TS-KS-W1019-0 To:
Specification Document
Single-circuit Water Leakage Detector AD–AS–1AM
(RoHS-directive-compatible)
Date:( ) <Manufacturer > System Equipment Division Electronic Materials & System Equipment Group TATSUTA Electric Wire & Cable Co., Ltd.
System Equipment Division Approved by: Checked by: Prepared by:
Warnings
<<<Important safety instructions>>>
Warning
Erroneous operation of this water leakage detector not complying with the warning labels or the following warnings may lead to fatal accident, serious injury, electric shock, fire, or detector failure.
Never modify or disassemble the detector.
Allow only persons responsible for handling this product to perform installation work on it or to adjust or inspect it with the outer cover opened.
Observe ratings of power supply voltage and contact capacity. * Application of AC 200 V to the AC 100 V terminal will destroy the detector.
After the detector is installed, do not leave it with the cover open, except for inspection and maintenance purposes.
Do not touch any internal component with wet hands.
When performing maintenance on the product, avoid using organic solvent. Use dry wiping rags or a small amount of diluted neutral detergent.
Check detector supply voltage and rated voltage before installing.
When installing and electrically connecting the detector, follow the instructions in the instruction manual.
When inspecting and maintaining the detector, follow the instructions in the instruction manual.
When using control output contacts, check the contact rated load in the instruction manual.
Locations easily accessible to the general public
Locations close to sources of vibration, organic gas or strong electromagnetic induction.
Locations with much waste and dust
Locations where there is possibility of water leakage and temperature and humidity are high
Strict Prohibitions
Checkpoints
Do not install the detector in the following locations!
Table of contents
Page
1. Scope ................................................................................................................ 1 2. Overview of Detector ......................................................................................... 1
2–1 Internal Configuration of Detector ................................................................. 1 2–2 Typical Configuration of Detecting System .................................................... 1
3. Specifications ..................................................................................................... 1
3–1 Ratings ......................................................................................................... 1 3–2 Performance ................................................................................................. 2 3–3 Control Output Contact Specifications ............................................................ 3
4. Operation Chart ................................................................................................. 3 Attached Drawing 1: Outside Dimensions of Water Leakage Detector (AD–AS–1AM(U)) Attached Drawing 2: Parts Layout of Water Leakage Detector (AD–AS–1AM(U)) Attached Drawing 3: Dimensional drawing for wall-embedded type detector of Water Leakage Detector (AD–AS–1AM(U))
- 1 -
1. Scope This specification document is applicable to the single-circuit-use water-leakage detector, model AD–AS–1AM(RoHS-directive-compatible), developed to protect computer rooms, important facilities, warehouses, valuable documents, and similar objects from unforeseeable water leakage.
2. Overview of the detector
2–1 Internal Configuration of Detector
Fig. 1 Detector configuration
2-2 Typical configuration of detecting system
Fig.2 Typical detecting system configuration * Make a secure connection from the water leakage sensor to the instrumentation line and to the
break detection terminal; insulate connections with vinyl tape or similar material. It is recommended that the connections and the break detection terminal be housed in a joint box to be installed in a location safe from submersion in water.
3. Specifications
3-1. Ratings See Table 1 for the ratings.
Table 1 Ratings Item Specification
Rated voltage AC 100 V/200 V (common to 50 Hz and 60 Hz) Supply voltage fluctuation ±10% of the rated voltage
Power consumption 3 VA or less Control output contact Check Subsection 3-3, Control Output Contact Specifications. Sensor applied voltage AC 2.8 V or less
Working ambient temperature -10˚C to 50˚C (no icing) Working ambient humidity 35%RH to 85%RH (no condensation)
L1
Pow
er s
uppl
y ci
rcui
t
Transformer
AC100V
○
○
○
Signal amplification circuit
A-D conversion
input
Control circuit microcomputer
Pro
tect
ion
circ
uit
○
○
Sensors
AC200V
○Ground
COM
NC
NO
○
○
○
Wat
er le
akag
e al
arm
ou
tput
con
tact
s
L2 L3
Pulse output
B-SW
Fail-safe setting switchAlarm hold setting switchBreak detection setting switch
TF
TF: Temperature fuse, 250 V 2.0 A, 127°C to 133°CPS1: Polymer PTC (Poliswitch) PS2: Polymer PTC (Poliswitch) L1: Power indicator LED (stays lit yellow)L2: Water leakage indicator LED (flashes red)L3: Break indicator LED (flashes green)B: BuzzerB-SW: Buzzer sounding setting switch
Power supply
COM
NC
NO
○
○
○Brea
k al
arm
out
put
cont
act
Buzzer stop button
Reset button
Buzzer volume adjuster
Test circuit
PS1
PS2
B
Detection level setting adjuster
AC power supply
Instrumentation line forcontrol output contacts
Instrumentation line for sensors:0.3 SQ or more, within 100 m
Water leakage sensor: within 100 m
Break detectionterminal
AD-AS-1AM
P O W E R
WATER LEAKAGE
CUT-OFF SENCOR
BUZZER STOP
R E S E T
WATER-LEAKAGEDETECTOR
Connected to thecentral monitorpanel and others
Tatsuta Electric Wire & Cable Co., Ltd.
