Page 1: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

Presentation on Presentation on

““FREE GOVERNOR MODE OPERATION”FREE GOVERNOR MODE OPERATION”

Page 2: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

FREE GOVERNOR OPERATION

WHYFREQ COMPARISION

MAY-02 & MAY-03

GOVERNOR

BEFORE GOVERNORGOVERNOR RESPONSE

IN NER

DEAD BAND GOVERNOR TIME LAG

BLOCKED GOVERNOR

ROLE

DROOPFREQUENCY DECAY RATEBACKLASH

TYPES OF CONTROLSDROOP RESPONSE IN SR

ABT & GOVERNOR

ADVANTAGES

GOVERNOR TYPES

TIME DELAY

CHARACTERISTICS

PROBLEMSUCPE/NERC

LIST OF GENERATORS

FREQUENCY BASED DISPATCH

FREQUENCY BASED DISPATCH

SUPPRESSED GOVERNORACTION

PID CONTROLPTI TAPE ORDERS

Page 3: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

ORDERS

IEGC 6.2 (e) & 6.2(f)IEGC 1.6 IEGC 6.2 (g)

IEGC 6.2 (h)CERC ORDER ON

WB dt 02/01/01

KERALA LETTER ON FGM

FREE GOVERNOR OPERATION

Page 4: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

ROLE OF SYSTEM OPERATOR

• LOAD GENERATION BALANCE

50

Page 5: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

WHY DOES FREQUENCY DROP ?WHY DOES FREQUENCY DROP ?

Sudden addition of load causes a drop in frequency.

An increased load is supplied through an increase in the load angle by which the rotor lags the stator field.

It means a loss of Kinetic Energy of the rotating M/c and a slower speed of rotation i.e. a lower frequency.

f = (P/2) X (N/60)

Where f = frequency of the system

P = no of poles of the M/c.

N = rpm of the M/c.

Page 6: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

• Load dependent on frequency

• Free Governor Operation

• Under Frequency Operation

PRIMARY CONTROLSPRIMARY CONTROLS

Page 7: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

PRIMARY CONTROL …… PRIMARY CONTROL …… (UCPE)(UCPE)

Primary control involves the action of Primary control involves the action of turbine speed governors in generating turbine speed governors in generating units, which will respond where the units, which will respond where the speed (frequency) deviates from the speed (frequency) deviates from the speed (frequency) set point as a result of speed (frequency) set point as a result of an imbalance between generation and an imbalance between generation and demand in the synchronously demand in the synchronously interconnected network as a whole. interconnected network as a whole. Technical solidarity between members Technical solidarity between members will involve the simultaneous action of will involve the simultaneous action of primary control on all generating units primary control on all generating units involved in system control.involved in system control.

Page 8: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

PRIMARY CONTROL…… PRIMARY CONTROL…… (UCPE)(UCPE) The various assumptions, characteristics and The various assumptions, characteristics and

parameters applied to primary control are as parameters applied to primary control are as follows:follows:

► The maximum instantaneous deviation ∆P between The maximum instantaneous deviation ∆P between generation and demand to be corrected by primary generation and demand to be corrected by primary control is 2000 MW control is 2000 MW

► For the whole system, with a peak load of the order For the whole system, with a peak load of the order of 20000 MW and an off-peak load of the order of of 20000 MW and an off-peak load of the order of 12000 MW, assuming 1% self-regulation of load, the 12000 MW, assuming 1% self-regulation of load, the quasi-steady-state frequency deviation must not quasi-steady-state frequency deviation must not exceed 180 mHz and the instantaneous frequency exceed 180 mHz and the instantaneous frequency must not fall below 49.2 Hz in response to a must not fall below 49.2 Hz in response to a shortfall in generation capacity equal to or less than shortfall in generation capacity equal to or less than 2000 MW. The overall network power frequency 2000 MW. The overall network power frequency characteristic for the system is set at 1000 MW/Hzcharacteristic for the system is set at 1000 MW/Hz

Page 9: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

FREQUENCY RESPONSE …… FREQUENCY RESPONSE …… (NERC)(NERC)

