53
NFPA Technical Committee on Building Construction NFPA 5000, NFPA 220 and NFPA 221 FIRST DRAFT MEETING AGENDA Monday, May 21, 8:00 a.m.-5:00 p.m. Tuesday, May 22, 2012 8:00 a.m. - Noon Indianapolis Convention Center – Room 126 Indianapolis, IN 1. Call to Order. Call meeting to order by Chair Joseph Versteeg at 8:00 a.m. Eastern on May 21, 2012 at the Indianapolis Convention Center, Indianapolis, IN. 2. Introduction of Committee Members and Guests. For a current committee roster, see page. 02. 3. Approval of Prior Meeting Minutes. Approve the October 6, 2010 meeting minutes see page 05. 4. New Process Review and Staff Liaison Report, see page 08. 5. NFPA 5000 First Draft (formerly ROP) Preparation. For Public Input Review, see page 23. 6. NFPA 220 First Draft (formerly ROP) Preparation. For Public Input Review, see page 35. 7. NFPA 221 First Draft (formerly ROP) Preparation. For Public Input Review, see page 38. 8. Task Group Discussion, see page 43. a. NFPA 5000 Chapter 7 Task Group b. NFPA 221 Task Group 9. Suggested Editorial Revisions, see page 53. 10. Other Business. 11. Future Meetings. 12 Adjournment. Page 1 of 53

NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

  • Upload
    others

  • View
    39

  • Download
    1

Embed Size (px)

Citation preview

Page 1: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

 

NFPA Technical Committee on Building Construction NFPA 5000, NFPA 220 and NFPA 221 FIRST DRAFT MEETING AGENDA

Monday, May 21, 8:00 a.m.-5:00 p.m. Tuesday, May 22, 2012 8:00 a.m. - Noon Indianapolis Convention Center – Room 126

Indianapolis, IN

1. Call to Order. Call meeting to order by Chair Joseph Versteeg at 8:00 a.m. Eastern on

May 21, 2012 at the Indianapolis Convention Center, Indianapolis, IN.

2. Introduction of Committee Members and Guests. For a current committee roster, see page. 02.

3. Approval of Prior Meeting Minutes. Approve the October 6, 2010 meeting minutes

see page 05.

4. New Process Review and Staff Liaison Report, see page 08.

5. NFPA 5000 First Draft (formerly ROP) Preparation. For Public Input Review, see page 23.

 

6. NFPA 220 First Draft (formerly ROP) Preparation. For Public Input Review, see page 35.

7. NFPA 221 First Draft (formerly ROP) Preparation. For Public Input Review, see page 38.

8. Task Group Discussion, see page 43. a. NFPA 5000 Chapter 7 Task Group b. NFPA 221 Task Group

9. Suggested Editorial Revisions, see page 53. 10. Other Business. 11. Future Meetings. 12 Adjournment.

Page 1 of 53

Page 2: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

Address List No PhoneBuilding Construction BLD-BLC

Building Code

Tracy L. Golinveaux05/16/2012

BLD-BLC

Joseph H. Versteeg

ChairVersteeg Associates86 University DriveTorrington, CT 06790International Fire Marshals Association

E 10/27/2005BLD-BLC

Farid Alfawakhiri

PrincipalAmerican Iron and Steel Institute380 Cottonwood LaneNaperville, IL 60540Alternate: Jonathan Humble

M 7/23/2008

BLD-BLC

Raymond J. Battalora

PrincipalAon Fire Protection Engineering1701 North Collins Blvd., Suite 235Richardson, TX 75080-3553Alternate: James P. Hurst

I 7/26/2007BLD-BLC

Jesse J. Beitel

PrincipalHughes Associates, Inc.3610 Commerce Drive, Suite 817Baltimore, MD 21227-1652

SE 4/3/2003

BLD-BLC

David S. Collins

PrincipalThe Preview Group, Inc.632 Race StreetCincinnati, OH 45202American Institute of Architects

SE 7/16/2003BLD-BLC

Richard J. Davis

PrincipalFM Global1151 Boston-Providence TurnpikePO Box 9102Norwood, MA 02062-9102Alternate: Scott K. Anderson

I 4/3/2003

BLD-BLC

Alan J. Dopart

PrincipalWillis of New Jersey350 Mt. Kemble AvenueMorristown, NJ 07962

I 4/3/2003BLD-BLC

Victor L. Dubrowski

PrincipalCode Consultants, Inc.2043 Woodland ParkwaySt. Louis, MO 63146-4235

SE 7/16/2003

BLD-BLC

David W. Frable

PrincipalUS General Services AdministrationPublic Buildings Service665 Green Meadow LaneGenera, IL 60134Alternate: Joshua W. Elvove

U 4/3/2003BLD-BLC

Sam W. Francis

PrincipalAmerican Wood Council1 Dutton Farm LaneWest Grove, PA 19390American Forest & Paper AssociationAlternate: Dennis L. Pitts

M 4/3/2003

BLD-BLC

Joseph T. Holland

PrincipalHoover Treated Wood Products1225 North Halifax AvenueDaytona Beach, FL 32118Alternate: David G. Bueche

M 7/16/2003BLD-BLC

Jeffrey M. Hugo

PrincipalNational Fire Sprinkler Association, Inc.1088 West Borton RoadEssexville, MI 48732Alternate: Robert B. Treiber

M 7/26/2007

BLD-BLC

Robert L. Lemon, Jr.

PrincipalAmericana Construction Group, Inc.Americana Inspection Services12213 Bucky AvenuePO Box 4838Hagerstown, MD 21740

SE 8/9/2011BLD-BLC

Dale Litton

PrincipalTexas Instruments, Inc.13020 TI Boulevard, MS 3619Dallas, TX 75243Semiconductor Industry AssociationAlternate: William E. Koffel

U 10/27/2009

1Page 2 of 53

Page 3: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

Address List No PhoneBuilding Construction BLD-BLC

Building Code

Tracy L. Golinveaux05/16/2012

BLD-BLC

Gregory F. Masterson

PrincipalLiberty Mutual Property200 Galleria Parkway, SWAtllanta, GA 30339Property Casualty Insurers Association of America

I 3/4/2008BLD-BLC

Joe McElvaney

PrincipalPhoenix Fire Department150 South 12th streetPhoenix, AZ 85034

E 10/27/2005

BLD-BLC

Renato R. Molina

PrincipalThe RJA Group, Inc.Rolf Jensen & Associates, Inc.14502 Greenview Drive, Suite 500Laurel, MD 20708Alternate: Thomas Izbicki

SE 4/3/2003BLD-BLC

John G. Richards

PrincipalUS Army Corps of Engineers404 Longview AveWinchester, VA 22601

U 3/1/2011

BLD-BLC

Brad Schiffer, AIA

PrincipalBrad Schiffer/Taxis, Inc.520 Sugar Pine LaneNaples, FL 34108

SE 4/3/2003BLD-BLC

Stephen V. Skalko

PrincipalPortland Cement Association128 Summerfield DriveMacon, GA 31210

M 4/3/2003

BLD-BLC

Robert A. Wessel

PrincipalGypsum Association6525 Belcrest Road, Suite 480Hyattsville, MD 20782Alternate: Michael A. Gardner

M 4/3/2003BLD-BLC

Peter J. Willse

PrincipalXL Global Asset Protection Services100 Constitution Plaza, 12th FloorHartford, CT 06103

I 4/3/2003

BLD-BLC

Michael W. Ashley

Voting AlternateAlliance for Fire & Smoke Containment & Control Inc.4 Brookhollow Road, SWRome, GA 30165Voting Alt. to AFSCC Rep.

M 10/4/2007BLD-BLC

Robert G. Backstrom

Voting AlternateUL LLC333 Pfingsten RoadNorthbrook, IL 60062-2096Voting Alt. to UL Rep.

RT 4/3/2003

BLD-BLC

Scott K. Anderson

AlternateFM Global1151 Boston Providence TurnpikePO Box 9102Norwood, MA 02062-9102Principal: Richard J. Davis

I 3/21/2006BLD-BLC

David G. Bueche

AlternateHoover Treated Wood Products13768 West Asbury CircleLakewood, CO 80228Principal: Joseph T. Holland

M 11/2/2006

BLD-BLC

Joshua W. Elvove

AlternateUS General Services AdministrationPublic Buildings Service3478 South Cimarron WayAurora, CO 80014-3912Principal: David W. Frable

U 03/05/2012BLD-BLC

Michael A. Gardner

AlternateGypsum Association6525 Belcrest Road, Suite 480Hyattsville, MD 20782Principal: Robert A. Wessel

M 7/16/2003

2Page 3 of 53

Page 4: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

Address List No PhoneBuilding Construction BLD-BLC

Building Code

Tracy L. Golinveaux05/16/2012

BLD-BLC

Jonathan Humble

AlternateAmerican Iron and Steel Institute45 South Main Street, Suite 312West Hartford, CT 06107-2402Principal: Farid Alfawakhiri

M 7/23/2008BLD-BLC

James P. Hurst

AlternateAon/Schirmer Engineering Corporation1420 5th Avenue, Suite 1200Seattle, WA 98101Principal: Raymond J. Battalora

I 10/27/2009

BLD-BLC

Thomas Izbicki

AlternateThe RJA Group, Inc.Rolf Jensen & Associates, Inc.2301 West Plano Parkway, Suite 210Plano, TX 75075Principal: Renato R. Molina

SE 8/9/2011BLD-BLC

William E. Koffel

AlternateKoffel Associates, Inc.8815 Centre Park Drive, Suite 200Columbia, MD 21045-2107Semiconductor Industry AssociationPrincipal: Dale Litton

U 7/16/2003

BLD-BLC

Dennis L. Pitts

AlternateAmerican Wood Council1721 West Plano Parkway, #224Plano, TX 75075American Forest & Paper AssociationPrincipal: Sam W. Francis

M 4/3/2003BLD-BLC

Robert B. Treiber

AlternateNational Fire Sprinkler Association, Inc.2366 Georgeland TrailCenterville, OH 45459Principal: Jeffrey M. Hugo

M 10/23/2003

BLD-BLC

Tracy L. Golinveaux

Staff LiaisonNational Fire Protection Association1 Batterymarch ParkQuincy, MA 02169-7471

01/04/2010

3Page 4 of 53

Page 5: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010

Page 1 of 3

NFPA Technical Committee on Building Construction ROC Meeting Minutes

NFPA 220, NFPA 221 and NFPA 5000 Wednesday, October 6, 2010

Hotel Monteleone New Orleans, LA

Item 1, Call to Order. The ROC meeting of the NFPA 220, 221, and NFPA 5000 Technical Committee on Building Construction was called to order by Chair, Joe Versteeg at 8:00 a.m. on Wednesday, October 6, 2010, at the Hotel Monteleone, New Orleans, LA. Item 2, Introduction of Attendees. The chair opened the meeting with welcoming remarks, and self-introductions of meeting attendees and guests were conducted. The following Principal and Alternate members were present: NAME COMPANY Joseph Versteeg, Chair Versteeg Associates Rep. International Fire Marshals Association Raymond Battalora, Principal Aon/Schirmer Engineering Corporation David Bueche Hoover Treated Wood Products (Alternate to J. Holland) David Collins, Principal The Preview Group, Inc. Rep. American Institute of Architects Richard Davis, Principal FM Global Alan Dopart, Principal Willis of New Jersey Victor Dubrowski, Principal Code Consultants, Inc. Daniel Gemeny, Principal The RJA Group, Inc. David Frable, Principal US General Services Administration Jeffrey Hugo, Principal National Fire Sprinkler Association, Inc. William Koffel Koffel Associates, Inc. (Alternate to D. Litton) Dale Litton, Principal Texas Instruments Rep. Semiconductor Industry Association Gregory Masterson, Principal Liberty Mutual Property Rep. Property Casualty Insurers Association of America Joe McElvaney, Principal Phoenix Fire Department

Page 5 of 53

Page 6: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010

Page 2 of 3

Dennis Pitts American Forest & Paper Association (Alternate to S. Francis) Rick Thornberry, Principal The Code Consortium, Inc. Rep. Alliance for Fire & Smoke Containment & Control Inc. Robert Wessel, Principal Gypsum Association Peter Willse, Principal XL Global Asset Protection Services Tracy Golinveaux, Staff NFPA Staff The following Technical Committee Principal Members (with no alternate present) and Voting Alternates were absent: NAME COMPANY Farid Alfawakhiri, Principal American Iron and Steel Institute Jesse Beitel, Principal Hughes Associates, Inc. Sam Francis, Principal American Forest & Paper Association Carmen Rao, Principal City of Danbury Fire Department Brad Schiffer, Principal Brad Schiffer/Taxis, Inc. Stephen Skalko, Principal Portland Cement Association Robert Backstrom Underwriters Laboratories Inc. (Voting Alternate) The following Guests were in attendance: NAME COMPANY Bonnie Manley American Iron and Steel Institute Alan Fraser NFPA Staff Item 2, Staff Presentation Ms. Golinveaux introduced a PowerPoint presentation explaining the actions the committee can take at the ROC phase of the revision cycle. In addition, she discussed the new Document Information pages on NFPA’s website. It should be noted that all meeting information including agendas and minutes will be posted under the “next edition” tab of these pages. The pages can be accessed at www.nfpa.org/5000 or www.nfpa.org/220 . Item 3, Approval of Minutes. The September 23, 2009 Meeting Minutes were approved as written and distributed. Item 4, NFPA 5000 Public Comment Preparation (ROC). All comments were reviewed and acted on. See the ROC Ballot.

