Upload
nguyentuyen
View
228
Download
1
Embed Size (px)
Citation preview
ServiceMeteringApplic ationRelia bilit yTrade Price
Monitoring and analysing your power consumption
Dimensions
Smart on...
FeaturesDIN96 panel mounting enclosureBacklit LCD displayProgrammable CT ratios17 electrical parametersTHD measurement up to 60thPulse output and RS485 Modbus
BenefitsCost effectiveSimple navigationRenowned qualit y
ApprovalsIEC 61326IEC 61010-1IEC 62053-21RoHS complia nt
Smart Power Meter Series X835/X825Three Phase Multi Function Panel Mounting
The Smart X835 digital metering system (dms) represents the first model of a new generation of digital metering systems designed to complement the current Eastron Electronic Intruments Smart series.
The Smart X835 meter is an accurate and cost effective solution for measurement and display of all major electrical and power qualityparameters. Its easy programming, mounting and user-friendly navigation make the Smart X835 dms an ideal choice for customers who require reliable energy measurement.
Smart X835 dms is built to high quality standards utilising the latest ‘state-of-the-art’ microprocessor and manufacturin technology.Designed, developed and manufactured in ISO9001:2008 company, Smart X835 dms builds on Eastron Electronic Intruments’ long established reputation for metering product quality.
Smart X835 Digital Metering System
Input Output
Nominal input voltage
Max. conti nuous input overl oad voltage
Max. short dura tion input voltage
Nominal input voltage burden
Nominal Input Current
Max. conti nuous input overl oad curr nt
Max. short dura tion input curr ent
Star ting curr ent
Nominal input curr ent burden
Puls e Output
Puls e 1 constant
Puls e 2 constant
Puls e weight
Type
Remote module type
Rs485 module type
Protocol
Baudr ate
Pari ty
Frequency
Min. Input Current
Slave ID
20-280V AC L-N 20-480V AC L-L
120% of nom inal
2x Max. (1 second application repeated 5 time at 5 minute interval)
<0. 2VA rms
1/5A AC
120% of nom inal Current
120% of Imax.
5% of nom inal curr ent
0.4% of nom inal curr ent
0.6VA per phase
45-66Hz
2
0~65535i mp/kW h
Confi gurable 200/100/60m S
Pass ive puls e output
RS 485
2-wire hal f duplex
Mobdus RTU
1200/2400/4800/9600/19200/38400/ 115200bps
NONE
1-247
Buttons--Parameters Environment &Enclosure
Mater ial
Weight
96x 96mm
Ip52
Operat ion temperat ure
Storage tem perat ure
Rel ative hum idity
Sho ck
Vibrat ion
-20~ +50
-30~ +70
0~9 0% non- con den sing
30g in 3 pla nes
10Hz to 50Hz
Wiring Diagram
Auxil iary Power 65~275V AC 90-380V DC
System CT primary Value 1~50000A
1312
L N
3 phase 3 wire3 phase 4 wire
Storage hum idity 95%
Stop bit
Data bit
1
8
Enc losure sty le
Dimensi on
Front protec tion Rati ng
Panel Boa rd mounti ng
Pol ycar bonat e to UL94V0
350 g
Voltage
Cur rent
Frequ enc y
Power fact or
Act ive energ y
Reac tive energ y
Appa rent power
Act ive energ y
Reac tive energ y
THD
Resp ons e time
Netu ral Cur rent
0.5%
0.5%
0.1Hz
1% of Uni ty
+/-1% of range
+/-1% of range
+/-0.5% of range
Class 1 (IEC620 53- 21)
+/-1% of range
1% up to 60t h har moni c
1 seco nd
Class 0.5
Accuracy
U/I
M
P
U1-2 U2-3 U3-1
U1 U2 U3
I1 I2 I3
PF total Hz
PF1 PF2 PF3
THD of U1 U2 U3
THD of I1 I2 I3
P1 P2 P3
Q1 Q2 Q3
S1 S2 S3
Total kW, kVar, kVA
Volta ge Dmd & Max. Current Dmd &Max.