NERC

Page 10: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

ABT AND GOVERNORABT AND GOVERNOR

POST ABT FREQUENCY WITHIN 49 TO 50.5HZ

ACHIEVED BY STAGGERING OF LOADS

FLUCTUATION IN FREQUENCY INCREASED

Page 11: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

FREQUENCY COMPARISON FOR

47.50

48.00

48.50

49.00

49.50

50.00

50.50

51.00

51.50

00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23

04-MARCH 02 & 03

Frequency Variation based on data integrated over ONE minute interval

2003

2002

Page 12: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

HUMAN GOVERNOR OPERATIONHUMAN GOVERNOR OPERATION

SYSTEM~TGX

GOVERNOR

Page 13: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

GOVERNORGOVERNOR

SPEED GOVERNOR IS THE CONTROLLING MECHANISM WHICH

CONTROLS THE INPUT TO THE PRIME MOVER AUTOMATICALLY

WHEN THERE IS A CHANGE IN SYSTEM SPEED (FREQUENCY)

WHEN THERE IS A CHANGE IN SYSTEM FREQUENCY GOVERNOR

RESPONSE BY CAUSING VALVES/GATES TO OPEN/CLOSE TO

INCREASE/DECREASE THE INPUT TO THE PRIME MOVER

Page 14: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

MISCONCEPTIONMISCONCEPTION

Governors attempt to restore frequency to normal.

In reality, Governors attempt to restore load generation balance, using frequency change as a signal.

Page 15: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE
Page 16: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE
Page 17: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

CHARACTERISTICSCHARACTERISTICS

1.1. Respond promptly to a small change Respond promptly to a small change in in speed.speed.

2.2. Adjust the throttle valve with a Adjust the throttle valve with a minimum minimum of overshoot.of overshoot.

3.3. Have sufficient power to overcome Have sufficient power to overcome friction losses and unbalance forces in friction losses and unbalance forces in

the throttle valve.the throttle valve.4.4. Permit very little speed fluctuation Permit very little speed fluctuation

under under constant load and steam constant load and steam conditions.conditions.

Page 18: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

TYPES OF GOVERNORSTYPES OF GOVERNORS

►Mechanical shaftMechanical shaft►Direct acting orifice Direct acting orifice ►Oil relay Oil relay ►Precision oil relay Precision oil relay ►Electronic governorElectronic governor

Page 19: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

DEAD BANDDEAD BAND

DEAD BAND OF THE SPEED GOVERNORING SYSTEM IS THE TOTAL AMOUNT OF CHANGE IN STEADY STATE SPEED WITHIN WHICH

THERE IS NO ACTION BY GOVERNOR.

Turbine rated Turbine rated output MWoutput MW

Dead band percent of Dead band percent of rated speedrated speed

IN 50HZ BASEIN 50HZ BASE

< 5MW< 5MW 0.150.15 0.075HZ0.075HZ

5 to 30mw5 to 30mw 0.100.10 0.050HZ0.050HZ

> 30mw > 30mw 0.060.06 0.030HZ0.030HZ

IEC - 45

Page 20: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE
Page 21: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

DROOP CHARACTERISTICSDROOP CHARACTERISTICS

THE AMOUNT OF SPEED (OR FREQUENCY) CHANGE THAT IS NECESSARY TO CAUSE THE MAIN PRIME MOVER CONTROL

MECHANISM TO MOVE FROM FULLY CLOSED TO FULLY OPEN.

NORMAL RANGE - 3 TO 5%

THE MINIMUM RATE OF CHANGE OF SPEED SHOULD NOT BE LESS THAN 0.4 TIMES OF ITS DROOP.

THE MAXIMUM RATE OF CHANGE OF SPEED SHOULD NOT BE MORE THAN 3 TIMES OF ITS DROOP.

Page 22: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

5% DROOP ON 200MW GENERATOR

0

40

80

120

160

200

49 49.5 50 50.5 51 51.5

FREQ IN HZ --->

GE

NE

RA

TIO

N I

N M

W -

-->

Page 23: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

PARTICIPATION OF 5% DROOP ON 200MW & 500MW GENERATORS

0

100

200

300

400

500

600

49 49.5 50 50.5 51 51.5

FREQ IN HZ --->

GE

NE

RA

TIO

N IN

MW

---

>

100MW for 0.5HZ Frequency

40MW for 0.5HZ Frequency

Page 24: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

GOVERNOR DROOP 5% (500MW UNIT)

0

100

200

300

400

500

600

47 47.5 48 48.5 49 49.5 50 50.5 51 51.5 52 52.5 53

FREQ IN HZ --->

GE

NE

RA

TIO

N IN

MW

---

->

600

500

300

200

0

Page 25: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

GOVERNOR DROOP 5% (210MW UNIT)