Item 5, NFPA 220 Public Comment Preparation (ROC). All comments were reviewed and acted on. See the ROC Ballot. Item 6, NFPA 221 Public Comment Preparation (ROC). All comments were reviewed and acted on. See the ROC Ballot.

Page 6 of 53

Page 7: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010

Page 3 of 3

Item 7, NFPA 5000/1124 Task Group Update The BLD-BLC/1124 task group reviewed and revised the draft proposals submitted by the Pyrotechnics Committee. Rick Thornberry provided a brief report on the Pyrotechnics Committee’s response to the proposed changes. A ballot will be sent to BLD-BLC to approve the Pyrotechnic Committee’s actions.

Item 7, New Business. Ms. Golinveaux reviewed two requests from the Fire Protection Research Foundation for ideas for new research and feedback on the new NIST laboratory. Item 8, Date and Location of Next Meeting. The committee will meet in the Fall of 2012 to prepare the Reports on Proposals (ROPs) for the 2015 editions of NFPA 101 and NFPA 5000. Meeting notices will be distributed when the date and location have been confirmed. Item 9, Adjournment. The meeting was adjourned at 5:00 PM. Attachments

Page 7 of 53

Page 8: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

5/16/2012

1

NFPA First Draft Meetings

Welcome TCs on

May 21, 2012

Building Construction

5/16/2012

Indianapolis, IN

NFPA First Draft Meetings

At this and all NFPA committee meetings we are concerned with your safety. If the fire alarm sounds,concerned with your safety. If the fire alarm sounds, please proceed to an exit.

5/16/2012

Page 8 of 53

Page 9: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

5/16/2012

2

NFPA First Draft Meetings

Members, please verify/update your contact informationinformation

Use of tape recorders or other means capable of reproducing verbatim transcriptions of this or any NFPA meeting is not permitted

5/16/2012

NFPA First Draft Meetings

Guests All guests are required to sign in and identify All guests are required to sign in and identify

their affiliations. Participation is limited to those individuals who

have previously requested of the chair time to address the committee on a particular subject or individuals who wish to speak to Public Input they have submitted

5/16/2012

they have submitted.Guest chairs are located around the room as a

courtesy.

Page 9 of 53

Page 10: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

5/16/2012

3

NFPA First Draft Meetings

Members categorized in ANY interest category who have been retained to represent thewho have been retained to represent the interests of ANOTHER interest category (with respect to a specific issue or issues that are to be addressed by a TC/CC) shall declare those interests to the committee and refrain from voting on any Public Input Comment or other

5/16/2012

voting on any Public Input, Comment, or other matter relating to those issues.

NFPA First Draft MeetingsNew Process

General ProceduresFollow Robert’s Rules of Order.

Discussion requires a motion.

5/16/2012

Page 10 of 53

Page 11: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

5/16/2012

4

Motions for Ending Debate Previous Question or “Call the Question”

NFPA First Draft Meetings

Call the Question Not in order when another has the floor

Requires a second

This motion is not debatable and DOES NOT automatically stop debate

A 2/3 affirmative vote will immediately close debate and

5/16/2012

return to the original motion on the floor. Less then 2/3 will allow debate to continue.

NFPA First Draft Meetings

Committee member actions:

Member addresses the chair.

Receives recognition from the chair.

Introduces the motion.

Another member seconds the motion.

5/16/2012

Page 11 of 53

Page 12: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

5/16/2012

5

Committee chair actions:

NFPA First Draft Meetings

States the motion.

Calls for discussion.

Ensures all issues have been heard.

Takes the vote.

5/16/2012

Announces the result of the vote.

NFPA First Draft Meetings

Technical Committee on Building Construction Enforcers 2 Members: 8% Enforcers, 2 Members: 8%

Insurance,5 Members: 21%

Installer/Maintainer, 0 Members: 0%

Labor, 0 Member: 0%

Manufacturers, 7 Members: 29%

Research & Testing,1 Member: 4%

S i l E t 6 M b 25%

5/16/2012

Special Experts, 6 Members: 25%

Users, 3 Members: 13%

Page 12 of 53

Page 13: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

5/16/2012

6

NFPA First Draft Meetings

Timeline Public Input Stage (First Draft):

Fi t D ft M ti M 21 2012 First Draft Meeting: May 21, 2012 Posting of First Draft for Balloting Date: October 12, 2012 Posting of First Draft for Public Comment: November 16, 2012

Comment Stage (Second Draft): Public Comment Closing Date: May 3, 2013 Second Draft Meeting Period: May – July 12, 2013 Posting of Second Draft for Balloting Date: September 13, 2013 Posting of Second Draft for NITMAM: January 3, 2014

Tech Session Preparation: NITMAM Closing Date: February 7, 2014

5/16/2012

g y , NITMAM /CAM Posting Date: April 4, 2014 NFPA Annual Meeting: June 9-12, 2014

Standards Council Issuance: Issuance of Consent Documents: June 2014 with 2015 edition date Issuance of Documents with CAM: August 14, 2014 with 2015 edition date

NFPA First Draft MeetingsNew Process – What’s New?

Changes in Terms:

New Term Old Term

Input Stage ROP Stage

Public Input Proposal

First Draft Meeting ROP Meeting

Committee Input“Trial Balloon”

(or later, FR that fails ballot)

Committee Statement (CS) Committee Statement

5/16/2012

Committee Statement (CS) Committee Statement

First Revision (FR)Committee Proposal or Accepted

Public Proposal

First Draft Report ROP

First Draft ROP Draft

Page 13 of 53

Page 14: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

5/16/2012

7

NFPA First Draft MeetingsNew Process – What’s New?

Changes in Terms:

New Term Old Term

Comment Stage ROC Stage

Public Comment Public Comment

Second Draft Meeting ROC Meeting

Committee CommentComment that Failed Ballot

(Second Revision that failed ballot)

5/16/2012

( )

Second RevisionCommittee Comment or Accepted

Public Comment

Second Draft Report ROC

Second Draft ROC Draft

Flowchart

See page 4 for flowchart overview

5/16/2012

Page 14 of 53

Page 15: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

5/16/2012

8

NFPA First Draft MeetingsNew Process

NEW Committee Actions and Motions:

Resolve Public Input

Create a First Revision

Create a Committee Input (Trial Balloon)

5/16/2012

First DraftNew Process

• Resolve a Public Input (No Change to Text):

Committee does not want to incorporate the Public Input as a revision.

Committee develops a Committee Statement (CS) to respond (resolve) a Public Input.

Committee must clearly indicate reasons for not ti th d ti i CS

5/16/2012

accepting the recommendation in CS.

Does not get balloted

Page 15 of 53

Page 16: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

5/16/2012

9

First DraftNew Process

• Create a First Revision (FR) Committee wants to make a change to a current

section.

Committee develops a Committee Statement (CS) substantiating the change.

If the revision is associated with one or more P bli I t ( ) th C itt d l CS t

5/16/2012

Public Input (s), the Committee develops a CS to respond to each PI.

Each FR gets balloted

First DraftNew Process

• Create a Committee Input (Trial B ll )Balloon) Committee wants to receive Public Comment on a

topic, but not ready to incorporate it into the draft

Need to have a Committee Statement

Does not get balloted

5/16/2012

Page 16 of 53

Page 17: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

5/16/2012

10

First DraftNew Process

Committee Statements (Substantiation):

All P bli I t t h C ittAll Public Input must have a Committee Statement

Must include a valid technical reason

No vague references to “intent”

Explain how the submitter’s substantiation

5/16/2012

Explain how the submitter’s substantiation is inadequate

First DraftNew Process

Committee Statements (Substantiation):

Sh ld f th Fi t R i i if itShould reference the First Revision if it addresses the intent of the Submitter’s Public Input

5/16/2012

Page 17 of 53

Page 18: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

5/16/2012

11

First DraftNew Process

Formal voting Voting during meeting is used to establish

a sense of agreement (simple majority)

Secured by letter ballot (2/3 agreement)

Only the results of the formal ballot determine the official position of the

5/16/2012

determine the official position of the committee on the First Draft

First DraftNew Process

Ballots are on the First Revisions (FR) ONLY Public Input and Committee Input not balloted Public Input and Committee Input not balloted Reference materials are available:

First Draft, PI, CI, CS, etc

Ballot form allows you to vote: Affirmative on all FR Affirmative on all FR with exceptions specifically noted

Ballot form provides a column for affirmative

5/16/2012

Ballot form provides a column for affirmative with comment Note: This box only needs to be checked if there is an

accompanying comment.

Reject or abstain requires a reason.

Page 18 of 53

Page 19: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

5/16/2012

12

First DraftNew Process

Initial ballot Initial ballotCirculation of negatives and commentsMembers may change votes during

circulation First Revision that fails letter ballot

5/16/2012

becomes Committee Input (CI) – just like the trial balloon version of CI – so as to solicit Public Comment

First DraftNew Process

Balloting

Ballots will be an online formatBallots will be an online format

Alternates are strongly encouraged to return ballots

5/16/2012

Page 19 of 53

Page 20: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

5/16/2012

13

NFPA First Draft Meetings

No New Material after the Public Input Stage

What constitutes new material is to some extent a judgment call

5/16/2012

TC Struggles with an Issue

Code Fund Lends a Hand

Research Project Carried Outwith an Issue

• TC needs data on a new technology or emerging issue

• Two opposing views on an issue with no real data

a Hand

• TC rep and/or staff liaison submits a Code Fund Request

• Requests are reviewed by a Panel and chosen based

Carried Out

• Funding for project is provided by the Code Fund and/or industry sponsors

• Project is completed real data

• Data presented is not trusted by committee

chosen based on need / feasibility

completed and data is available to TC

www.nfpa.org/codefund5/16/2012

Page 20 of 53

Page 21: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

5/16/2012

14

Legal

Antitrust: the single most important provision-Federal law prohibits contracts combinationsFederal law prohibits contracts, combinations, or conspiracies which unreasonably restrain trade or commerce. Section 1 of the Sherman Act

Patent: Disclosures of essential patent claims should be made by the patent holder, but others may also notify NFPA if they believe that a

5/16/2012

y y yproposed or existing NFPA standard includes an essential patent claim.

Legal

Activities Disapproved by the CourtsP ki ti Packing meetings

Hiding commercial interest throwing the committees out of balance

No final decision-making authority to unbalanced Task Groups; include all interested parties.

5/16/2012

Hiding scientific or technical information from committees

Page 21 of 53

Page 22: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

5/16/2012

15

Doc Info Pages

Document Information Next Edition Technical Committee

• Document scope• Current/Previous

Edition information• Issued TIAs, FIs and

Errata• Archived revision

information• Standard Council

Decisions

• Meetings and Ballots• ROP/ROC or First

Draft Report and Second Draft Report

• NITMAM and Standard Council Decisions

• Submission of Public Input/Comment

f

• Committee name, responsibility and scope

• Staff liaison• Committee list

• Private committee contact information

• Current committee documents in PDF f

5/16/2012

• Articles and Reports• Read only document

• Private TC info• Ballot circulations,

informational ballots and other committee info

format• Committees seeking

members and committee online application

NFPA First Draft Meetings

Thank you for participating!Thank you for participating!

Any questions?

5/16/2012

Page 22 of 53

Page 23: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

Report on Proposals – June 2014 NFPA 5000_______________________________________________________________________________________________5000- Log #265 BLD-BLC

_______________________________________________________________________________________________Jeffrey M. Hugo, National Fire Sprinkler Association, Inc.

Add a new section to read:Every building shall have a water supply available to the premises that is capable of producing the

required fire flow as calculated in accordance with NFPA 1 for the required duration as determined by NFPA 1.Builders and developers need to provide sufficient water for fighting a fire at the buildings that they

construct. The fire department should not be responsible for bringing water with them to fight a fire. In rural communitieswithout public mains and hydrants, stored water needs to be available to fight fires. In communities with water utilitiesand fire hydrants, sufficiently sized mains need to be placed in service to provide reasonable fire flow. Section 18.4 ofNFPA 1 provides a method for determining the required fire flow and duration for all properties. This procedure needs tobe followed and implemented when a building is being constructed and the beginning of Chapter 7 brings the issue tothe beginning of the design.