- 2 -
3-2. Performance See Table 2 for the performance.
Table 2 Performance Items Specification
Number of sensor circuits One Water leakage detection/recovery
level ±20% With the break detection setting “activated”:
(Factory default setting) With the break detection setting “not activated”
Adjuster position Detection level Recovery level Detection level Recovery level Adjuster at the minimum
setting 2.0 kW 2.8 kW 2.2 kW 3.3 kW
3.0 kW 4.2 kW 3.5 kW 5.3 kW 4.0 kW 5.5 kW 5.0 kW 7.5 kW
Adjuster at the middle setting
(Factory default setting)
5.0 kW 6.7 kW 6.7 kW 10.1 kW
6.0 kW 7.8 kW 8.6 kW 12.9 kW 7.0 kW 9.0 kW 10.8 kW 16.2 kW 8.0 kW 10.0 kW 13.3 kW 20.0 kW 9.0 kW 11.0 kW 16.4 kW 24.6 kW
Adjuster at the maximum setting 14.0 kW 15.6 kW 46.7 kW 70.0 kW
* The factory default setting is the value at which our water leakage sensor*1 can properly detect the presence of common city water. *1: Line sensors (AD, AD-R, AD-H, and FR-AD): within 100 m; point sensor (AD-PA)
* Our suggestions: When seeking to detect a low conductivity liquid or when using a low-sensitivity water leakage sensor (such as AD-F), raise the detection level; conversely, when seeking to detect a high conductivity liquid or when installing the detector in a high-temperature, high-humidity environment, lower the detection level.
Break judgment level 30 kΩ ±20% or more Break recovery level 25 kΩ ±20% or less
Function of the outer cover operating button
Function Buzzer stop button
Reset button Action
Buzzer stop ¾ Pressing this button when the alarm is on stops the buzzer temporarily. * A new alarm causes the buzzer to sound again.
Alarm hold cancel ¾ This button cancels the alarm contact output and buzzer when alarm is being held as a result of activation of the alarm hold setting.
Lamp test ¾ Pressing this button causes all indicator lamps to light and the buzzer to sound when the alarm hold setting is not activated and under normal condition.
Water leakage/ break simulation test
Pressing this button for three seconds or longer outputs the alarm for a simulated water leakage detection state; three seconds later, the alarm for a simulated break is output.
Outer cover LED indication Power indicator lamp, yellow: One (stays lit) Water leakage indicator lamp, red: One (flashes) Break indicator lamp, green: One (flashes)
Alarm buzzer Water leakage: sound varies in frequency between 4 kHz and 2 kHz (repeated howling); break: sound alternates between 4 kHz and 2 kHz (repeated pee-poh sound)
Function setting and adjustment With the outer cover open, the following settings can be input using the internal switches and knobs:
Setting/adjustment item Setting/adjustment range Factory default setting
Break detection setting Break detection setting activated/not activated
Break detection setting activated DIP-SW-4 ON
Alarm hold setting Alarm hold setting activated/not activated
Alarm hold setting not activated DIP-SW-3 OFF
Fail-safe setting Fail-safe output activated/not activated Fail-safe output not activated DIP-SW-2 OFF
Buzzer sounding setting Buzzer sounding activated/not activated Buzzer sounding activated DIP-SW-1 ON
Buzzer volume adjustment Buzzer volume “low” to “high” Buzzer volume “high” VR-1 Clockwise to maximum
Detection level adjustment ±20% of 2 kΩ, 5 kΩ, and 14 kΩ 5.0 kΩ ± 20% VR-2 Middle position
Control output contacts Contact configuration
Control output contacts (See Subsection 3-3 under 3.Specifications.) Water leakage: 1c; break: 1c
Withstand voltage Between all power supply terminals bundled and main body enclosure: AC 1,500 V (50/60 Hz) for 1 min. Between all power supply terminals bundled and all control output contact terminals bundled: AC 1,500 V (50/60 Hz) for 1 min.