Max.& Min. kW, kVar, kVA
Smart Power Meter Series X835/X825
1 phase 2 wire
Power
0~65535i mp/kV arh
Monitoring and analysing your power consumption
Dimensions
FeaturesA complete wiring solution with Integral connectors and earthingScrewless terminal connectionsVibration proof and maintenance freeReduces intallation time by at least80% over standard methodsEliminates potential cost of errors in electrical connections or programmingTidy solution to cable management
ApprovalsIEC 61326IEC 61010-1IEC 62053-21IEC60044-1CE
Smart Power Meter Series SMARTconnect X835Plug-in Type Easy Connection
The SMARTconnect X835 quick wiring solution provides simple yet fast installation utilising pulg-in connections and pre-cut wiring cable,which allow the installer to easily connect the digital meter and thecurrent transformer to the incoming or outgoing supply.
The SMARTconnect X835 meter is an accurate and cost effective solution for measurement and display of all major electrical and power quality parameters. Its easy programming, mounting and user-friendly navigation make it an ideal choice for customers who require reliable energy measurement.
SMARTconnect X835 is built to high quality standards utilising the latest ‘state-of-the-art’ microprocessor and manufacturin technology.Designed, developed and manufactured in ISO9001:2008 company, SMARTconnect X835 builds on Eastron Electronic Intruments’ long established reputation for metering product quality.
SMARTconnect X835
Components includesSMARTconnect X8353-in-1 CTWiring Cable in various lengths
Input Output
Nominal input voltage
Max. conti nuous input overl oad voltage
Max. short dura tion input voltage
Nominal input voltage burden
Nominal Input Current
Max. conti nuous input overl oad curr nt
Max. short dura tion input curr ent
Star ting curr ent
Nominal input curr ent burden
Puls e Output
Puls e 1 constant
Puls e 2 constant
Puls e weight
Type
Remote module type
Rs485 module type
Protocol
Baudr ate
Pari ty
Frequency
Min. Input Current
Slave ID
20-280V AC L-N 20-480V AC L-L
120% of nom inal
2x Max. (1 second application repeated 5 time at 5 minute interval)
<0. 2VA rms
1/5A AC
120% of nom inal Current
120% of Imax.
5% of nom inal curr ent
0.4% of nom inal curr ent
0.6VA per phase
45-66Hz
2
0~65535i mp/kW h
Confi gurable 200/100/60m S
Pass ive puls e output
RS 485
2-wire hal f duplex
Mobdus RTU
1200/2400/4800/9600/19200/38400/ 115200bps
NONE
1-247
Buttons--Parameters Environment &Enclosure
Mater ial
Weight
96x 96mm
Ip52
Operat ion temperat ure
Storage tem perat ure
Rel ative hum idity
Sho ck
Vibrat ion
-20~ +50
-30~ +70
0~9 0% non- con den sing
30g in 3 pla nes
10Hz to 50Hz
Wiring Diagram
Auxil iary Power 65~275V AC 90-380V DC
System CT primary Value 1~50000A
Storage hum idity 95%
Stop bit
Data bit
1
8
Enc losure sty le
Dimensi on
Front protec tion Rati ng
Panel Boa rd mounti ng
Pol ycar bonat e to UL94V0
350 g
Voltage
Cur rent
Frequ enc y
Power fact or
Act ive energ y
Reac tive energ y
Appa rent power
Act ive energ y
Reac tive energ y
THD
Resp ons e time
Netu ral Cur rent
0.5%
0.5%
0.1Hz
1% of Uni ty
+/-1% of range
+/-1% of range
+/-0.5% of range
Class 1 (IEC620 53- 21)
+/-1% of range
1% up to 60t h har moni c
1 seco nd
Class 0.5
Accuracy
U/I
M
P
U1-2 U2-3 U3-1
U1 U2 U3
I1 I2 I3
PF total Hz
PF1 PF2 PF3
THD of U1 U2 U3
THD of I1 I2 I3
P1 P2 P3
Q1 Q2 Q3
S1 S2 S3
Total kW, kVar, kVA
Volta ge Dmd & Max. Current Dmd &Max.