_______________________________________________________________________________________________5000- Log #93 BLD-BLC

_______________________________________________________________________________________________Marcelo M. Hirschler, GBH International

Add text to read as follows:7.1.4.3* . A listed wood product impregnated with chemical by a pressure process or

other means during manufacture, which complies with the requirements of ASTM E2786.ASTM has now issued a test method, ASTM E2768, which contains the three requirements discussed

in this section, namely that a product be tested in accordance with ASTM E84 or UL 723, and exhibit a flame spreadindex of 25 or less, show no evidence of significant progressive combustion when the test is continued for 30 minutes(i.e. an additional 20-minute period over the standard ASTM E84 duration of 10 minutes) and that the flame front notprogress more than 101/2 feet (3200 mm) beyond the centerline of the burners at any time during the test. This changereplaces the lengthy information about requirements with a reference to the standard.The NFPA Manual of Style does not allow requirements in definitions. Therefore this change places the requirementsinto a new section in Chapter 7, immediately following the requirements for noncombustible material and limitedcombustible material.

1Printed on 5/16/2012

Page 23 of 53

Page 24: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

Report on Proposals – June 2014 NFPA 5000_______________________________________________________________________________________________5000- Log #176 BLD-BLC

_______________________________________________________________________________________________Scott J. Harrison, Marioff Inc.

Revise text to read as follows:   When buildings are protected throughout with an approved automatic sprinkler system that is installed in

accordance with NFPA 13, ; NFPA 13D,, or NFPA 13R,

, or an approvedautomatic water mist system installed in accordance with NFPA 750, ,the distance shall be permitted to be increased to 450 ft (137 m). [ 18.2.3.2.2.1]

Water Mist systems have been approved and installed in many sprinkler applications globally for over15 yrs. They have been listed by national and internationally recognized testing laboratories such as: (OrdinaryHazard Group 1 occupancies), (Light Hazard occupancies, Computer Rooms, Subfloors, Special Hazard Machinery& spaces), (Light Hazard Occupancies, Combustion Turbines, Machinery Spaces),(Light Hazard, Ord Haz Grp I,II parking garages & III selected occupancies, Cable Tunnels), (Light Hazard,Ord Haz Grp I, Combustion Turbines) and other agencies. These listings and installations have demonstratedequivalent fire protection to the authority having jurisdiction (AHJ). The addition of the proposed text will provide theAHJ a clear option to accept water mist systems as an equivalent system to an approved automatic sprinkler systemthereby allowing construction alternatives without having to prove equivalency or be considered an alternativeextinguishing system.

_______________________________________________________________________________________________5000- Log #256 BLD-BLC

_______________________________________________________________________________________________Dennis L. Pitts, American Wood Council

Revise to read:Type IV (2HH) construction shall be that type in which fire walls, exterior walls, and

interior bearing walls and structural elements that are portions of such walls are of approved noncombustible orlimited-combustible materials except as allowed for exterior walls in 7.2.5.6.7. Other interior structural elements, arches,floors, and roofs shall be of solid or laminated wood or cross-laminated timber without concealed spaces and shallcomply with the allowable dimensions of 7.2.5.5.

Cross-laminated timber (CLT) is a new technology developed in Europe. It is generally analogous tolarge section members currently associated with heavy timber in the current code. Its fire performance is most like thatof glued-laminated beams, or glu-lams, in traditional Type IV (2HH) (heavy timber) construction. Therefore it isproposed that the CLT be included in Type IV (2HH). To properly accomplish this, several proposals are beingsubmitted to add a definition of CLT, add a consensus-developed product standard and then modify the text of Type IV(2HH) to accommodate CLT.More information on the cross-laminated timber product can be found at our website, www.AWC.org.

2Printed on 5/16/2012

Page 24 of 53

Page 25: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

Report on Proposals – June 2014 NFPA 5000_______________________________________________________________________________________________5000- Log #257 BLD-BLC

_______________________________________________________________________________________________Dennis L. Pitts, American Wood Council

Revise to read:All dimensions in 7.2.5.5 for solid sawn members shall be considered nominal. The net finished dimensions of

glued-laminated members shall be equivalent to the nominal dimensions of solid sawn timbers. Cross-laminated timberdimensions shall be actual dimensions.

Cross-laminated timber (CLT) is a new technology developed in Europe. It is generally analogous tolarge section members currently associated with heavy timber in the current code. Its fire performance is most like thatof glued-laminated beams, or glu-lams, in traditional Type IV (heavy timber) construction. Therefore it is proposed thatthe CLT be included in Type IV (2HH). To properly accomplish this, this proposal adds a definition of CLT, adds aconsensus-developed product standard and then modifies the text of Type IV (2HH) to accommodate CLT.This proposal is intended to clarify dimensions for solid sawn and glued-laminated timbers. CLT timbers are added.

_______________________________________________________________________________________________5000- Log #258 BLD-BLC

_______________________________________________________________________________________________Dennis L. Pitts, American Wood Council

Revise to read:Floors shall be constructed of spline without concealed spaces and shall be permitted to be of the

following materials.(1) Spline or tongue-and-groove plank not less than 3 in. (75 mm) in thickness that is covered with 1 in. (25 mm)tongue-and-groove flooring, laid crosswise or diagonally to the plank, or with 1⁄2 in. (13 mm) wood structural panel; orthey shall be constructed of laminated planks not less than 4 in. (100 mm) in width, set close together on edge, spiked atintervals of 18 in. (455 mm), and covered with 1 in. (25 mm) tongue-and-groove flooring, laid crosswise or diagonally tothe plank, or with 1⁄2 in. (13 mm) wood structural panel.(2) Cross-laminated timber complying with 45.5.7 shall be not less than 4 inches (102 cm) thick and shall be continuousbetween supports. Individual timbers shall be fastened to one another. Cross-laminated timbers shall be permitted tobe connected to walls without shrinkage gaps provided dimensional changes are considered in design.

Cross-laminated timber (CLT) is a new technology developed in Europe. It is generally analogous tolarge section members currently associated with heavy timber in the current code. Its fire performance is most like thatof glued-laminated beams, or glu-lams, in traditional Type IV (heavy timber) construction. Therefore it is proposed thatthe CLT be included in Type IV (2HH). To properly accomplish this, this proposal adds a definition of CLT, adds aconsensus-developed product standard and then modifies the text of Type IV (2HH) to accommodate CLT.CLT floors are slightly different than HT so it is put into a separate subparagraph with its own requirements. Among

the differences is thickness (CLT=4 inches; HT=3 inches topped with a sheathing).

3Printed on 5/16/2012

Page 25 of 53

Page 26: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

Report on Proposals – June 2014 NFPA 5000_______________________________________________________________________________________________5000- Log #259 BLD-BLC

_______________________________________________________________________________________________Dennis L. Pitts, American Wood Council

Revise to read:Roof decks shall be constructed of spline or tongue-and-groove plank not less than 2 in. (51

mm) in thickness; or of laminated planks not less than 3 in. (75 mm) in width, set close together on edge, and laid asrequired for floors; or of 1 1⁄8 in. (29 mm) thick interior wood structural panel (exterior glue); of cross-laminated timber;or of approved noncombustible or limited-combustible materials of equivalent fire durability.

Cross-laminated timber (CLT) is a new technology developed in Europe. It is generally analogous tolarge section members currently associated with heavy timber in the current code. Its fire performance is most like thatof glued-laminated beams, or glu-lams, in traditional Type IV (heavy timber) construction. Therefore it is proposed thatthe CLT be included in Type IV (2HH). To properly accomplish this, this proposal adds a definition of CLT, adds aconsensus-developed product standard and then modifies the text of Type IV (2HH) to accommodate CLT.In this proposal CLT is added to the section dealing with roof decks.

_______________________________________________________________________________________________5000- Log #260 BLD-BLC

_______________________________________________________________________________________________Dennis L. Pitts, American Wood Council

Revise to read:Structural elements shall be of heavy timber members (sawn or glued-laminated),

cross-laminated timber, or of fire resistance–rated construction as set forth in Table 7.2.1.1 when materials other thanheavy timber or cross-laminated timber are used.

Cross-laminated timber (CLT) is a new technology developed in Europe. It is generally analogous tolarge section members currently associated with heavy timber in the current code. Its fire performance is most like thatof glued-laminated beams, or glu-lams, in traditional Type IV (heavy timber) construction. Therefore it is proposed thatthe CLT be included in Type IV (2HH). To properly accomplish this, this proposal adds a definition of CLT, adds aconsensus-developed product standard and then modifies the text of Type IV (2HH) to accommodate CLT.This proposal adds CLT to the provisions addressing structural elements.

4Printed on 5/16/2012

Page 26 of 53

Page 27: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

Report on Proposals – June 2014 NFPA 5000_______________________________________________________________________________________________5000- Log #254 BLD-BLC

_______________________________________________________________________________________________Dennis L. Pitts, American Wood Council

Revise to read:Exterior walls having a required fire resistance rating of 2 hours or less are permitted to be

constructed with the following materials.(1) Noncombutible material, or(2) Fire retardant treated wood. Approved fire-retardant-treated wood framing shall be permitted within the assembly ofexterior walls having a required fire resistance rating of 2 hours or less and a horizontal separation of not less than 60 in.(1525 mm), provided that the fire resistance rating is maintained and the exposed outer and inner faces of such wallsare constructed of limited-combustible or noncombustible materials.(3) Cross-laminated timber complying with 45.5.7 shall be permitted provided the exterior surface of the cross-laminatedtimber is protected by(a) Fire retardant treated wood not less than 15/32 inch thick, or(b) Gypsum board not less than 1/2 inch thick, or(c) Noncombustible material.

Cross-laminated timber (CLT) is a new technology developed in Europe. It is generally analogous tolarge section members currently associated with heavy timber in the current code. Its fire performance is most like thatof glued-laminated beams, or glu-lams, in traditional Type IV (2HH) (heavy timber) construction. Therefore it isproposed that the CLT be included in Type IV (2HH). To properly accomplish this, several proposals are beingsubmitted to add a definition of CLT, add a consensus-developed product standard and then modify the text of Type IV(2HH) to accommodate CLT.In this proposal, 7.2.5.6.7 is reorganized to retain the existing language, to make it easier to read, and to incorporate

CLT.

_______________________________________________________________________________________________5000- Log #177 BLD-BLC

_______________________________________________________________________________________________Scott J. Harrison, Marioff Inc.

Revise text to read as follows:(1) Where the building is protected throughout with an approved, electrically supervised automatic sprinkler system inaccordance with NFPA 13, NFPA 13D, and NFPA 13R or approved, electrically supervised automatic water mist systemin accordance with NFPA 750.

Water Mist systems have been approved and installed in many sprinkler applications globally for over15 yrs. They have been listed by national and internationally recognized testing laboratories such as: (OrdinaryHazard Group 1 occupancies), (Light Hazard occupancies, Computer Rooms, Subfloors, Special Hazard Machinery& spaces), (Light Hazard Occupancies, Combustion Turbines, Machinery Spaces),(Light Hazard, Ord Haz Grp I,II parking garages & III selected occupancies, Cable Tunnels), (Light Hazard,Ord Haz Grp I, Combustion Turbines) and other agencies. These listings and installations have demonstratedequivalent fire protection to the authority having jurisdiction (AHJ). The addition of the proposed text will provide theAHJ a clear option to accept water mist systems as an equivalent system to an approved automatic sprinkler systemthereby allowing construction alternatives without having to prove equivalency or be considered an alternativeextinguishing system.

5Printed on 5/16/2012

Page 27 of 53

Page 28: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

Report on Proposals – June 2014 NFPA 5000_______________________________________________________________________________________________5000- Log #178 BLD-BLC

_______________________________________________________________________________________________Scott J. Harrison, Marioff Inc.

Revise text to read as follows:  The height of one-story aircraft hangars shall not be limited where the building is

surrounded by public space, streets, or permanent open yards not less in width than 1 1/2 times the height of the buildingand where the building is protected with an approved, electrically supervised sprinkler system in accordance with NFPA13 or approved, electrically supervised water mist system in accordance with NFPA 750.

Water Mist systems have been approved and installed in many sprinkler applications globally includingaircraft hangars. They have been listed by national and internationally recognized testing laboratories such as:(Ordinary Hazard Group 1), (Light Hazard occupancies, Computer Rooms, Subfloors, Special Hazard Machinery &spaces), (Light Hazard Occupancies, Combustion Turbines, Machinery Spaces), (LightHazard, Ord Haz Grp I,II parking garages & III selected occupancies, Cable Tunnels), (Light Hazard, OrdHaz Grp I, Combustion Turbines) and other agencies. These listings and installations have demonstrated equivalent fireprotection to the authority having jurisdiction (AHJ). The addition of the proposed text will provide the AHJ a clear optionto accept water mist systems as an equivalent system to an approved automatic sprinkler system thereby allowingconstruction alternatives without having to prove equivalency or be considered an alternative extinguishing system.Water mist systems are designed and installed in accordance with NFPA 750

, a performance based standard enabling the application of water mist systems in most hazards through acombination of fire design calculations, modeling and fire testing. This has resulted in numerous military and civilianaircraft hangars and related occupancies being fully protected with water mist systems.