0

50

100

150

200

250

47 47.5 48 48.5 49 49.5 50 50.5 51 51.5 52 52.5 53

FREQ IN HZ --->

GE

NE

RA

TIO

N IN

MW

---

->

250

210

125

85

0

Page 26: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

RESPONSE BY A 500 MW GENERATOR WITH DIFFRENT DROOP

0

375

125

0

200

500

400

300

100

500

250

0

50

100

150

200

250

300

350

400

450

500

48 48.5 49 49.5 50 50.5 51 51.5HZ->

MW

->

5 % DROOP

4 % DROOP

Page 27: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

GOVERNOR TIME LAGGOVERNOR TIME LAG

TIME TAKEN BY GOVERNOR TO JUST BEGIN CHANGING POWER OUTPUT TO STABILISE FREQUENCY.

OR

TIME BETWEEN A CHANGE IN GENERATOR SPEED & CHANGE IN TURBINE POWER.

Page 28: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

• Dead band 0.25 sec

• Valve opening 0.5 sec

• Steam flow 4 seconds

• During transient state Governor is of little help.

• Effect is felt during steady state

TIME DELAY IN GOVERNOR TIME DELAY IN GOVERNOR OPERATIONOPERATION

Page 29: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

BLOCKED GOVERNORBLOCKED GOVERNOR

BYPASSING THE GOVERNING FEEDBACK MECHANISM TO MAINTAIN FIXED GENERATOR OUTPUT.

DISADVANTAGES:-

• SYSTEM INSTABILITY

• RESTORATION OF SYSTEM FREQUENCY TO NORMAL TAKES MORE TIME AFTER A DISTURBANCE.

Page 30: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

FREQUENCY DECAY RATEFREQUENCY DECAY RATE

Approximate Freq 5 X Lost Generation

Decay Rate = --------------------------------------

In Hz / sec Remaining Generation

Example:-

2200MW200MW

Generation Lost

Freq decay rate = (5 X 200) / 2000 = 0.5 Hz /second

Page 31: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

NEYVELI U-4 ON FGM ON 19/06/2003

160

170

180

190

200

210

220

11:00 11:15 11:30 11:45 12:00 12:15 12:30 12:45 13:00

TIME ->

MW

->

49

49.2

49.4

49.6

49.8

50

50.2

50.4

HZ

->

GENERATION

FREQUENCY

Page 32: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

DROOP CHARACTERISTICS OF NYL U4

170

175

180

185

190

195

200

205

210

49.6 49.7 49.8 49.9 50 50.1 50.2 50.3 50.4 50.5

FREQ CHANGE 49.7 - > 50.4 0.7HzGEN CHANGE 205 -> 177 35MW CHANGE IN GEN 28 MW FOR 0.7 Hz CHANGE IN FREQFOR 200 MW CHANGE IN GEN FREQ CHANGE REQD =(200*0.7)/28 = 5 Hzi.e 5*100 /50 = 10% Droop

Page 33: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

NLY U6 ON FGM ON 15/07/03

145

150

155

160

165

170

175

180

185

190

195

11:30 11:45 12:00 12:15 12:30

TIME-->

MW

-->

49

49.2

49.4

49.6

49.8

50

50.2

50.4

50.6

HZ

-->

GENERATION

FREQUENCY

Page 34: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

DROOP CHARACTERISTICS OF NYL U6

160

165

170

175

180

185

190

195

49.8 49.9 50 50.1 50.2 50.3 50.4 50.5 50.6 50.7

FREQ CHANGE 49.9 - > 50.5 0.6HzGEN CHANGE 191 -> 168 23MW CHANGE IN GEN 24 MW FOR 0.6 Hz CHANGE IN FREQFOR 200 MW CHANGE IN GEN FREQ CHANGE REQD =(200*0.6)/24 = 5 Hzi.e 5*100 /50 = 10% Droop

Page 35: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

IDUKKI GENERATION ON 16/07/2003

0

50

100

150

200

250

300

350

400

0 2 4 6 8 10 12 14 16 18 20 22 0

MW

48.5

49

49.5

50

50.5

51

FR

EQ

->

FREQUENCY

GENERATION

Page 36: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

DROOP CHARACTERSTICS OF IDUKKI

0

50

100

150

200

250

300

350

400

49.3 49.4 49.5 49.6 49.7 49.8 49.9 50 50.1

Page 37: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

49.849.1 49.749.649.549.449.2 49.3 49.9

POINT APOINT B

POINT C

POINT D

POINT A - GENERATION LOSS

POINT B – GOVERNOR ACTION STARTED

POINT C - FREQUENCY AFTER GOVERNER ACTION

POINT D – FREQUENCY AFTER OPERATOR ACTION

Page 38: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

The distance through which one part of connected machinery, as a

wheel, piston, or screw, can be moved without moving the connected parts.

