarm contact COM2

Break alarm contact NO2

AC power 0V

AC power 100V

AC power 200V

Ground

Sensor

Sensor

Wire entry hole Wire entry hole

DrawingNumber

Desig-nation

Drawn byCheckedby

Approvedby Scale

Unit

Drawnon

TATSUTA Electric Wire & Cable Co., LTD

Power indicator LED(yellow)

Water leakage indicatorLED (red)

Power indicator LED(yellow)

Water leakage indicatorLED (red)

CN1

Break detectionAlarm holdFail-safeBuzzer

VR1 VR2

Power

Water leakage

Break Sensitivity adjustment

ON OFFReset →

Buzzer stop

H

M

L

Buzzer volume

Detection sensitivity

Loud High

100V

200V

Ground

Sensor (I)

Sensor (O)

AC power inputNC

COM

NO

NC

COM

NO

■Electric shock!* Do not remove this

protective sheet.* Do not insert foreign

bodies into the opening.

* Do not touch with wet hands.

Caution

Long-pushing the buzzer stop and reset buttons together (for 2 sec.) allows you to check how the detector circuit and relay operate.

Water leakage

Break

Tatsuta Electric Wire & Cable Co.,Ltd.

Page 9: Specification Document Single-circuit Water Leakage ...€¦ · facilities, warehouses, valuable documents, and similar objects from unforeseeable water leakage. 2. Overview of the

H

G

F

E

D

C

B

A

8 7 6 5 4 3 2 1

H

G

F

E

D

C

B

A

8 7 6 5 4 3 2 1Attached Drawing 3

Dimensional drawing for wall-embedded type detector of

Water Leakage Detector(AD-AS-1AM)

TTS-KS-W3064-0

mm

-/-

September14, 2009

48

124

120 3315

63

74

Examples of wall-embedded work execution (using standard boxes and fittings)

AD-AS-1AM-1

AD-AS-1AM-1

AD-AS-1AM-1

Position of fixing screw Rear view (back of wall)Side view(wall cross section)

Example of work execution with switch box

Example of work execution with clamp fittings

Example of work execution with retaining fittings

Panasonic DM8020K

Panasonic WN3993020

Panasonic WN3997

ON 1

23

AD-AS-1AM-1

45

82

98

Six 5x10-mm holes (for countersunk head screws)

78

66

98

Outside dimensions withenclosure removed

Inside dimensions withouter cover removed

0 to 25 mm

7 to 18 mm

9 to 30 mm

DrawingNumber

Desig-nation

Drawn byCheckedby

Approvedby Scale

Unit

Drawnon

TATSUTA Electric Wire & Cable Co., LTD

AD-AS-1AM

P O W E R

WATER LEAKAGE

CUT-OFF SENCOR

BUZZER STOP

R E S E T

WATER-LEAKAGEDETECTOR

Tatsuta Electric Wire & Cable Co.,Ltd.