_______________________________________________________________________________________________5000- Log #179 BLD-BLC

_______________________________________________________________________________________________Scott J. Harrison, Marioff Inc.

Revise text to read as follows:(b) Business, mercantile, and assembly occupancies having an assembly room with an occupant load of less than 300shall be permitted in addition to those uses incidental to the operation of the building (including storage areas), providedthat the entire structure below the horizontal assembly is protected throughout by an approved, electrically supervisedautomatic sprinkler system installed in accordance with NFPA 13. or approved electrically supervised water mist systeminstalled in accordance with NFPA 750.

Water Mist systems have been approved and installed in many sprinkler applications globally for over15 years. They have been listed by national and internationally recognized testing laboratories such as: (OrdinaryHazard Group 1), (Light Hazard occupancies, Computer Rooms, Subfloors, Special Hazard Machinery & spaces),

(Light Hazard Occupancies, Combustion Turbines, Machinery Spaces), (Light Hazard,Ord Haz Grp I,II parking garages & III selected occupancies, Cable Tunnels), (Light Hazard, Ord Haz Grp I,Combustion Turbines) and other agencies. These listings and installations have demonstrated equivalent fire protectionto the authority having jurisdiction (AHJ). The addition of the proposed text will provide the AHJ a clear option to acceptwater mist systems as an equivalent system to an approved automatic sprinkler system thereby allowing constructionalternatives without having to prove equivalency or be considered an alternative extinguishing system.

6Printed on 5/16/2012

Page 28 of 53

Page 29: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

Report on Proposals – June 2014 NFPA 5000_______________________________________________________________________________________________5000- Log #181 BLD-BLC

_______________________________________________________________________________________________Scott J. Harrison, Marioff Inc.

Revise text to read as follows:   The allowable area per story specified in Table 7.4.1 shall be permitted to be increased to

account for frontage ( ) and automatic sprinkler system or automatic water mist system protection ( ) in accordancewith the following equation:

****Insert Existing Equation Here****

Where:= allowable area per story (ft2 or m2)= allowable area per story (ft2 or m2) in accordance with Table 7.4.1

= percentage area increase for frontage, as determined in accordance with 7.6.2.1= percentage area increase for automatic sprinkler system or automatic water mist system protection, as determined

in accordance with 7.6.2.2 and 7.6.2.2.1.Water Mist systems have been approved and installed in many sprinkler applications globally for over

15 years. They have been listed by national and internationally recognized testing laboratories such as: (OrdinaryHazard Group 1), (Light Hazard occupancies, Computer Rooms, Subfloors, Special Hazard Machinery & spaces),

(Light Hazard Occupancies, Combustion Turbines, Machinery Spaces), (Light Hazard,Ord Haz Grp I, II parking garages & III selected occupancies, Cable Tunnels), (Light Hazard, Ord Haz Grp I,Combustion Turbines) and other agencies. These listings and installations have demonstrated equivalent fire protectionto the authority having jurisdiction (AHJ). The addition of the proposed text will provide the AHJ a clear option to acceptwater mist systems as an equivalent system to an approved automatic sprinkler system thereby allowing constructionalternatives without having to prove equivalency or be considered an alternative extinguishing system.

7Printed on 5/16/2012

Page 29 of 53

Page 30: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

1 100 100

Page 30 of 53

Page 31: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

Report on Proposals – June 2014 NFPA 5000_______________________________________________________________________________________________5000- Log #180 BLD-BLC

_______________________________________________________________________________________________Scott J. Harrison, Marioff Inc.

   Buildings other than thosecontaining high hazard contents requiring Protection Level 1 or Protection Level 2, as specified in Chapter 34, andprotected with an approved, electrically supervised automatic water mist system in accordance with NFPA 750 shall bepermitted to have the following automatic water mist system protection increase ( ) applied to the allowable area perstory:● (1)200 percent ( = 200) for buildings where the number of stories is two or more● (2)300 percent ( = 300) for one-story buildings

Water Mist systems have been approved and installed in many sprinkler applications globally for over15 years. They have been listed by national and internationally recognized testing laboratories such as: (OrdinaryHazard Group 1), (Light Hazard occupancies, Computer Rooms, Subfloors, Special Hazard Machinery & spaces),

(Light Hazard Occupancies, Combustion Turbines, Machinery Spaces), (Light Hazard,Ord Haz Grp I, II parking garages & III selected occupancies, Cable Tunnels), (Light Hazard, Ord Haz Grp I,Combustion Turbines) and other agencies. These listings and installations have demonstrated equivalent fire protectionto the authority having jurisdiction (AHJ). The addition of the proposed text will provide the AHJ a clear option to acceptwater mist systems as an equivalent system to an approved automatic sprinkler system thereby allowing constructionalternatives without having to prove equivalency or be considered an alternative extinguishing system.

_______________________________________________________________________________________________5000- Log #182 BLD-BLC

_______________________________________________________________________________________________Scott J. Harrison, Marioff Inc.

Revise text to read as follows:   A one-story building used for business, industrial occupancies with ordinary hazard contents, or mercantile

occupancies, and assembly uses intended for viewing of indoor sporting events with spectator seating, shall not belimited in area where the building is provided with an approved, electrically supervised automatic sprinkler system inaccordance with NFPA 13 or an approved, electrically supervised automatic water mist system in accordance withNFPA 750 and is surrounded and adjoined by public ways or yards not less than 60 ft (18 m) in width.

Water Mist systems have been approved and installed in many sprinkler applications globally for over15 years. They have been listed by national and internationally recognized testing laboratories such as: (OrdinaryHazard Group 1), (Light Hazard occupancies, Computer Rooms, Subfloors, Special Hazard Machinery & spaces),

(Light Hazard Occupancies, Combustion Turbines, Machinery Spaces), (Light Hazard,Ord Haz Grp I,II parking garages & III selected occupancies, Cable Tunnels), (Light Hazard, Ord Haz Grp I,Combustion Turbines) and other agencies. These listings and installations have demonstrated equivalent fire protectionto the authority having jurisdiction (AHJ). The addition of the proposed text will provide the AHJ a clear option to acceptwater mist systems as an equivalent system to an approved automatic sprinkler system thereby allowing constructionalternatives without having to prove equivalency or be considered an alternative extinguishing system.

8Printed on 5/16/2012

Page 31 of 53

Page 32: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

Report on Proposals – June 2014 NFPA 5000_______________________________________________________________________________________________5000- Log #183 BLD-BLC

_______________________________________________________________________________________________Scott J. Harrison, Marioff Inc.

Revise text to read as follows:(1) The entire building is protected throughout with an approved, electrically supervised automatic sprinkler systeminstalled in accordance with NFPA 13 or an approved, electrically supervised automatic water mist system inaccordance with NFPA 750.

Water Mist systems have been approved and installed in many sprinkler applications globally for over15 years. They have been listed by national and internationally recognized testing laboratories such as: (OrdinaryHazard Group 1), (Light Hazard occupancies, Computer Rooms, Subfloors, Special Hazard Machinery & spaces),

(Light Hazard Occupancies, Combustion Turbines, Machinery Spaces), (Light Hazard,Ord Haz Grp I,II parking garages & III selected occupancies, Cable Tunnels), (Light Hazard, Ord Haz Grp I,Combustion Turbines) and other agencies. These listings and installations have demonstrated equivalent fire protectionto the authority having jurisdiction (AHJ). The addition of the proposed text will provide the AHJ a clear option to acceptwater mist systems as an equivalent system to an approved automatic sprinkler system thereby allowing constructionalternatives without having to prove equivalency or be considered an alternative extinguishing system.

_______________________________________________________________________________________________5000- Log #208 BLD-BLC

_______________________________________________________________________________________________Scott J. Harrison, Marioff Inc.

Revise text to read as follows:   A two-story building used for business, industrial, or mercantile occupancies

shall not be limited in area where the building is provided with an approved, electrically supervised automatic sprinklersystem installed in accordance with NFPA 13 or an approved, electrically supervised water mist system in accordancewith NFPA 750 and is surrounded and adjoined by public ways or yards not less than 60 ft (18 m) in width.

Water Mist systems have been approved and installed in many sprinkler applications globally for over15 years. They have been listed by national and internationally recognized testing laboratories such as: (OrdinaryHazard Group 1), (Light Hazard occupancies, Computer Rooms, Subfloors, Special Hazard Machinery & spaces),

(Light Hazard Occupancies, Combustion Turbines, Machinery Spaces), (Light Hazard,Ord Haz Grp I,II parking garages & III selected occupancies, Cable Tunnels), (Light Hazard, Ord Haz Grp I,Combustion Turbines) and other agencies. These listings and installations have demonstrated equivalent fireprotection to the authority having jurisdiction (AHJ). The addition of the proposed text will provide the AHJ a clear optionto accept water mist systems as an equivalent system to an approved automatic sprinkler system thereby allowingconstruction alternatives without having to prove equivalency or be considered an alternative extinguishing system.

9Printed on 5/16/2012

Page 32 of 53

Page 33: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

Report on Proposals – June 2014 NFPA 5000_______________________________________________________________________________________________5000- Log #184 BLD-BLC

_______________________________________________________________________________________________Scott J. Harrison, Marioff Inc.

Revise text to read as follows:(2) The building shall be equipped throughout with an approved, electrically supervised automatic sprinkler system inaccordance with NFPA 13. or an approved, electrically supervised water mist system in accordance with NFPA 750.

Water Mist systems have been approved and installed in many sprinkler applications globally for over15 years. They have been listed by national and internationally recognized testing laboratories such as: (OrdinaryHazard Group 1), (Light Hazard occupancies, Computer Rooms, Subfloors, Special Hazard Machinery & spaces),

(Light Hazard Occupancies, Combustion Turbines, Machinery Spaces), (Light Hazard,Ord Haz Grp I,II parking garages & III selected occupancies, Cable Tunnels), (Light Hazard, Ord Haz Grp I,Combustion Turbines) and other agencies. These listings and installations have demonstrated equivalent fire protectionto the authority having jurisdiction (AHJ). The addition of the proposed text will provide the AHJ a clear option to acceptwater mist systems as an equivalent system to an approved automatic sprinkler system thereby allowing constructionalternatives without having to prove equivalency or be considered an alternative extinguishing system.

_______________________________________________________________________________________________5000- Log #185 BLD-BLC

_______________________________________________________________________________________________Scott J. Harrison, Marioff Inc.

Revise text to read as follows:   One-story motion picture theaters in buildings of Type II or

Type III (211) construction shall not be limited in area where the buildings is provided with an approved, electricallysupervised automatic sprinkler system throughout in accordance with NFPA 13 or an approved, electrically supervisedwater mist system in accordance with NFPA 750 and is surrounded and adjoined by public ways or yards not less than60 ft (18 m) in width.

Water Mist systems have been approved and installed in many sprinkler applications globally for over15 years. They have been listed by national and internationally recognized testing laboratories such as: (OrdinaryHazard Group 1), (Light Hazard occupancies, Computer Rooms, Subfloors, Special Hazard Machinery & spaces),

(Light Hazard Occupancies, Combustion Turbines, Machinery Spaces), (Light Hazard,Ord Haz Grp I,II parking garages & III selected occupancies, Cable Tunnels), (Light Hazard, Ord Haz Grp I,Combustion Turbines) and other agencies. These listings and installations have demonstrated equivalent fire protectionto the authority having jurisdiction (AHJ). The addition of the proposed text will provide the AHJ a clear option to acceptwater mist systems as an equivalent system to an approved automatic sprinkler system thereby allowing constructionalternatives without having to prove equivalency or be considered an alternative extinguishing system.

10Printed on 5/16/2012

Page 33 of 53

Page 34: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

Report on Proposals – June 2014 NFPA 5000_______________________________________________________________________________________________5000- Log #186 BLD-BLC

_______________________________________________________________________________________________Scott J. Harrison, Marioff Inc.

Revise text to read as follows:(2) The building shall be equipped with an approved, electrically supervised automatic sprinkler system in accordancewith NFPA 13 or an approved, electrically supervised water mist system in accordance with NFPA 750.

Water Mist systems have been approved and installed in many sprinkler applications globally for over15 years. They have been listed by national and internationally recognized testing laboratories such as: (OrdinaryHazard Group 1), (Light Hazard occupancies, Computer Rooms, Subfloors, Special Hazard Machinery & spaces),

(Light Hazard Occupancies, Combustion Turbines, Machinery Spaces), (Light Hazard,Ord Haz Grp I, II parking garages & III selected occupancies, Cable Tunnels), (Light Hazard, Ord Haz Grp I,Combustion Turbines) and other agencies. These listings and installations have demonstrated equivalent fire protectionto the authority having jurisdiction (AHJ). The addition of the proposed text will provide the AHJ a clear option to acceptwater mist systems as an equivalent system to an approved automatic sprinkler system thereby allowing constructionalternatives without having to prove equivalency or be considered an alternative extinguishing system.