Insulation resistance Between all power supply terminals bundled and main body enclosure: 10 MΩ or more (with a DC 500 V megger) Between all power supply terminals bundled and all control output contact terminals bundled: 10 MΩ or more (with a DC 500 V megger)
Noiseproof property
Power supply noise: ±1,000 V with a pulse width of 1 msec. (with noise simulator) (between each phase and the ground) Static charge: ±10 kV applied through a series combination of a 150-pF capacitor and a 330-Ω resistor, with results of no breakdown and no malfunction (Contact discharge to sensor terminals)
Outside dimensions W120 x H124 x D55 (in mm; see Attached Drawing 1.) Weight, enclosure material and
color 300 g ± 20 g; ABS; ivory white
- 3 -
3-3. Control Output Contact Specifications Refer to Table 3 for control output contacts.
Table 3 Control output contact specifications Item Resistive load Inductive load
Rated load AC250 V 6.0 A DC24 V 6.0 A
AC250 V 3.0 A DC24 V 3.0 A
(Relay contacts: FTR-LYCA005 according to a catalog of Fujitsu Component Limited) 4. Operation Chart
Refer to Fig. 3 for the operation chart.
Fig. 3 Operation Chart
Water leakage
Power-on
Water leakage alarm indication LED
Water leakage control output contacts (COM-NO)
Sensor state Break
OpenClosed
Open
ONOFF OFF
Power indicator LED Switched off
Switched on
Break alarm indicator LED
Normal
Flashing
Buzzer stop button* To perform a simulation test, push and hold the button together with the reset button.
ON
OFF
Switched off
Buzzer soundingON
OFFON ON
OFF OFF OFF
Closed
Water leakage control output contacts with the fail-safe setting activated * (COM-NC) Open
Closed ClosedOpenOpen
Closed Closed
Normal Normal
OFF
Break control output contacts (COM-NO)
OpenClosed
Open
Break control output contacts with the fail-safe setting activated * (COM-NC) Open
ClosedOpen
Closed Closed
Reset button* To perform a lamp test, push this button when the system is in normal state.
ResetON
OFF OFF
Open
Extended when alarm hold setting is activated.
Extended when alarm hold setting is activated.
ON
Switched on
Switched on
Push and hold both for three seconds or longer.
Extended when alarm hold setting is activated.
Flashing (for three seconds)
Flashing
Closed
Closed
Open
Open
ON
Flashing
Extended when alarm hold setting is activated.
Extended when alarm hold setting is activated.
Extended when alarm hold setting is activated.
Switched off
OFF
Open
Open
ON
OFF OFF
Simulated water leakage/
break test
Simulated water leakage/
break test
* To perform a simulated water leakage/break test, push and hold the buzzer stop button together with the reset button .
OFFOFF
Normal
Lamp test
ON
ON
Switched off
Switched off
Switched off
Switched off
Switched off
Switched off
Switched off
DrawingNumber
Desig-nation
Drawn byCheckedby
Approvedby
H
G
F
E
D
C
B
A
8 7 6 5 4 3 2 1
H
G
F
E
D
C
B
A
8 7 6 5 4 3 2 1Attached Drawing 1
55
124
120
Outside Dimension ofWater Leakage Detector
(AD-AS-1AM)
TTS-KS-W3062-0
mm
-/-Scale
Unit
Drawnon
TATSUTA Electric Wire & Cable Co., Ltd.