Max.& Min. kW, kVar, kVA
Smart Power Meter Series SMARTconnect X835
0~65535i mp/kV arh
Smart Power Meter Series SMARTconnect X835
Current Transformers
A range of 3-in-1 current transformers for use with smart conection solution. The 3-in-1 current transformers combine three traditional current transformersin one moulded case with a pluggable locking connectors for simple and easy installation.
Reversible mounting LHS and RHSInternal grounding/earthing facilitySupplied with connectorCompact in sizeEasy connection
Model RatioBurden VAClass 0.5
Burden VAClass 1.0
Item Code
SCT2851A
SCT2851A
SCT2851A
SCT2851A
SCT2851A
SCT2851A
SCT2851B
SCT2851B
SCT2851B
SCT2851B
SCT2851B
SCT2851B
SCT2851C
SCT2851C
SCT2851C
SCT2851C
SCT2851C
SCT2851C
60/5
100/5
125/5
150/5
160/5
200/5
100/5
125/5
150/5
160/5
200/5
250/5
250/5
300/5
400/5
500/5
600/5
630/5
----
----
----
----
----
----
----
----
----
----
----
----
1.5
1.5
1.5
1.5
2.5
1.5
1.5
1.5
1.5
1.5
2.5
1.5
1.5
1.5
2.5
2.5
2.5
2.5
3.75
3.75
3.75
3.75
3.75
2.5
828510001
828510002
828510003
828510004
828510005
828510006
828510007
828510008
828510009
828510010
828510011
828510012
828510013
828510014
828510015
828510016
828510017
828510018
Wiring Cables
Wiring Cables with Integral Clips
High Pull resistance connectors for durable usePre-cut specific to applicationfor easier cable dressingVoltage cables are multipurpose- can be used for fisrt incomingvoltage supply and for additionalmeter looping
883510001
883510002
883510003
883510004
883510005
883510006
883510007
883510008
883510009
883510010
883510011
883510012
883510013
883510014
883510015
883510016
883510017
883510018
Cable Function Length Item Code
1
2
2
1
1
1
1
1
2
2
2
2
2
3
3
3
3
3
Fuses to voltage
Fuses to voltage
Fuses to voltage
Fuses to voltage
Fuses to voltage
Fuses to voltage
Meter to CT
Meter to CT
Meter to CT
Meter to CT
Meter to CT
Meter to CT
Meter to CT
Voltage to voltage
Voltage to voltage
Voltage to voltage
Voltage to voltage
Voltage to voltage
2M
1.5M
1.3M
1M
0.5M
0.3M
1.5M
1.3M
1M
0.5M
0.3M
2M
3M
1.5M
1.3M
1M
0.5M
0.3M
883510017
883510018
3
3
Voltage to voltage
Voltage to voltage 3M
2M
ServiceMeteringApplicationReliabilityTrade Price
The smart choice for your metering needs
35
Dimension
Smart on...
Features
DIN-rail enclosure DIN 43880Backlit LCD screenProgrammable CT ratioTrue rms meaurementUser programmable system configurationPulsed output and Modbus as standard
BenefitsCost effecti veSimple navigationRenowned quali ty
Approvals
IEC 61326IEC 61010-1IEC 62053-21
The unit measurees and displays the characteristics of single phase two wires, three phase three wires and three phases four wires suppliesincluding voltage,frequency,curren t,power and active and reactive energy,imported or exported. Energy is measured in terms of kWh,kVarh.Max.demand curren t can be meaured over present periods of up to 60minutes. In order to measure energy,the unit requires voltage and curren t inputs in addition to the supply requrired ti power the product.The requested curren t input(s) are obtained via curren t trans formers (CT).