_______________________________________________________________________________________________5000- Log #94 BLD-BLC

_______________________________________________________________________________________________Marcelo M. Hirschler, GBH International

Add text to read as follows:A.7.1.4.3 A material complying with ASTM E2786 needs to be tested in accordance with ASTM E84,

, or ANSI/UL 723,, and exhibit a flame spread index of 25 or less, show no evidence of

significant progressive combustion when the test is continued for an additional 20-minute period (with a total testduration of 30 minutes) and have a flame front that does not progress more than 10.5 ft (3.2 m) beyond the centerline ofthe burners at any time during the test.

ASTM has now issued a test method, ASTM E2768, which contains the three requirements discussedin this section, namely that a product be tested in accordance with ASTM E84 or UL 723, and exhibit a flame spreadindex of 25 or less, show no evidence of significant progressive combustion when the test is continued for 30 minutes(i.e. an additional 20-minute period over the standard ASTM E84 duration of 10 minutes) and that the flame front notprogress more than 101/2 feet (3200 mm) beyond the centerline of the burners at any time during the test. This changereplaces the lengthy information about requirements with a reference to the standard.The NFPA Manual of Style does not allow requirements in definitions. Therefore this change places the requirementsinto a new section in Chapter 7, immediately following the requirements for noncombustible material and limitedcombustible material.

11Printed on 5/16/2012

Page 34 of 53

Page 35: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

Report on Proposals – June 2014 NFPA 220_______________________________________________________________________________________________220- Log #5 BLD-BLC

_______________________________________________________________________________________________Marcelo M. Hirschler, GBH International

Revise text to read as follows:ASTM International, P.O. Box C700, 100 Barr Harbor Drive, West Conshohocken, PA

19428-2959.ASTM E84, , 2012 2004.ASTM E 119, , 2012 2009.ASTM E 136, 2011 2009.ASTM E 2652,

2009a.Standards update.

_______________________________________________________________________________________________220- Log #2 BLD-BLC

_______________________________________________________________________________________________John F. Bender, UL LLC

Revise text as follows:Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096.

ANSI/UL 263, 2003, Revised 2007 2011.ANSI/UL 723, 2008, Revised 2010.

Update referenced standards to most recent edition as indicated.

_______________________________________________________________________________________________220- Log #4 BLD-BLC

_______________________________________________________________________________________________Marcelo M. Hirschler, GBH International

Revise definition to read as follows:The time, in minutes or hours, that materials or assemblies have withstood a fire

exposure as established in accordance with the test procedures of NFPA 251. The time, in minutes or hours, thatmaterials or assemblies have withstood a fire exposure as determined by the tests, or methods based on tests,prescribed by this standard. [ 2012].

NFPA 251 has been withdrawn. This definition should be extracted from NFPA 5000.

1Printed on 5/16/2012

Page 35 of 53

Page 36: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

Report on Proposals – June 2014 NFPA 220_______________________________________________________________________________________________220- Log #1 BLD-BLC

_______________________________________________________________________________________________

Joseph H. Versteeg, Versteeg Associates

(See 4.1.6) Refers to a building construction material not complying with thedefinition of noncombustible that, in the form in which it is used, has a potential heat value not exceeding 8141 kJ/kg(3500 Btu/lb), where tested in accordance with NFPA259 and includes either (1) materials having a structural base ofnoncombustible material, with a surfacing not exceeding a thickness of 3.2 mm (1/8 in.) that has a flame spread indexnot greater than 50, or (2) materials, in the form and thickness used having neither a flame spread index greater than 25nor evidence of continued progressive combustion, and of such composition that surfaces that would be exposed bycutting through the material on any plane would have neither a flame spread index greater than 25 nor evidence ofcontinued progressive combustion, when tested in accordance with ANSI/ UL 723 or ASTM E 84.

(See 4.1.5) A material that, in the form in which it is used and under the conditionsanticipated, will not ignite, burn, support combustion, or release flammable vapors when subjected to fire or heat.Materials that are reported as passing ASTM E 136 are considered noncombustible materials.

A material that is reported as passing ASTM E 136,, shall be considered a noncombustible material.

A material that is reported as complying with the pass/fail criteria of ASTM E 136 when tested in accordancewith the test method and procedure in ASTM E 2652,

, shall be considered a noncombustible material.Where the term limited-combustible is used in this Code, it shall also include noncombustible.

A material that complies with any of the following shall be considered a noncombustible material:(1)* A material that, in the form in which it is used and under the conditions anticipated, will not ignite, burn, support

combustion, or release flammable vapors, when subjected to fire or heat(2) A material that is reported as passing ASTM E 136,

(3) A material that is reported as complying with the pass/fail criteria of ASTM E 136 when tested in accordance withthe test method and procedure in ASTM E 2652,

. [ 7.1.4.1.1]Where the term limited-combustible is used in this Code, it shall also include the term noncombustible.

[ 7.1.4.1.2]The provisions of 4.1.5.1 do not require inherently noncombustible materials to be tested in order to be

classified as noncombustible materials. [ A.7.1.4.1]Examples of such materials include steel, concrete, masonry and glass. [ A.7.1.4.1.1(1)]

A material shall be considered a limited combustible material where all theconditions of 4.1.6.1 and 4.1.6.2, and the conditions of either 4.1.6.3 or 4.1.6.4 are met. [ 7.1.4.2]

The material does not comply with the requirements for a noncombustible material, in accordance with 4.1.5.[ 7.1.4.2.1]

The material, in the form in which it is used, exhibits a potential heat value not exceeding 3500 Btu/lb (8141kJ/kg), when tested in accordance with NFPA 259, .[ 7.1.4.2.2]

The material has a structural base of a noncombustible material with a surfacing not exceeding a thickness of1/8 in. (3.2 mm) where the surfacing exhibits a flame spread index not greater than 50 when tested in accordance withASTM E 84, or ANSI/UL 723,

2Printed on 5/16/2012

Page 36 of 53

Page 37: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

Report on Proposals – June 2014 NFPA 220. [ 7.1.4.2.3]

The material is composed of materials which, in the form and thickness used, neither exhibit a flame spreadindex greater than 25 nor evidence of continued progressive combustion when tested in accordance with ASTM E 84 orANSI/UL 723, and are of such composition that all surfaces that would be exposed by cutting through the material onany plane would neither exhibit a flame spread index greater than 25 nor exhibit evidence of continued progressivecombustion when tested in accordance with ASTM E 84 or ANSI/UL 723. [ 7.1.4.2.4]

Where the term limited-combustible is used in this Code, it shall also include the term noncombustible.[ 7.1.4.2.5]

NFPA 220 is an extract document of NFPA 5000, . Duringthe ROC stage, NFPA 5000 revised and relocated the language for Noncombustible Materials and Limited-CombustibleMaterials. The TCC further revised the language. NFPA 220 was not updated to contain the new sections. This TIA iscontingent on the final actions taken on NFPA 5000-35 and 5000-38 during the Technical Association Meeting.

The new language in NFPA 5000 creates a conflict with the existing language in NFPA 220.NFPA 101, The Life Safety Code references both NFPA 220 and NFPA 5000. Coordinating the documents to containthe same language puts NFPA 220 back in sync with NFPA 5000 and NFPA 101.

_______________________________________________________________________________________________220- Log #6 BLD-BLC

_______________________________________________________________________________________________Marcelo M. Hirschler, GBH International

Revise text to read as follows:ASTM International, P.O. Box C700, 100 Barr Harbor Drive, West Conshohocken, PA

19428-2959.ASTM E84, , 2012 2004.ASTM E 119, , 2012 2009.

Standards update.

_______________________________________________________________________________________________220- Log #3 BLD-BLC

_______________________________________________________________________________________________John F. Bender, UL LLC

Revise text as follows:Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096.

ANSI/UL 263, , 2003, Revised 2007 2011.ANSI/UL 723, , 2008, Revised 2010.

Update referenced standard to most recent edition as indicated.

3Printed on 5/16/2012

Page 37 of 53

Page 38: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

Report on Proposals – June 2014 NFPA 221_______________________________________________________________________________________________221- Log #12 BLD-BLC

_______________________________________________________________________________________________Marcelo M. Hirschler, GBH International

Revise text to read as follows:ASTM International, P.O. Box C700, 100 Barr Harbor Drive, West Conshohocken, PA

19428-2959.ASTM E 119, , 2012 2009.ASTM E 814, , 2011a 2002.ASTM E 1966, , 1997 (2011) 2001.

Standards update.

_______________________________________________________________________________________________221- Log #1 BLD-BLC

_______________________________________________________________________________________________John F. Bender, UL LLC

Revise text as follows:Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096.

ANSI/UL 10C, , 2009.ANSI/UL 263, , 2003, Revised 2007 2011.ANSI/UL 555, , 2006, Revised 2010 2011.ANSI/UL 1479, , 2003, Revised 2010.ANSI/UL 2079, , 2004, Revised 2008.

Update referenced standards to the most recent edition as indicated.

_______________________________________________________________________________________________221- Log #4 BLD-BLC

_______________________________________________________________________________________________Marcelo M. Hirschler, GBH International

Revise text to read as follows:* A reference plane representing the average of the finished ground level adjoining the building at all

exterior walls. When the finished ground level slopes down from the exterior walls, the grade plane is established by thelowest points within the area between the building and the lot line or, when the lot line is more than 6 ft (1.8 m) from thebuilding, between the building and a point 6 ft (1.8 m) from the building.

The NFPA Manual of Style does not allow requirements in definitions. Therefore this change places therequirements into a new section in Chapter 4, at the end of the chapter in a new section.

_______________________________________________________________________________________________221- Log #7 BLD-BLC

_______________________________________________________________________________________________Marcelo M. Hirschler, GBH International

Revise text to read as follows:An exterior wall that intersects with a high challenge fire wall at an exterior angle of more than 135

degrees at the end of the high challenge fire wall.The NFPA Manual of Style does not allow requirements in definitions. Therefore this change places the

comments about the figures in the annex.

1Printed on 5/16/2012

Page 38 of 53

Page 39: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

Report on Proposals – June 2014 NFPA 221_______________________________________________________________________________________________221- Log #9 BLD-BLC

_______________________________________________________________________________________________Marcelo M. Hirschler, GBH International

Revise text to read as follows:

The fire resistance rating of assemblies shall be determined in accordance with NFPA 251,ASTM E 119,

or ANSI/UL 263, orother approved test methods or analytical methods in accordance with 4.3.3 4.3.2.

The NFPA Manual of Style does not allow requirements in definitions. The definition of fire protectionrating in this standard (as shown below) is an extract from NFPA 5000 and the public input will be directed to that code.However, if that reference gets eliminated the information would be lost to the user of NFPA 221 unless a change suchas the one proposed is made.NFPA 251 has been withdrawn.

_______________________________________________________________________________________________221- Log #10 BLD-BLC

_______________________________________________________________________________________________Marcelo M. Hirschler, GBH International

Add text to read as follows:4.3.2 The fire protection rating of a fire door assembly or of a fire window assembly shall be determined in accordancewith NFPA 252 or NFPA 257, respectively.Renumber 4.3.2 as 4.3.3, and make any other needed renumbering.

The NFPA Manual of Style does not allow requirements in definitions. The definition of fire protectionrating in this standard (as shown below) is an extract from NFPA 5000 and the public input will be directed to that code.However, if that reference gets eliminated the information would be lost to the user of NFPA 221 unless a change suchas the one proposed is made.NFPA 251 has been withdrawn.

_______________________________________________________________________________________________221- Log #6 BLD-BLC

_______________________________________________________________________________________________Marcelo M. Hirschler, GBH International

Add text to read as follows:When the finished ground level slopes down from the exterior walls, the grade plane shall be

established by the lowest points within the area between the building and the lot line or, when the lot line is more than 6ft (1.8 m) from the building, between the building and a point 6 ft (1.8 m) from the building.

The NFPA Manual of Style does not allow requirements in definitions. Therefore this change places therequirements into a new section in Chapter 4, at the end of the chapter in a new section.

2Printed on 5/16/2012

Page 39 of 53

Page 40: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

Report on Proposals – June 2014 NFPA 221_______________________________________________________________________________________________221- Log #15 BLD-BLC

_______________________________________________________________________________________________Scott J. Harrison, Marioff Inc.