BACKLASHBACKLASH

Page 39: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

BOILER CONTROLSBOILER CONTROLS

• BOILER FOLLOWING SYSTEM

• TURBINE FOLLOWING SYSTEM

• INTEGRATED CONTROL SYSTEM

Page 40: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE
Page 41: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE
Page 42: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

50

Page 43: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

ADVANTAGESADVANTAGES

1. Reduce the random change of frequency

2. Mitigate effect of load generation mismatch

3. Prevents wastage of fuel during low load condition

4. Faster restoration from grid disturbance

Page 44: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

PROBLEMSPROBLEMS1.1. Steam deposits on the valve stem .Steam deposits on the valve stem .

2.2. Lubrication deposits (i.e., soaps, dirt, detergents, Lubrication deposits (i.e., soaps, dirt, detergents, etc.) in the top works of the valve exposed to the etc.) in the top works of the valve exposed to the

elements.elements.3.3. Mechanical failures of the valve resulting from Mechanical failures of the valve resulting from bent stems, either in the valve proper or the upper bent stems, either in the valve proper or the upper

works, damaged split couplings, etc., all within works, damaged split couplings, etc., all within about a 6" area near the center of the valve about a 6" area near the center of the valve

mechanism.mechanism.4.4. Galling of the piston in the hydraulic latch cylinder.Galling of the piston in the hydraulic latch cylinder.

5.5. Jamming of the screw spindle in the larger Jamming of the screw spindle in the larger cylinder-type valve design due to forcing by cylinder-type valve design due to forcing by

operations personneloperations personnel

Page 45: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

FREE GOVERNOR OPERATIONFREE GOVERNOR OPERATION

Mother of all Controls

Self healing mechanism

Collectively Control

Most equitable

Reduces risk of collapse

Makes restoration easy

World wide mandatory practice

Page 46: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE
Page 47: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