September14, 2009
AD-AS-1AM
P O W E R
WATER LEAKAGE
CUT-OFF SENCOR
BUZZER STOP
R E S E T
WATER-LEAKAGEDETECTOR
70
70
27
27
2525
13
20 18 206 6
12 wire entry holes
Four 5-mm-diametermounting holes
Two 6x1.5-mm notches to permit outer cover removal
Tatsuta Electric Wire & Cable Co.,Ltd.
ON 1
23
4
AD-AS-1AM-1
H
G
F
E
D
C
B
A
8 7 6 5 4 3 2 1
H
G
F
E
D
C
B
A
8 7 6 5 4 3 2 1Attached Drawing 2
Parts layout ofWater Leakage Detector
(AD-AS-1AM)
TTS-KS-W3063-0
mm
-/-
September14, 2009
AD-AS-1AM
P O W E R
WATER LEAKAGE
CUT-OFF SENCOR
BUZZER STOP
R E S E T
WATER-LEAKAGEDETECTOR
Break indicator LED(green)
Buzzer stop button
Reset button Reset button
Buzzer stop button
Break indicator LED(green)
Buzzer
VR-1:Buzzer volume adjustingknob
VR-2: Detection leveladjusting knob
DIP-SW:Function-setting switches
Output terminal blockPower supply andsensor terminal block
Outer cover (front view) Internal layout
Insulating sheet
Detector construction
Outer cover Insulatingsheet
Circuitboard
EnclosureIntermediateboard
Dustproof cover
ON 1
23
4
AD-AS-1AM-1
Terminal blockdescription
Water leakage alarm contact NC1
Water leakage alarm contact COM1
Water leakage alarm contact NO1
Break alarm contact NC2
Break alarm contact COM2
Break alarm contact NO2
AC power 0V
AC power 100V
AC power 200V
Ground
Sensor
Sensor
Wire entry hole Wire entry hole
DrawingNumber
Desig-nation
Drawn byCheckedby
Approvedby Scale
Unit
Drawnon
TATSUTA Electric Wire & Cable Co., LTD
Power indicator LED(yellow)
Water leakage indicatorLED (red)
Power indicator LED(yellow)
Water leakage indicatorLED (red)
CN1
Break detectionAlarm holdFail-safeBuzzer
VR1 VR2
Power
Water leakage
Break Sensitivity adjustment
ON OFFReset →
Buzzer stop
H
M
L
Buzzer volume
Detection sensitivity
Loud High
100V
200V
Ground
Sensor (I)
Sensor (O)
AC power inputNC
COM
NO
NC
COM
NO
!
■Electric shock!* Do not remove this
protective sheet.* Do not insert foreign
bodies into the opening.
* Do not touch with wet hands.
Caution
Long-pushing the buzzer stop and reset buttons together (for 2 sec.) allows you to check how the detector circuit and relay operate.
Water leakage
Break
Tatsuta Electric Wire & Cable Co.,Ltd.
H
G
F
E
D
C
B
A
8 7 6 5 4 3 2 1
H
G
F
E
D
C
B
A
8 7 6 5 4 3 2 1Attached Drawing 3
Dimensional drawing for wall-embedded type detector of
Water Leakage Detector(AD-AS-1AM)
TTS-KS-W3064-0
mm
-/-
September14, 2009
48
124
120 3315
63
74
Examples of wall-embedded work execution (using standard boxes and fittings)
AD-AS-1AM-1
AD-AS-1AM-1
AD-AS-1AM-1
Position of fixing screw Rear view (back of wall)Side view(wall cross section)
Example of work execution with switch box
Example of work execution with clamp fittings
Example of work execution with retaining fittings
Panasonic DM8020K
Panasonic WN3993020
Panasonic WN3997
ON 1
23
4
AD-AS-1AM-1
45
82
98
Six 5x10-mm holes (for countersunk head screws)
78
66
98
Outside dimensions withenclosure removed
Inside dimensions withouter cover removed
0 to 25 mm
7 to 18 mm
9 to 30 mm
DrawingNumber
Desig-nation
Drawn byCheckedby
Approvedby Scale
Unit
Drawnon
TATSUTA Electric Wire & Cable Co., LTD
AD-AS-1AM
P O W E R
WATER LEAKAGE
CUT-OFF SENCOR
BUZZER STOP
R E S E T
WATER-LEAKAGEDETECTOR
Tatsuta Electric Wire & Cable Co.,Ltd.