Revise text to read as follows:(b) Business, mercantile occupancies, and assembly occupancies having an assembly room with an occupant load of

less than 300 shall be permitted in addition to those uses incidental to the operation of the building (including storageareas), provided that the entire structure below the horizontal assembly is protected throughout by an approved,electrically supervised automatic sprinkler system installed in accordance with NFPA 13,

or NFPA 750, .Water Mist systems have been approved and installed in many sprinkler applications globally for over

15 years. They have been listed by national and internationally recognized testing laboratories such as: UL (OrdinaryHazard Group 1 Occupancies), FM (Light Hazard occupancies, Computer Rooms, Subfloors, Special Hazard Machinery& spaces), City of New York (Light Hazard Occupancies, Combustion Turbines, Machinery Spaces), VdS Germany(Light Hazard, Ord Haz Grp I,II parking garages & III selected occupancies, Cable Tunnels), KfV Austria (Light Hazard,Ord Haz Grp I, Combustion Turbines) and other agencies. These installations have demonstrated equivalent fireprotection to the authority having jurisdiction (AHJ). The addition of the proposed text will provide the AHJ a clear optionto accept water mist systems as an equivalent system to an approved automatic sprinkler system thereby allowingconstruction alternatives without having to prove equivalency or be considered an alternative extinguishing system.

_______________________________________________________________________________________________221- Log #16 BLD-BLC

_______________________________________________________________________________________________Scott J. Harrison, Marioff Inc.

Revise text to read as follows:Single opening protectives in fire walls shall not be limited in size where the buildings on both sides of the fire

wall are protected throughout by automatic sprinkler systems in accordance with NFPA 13,, or NFPA 13R,

or NFPA 750 Standard on Water Mist Fire Protection Systems.Water Mist systems have been approved and installed in many sprinkler applications globally for over

15 years. They have been listed by national and internationally recognized testing laboratories such as: UL (OrdinaryHazard Group 1 Occupancies), FM (Light Hazard occupancies, Computer Rooms, Subfloors, Special Hazard Machinery& spaces), City of New York (Light Hazard Occupancies, Combustion Turbines, Machinery Spaces), VdS Germany(Light Hazard, Ord Haz Grp I,II parking garages & III selected occupancies, Cable Tunnels), KfV Austria (Light Hazard,Ord Haz Grp I, Combustion Turbines) and other agencies. These installations have demonstrated equivalent fireprotection to the authority having jurisdiction (AHJ). The addition of the proposed text will provide the AHJ a clear optionto accept water mist systems as an equivalent system to an approved automatic sprinkler system thereby allowingconstruction alternatives without having to prove equivalency or be considered an alternative extinguishing system.

_______________________________________________________________________________________________221- Log #11 BLD-BLC

_______________________________________________________________________________________________Marcelo M. Hirschler, GBH International

Revise text to read as follows:The fire test exposure should be established in accordance with the test procedures of

NFPA 251, . ASTM E 119,or of and ANSI/UL 263,

are similar to NFPA 251.NFPA 251 has been withdrawn.

3Printed on 5/16/2012

Page 40 of 53

Page 41: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

Report on Proposals – June 2014 NFPA 221_______________________________________________________________________________________________221- Log #5 BLD-BLC

_______________________________________________________________________________________________Marcelo M. Hirschler, GBH International

Add text to read as follows:A.3.3.9 See section 4.10 for establishment of the grade plane.

The NFPA Manual of Style does not allow requirements in definitions. Therefore this change places therequirements into a new section in Chapter 4, at the end of the chapter in a new section.

_______________________________________________________________________________________________221- Log #8 BLD-BLC

_______________________________________________________________________________________________Marcelo M. Hirschler, GBH International

Add text to read as follows:A.3.3.14.4 See Figure 5.16.2.1(a), Figure 5.16.2.1(b), and Figure 5.16.2.3 for details of end walls.

The NFPA Manual of Style does not allow requirements in definitions. Therefore this change places thecomments about the figures in the annex.

_______________________________________________________________________________________________221- Log #13 BLD-BLC

_______________________________________________________________________________________________Marcelo M. Hirschler, GBH International

Revise text to read as follows:ASTM International, P.O. Box C700, 100 Barr Harbor Drive, West Conshohocken, PA

19428-2959.ASTM E 119, , 2012 2009.ASTM E 814, , 2011a 2002.ASTM E 1966, , 1997 (2011) 2001.

Standards update.

_______________________________________________________________________________________________221- Log #2 BLD-BLC

_______________________________________________________________________________________________John F. Bender, UL LLC

Revise text as follows:Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096.

ANSI/UL 263, , 2003 2011.ANSI/UL 1479, , 2003, Revised 2007 2010.ANSI/UL 2079, , 2004, Revised 2008.

Update referenced standards to the most recent edition as indicated.

4Printed on 5/16/2012

Page 41 of 53

Page 42: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

Report on Proposals – June 2014 NFPA 221_______________________________________________________________________________________________221- Log #3 BLD-BLC

_______________________________________________________________________________________________John F. Bender, UL LLC

Revise text as follows:Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096.

2010 2012.Update referenced document to the most recent edition as indicated.

5Printed on 5/16/2012

Page 42 of 53

Page 43: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

NFPA

5000 3

Move Section 7.1.5 to Chapter 55 :

7.1.5 Fire Department Access. [1:18.2]

7.1.5.1 Fire department access and fire department access roads shall be provided and

maintained in accordance with 7.1.5. [1:18.2.1]

7.1.5.2 Fire Department Access Roads. [1:18.2.3]

7.1.5.2.1 Required Access.

7.1.5.2.1.1 Approved fire department access roads shall be provided in accordance with 7.1.5

for every facility, building, or portion of a building hereafter constructed or relocated.

[1:18.2.3.1.1]

7.1.5.2.1.2 The provisions of 7.1.5.2.1 through 7.1.5.2.3.2 shall be permitted to be modified

by the AHJ where any of the following conditions exists:

(1) One- and two-family dwellings protected by an approved automatic sprinkler system in

accordance with Section 13.1 of NFPA 1

(2) Existing one- and two-family dwellings

(3) Private garages having an area not exceeding 400 ft2

(4) Carports having an area not exceeding 400 ft2

(5) Agricultural buildings having an area not exceeding 400 ft2

(6) Sheds and other detached buildings having an area not exceeding 400 ft2

[1:18.2.3.1.3]

7.1.5.2.1.3 When fire department access roads cannot be installed due to location on property,

topography, waterways, nonnegotiable grades, or other similar conditions, the authority having

jurisdiction shall be authorized to require additional fire protection features. [1:18.2.3.1.4]

7.1.5.2.2 Access to Building.

7.1.5.2.2.1 A fire department access road shall extend to within 50 ft (15 m) of at least one

exterior door that can be opened from the outside and that provides access to the interior of the

building. [1:18.3.2.1]

7.1.5.2.2.2 Where a one- or two-family dwelling, or townhouse, is protected with an

approved automatic sprinkler system that is installed in accordance with NFPA 13D or NFPA

13R, as applicable, the distance in 7.1.5.2.2.1 shall be permitted to be increased to 150 ft (46

m). [1: 18.2.3.2.1.1]

7.1.5.2.3 Additional Requirements.

7.1.5.2.3.1 Fire department access roads shall be provided such that any portion of the facility

or any portion of an exterior wall of the first story of the building is located not more than 150

ft (46 m) from fire department access roads as measured by an approved route around the

exterior of the building or facility. [1:18.2.3.2.2]

7.1.5.2.3.2 When buildings are protected throughout with an approved automatic sprinkler

system that is installed in accordance with NFPA 13, Standard for the Installation of Sprinkler

Systems; NFPA 13D, Standard for the Installation of Sprinkler Systems in One- and Two-

Family Dwellings and Manufactured Homes; or NFPA 13R, Standard for the Installation of

Sprinkler Systems in Residential Occupancies up to and Including Four Stories in Height, the

distance shall be permitted to be increased to 450 ft (137 m). [1:18.2.3.2.2.1]

The NFPA BLD had organized a task group

with the goal to review and provide

recommendations in regard to the

organization of Chapter 7, Construction

Types and Height and Area Requirements.

The subgroup has reviewed the assignment

and is recommending the following for

consideration.

The subgroup recommends that this section

be incorporated into Chapter 55 in a new

Section 55.8 Fire Department Access where

it is more appropriate. Existing Sections

55.8 through 55.12 should be re-numbered

to Sections 55.9 through 55.13. Fire

Department access provisions are not

appropriate in Chapter 7.

Page 43 of 53

Page 44: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

7.1.5.2.4 Multiple Access Roads. More than one fire department access road shall be

provided when it is determined by the authority having jurisdiction that access by a single road

could be impaired by vehicle congestion, condition of terrain, climatic conditions, or other

factors that could limit access. [1:18.2.3.3]

7.1.5.2.5 Specifications. [1:18.2.3.4]

7.1.5.2.5.1 Dimensions. [1:18.2.3.4.1]

(A) Fire department access roads shall have an unobstructed width of not less than 20 ft

(6100 mm). [1:18.2.3.4.1.1]

(B) Fire department access roads shall have an unobstructed vertical clearance of not less

than 13 ft 6 in. (4.1 m). [1:18.2.3.4.1.2]

(C) Vertical clearance shall be permitted to be reduced, provided such reduction does not

impair access by fire apparatus, and approved signs are installed and maintained indicating the

established vertical clearance when approved. [1:18.2.3.4.1.2.1]

(D) Vertical clearances or widths shall be increased when vertical clearances or widths are

not adequate to accommodate fire apparatus. [1:18.2.3.4.1.2.2]

7.1.5.2.5.2 Surface. Fire department access roads shall be designed and maintained to support

the imposed loads of fire apparatus and shall be provided with an all-weather driving surface.

[1:18.2.3.4.2]

7.1.5.2.5.3 Turning Radius.

(A) The turning radius of a fire department access road shall be as approved by the authority

having jurisdiction. [1:18.2.3.4.3.1]

(B) Turns in fire department access roads shall maintain the minimum road width.

7.1.5.2.5.4 Dead Ends. Dead-end fire department access roads in excess of 150 ft (46 m) in

length shall be provided with approved provisions for the fire apparatus to turn around.

[1:18.2.3.4.4]

7.1.5.2.5.5 Bridges. [1:18.2.3.4.5]

(A) When a bridge is required to be used as part of a fire department access road, it shall be

constructed and maintained in accordance with nationally recognized standards.

[1:18.2.3.4.5.1]

(B) The bridge shall be designed for a live load sufficient to carry the imposed loads of fire

apparatus. [1:18.2.3.4.5.2]

(C) Vehicle load limits shall be posted at both entrances to bridges where required by the

authority having jurisdiction. [1:18.2.3.4.5.3]

7.1.5.2.5.6 Grade. [1:18.2.3.4.6]

(A) The gradient for a fire department access road shall not exceed the maximum approved.

[1:18.2.3.4.6.1]

(B)* The angle of approach and departure for any means of fire department access shall not

exceed 1 ft drop in 20 ft (305 mm drop in 6100 mm) or the design limitations of the fire

apparatus of the fire department, and shall be subject to approval by the authority having

jurisdiction. [1:18.2.3.4.6.2]

7.1.5.2.5.7 Marking of Fire Department Access Road. Where required by the authority

having jurisdiction, approved signs or other approved notices shall be provided and maintained

Page 44 of 53

Page 45: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

to identify fire department access roads or to prohibit the obstruction thereof or both.

[1:18.2.3.5.1]

NFPA

5000 4

Delete Section 7.2.3.2.14, 7.2.3.2.15, 7.2.3.2.16, 7.2.3.2.17, 7.2.3.2.18, and 7.2.3.2.19 without

substitution, and renumber the remaining provisions as necessary

7.2.3.2.14* Ceiling Cavity Plenums and Raised Floor Plenums. Ceiling cavity plenums and raised

floor plenums shall be permitted to be used to supply air to the occupied area or return and exhaust air

from the occupied area, provided that the requirements of NFPA 90A are met.

7.2.3.2.14.1 Storage. [90A:4.3.11.1]

(A) Plenums shall not be used for occupancy or storage. [90A:4.3.11.1.1]

(B) Accessible abandoned material shall be deemed to be storage and shall not be permitted to remain.

[90A:4.3.11.1.2]

7.2.3.2.14.2 Ceiling Cavity Plenum. The space between the top of the finished ceiling and the

underside of the floor or roof above shall be permitted to be used to supply air to the occupied area, or

return or exhaust air from the occupied area, provided that the conditions in 7.2.3.2.14.2(A) through

7.2.3.2.14.2(J) are met. [90A:4.3.11.2]

(A) The integrity of the fire and smoke stopping for penetrations shall be maintained. [90A:4.3.11.2.1]

(B) Light diffusers, other than those made of metal or glass, used in air-handling light fixtures shall be

listed and marked “Fixture Light Diffusers for Air-Handling Fixtures.”

(C) The temperature of air delivered to these plenums shall not exceed 250°F (121°C).