The SDM630 can be configured to work with a wide range of cts,giving the unit a wide range of operation.Built-ininterfaces provide pulse and Rs485 Modbus RTU outputs.Configuration is password protected.
The unt can be powered from a seperate auxiliary (AC or DC) supply.Alternatively it can be powered from the monitored supply,where appropriate.
72
94
72
Front view
94
33
51
65
Back viewlateral view
1 2 4 5 6 7 83
9 10 1112 1314 151617181920
Input OutputNominal input voltage
Max. conti nuous input overl oad voltage
Max. short dura tion input voltage
Nominal input voltage burden
Nominal Input Current
Max. conti nuous input overl oad curr nt
Max. short dura tion input curr ent
Star ting curr ent
Nominal input curr ent burden
Puls e Output
Puls e 1 constant
Puls e 2 constant
Puls e weight
Type
Remote module type
Rs485 module type
Protocol
Baudr ate
Pari ty
Frequency
Min. Input Current
Slave ID
100-270V AC L-N 173-467V AC L-L
120% of nom inal
2x Max. (1 second application repeated 5 time at 5 minute interval)
<0. 2VA rms
1/5A AC
120% of nom inal Current
120% of Imax.
5% of nom inal curr ent
0.4% of nom inal curr ent
0.6VA per phase
45-66Hz
2
Confi gurable 100/10/1/0. 1/0. 01kW h(kV arh) /imp
3200i mp/kW h
Confi gurable 200/100/60m S
Pass ive puls e output
Rs485
2-wire hal f duplex
Mobdus RTU
2400/4800/9600/19200/38400bps
NONE/EVEN /OD D
1-247
Accuracy EnvironmentEnclosure
Voltage
Cur rent
Frequ enc y
Power fact or
Act ive energ y
Reac tive energ y
Appa rent power
Act ive energ y
Reac tive energ y
THD
Resp ons e time
Real time clock
0.5%
0.5%
0.1Hz
1% of Uni ty
+/-1% of range
+/-1% of range
+/-1% of range
Class 1 (IEC620 53- 21)
+/-1% of range
1% up to 31st harmoni c
1 seco nd
0.5S/D
Enc losure sty le
Dimensi on
Front protec tion Rati ng
Cas e protec tion
Mater ial
Weight
Termin al block
Termin al size
DIN-rai l mounti ng
72x 100 mm
Ip52
Ip40
Pol ycar bonat e to UL94V0
400 g
Nyl on + fiber glass
8x8mm
Operat ion temperat ure
Storage tem perat ure
Rel ative hum idity
Sho ck
Vibrat ion
-25~ +55
-40~ +70
0~9 0% non- con den sing
30g in 3 pla nes
10Hz to 50Hz
Wiring Diagram
Auxil iary Power 110-400V AC 120-250VDC
System CT primary Value 1~9999
L1
L2
L3
1A FASTBLOW FUSE
1A FASTBLOW FUSE
1 2 3 4 5 6 7 8
AUX
LOAD
Voltage inputs
9 10 11 12 13 14 15 16 17 18 19 20
Current inputs
L1
L2
L3LOAD
P1
S1
P1
S1
B A1 2
L1
L2
L3
1A FASTBLOW FUSE
1A FASTBLOW FUSE
1 2 3 4 5 6 7 8
AUX
LOAD
Voltage inputs
9 10 11 12 13 14 15 16 17 18 19 20
Current inputs
L1
L2
L3
LOAD
P1
S1
P1
S1B A1 2
three phase three wiresthree phase four wiressingle phase two wires
N
N
P1
S1
L1
L2
L3
1A FASTBLOW FUSE
1A FASTBLOW FUSE
1 2 3 4 5 6 7 8
AUX
LOAD
9 10 11 12 13 14 15 16 17 18 19 20
L1
NLOAD
P1
S1
B A1 2
Current inputs
Voltage inputs
ServiceMeteringApplicationReliabilityTrade Price
Making sense of your energy
Smart on...
Features
DIN-rail enclos ure DIN 43880Backlit LCD scr eenMax.1 00A direct inputTrue rms meaurementUser programmable system configurationPulsed output and Modbus RTU standard
BenefitsCost effectiveSimple navigationRenowned quality
Approvals
IEC 61326IEC 61010-1IEC 62053-21
The uni t measur es and displ ays the char act er ist ics of singl e phase two wires , three phase three wires, three phases four wires suppl ies,incl udi ng vol tage, frequency ,cur rent ,pow er and act ive and react ive ener gy,import ed or expor ted, Max. Demand, THD of vol tage and cur rent . Energy is measur ed in terms of kWh,kVarh.Max. dem and cur rent can be meaur ed over present per iods of up to 60m inut es. The SDM630M DC is the smal lest three phase ener gy meter that can work up to 100A load for each phase. It save the cost for CT and labor work for CT connect ion. Bui lt-in interfaces provi de pul se and RS485 Modb us RTU out put s.
The uni t has sel f-pow er sour ce, it can work when any phase has pow er on. touch scr een but tons are on the front panel to ensur e user -friendl y oper at ion and efficiency .
SMART DIN-rail Meter SDM630 DCMulti function / Multi Tariff
Dimension
100
72 66
51
35
laterial view
8 8
back viewfront view
Input Output
SMART DIN-rail Meter SDM630 DC
Nominal input voltage
Max. continuous input overload voltage
Max. short duration input voltage
Nominal input voltage burden
Nominal Input Current
Max. continuous input overload currnt
Max. short duration input current
Starting current
Nominal input current burden
Pulse Output
Pulse 1 constant
Pulse 2 constant
Pulse weight
Type
Remote module type
Rs485 module type
Protocol
Baudrate
Parity
Frequency
Min. Input Current
Slave ID
100-270V AC L-N 173-467V AC L-L
120% of nominal
2x Max. (1 second application repeated 5 time at 5 minute interval)
<0.2VA rms
10A AC
100A
120% of Imax.
5% of nominal current
0.4% of nominal current
0.6VA per phase
45-66Hz
2
Configurable 100/10/1/0.1/0.01/0.001kWh/imp
1000imp/kWh
Configurable 200/100/60mS
Passive pulse output
Rs485
2-wire half duplex
Mobdus RTU
2400/4800/9600/19200/38400bps
NONE/EVEN/ODD
1-247
Accuracy EnvironmentEnclosure
Voltage
Current
Frequency
Power factor
Active energy
Reactive energy
Apparent power
Active energy
Reactive energy
THD
Response time
Real time clock
0.5%
0.5%
0.1Hz
1% of Unity
+/-1% of range
+/-1% of range
+/-1% of range
Class 1 (IEC62053-21)
+/-1% of range
1% up to 31st harmonic
1 second
0.5S/D
Enclosure style
Dimension
Front protection Rating
Case protection
Material
Weight
Terminal block
Terminal size
DIN-rail mounting
72x100mm
Ip52
Ip40
Polycarbonate to UL94V0
400g
Nylon + fiberglass
8x8mm
Operation temperature
Storage temperature
Relative humidity
Shock
Vibration
-25~+55
-40~+70
0~90% non-condensing
30g in 3 planes
10Hz to 50Hz
Wiring Diagram
SDM630 M DC
1 2 3 4
5 6 78 9 10
11 12 13
L1 L2 L3 N
U/ I
M
P
E
BA
1
2
SDM630M DC
1 2 3 4
5 6 78 9 10
11 12 13
L1 N
U/ I
M
P
E
BA
1
2
SDM630M DC
1 2 3 4
5 6 78 9 10
11 12 13
L1 L3
U/ I
M
P
E
BA
1
2
L2
6