5% DROOP OF 210MW UNIT OF STATION AVARIABLE COST = 140 Ps

140

150

160

170

180

190

200

210

49 49.1 49.2 49.3 49.4 49.5 49.6 49.7 49.8 49.9 50 50.1 50.2 50.3 50.4 50.5

FREQ IN HZ --->

GE

NE

RA

TIO

N I

N M

W -

-->

0

60

120

180

240

300

360

420

UI P

RIC

E -

->

STEADY STATE OPERATION

AT 50 HZ GEN= 190MW

Page 48: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

5% DROOP OF 210MW UNIT OF STATION AVARIABLE COST = 140 Ps

140

150

160

170

180

190

200

210

49 49.1 49.2 49.3 49.4 49.5 49.6 49.7 49.8 49.9 50 50.1 50.2 50.3 50.4 50.5

FREQ IN HZ --->

GE

NE

RA

TIO

N I

N M

W -

-->

0

60

120

180

240

300

360

420

UI P

RIC

E -

->

OVER GENERATED BY 5%

FREQUENCY DIPPED TO 49.8 HZ

GENERATION INCREASED BY 10 MW

Page 49: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

5% DROOP OF 210MW UNIT OF STATION AVARIABLE COST = 140 Ps

140

150

160

170

180

190

200

210

49 49.1 49.2 49.3 49.4 49.5 49.6 49.7 49.8 49.9 50 50.1 50.2 50.3 50.4 50.5

FREQ IN HZ --->

GE

NE

RA

TIO

N I

N M

W -

-->

0

60

120

180

240

300

360

420

UI P

RIC

E -

->

OVER GENERATED BY 5%

Page 50: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

5% DROOP OF 210MW UNIT OF STATION AVARIABLE COST = 140 Ps

140

150

160

170

180

190

200

210

49 49.1 49.2 49.3 49.4 49.5 49.6 49.7 49.8 49.9 50 50.1 50.2 50.3 50.4 50.5

FREQ IN HZ --->

GE

NE

RA

TIO

N I

N M

W -

-->

0

60

120

180

240

300

360

420

UI P

RIC

E -

->

STEADY STATE OPERATION

AT 50 HZ GEN= 190MW

Page 51: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

5% DROOP OF 210MW UNIT OF STATION AVARIABLE COST = 140 Ps

140

150

160

170

180

190

200

210

49 49.1 49.2 49.3 49.4 49.5 49.6 49.7 49.8 49.9 50 50.1 50.2 50.3 50.4 50.5

FREQ IN HZ --->

GE

NE

RA

TIO

N I

N M

W -

-->

0

60

120

180

240

300

360

420

UI P

RIC

E -

->

UI PRICE = 84 Ps

FREQUENCY RISE UPTO 50.2 HZ

GENERATION DECREASED BY 17MW

INITIAL

Page 52: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

5% DROOP OF 210MW UNIT OF STATION BVARIABLE COST = 70 Ps

140

150

160

170

180

190

200

210

49 49.1 49.2 49.3 49.4 49.5 49.6 49.7 49.8 49.9 50 50.1 50.2 50.3 50.4 50.5

FREQ IN HZ --->

GE

NE

RA

TIO

N I

N M

W -

-->

0

60

120

180

240

300

360

420

UI P

RIC

E -

->

UI PRICE = 84 Ps

FREQUENCY RISE UPTO 50.2 HZ

GENERATION DECREASED BY 17MW

INITIAL

Page 53: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

5% DROOP OF 210MW UNIT OF STATION BVARIABLE COST = 70 Ps

140

150

160

170

180

190

200

210

49 49.1 49.2 49.3 49.4 49.5 49.6 49.7 49.8 49.9 50 50.1 50.2 50.3 50.4 50.5

FREQ IN HZ --->

GE

NE

RA

TIO

N I

N M

W -

-->

0

60

120

180

240

300

360

420

UI P

RIC

E -

->

GENERATION INCREASED BY 17MW

FINALSINCE VARIABLE COST OF

STATION B < UI PRICE

Page 54: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

5% DROOP OF 210MW UNIT OF STATION AVARIABLE COST = 140 Ps

140

150

160

170

180

190

200

210

49 49.1 49.2 49.3 49.4 49.5 49.6 49.7 49.8 49.9 50 50.1 50.2 50.3 50.4 50.5

FREQ IN HZ --->

GE

NE

RA

TIO

N I

N M

W -

-->

0

60

120

180

240

300

360

420

UI P

RIC

E -

->

FINAL

GENERATION FURTHER REDUCED BY 17MW

SINCE VARIABLE COST OF

STATION A > UI PRICE

Page 55: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

Kc∑

FB

PROPORTIONAL CONTROL

A simple form of control, where the controller response is proportional to the control error.

Provides immediate controller response to setpoint change, but speed may not settle exactly on SP using proportional control alone

Page 56: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE
Page 57: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

FB

∫ fdt1/Tc

INTEGRAL CONTROL

Control action is control error integrated over time.

–Integrates the error over time to overcome the offset from Proportional alone such that speed = SP. However, Integral action may cause overshoot, oscillation and/or instability problems

Kc

Page 58: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

PID Parameter Tuning – PI only

Page 59: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

FB

df/dtTd

DIFFERENTIAL CONTROL

In differential control, control action is based on the change (derivative) of the control error.

Used to put the reigns on PI control to prevent overshoot and oscillation and to add stability

Kc

Page 60: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

A form of control based on the three basic types of control: proportional, integral and differential control. PID Controllers are created by combining P, I and D elements to get the desired control characteristic.

PID CONTROL

Page 61: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE
Page 62: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE
Page 63: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

SUPPRESSED GOVERNOR OPERATION

OPEN

Page 64: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE
Page 65: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

1.6 Free-Governor Action:The dates from which the stipulations under sections 4.8(c), 4.8(d), 6.2(e), 6.2(f),

6.2(g) and 6.2(h) would come into effect shall be as under : (i) All thermal generating units of installed capacity 200 MW and above and reservoir based hydro units of installed capacity 50 MW and above :

Southern Region } }

Eastern Region } }

Northern Region } The date for the } implementation of the

Western Region } Commercial mechanism} mentioned in Section 7.1(d)

(ii) All thermal and reservoir based hydro } for the respective region. generating units of installed capacity } 10 MW and above in North Eastern Region } (iii) All other generating units - three months after the above dates for the respective regions except in the case of Nuclear Power Stations which shall be exempted till the next review of the IEGC.

Any exemption from the above may be granted only by CERC for which the concerned constituent shall file a petition in advance.