[90A:4.3.11.2.2]

(D) Materials used in the construction of a ceiling plenum shall be noncombustible or shall be limited-

combustible having a maximum smoke developed index of 50, except as permitted in 7.2.3.2.14.2.4.1

through 7.2.3.2.14.2.4.3, and shall be suitable for continuous exposure to the temperature and humidity

conditions of the environmental air in the plenum. [90A:4.3.11.2.4]

(E) Materials used in the construction of a plenum space between the ceiling and roof (or floor) of

other than the fire-resistive assemblies covered in 5.3.3 shall be permitted as specified in 7.2.3.2.14.2.4.2

and 7.2.3.2.14.2.4.3. [90A:4.3.11.2.4.1]

(F) The ceiling material shall have a flame spread index of not more than 25 and a smoke developed

index not greater than 50. All surfaces, including those that would be exposed by cutting through the

material in any way, shall meet these requirements. [90A:4.3.11.2.4.2]

(G) The ceiling materials shall be supported by noncombustible material. [90A:4.3.11.2.4.3]

(H) Where the plenum is a part of a floor-ceiling or roof-ceiling assembly that has been tested or

The NFPA BLD-BLC committee had organized

a task group with the goal to review and provide

recommendations in regard to the disposition of

Section 7.2.3.2.14 “Ceiling Cavity Plenums and

Raised Plenums.” The subgroup has reviewed

the assignment and is recommending the

following for consideration.

The subgroup recommends that the extracted

NFPA 90A provisions be deleted from Chapter

7 without substitution, and the addition of

language in Chapter 50 be incorporated as part

of our recommendation.

Why?

If we look at NFPA 90A-2012 edition the

subgroup finds that provisions of that standard

represent 19 pages of requirements (Pages 4

through 23) whereas, Chapter 7 contains

approximately 3 pages of extracted text from

NFPA 90A. The question then becomes “Is it

necessary to extract this quantity of text versus

having the user of NFPA 5000 referring to the

entire document?” The subgroup would submit

no since reading NFPA 90A does not represent a

substantial impact to the user.

Is there a need to extract?

The subgroup would recommend no there is not.

The provisions which were originally extracted

appear to have text which has a greater

relationship with NFPA 90A than they do with

NFPA 5000 Chapter 7. While portions of the

extracted text do contain construction and fire

related text, the subgroup recommends that the

above proposal would be more appropriate since

NFPA 90A is recognized as the standard for the

installation of air-conditioning and ventilating

systems.

Is there a need to have NFPA 90A language

in NFPA 5000?

The subgroup would recommend no there is not.

Page 45 of 53

Page 46: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

investigated and assigned a fire resistance rating of 1 hour or more, the assembly shall meet the

requirements of 5.3.3. [90A:4.3.11.2.5]

(I) Materials within a ceiling cavity plenum exposed to the airflow shall be noncombustible or comply

with the following as applicable:

(1)* Electrical wires and cables and optical fiber cables listed to UL Subject 2424, Outline of

Investigation for Cable Marked Limited Combustible, are considered to be suitable for use wherever

cables tested in accordance with NFPA 262, Standard Method of Test for Flame Travel and Smoke of

Wires and Cables for Use in Air-Handling Spaces, are required.

(2) Pneumatic tubing for control systems shall be listed as having a maximum peak optical density

of 0.5 or less, an average optical density of 0.15 or less, and a maximum flame spread distance of 5 ft

(1.5 m) or less when tested in accordance with ANSI/UL 1820, Standard for Safety Fire Test of

Pneumatic Tubing for Flame and Smoke Characteristics. [90A:4.3.11.2.6.2]

(3) Nonmetallic fire sprinkler piping shall be listed as having a maximum peak optical density of

0.5 or less, an average optical density of 0.15 or less, and a maximum flame spread distance of 5 ft (1.5

m) or less when tested in accordance with ANSI/UL 1887, Standard for Safety Fire Test of Plastic

Sprinkler Pipe for Visible Flame and Smoke Characteristics. [90A:4.3.11.2.6.3]

(4) Optical fiber and communication raceways shall be listed as having a maximum peak optical

density of 0.5 or less, an average optical density of 0.15 or less, and a maximum flame spread distance of

5 ft (1.5 m) or less when tested in accordance with ANSI/UL 2024, Standard for Safety Optical-Fiber

and Communications Cable Raceway. [90A:4.3.11.2.6.4]

(5) Loudspeakers, recessed lighting fixtures, and other electrical equipment with combustible

enclosures, including their assemblies and accessories, cable ties, and other discrete products shall be

permitted in the ceiling cavity plenum where listed as having a maximum peak optical density of 0.5 or

less, an average optical density of 0.15 or less, and a peak heat release rate of 100 kW or less when tested

in accordance with UL 2043, Standard for Safety Fire Test for Heat and Visible Smoke Release for

Discrete Products and Their Accessories Installed in Air-Handling Spaces. [90A:4.3.11.2.6.5]

(6) Supplementary materials for air distribution systems shall be permitted when complying with

the provisions of 4.3.3. [90A:4.3.11.2.6.6]

(7) Smoke detectors shall not be required to meet the provisions of this sections 7.2.3.2.14.2(A)

thru 7.2.3.2.14.2(J). [90A:4.3.11.2.6.7]

(8) Air ducts complying with 4.3.1.2 and air connectors complying with 4.3.2 shall be permitted.

[90A:4.3.11.2.6.8]

(9) Materials that, in the form in which they are used, have a potential heat value not exceeding

3500 Btu/lb (8141 kJ/kg), where tested in accordance with NFPA 259, Standard Test Method for

Potential Heat of Building Materials, and include either of the following:

As noted in the paragraph above, the subgroup

did not find sufficient cause to suggest that there

was enough language in the extracted language

from NFPA 90A to adequately support that

NFPA 5000 be the preferred location. Further,

the subgroup questioned the impact of this

extraction considering the other relationships in

NFPA 90A with the language that was originally

extracted.

What about NFPA 90A Section 1.3

Application?

Section 1.3 applies to spaces greater than 708

m3 (25,000 ft2), for building construction Types

III, IV and V greater than 3 stories regardless of

volume, buildings and spaces not covered by

other applicable NFPA standards, and occupants

and processes not covered by NFPA standards.

On the other hand NFPA 5000 did not include

those parameters for the applications of

plenums. As a result, the subgroup recommends

that the intent of NFPA continue in spirit with

this proposal with the introduction of the second

sentence in the proposal.

Is the simple reference to NFPA 90A too

broad?

If the BLD committee believes that the proposal

is too broad in its applications, and that as a

result the proposal looses the original intent of

the extracted provisions from NFPA 90A into

Chapter 7 of NFPA 5000, the following might

be considered an a compromise.

Page 46 of 53

Page 47: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

(a) Materials having a structural base of noncombustible material, with a surfacing not exceeding a

thickness of 1⁄8 in. (3.2 mm) that has a flame spread index not greater than 50

(b) Materials, in the form and thickness used, having neither a flame spread index greater than 25

nor evidence of continued progressive combustion, and of such composition that surfaces that would be

exposed by cutting through the material on any plane would have neither a flame spread index greater

than 25 nor evidence of continued progressive combustion, when tested in accordance with ASTM E 84,

Standard Test Method of Surface Burning Characteristics of Building Materials, or ANSI/UL 723,

Standard Test Method of Surface Burning Characteristics of Building Materials [90A:4.3.11.2.6.9]

(J) The accessible portion of abandoned materials exposed to airflow shall be removed.

[90A:4.3.11.2.7]

7.2.3.2.14.3 Apparatus Casing Plenum. [90A:4.3.11.3]

(A) A fabricated plenum and apparatus casing shall be permitted to be used for supply, return, or

exhaust air service. [90A:4.3.11.3.1]

(B) Fabricated plenum and apparatus casing shall be constructed of materials and by methods specified

in 4.3.1 and in accordance with the following:

(1) The casing and plenum construction standards in SMACNA HVAC Duct Construction

Standards — Metal and Flexible

(2) ASHRAE Handbook — HVAC Systems and Equipment

(3) Subsection 4.3.3 for all air duct coverings, duct lining, acoustical liner/cells, and miscellaneous

materials [90A:4.3.11.3.2]

(C) Electrical wires and cables or optical fiber cables, or optical fiber and communications raceways,

shall comply with 4.3.4. [90A:4.3.11.3.3]

7.2.3.2.14.4 Air-Handling Unit Room Plenum. [90A:4.3.11.4]

(A) Individual rooms containing an air-handling unit(s) shall gather air from various sources and

combine the air within the room for return to the air-handling unit. [90A:4.3.11.4.1]

(B) Duct covering, duct lining, acoustical liner/cells, and miscellaneous materials shall comply with

4.3.3. [90A:4.3.11.4.2]

(C) Air-handling unit room plenums shall not be used for storage or occupancy other than during

equipment servicing. [90A:4.3.11.4.3]

(D) Accessible abandoned materials shall be deemed to be storage and shall not be permitted to

Page 47 of 53

Page 48: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

remain. [90A:4.3.11.4.4]

(E) Materials used in the construction of an air-handling unit room plenum shall be noncombustible or

shall be limited-combustible having a maximum smoke developed index of 50, and shall be suitable for

continuous exposure to the temperature and humidity conditions of the environmental air in the plenum.

[90A:4.3.11.4.5]

(F) Electrical wires and cables and optical fiber cables shall be listed as having a maximum peak

optical density of 0.50 or less, an average optical density of 0.15 or less, and a maximum flame spread

distance of 5 ft (1.5 m) or less when tested in accordance with NFPA 262, Standard Method of Test for

Flame Travel and Smoke of Wires and Cables for Use in Air-Handling Spaces, or shall be installed in

metal raceways, metal sheathed cable, or totally enclosed nonventilated busway. [90A:4.3.11.4.6]

7.2.3.2.14.5 Raised Floor Plenum. [90A:4.3.11.5]

(A) The space between the top of the finished floor and the underside of a raised floor shall be

permitted to be used to supply air to the occupied area, or return or exhaust air from from the occupied

area, provided that all of the following conditions are met: [90A:4.3.11.5.1]

(B) The integrity of the firestopping for penetrations shall be maintained. [90A:4.3.11.5.2]

(C) The temperature of air delivered to these plenums shall not exceed 121°C (250°F).

[90A:4.3.11.5.3]

(D) Materials used in the construction of a raised floor plenum shall be noncombustible or limited-

combustible materials, shall have a maximum peak smoke developed index of 50, and shall be suitable

for continuous exposure to the temperature and humidity conditions of the environmental air in the

plenum. [90A:4.3.11.5.4]

(E) Materials within a raised floor plenum exposed to the airflow shall comply with the following, as

applicable: [90A:4.3.11.5.5]

(1)* Electrical wires and cables and optical fiber cables shall be listed as having a maximum peak

optical density of 0.50 or less, an average optical density of 0.15 or less, and a maximum flame spread

distance of 5 ft (1.5 m) or less when tested in accordance with NFPA 262, Standard Method of Test for

Flame Travel and Smoke of Wires and Cables for Use in Air-Handling Spaces, or shall be installed in

metal raceways, metal-sheathed cable, or totally enclosed nonventilated busway. [90A:4.3.11.5.5.1]

(2) Pneumatic tubing for control systems shall be listed as having a maximum peak optical density

of 0.5 or less, an average optical density of 0.15 or less, and a maximum flame spread distance of 5 ft

(1.5 m) or less when tested in accordance with ANSI/UL 1820, Standard for Safety Fire Test of

Pneumatic Tubing for Flame and Smoke Characteristics. [90A: 4.3.11.5.5.2]

(3) Nonmetallic fire sprinkler piping shall be listed as having a maximum peak optical density of

0.5 or less, an average optical density of 0.15 or less, and a maximum flame spread distance of 5 ft (1.5

Page 48 of 53

Page 49: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

m) or less when tested in accordance with ANSI/UL 1887, Standard for Safety Fire Test of Plastic

Sprinkler Pipe for Visible Flame and Smoke Characteristics. [90A: 4.3.11.5.5.3]

(4) Optical fiber and communications raceways shall be listed as having a maximum peak optical

density of 0.5 or less, an average optical density of 0.15 or less, and a maximum flame spread distance of

5 ft (1.5 m) or less when tested in accordance with ANSI/UL 2024, Standard for Safety Optical-Fiber

and Communication Cable Raceway.

(5) Cables installed within the raceways specified in item (4) shall be listed as plenum cable in

accordance with the requirements in 7.2.3.2.14.5.5.1. [90A: 4.3.11.5.5.4]

(6) Raised floors, intermachine cables, electrical wires, listed plenum communication and optical-

fiber raceways, and optical-fiber cables in computer/data processing rooms where these rooms are

designed and installed in accordance with NFPA 75, Standard for the Protection of Information

Technology Equipment. [90A: 4.3.11.5.5.5]

(7) Loudspeakers, recessed lighting fixtures, and other electrical equipment with combustible

enclosures, including their assemblies and accessories, cable ties, and other discrete products, shall be

permitted in the raised floor plenum where listed as having a maximum peak optical density of 0.5 or

less, an average optical density of 0.15 or less, and a peak heat release rate of 100 kW or less when tested

in accordance with UL 2043, Standard for Safety Fire Test for Heat and Visible Smoke Release for

Discrete Products and Their Accessories Installed in Air-Handling Spaces. [90A: 4.3.11.5.5.6]

(8) Air ducts complying with 4.3.1.2 and air connectors complying with 4.3.2 shall be permitted.

[90A: 4.3.11.5.5.7]

(9) Materials that, in the form in which they are used, have a potential heat value not exceeding

3500 Btu/lb (8141 kJ/kg), where tested in accordance with NFPA 259, Standard Test Method for

Potential Heat of Building Materials, shall be permitted and include either of the following:

(a) Materials having a structural base of noncombustible material, with a surfacing not exceeding a

thickness of 1⁄8 in. (3.2 mm) that has a flame spread index not greater than 50

(b) (2) Materials, in the form and thickness used, having neither a flame spread index greater than

25 nor evidence of continued progressive combustion, and of such composition that surfaces that would

be exposed by cutting through the material on any plane would have neither a flame spread index greater

than 25 nor evidence of continued progressive combustion, when tested in accordance with ASTM E 84,

Standard Test Method of Surface Burning Characteristics of Building Materials, or ANSI/UL 723,

Standard Test Method for Surface Burning Characteristics of Building Materials. [90A: 4.3.11.5.5.8]

(F) Smoke detectors shall not be required to meet the requirements of 7.2.3.2.14.5.1. [90A: 4.3.11.5.6]

(G) Supplementary materials for air distribution systems shall be permitted when complying with

4.3.3. [90A: 4.3.11.5.7]

Page 49 of 53

Page 50: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

(H) The accessible portion of abandoned materials exposed to airflow shall be removed. [90A:

4.3.11.5.8]

7.2.3.2.14.6 Wall or Ceiling Finish in Plenums. [90A: 4.3.11.6]

(A) Wall or ceiling finish in plenums, except as indicated in 7.2.3.2.14.6.2, shall be noncombustible or

shall exhibit a flame spread index of 25 or less and a smoke developed index of 50 or less, when tested in

accordance with ASTM E 84, Standard Test Method for Surface Burning Characteristics of Building

Materials, or ANSI/UL 723, Standard Test Method for Surface Burning Characteristics of Building

Materials, at the maximum thickness intended for use. [90A: 4.3.11.6.1]

(B) Foam plastic insulation shall not be used as wall or ceiling finish in plenums, unless the insulation

meets one of the criteria shown in the following: [90A: 4.3.11.6.2]

(1) The foam plastic insulation material both (a) exhibits a flame spread index of 25 or less, and a

smoke developed index of 50 or less, when tested in accordance with ASTM E 84, Standard Test

Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard Test

Method for Surface Burning Characteristics of Building Materials, at the maximum thickness intended

for use, and (b) complies with the following criteria: (1) flame does not spread to the ceiling during the

40 kW exposure, (2) flame does not spread to the outer extremities of the sample, (3) flashover does not

occur, (4) the peak heat release rate does not exceed 800 kW, and (5) the total smoke release does not

exceed 1196 yd2 (1000 m2) when tested in accordance with NFPA 286, Standard Methods of Fire Tests

for Evaluating Contribution of Wall and Ceiling Interior Finish to Room Fire Growth (where the testing

is performed on the finished foam plastic assembly related to the actual end-use configuration and on the

maximum thickness intended for use). [90A: 4.3.11.6.2.1]

(2) The foam plastic insulation material both (a) is covered by corrosion-resistant steel having a

base metal thickness of not less than 0.4 mm (0.0160 in.) and (b) exhibits a flame spread index of 75 or

less, and a smoke developed index of 450 or less, when tested in accordance with ASTM E 84, Standard

Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard Test

Method for Surface Burning Characteristics of Building Materials, at the maximum thickness intended

for use. [90A: 4.3.11.2.2]

(3) The foam plastic insulation material both (a) is separated from the plenum by an approved

thermal barrier of 0.5 in. (12.7 mm) gypsum wallboard or equivalent material that will limit the average

temperature rise of the unexposed surface to not more than 250°F (139°C) after 15 minutes of fire

exposure, complying with the standard time–temperature curve of NFPA 251, Standard Methods of Tests

of Fire Resistance of Building Construction and Materials, and (b) exhibits a flame spread index of 75 or

less, and a smoke developed index of 450 or less, when tested in accordance with ASTM E 84, Standard

Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard Test

Method for Surface Burning Characteristics of Building Materials, at the maximum thickness intended

for use. [90A: 4.3.11.2.3]

7.2.3.2.15 Plenum Materials Combustibility. 7.2.3.2.15.1 Materials exposed to the airflow within ceiling cavity plenums and raised floor plenums

shall comply with NFPA 90A.

7.2.3.2.15.2 Fire-retardant-treated wood complying with Chapter 45 shall be permitted.

Page 50 of 53

Page 51: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

7.2.3.2.16 Plenum Fire Stopping. The integrity of the fire stopping for penetrations shall be

maintained.

7.2.3.2.17 Plenum Light Diffusers. Light diffusers, other than those made of metal or glass, used in

air-handling light fixtures shall be listed and marked as follows:

Fixture Light Diffusers for Air-Handling Fixtures 7.2.3.2.18 Plenum Air Temperature. The temperature of air delivered to plenums shall not exceed

250°F (121°C).

7.2.3.2.19 Plenum Materials Exposure. Materials used in the construction of a plenum shall be

suitable for continuous exposure to the temperature and humidity conditions of the environmental air in

the plenum.

NFPA

5000 5

Add new section for 50.4 as follows

50.4 Ceiling Cavity Plenums and Raised Plenums

50.4.1 General. Ceiling cavity plenums and raised floor plenums shall be permitted to be used

to supply air to the occupied area or return and exhaust air from the occupied area, provided the

requirements of NFPA 90A are met. For the purpose of this code the application of these

provisions for ceiling cavity plenums and raised plenums shall apply to all buildings, and shall

not be subject to the limitations as set forth in Section 1.3 of NFPA 90A.

The NFPA BLD-BLC committee had organized

a task group with the goal to review and provide

recommendations in regard to the disposition of

Section 7.2.3.2.14 “Ceiling Cavity Plenums and

Raised Plenums.” The subgroup has reviewed

the assignment and is recommending the

following for consideration.

The subgroup recommends that the extracted

NFPA 90A provisions be deleted from Chapter

7 without substitution, and the addition of

language in Chapter 50 be incorporated as part

of our recommendation.

NFPA

5000 6

Remove section 7.2.3.2.20 as follows

7.2.3.2.20 Ceiling Plenum Tested Assembly. Where the plenum is a part of a floor/ceiling or

roof/ceiling assembly that has been tested or investigated and assigned a fire resistance rating

of 1 hour or more, and the assembly contains air ducts and openings for air ducts, all the

materials and the construction of the assembly, including the air duct materials and the size and

protection of the openings, shall conform with the design of the fire resistance–rated assembly,

as tested in accordance with NFPA 251, Standard Methods of Tests of Fire Resistance of

Building Construction and Materials; ASTM E 119, Standard Test Methods for Fire Tests of

Building Construction and Materials; or UL 263, Standard for Fire Tests of Building

Construction and Materials.

The NFPA BLD-BLC committee had

organized a task group with the goal to

review and provide recommendations in

regard to the organization of Chapter 7,

Construction Types and Height and Area

Requirements. The subgroup has reviewed

the assignment and is recommending the

following for consideration.

The subgroup recommends that this section

be deleted from Chapter 7 and incorporated

into Section 8.2.1 Fire Resistance-Rated

Construction, General where it is more

appropriate.

NFPA

5000 7

Remove section 7.5 as follows: (and relocate in next FR)

7.5 Height Increases Permitted.

7.5.1 General. The allowable building heights and allowable number of stories of a building

shall be as shown in Table 7.4.1, as modified in 7.4.3.6.

The NFPA BLD-BLC committee organized

a task group with the goal to review and

provide recommendations in regard to the

organization of Chapter 7, Construction

Page 51 of 53

Page 52: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

7.5.2 Residential Sprinkler Increase. For buildings classified as residential occupancies

provided with an approved, electrically supervised automatic sprinkler system in accordance

with NFPA 13R, the allowable height for nonsprinklered buildings shall be permitted to be

increased by 20 ft (6100 mm), and the allowable number of stories for nonsprinklered buildings

shall be permitted to be increased by one story, provided that the building height does not

exceed 60 ft (18 m) and the number of stories above grade plane does not exceed four.

Types and Height and Area Requirements.

The subgroup has reviewed the assignment

and is recommending the following for

consideration.

The subgroup recommends that this section

be incorporated into Section 7.4.3 Building

Height and Number of Stories where it is

more appropriate.

NFPA

5000 8

Add relocated section to 7.4.3.6 as follows:

7.4.3.6 Height Increases Permitted.

7.4.3.6.1 General. The allowable building heights and allowable number of stories of a

building shall be as shown in Table 7.4.1, as modified in 7.4.3.6.

7.4.3.6.2 Residential Sprinkler Increase. For buildings classified as residential occupancies

provided with an approved, electrically supervised automatic sprinkler system in accordance

with NFPA 13R, the allowable height for nonsprinklered buildings shall be permitted to be

increased by 20 ft (6100 mm), and the allowable number of stories for nonsprinklered buildings

shall be permitted to be increased by one story, provided that the building height does not

exceed 60 ft (18 m) and the number of stories above grade plane does not exceed four.

The NFPA BLD-BLC committee organized

a task group with the goal to review and

provide recommendations in regard to the

organization of Chapter 7, Construction

Types and Height and Area Requirements.

The subgroup has reviewed the assignment

and is recommending the following for

consideration.

The subgroup recommends that this section

be incorporated into Section 7.4.3 Building

Height and Number of Stories where it is

more appropriate.

Page 52 of 53

Page 53: NFPA Technical Committee on Building Construction NFPA ...€¦ · NFPA Technical Committee on Building Construction ROC Meeting October 6, 2010 Page 2 of 3 Dennis Pitts American

Suggested Editorial Revisions 

NFPA 5000 1 

7.2.3.2.14.6 B(3) The foam plastic insulation material both (a) is separated from the plenum by an approved thermal barrier of 0.5 in. (12.7 mm) gypsum wallboard or equivalent material that will limit the average temperature rise of the unexposed surface to not more than 250°F (139°C) after 15 minutes of fire exposure, complying with the standard time–temperature curve of ASTM E 119, Standard Test Methods for Fire Tests of Building Construction and Materials, or ANSI/UL 263, Standard for Fire Tests of Building Construction and MaterialsNFPA 251, Standard Methods of Tests of Fire Resistance of Building Construction and Materials, and (b) exhibits a flame spread index of 75 or less, and a smoke developed index of 450 or less, when tested in accordance with ASTM E 84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard Test Method for Surface Burning Characteristics of Building Materials, at the maximum thickness intended for use. [90A: 4.3.11.2.3]  

NFPA 251 was withdrawn and replaced with referenced ASTM and UL standards. 

NFPA 5000 2 

7.2.3.2.20 Ceiling Plenum Tested Assembly. Where the plenum is a part of a floor/ceiling or roof/ceiling assembly that has been tested or investigated and assigned a fire resistance rating of 1 hour or more, and the assembly contains air ducts and openings for air ducts, all the materials and the construction of the assembly, including the air duct materials and the size and protection of the openings, shall conform with the design of the fire resistance–rated assembly, as tested in accordance with NFPA 251, Standard Methods of Tests of Fire Resistance of Building Construction and Materials; ASTM E 119, Standard Test Methods for Fire Tests of Building Construction and Materials; or UL 263, Standard for Fire Tests of Building Construction and Materials.  

NFPA 251 was withdrawn and replaced with referenced ASTM and UL standards. 

 

 

NFPA 221 1 

Global Revision Replace NFPA 251 as follows: NFPA 251 ASTM E 119, Standard Test Methods for Fire Tests of Building Construction and Materials, or UL 263, Standard for Fire Tests of Building Construction and Materials.

NFPA 251 has been withdrawn and replaced by the Fire Test Committee 

NFPA 221 2 

Global Revision Remove all extracts as follows: [NFPA 5000:#.#.#.]

NFPA 221 is a source document and should not contain extracts from NFPA 5000. The intent is to allow NFPA 221 to stand alone.  

NFPA 221 3 

Global Revision Add document titles to all references within NFPA 221

 

NFPA 221 4 

5.10.1 Fire dampers shall be installed and maintained in accordance with NFPA 90A, Standard for the Installation of Air Conditioning and Venting Systems NFPA 80, Standard for Fire Doors and Other Opening Protectives.

Fire damper requirements are located in NFPA 80. 

 

 

Page 53 of 53