CERC ORDER ON ‘IEGC’ DATED 22.02.2002QUOTE

UNQUOTE

Page 66: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

6.2(e) All generating units, which are synchronised with the grid, irrespective of

their ownership, type and size, shall have their governors in normal operation at all

times. If any generating unit of over fifty (50) MW size (10 MW for North Eastern

Region) is required to be operated without its governor in normal operation, the

RLDC shall be immediately advised about the reason and duration of such

operation. All governors shall have a droop of between 3% and 6%.

6.2(f) Facilities available with/in load limiters, Automatic Turbine Run up System

(ATRS), Turbine supervisory control, coordinated control system, etc. shall not be

used to suppress the normal governor action in any manner. No dead bands and/or

time delays shall be deliberately introduced.

CERC ORDER ON ‘IEGC’ DATED 22.02.2002QUOTE

UNQUOTE

Page 67: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

6.2(g) All Generating Units, operating at/up to 100% of their Maximum Continuous

Rating (MCR) shall normally be capable of (and shall not in any way be prevented from)

instantaneously picking up five per cent (5%) extra load for at least five (5) minutes or

within technical limits prescribed by the manufacturer when frequency falls due to a

system contingency. The generating units operating at above 100% of their MCR shall

be capable of (and shall not be prevented from) going at least up to 105% of their MCR

when frequency falls suddenly. Any generating unit of over fifty (50) MW size (10 MW for

NER) not complying with the above requirement, shall be kept in operation

(synchronised with the Regional grid) only after obtaining the permission of RLDC.

However, the constituent can make up the corresponding short fall in spinning reserve

by maintaining an extra spinning reserve on the other generating units of the constituent.

CERC ORDER ON ‘IEGC’ DATED 22.02.2002QUOTE

UNQUOTE

Page 68: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

6.2(h) The recommended rate for changing the governor setting, i.e. supplementary

control for increasing or decreasing the output (generation level) for all generating .units,

irrespective of their type and size, would be one (1.0) per cent per minute or as per

manufacturer's limits. However, if frequency falls below 49.5 Hz, all partly loaded

generating units shall pick up additional load at a faster rate, according to their capability.

CERC ORDER ON ‘IEGC’ DATED 22.02.2002QUOTE

UNQUOTE

Page 69: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

FREE GOVERNOR MODE OF OPERATION

Quote

6.2 (c) All generating units, which are synchronised with the grid, irrespective of their ownership, type and size, shall have

their governors in normal operation at all times. If any generating unit of over fifty (50) MW size (10 MW for North

Eastern Region) is required to be operated without its governor in normal operation, the RLDC shall be immediately advised

about the reason and duration of such operation. All governors shall have a droop of between 3% and 6%.

Unquote

CERC Order ON ‘IEGC’ dated 21.12.1999

SRLDC Requested all constituents including ISGS vide letter dated 3rd Jan 03 to take a lead in this matter.

Page 70: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

FREE GOVERNOR MODE OF OPERATION• The matter discussed in 368th OCC meeting

• All SR constituents/ISGS agreed to convey their readiness by 21.01.2003

• SRLDC again requested all constituents vide letter dt.21.01.03 to intimate unit/station wise status/ programme

• Matter discussed in 109th TCC/131st SREB meeting.

• ISGS/SR constituents agreed for FGM by 1st May 2003.

• Discussed in 369th, 370th, 371st & 372nd OCC meetings.

• KSEB & TNEB furnished unit wise/ station wise program/ constraint/ preparedness

• APTRANSCO conveyed readiness for FGM of all generators except thermal units of APGENCO

• Freq response characteristics calculation details covering 3 events furnished for examination & necessary

feedback by the constituents.

• Constituents Actual response Shortfall (AVG) (AVG)

AP 2 % 98 %

KAR 17 % 83 %

KER 29 % 71 %

TN 13 % 87 %

• Matter again discussed in 110th TCC/132nd SREB meeting.

• All SR constituents/ISGS agreed for FGM by 1st August 2003.

• Action by constituents to achieve the target to be discussed.

• Present status to be reviewed.

NLY-II U#4LETTERS

Page 71: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE

NEYVELI U-4 ON FGM ON 19/06/2003

160

170

180

190

200

210

220

11:00 11:15 11:30 11:45 12:00 12:15 12:30 12:45 13:00

49

49.2

49.4

49.6

49.8

50

50.2

50.4

NYL U-4 GENERATION

REDUCTION OF 21 MW IN 5 MTS

FREQUENCY

Page 72: Presentation on “FREE GOVERNOR MODE OPERATION”. FREE GOVERNOR OPERATION WHY FREQ COMPARISION MAY-02 & MAY-03 GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE