H Y U N D A I
MV & LV Circuit Breaker,Contactor & Overload Relay
MV & LV Circuit Breaker,Contactor & Overload Relay
Hyundai Circuit Breaker is one of the most reliable
and sophisticated products, which realizes the
optimum design through electric and kinetic analysis.
MCCB Molded Case Circuit Breakerup to 1200 A, 130 kA at 415 V
MC Magnetic Contactorup to 800 A
ACB Air Circuit Breakerup to 6300 A, 120 kA at 500 V
VCB Vacuum Circuit Breakerup to 38 kV, 40 kA, 3150 A
We build a better future!
Contents Molded Case Circuit Breaker | 04 Contactor & Overload Relay | 06 Vacuum Contactor | 15Air Circuit Breaker | 16 Vacuum Circuit Breaker | 18
Molded Case Circuit Breaker
Optimum design provides easy-to-use customer installation, while offering versatility and high performance to match today's demand for a reliable and cost-effective product, which is easy to maintain.
Qualified Standard & Approval
Standard IEC 60947-2NEMA AB-1KS C8321
Approval ISO 18001, 14001, 9001CE (Community European / TU
..V Rheinland)
TSEGOST-RCCCKR, LR, ABS, BV, NK, GL
Category Type Number ofpoles (P)Breaking Current (kA)
AC 600AC 415AC 220
E-Type
S-Type
H-Type *2 poles are the same as 3 poles except that the conducts ofmiddle pole are removed.
HiBE 50 2, 3, 4 10 5 2.5HiBE 60 2, 3, 4 10 5 2.5HiBE 100 2, 3, 4 25 10 5HiBE 225 2, 3, 4 35 18 7.5HiBE 250J 2, 3, 4 35 18 7.5HiBE 400 2, 3, 4 35 30 18HiBE 600 2, 3, 4 50 45 22HiBE 800 2, 3, 4 50 45 25HiBS 30 2, 3 10 5 2.5HiBS 50 2, 3, 4 25 10 5HiBS 60 2, 3, 4 25 10 5HiBS 100 2, 3, 4 50 25 10HiBS 100J 2, 3, 4 50 25 10HiBS 225 *2, 3, 4 50 25 10HiBS 250J 2, 3, 4 50 25 10HiBS 400 *2, 3, 4 50 42 22HiBS 600 *2, 3, 4 100 65 25HiBS 800 *2, 3, 4 100 65 25HiBS 400NE 3, 4 85 50 30HiBS 600NE 3, 4 100 65 35HiBS 800NE 3, 4 100 65 35HiBS 1000NE 3, 4 100 100 50HiBS 1200NE 3, 4 100 100 50HiBH 30 2, 3 25 10 5HiBH 50 2, 3, 4 50 25 10HiBH 100 2, 3, 4 65 35 18HiBH 100J 2, 3, 4 65 35 18HiBH 225 *2, 3, 4 65 35 18HiBH 250J 2, 3, 4 65 35 18HiBH 400 *2, 3, 4 85 65 25HiBH 600 *2, 3, 4 100 85 35HiBH 800 *2, 3, 4 100 85 35
Category Type Number ofpoles (P)Breaking Current (kA)
AC 600AC 415AC 220
L-Type
X-Type
Distributionand LightingProtection
Type
MiniatureCircuit
Breaker
HiBL 50NT 3, 4 125 85 35HiBL 100NT 3, 4 125 85 35HiBL 225NT 3, 4 125 85 35HiBL 400 *2, 3, 4 125 100 30HiBL 600 *2, 3, 4 125 100 35HiBL 800 *2, 3, 4 125 100 35HiBL 50NE 3, 4 125 85 35HiBL 100NE 3, 4 125 85 35HiBL 225NE 3, 4 125 85 35HiBL 400NE 3, 4 125 85 35HiBL 600NE 3, 4 125 85 42HiBL 800NE 3, 4 125 85 42HiBL 1000NE 3, 4 150 130 65HiBL 1200NE 3, 4 150 130 65HiBX 50NT 3, 4 150 130 65HiBX 100NT 3, 4 150 130 65HiBX 225NT 3, 4 150 130 65HiBX 400NE 3, 4 150 130 65HiBX 600NE 3, 4 150 130 65HiBX 800NE 3, 4 150 130 65HiBC 32 2 1.5HiBC 32h 2 2.5HBD 50 1, 2, 3 5 2.5HBD 50h 1, 2, 3 10 5HBD 52D 1, 2 5HiBD 63 1, 2, 3 6 (230 / 400 V)HiBD 100 1, 2, 3 10 (230 / 400 V)
04
M C C B
HiBS 803NEHiBL 203NEHiBS 103
MV & LV Circuit Breaker, Contactor & Overload Relay
?
?
?
?
?
Accessories
05
Terminal Cover [ TCF ]Prevents direct contact onthe terminals for protection.
Shunt Trip [ SHT ]Carries out the electricalremote trip of the breaker.
Plug-in Mounting Base [ TDM ]Allows the MCCB to be replacedwithout disconnecting the power.
Inter Pole Barrier [ TQQ ]
Terminal Cover [ TCF ]
Auxiliary Switch [ AUX ]Electrically indicates breakerstatus ON or OFF.
External Operating Handle [ TFG ]Surface attached type (Panel mounted type)The MCCB can be installed near the panel door.The operating mechanism is attached on the
MCCB, and the external operating handle ismounted on the panel door.
Under Voltage Trip [ UVT ]Automatically trips the breakerwhen control voltage dropsbelow predetermined value.
Inter Pole Barrier [ TQQ ]Enhances the insulation between poles of
the MCCB in the line side and load side.Can be attached easily onto the MCCB.
Alarm Trip Switch [ ALT ]Electrically indicates thetripped state of breaker.
External Operating Handle [ TFH ]Extended type (Panel mounted type)The MCCB can be installed inside the panel.The operating mechanism is attached on the MCCB,
and the external operating handle is mounted on thepanel door; where the handle and the mechanismare mechanically connected by a shaft.
Contactor & Overload Relay
M C
HYUNDAI Magnetic Contactor employs a modular design, which allows quick and simplemounting of auxiliary contact blocks, timers, mechanical latching blocks, etc. HiMC Contactor provides convenience, economic benefit and high reliability.
With highly advanced design for industrial applications such as motor control centers, theHiMC contactor is appropriate for various control systems. It is also favored by shipyardsand power plants whose criteria includes high reliability and performance.
Qualified Standard & Approval
Standard IEC 60947EN 60947UL 508BS 47794, BS 5424, BS 4941VDE 0660Det Norske VeritasKS C4504 JISC 8328, JEM 1038
Approval ISO 18001, 14001, 9001UL / C-ULCE (Community European / TU
..V Rheinland)
TSEGOST-RCCCKR, LR, ABS, BV, NK
Magnetic Contactor
Operational Voltage Capacity (AC 3, kW / A)Type
220~240 VAC DC AC / DC 380~440 V 500~550 V 660~690 V 1000 VAuxiliary Contact
HiMC 9HiMC 12HiMC 18HiMC 22HiMC 32HiMC 40HiMC 50HiMC 65HiMC 80HiMC 90HiMC 110, HiMC 110B2)
HiMC 130HiMC 150, HiMC 150B2)
HiMC 180HiMC 220HiMC 260HiMC 300HiMC 400HiMC 500HiMC 630HiMC 800
WWWWWWWWWWWWWWWWWWWWW
GGGGGGGGGGGGGGGGGGGGG
FFFFFFFFFFFFFF
2.2 / 103.7 / 134.5 / 185.5 / 227.5 / 3211 / 4015 / 50
18.5 / 7022 / 8025 / 9030 / 11037 / 13045 / 15055 / 18063 / 22075 / 26090 / 300
125 / 400140 / 500190 / 630220 / 800
4 / 95.5 / 127.5 / 1811 / 2215 / 32
18.5 / 4022 / 5030 / 6537 / 8045 / 90
55 / 11065 / 13075 / 15090 / 180110 / 220132 / 260160 / 300220 / 400250 / 500330 / 630440 / 800
4 / 77.5 / 128.5 / 1515 / 22
18.5 / 2822 / 3230 / 4537 / 6045 / 6450 / 80
60 / 11070 / 12090 / 140110 / 180132 / 200150 / 220160 / 273220 / 350300 / 426330 / 500500 / 720
5.5 / 77.5 / 97.5 / 915 / 18
18.5 / 2222 / 2625 / 3137 / 4445 / 5250 / 6055 / 6560 / 70
90 / 100110 / 120132 / 150160 / 173200 / 220250 / 300335 / 360400 / 412500 / 630
1a1b1a1b1a1b1a1b2a2b2a2b2a2b1)
2a2b1)
2a2b1)
2a2b1)
2a2b1)
2a2b1)
2a2b1)
2a2b1)
2a2b1)
2a2b1)
2a2b1)
2a2b1)
2a2b1)
2a2b1)
2a2b1)
-
-
-
-
-
-
-
-
-
-
65 / 5075 / 5490 / 66110 / 78132 / 96
160 / 113200 / 141250 / 178275 / 192300 / 213400 / 284
1) The auxiliary contact for DC is 2a1b2) Compact type contactor
HiMC 130F22HiMC 22 + HiTH 22
06
MV & LV Circuit Breaker, Contactor & Overload Relay
HiMC 65 ~ HiMC 800 [ Large Frame Size Contactor ]
1. Contactor : HiMC 9~8002. Auxiliary Contact Block3. Mechanical Latching Block 4. Electronic Timer Block5. Mechanical Interlock Unit6. Surge Absorber7. Insulation Barrier Unit8. Thermal Overload Relay9. Digital Motor Protection Relay
HiMC 9 ~ HiMC 50 [ Small Frame Size Contactor ]
6
21
15
8
9
4322
7 76
2
15
1 2
8
7
7
07
08
HiTH 130K80HiTH 90K(H)HiTH 50K(H)HiTH 40K(H)
CT Assembly
M C
Thermal Overload Relay
Category HiTH 22K(H) HiTH 50K(H) HiTH 90K(H)HiMC 9 ~ 22
0.18 ~ 22
3 Element
2 Element
1a1b
Manual / Auto Unit
K-Type Only1 ~ 6
2 0.75 ~ 2.5
0.17(0.16)
HiMC 32 ~ 4010 ~ 40
3 Element
2 Element
1a1b
Manual / Auto Unit
K-Type Only2 ~ 14
2 0.75 ~ 2.5
0.23(0.22)
HiMC 5026 ~ 50
3 Element
2 Element
1a1b
Manual / Auto Unit
K-Type Only2 ~ 22
2 0.75 ~ 2.5
0.28(0.27)
HiMC 65 ~ 9040 ~ 90
3 Element
2 Element
1a1b
Manual / Auto Unit
K-Type Only2 ~ 35
2 0.75 ~ 2.5
0.53(0.51)
Applied ContactorRated Current
Auxiliary ContactReset Type
Phase Fault Protection
Net Weight (kg) K-Type (H-Type)
Number of Element
Suitable Wire () Main CircuitControl Circuit
K-Type
H-Type
HiTH 40K(H)
Category HiTH 130K(H) HiTH 300K(H) HiTH 500K(H) HiTH 800K(H)HiMC 110 ~ 130
80 ~ 130
CT Assembly3 Element
2 Element
1a1b
Manual / Auto Unit
K-Type Only
2 0.75 ~ 2.5
1.65(1.3)
HiMC 150 ~ 220
130 ~ 220
CT Assembly3 Element
2 Element
1a1b
Manual / Auto Unit
K-Type Only
2 0.75 ~ 2.5
1.85(1.49)
HiMC 260 ~ 300
220 ~ 300
CT Assembly3 Element
2 Element
1a1b
Manual / Auto Unit
K-Type Only
2 0.75 ~ 2.5
1.94(1.59)
HiMC 400 ~ 500
300 ~ 500
CT Assembly3 Element
2 Element
1a1b
Manual / Auto Unit
K-Type Only
2 0.75 ~ 2.5
2.25(1.88)
HiMC 630 ~ 800
630 ~ 800
CT Assembly3 Element
2 Element
1a1b
Manual / Auto Unit
K-Type Only
2 0.75 ~ 2.5
5.7(4.62)
Applied Contactor
Rated CurrentFeature
Auxiliary ContactReset Type
Phase Fault Protection
Net Weight (kg)
Number of Element
Suitable Wire () Main CircuitControl Circuit
K-Type
H-Type
HiTH 220K(H)
Contactor & Overload Relay
09
Separate Mounting Unit
MV & LV Circuit Breaker, Contactor & Overload Relay
Type For use withOverload Relay Type Mounting
HiTH 22
HiTH 40
HiTH 50
HiTH 90
HiTHMB 22
HiTHMB 40
HiTHMB 50
HiTHMB 90
DIN Rail Screw
Saparate Mounting Unit (HiTHMB)
0.12~0.18 A0.18~0.26 A0.25~0.35 A0.34~0.5 A0.5~0.7 A0.6~0.9 A0.8~1.2 A1.1~1.6 A1.5~2.1 A2~3 A2.8~4.2 A3~5 A4~6 A5.6~8 A7~10 A9~13 A12~18 A16~22 A18~26 A24~32 A28~40 A36~50 A45~65 A60~80 A70~90 A48~80 A78~130 A108~180 A132~220 A180~300 A240~400 A300~500 A378~630 A480~800 A
Setting Range Relay Types (Standard Type)HiTH 22K HiTH 40K HiTH 50K HiTH 90K HiTH 130K HiTH 220K HiTH 300K HiTH 500K HiTH 800K
CT Operated Type
Ratings Overview
10
M C
Control Relay
Electronic Timer Block
Type Control Voltage Delay TimeHOKZE 1
HOKZE 2
AC / DC 90~240 V
AC / DC 24~60 V
0.15~220 sec
0.15~220 sec
Type Control VoltageAC 24, 48, 110, 220, 440 V / DC 24, 48, 110, 220 VHLB 2
Electronic Timer Block
Category Type Auxiliary Contact Additional Contact
AC
DC
HMX 22HMX 31HMX 40HMT 22HMT 31HMT 40
2a2b3a1b4a
2a2b3a1b4a
4a, 3a1b, 2a2b, 1a3b, 4b4a, 3a1b, 2a2b, 1a3b, 4b4a, 3a1b, 2a2b, 1a3b, 4b4a, 3a1b, 2a2b, 1a3b, 4b4a, 3a1b, 2a2b, 1a3b, 4b4a, 3a1b, 2a2b, 1a3b, 4b
Mechanical Interlock Unit
Type Contactors
HiTL 40HiTL 50HiTL 130HiTL 220HiTL 300HiTL 800
HiMC 9 ~ 40HiMC 50HiMC 65 ~ 130, 150BHiMC 150 ~ 220HiMC 260 ~ 300HiMC 400 ~ 800
Type Voltage Application
HiMC 110W ~ 300W
HMT, HiMC 9G ~ 50G
HiMC 50WHiMC 65W ~ 90W, 110B
HMXHiMC 9W ~ 40W
HRC 40 / 48HRC 40 / 220HRC 40 / 380HRC 90 / 48HRC 90 / 220HRC 90 / 380HRC 300 / 48HRC 300 / 220HRC 300 / 380HOKYZX 38
HMT & HMX
Mechanical Latching Block
Surge Absorber
Diagram
Surge Absorber
Mechanical Latching Block
Accessory
28 ~ 48 V110 ~ 220 V240 ~ 380 V28 ~ 48 V
110 ~ 220 V240 ~ 380 V28 ~ 48 V
110 ~ 220 V240 ~ 380 V
DC
Contactor & Overload Relay
Auxiliary Contact Block
ConsistType2NO + 2NC1NO + 3NC3NO + 1NC0NO + 4NC4NO + 0NC1NO + 1NC0NO + 2NC2NO + 0NC1NO + 1NC2NO + 2NC1NO + 3NC3NO + 1NC4NO + 0NC1NO + 1NC0NO + 2NC2NO + 0NC1NO + 1NC1NO + 1NC1NO + 1NC1NO + 1NC
HiAB 22HiAB 13HiAB 31HiAB 04HiAB 40HiAB 11HiAB 02HiAB 20HiAL 111)HiAC 22HiAC 13HiAC 31HiAC 40HiAC 11HiAC 02HiAC 20HiAL 5SHiAR 6SHiAL 7SHiAR 8S
Mounting ApplicationTop SideTop SideTop SideTop SideTop SideTop SideTop SideTop Side
Left Hand SideTop SideTop SideTop SideTop SideTop SideTop SideTop Side
Left Hand SideRight Hand SideLeft Hand Side
Right Hand Side
HiMC 9 ~ 50
1) The side mounting auxiliary contact block shall not be used with the top mounting aux. contact block at the same time.
HMX
HMT
HiMC 65 ~ 130, 150B
HiMC 9 ~ 22
HiMC 150 ~ 800
HiAC 22 HiAC 20 HiAL 11 HiAL 5S HiAR 6S
11
MV & LV Circuit Breaker, Contactor & Overload Relay
Capacitor Switching Contactor
HiMK
Type(AC Operation)
Contactor Capacitor Switching UnitAC-6b External Size
Rating of 3-phase Capacitor 50~60 Hz(at ambient temperature 55 ) Composed Devices Dimension
5 5 9.7 9.7 14 14 HiMC 9W
6.7 6.7 12.5 12.5 18 18 HiMC 12W
8.5 8.5 16.7 16.7 24 24 HiMC 18W
10 10 18 18 26 26 HiMC 22W
14 16 27.5 30 34 45 HiMC 32W
20 20 30 33.3 48 48 HiMC 40W
21 24 40 45 50 65 HiMC 50W
HiAD 1A 22 1 -HiAD 1B 22 - 1HiAD 1A 22 1 -HiAD 1B 22 - 1HiAD 1A 22 1 -HiAD 1B 22 - 1HiAD 1A 22 1 -HiAD 1B 22 - 1HiAD 1A 50 1 -HiAD 1B 50 - 1HiAD 1A 50 1 -HiAD 1B 50 - 1HiAD 1A 50 1 -HiAD 1B 50 - 1
HiMK 9W 21HiMK 9W 12HiMK 12W 21HiMK 12W 12HiMK 18W 21HiMK 18W 12HiMK 22W 21HiMK 22W 12HiMK 32W 32HiMK 32W 23HiMK 40W 32HiMK 40W 23HiMK 50W 32HiMK 50W 23
Max. Power AC Operational Type Auxiliary W x H x D200 V 230 V 400 V 440 V 500 V 690 V NO NC
240 V 415 V 550 V (53-54) (51-52)kVAR kVAR kVAR kVAR kVAR kVAR mm
44 x 166 x 123
63 x 166 x 123
70 x 178 x 136
Digital Motor Protection Relay
12
M C
Number of CTs
CharacteristicCurve
Type(Basic)
HiMP 22
HiMP 40
HiMP 50
Current Range AuxiliaryContact 1)Connection
Type Ordering Type
HiMP 22H-PE-06HiMP 22H-SE-06HiMP 22H-TE-06HiMP 22H-PS-06HiMP 22H-SS-06HiMP 22H-TS-06HiMP 22H-PE-22HiMP 22H-SE-22HiMP 22H-TE-22HiMP 22H-PS-22HiMP 22H-SS-22HiMP 22H-TS-22HiMP 40H-PE-40HiMP 40H-SE-40HiMP 40H-TE-40HiMP 40H-PS-40HiMP 40H-SS-40HiMP 40H-TS-40HiMP 50H-PE-50HiMP 50H-SE-50HiMP 50H-TE-50HiMP 50H-PS-50HiMP 50H-SS-50HiMP 50H-TS-50
222222222222222222222222
PinScrewTunnelPinScrewTunnelPinScrewTunnelPinScrewTunnelPinScrewTunnelPinScrewTunnelPinScrewTunnelPinScrewTunnel
1SPDT
2SPST
1SPDT
2SPST
1SPDT
2SPST
1SPDT
2SPST
0.6~6.0 A
2.2~22 A
4.0~40 A
6.0~50 A
Definite
Definite
Definite
Electron Wave and Noise ToleranceCompleted to EMS test.Secured from the magnetic field as using troidal CT.
Various Wiring MethodsPin type : Directly mountable to HiMC series contactorsScrew type : Connectable to other devices with screws and cablesTunnel type : Cables go through 12 mm cable holes
High ReliabilityHiMP series provides superior reliability by the Micro
Controller Unit (MCU)
Applicable to the Inverter Control CircuitHiMP series have high performance under the harmonic
noise, so they can be used for the inverter control circuit
under 20~200 Hz range.
1) 2SPST becomes 1a1b when control power is on. 1SPDT becomes 1c when control power is on.
Economic Type
Pin Type
Screw Type
Tunnel Type
HiMP 22
HiMP 40
HiMP 50
HiMP-D
Type Characteristic Curve
Definite
Inverse
DefiniteInverse
Definite
Inverse
Definite / Inverse
Current Range
0.3~3.0 A0.6~6.0 A2.2~22 A0.3~1.5 A1.0~5.0 A4.4~22 A4.0~40 A8.0~40 A5.0~50 A6.0~50 A10~50 A0.5~6.0 A5.0~60 A
Relay SelectionEcomomic Type Standard Type Deluxe Type
Ratings Overview
Contactor & Overload Relay
13
MV & LV Circuit Breaker, Contactor & Overload Relay
Standard Type
Number of CTs 1)
CharacteristicCurve
Type(Basic)
HiMP 22
HiMP 40
HiMP 50
Current Range AuxiliaryContact 2)Connection
Type Ordering Type
HiMP 22H-PD-03HiMP 22H-SD-03HiMP 22H-TD-03HiMP 22H-PD-22HiMP 22H-SD-22HiMP 22H-TD-22HiMP 22H-PI-01HiMP 22K-PI-01HiMP 22H-SI-01HiMP 22K-SI-01HiMP 22H-TI-01HiMP 22K-TI-01HiMP 22H-PI-05HiMP 22K-PI-05HiMP 22H-SI-05HiMP 22K-SI-05HiMP 22H-TI-05HiMP 22K-TI-05HiMP 22H-PI-22HiMP 22K-PI-22HiMP 22H-SI-22HiMP 22K-SI-22HiMP 22H-TI-22HiMP 22K-TI-22HiMP 22K-PN-01HiMP 22K-SN-01HiMP 22K-TN-01HiMP 22K-PN-05HiMP 22K-SN-05HiMP 22K-TN-05HiMP 22K-PN-22HiMP 22K-SN-22HiMP 22K-TN-22HiMP 40H-PD-40HiMP 40H-SD-40HiMP 40H-TD-40HiMP 40H-PI-40HiMP 40K-PI-40HiMP 40H-SI-40HiMP 40K-SI-40HiMP 40H-TI-40HiMP 40K-TI-40HiMP 40K-PN-40HiMP 40K-SN-40HiMP 40K-TN-40HiMP 50H-PD-50HiMP 50H-SD-50HiMP 50H-TD-50HiMP 50H-PI-50HiMP 50K-PI-50HiMP 50H-SI-50HiMP 50K-SI-50HiMP 50H-TI-50HiMP 50K-TI-50HiMP 50K-PN-50HiMP 50K-SN-50HiMP 50K-TN-50
222222232323232323232323333333333222232323333222232323333
PinScrewTunnelPinScrewTunnel
Pin
Screw
Tunnel
Pin
Screw
Tunnel
Pin
Screw
Tunnel
PinScrewTunnelPinScrewTunnelPinScrewTunnelPinScrewTunnel
Pin
Screw
Tunnel
PinScrewTunnelPinScrewTunnel
Pin
Screw
Tunnel
PinScrewTunnel
2SPST
2SPST
2SPST
2SPST
2SPST
2SPST
2SPST
2SPST
2SPST
2SPST
2SPST
2SPST
2SPST
2SPST
0.3~3.0 A
2.2~22 A
0.3~1.5 A
1.0~5.0 A
4.4~22 A
0.3~1.5 A
1.0~5.0 A
4.4~22 A
4.0~40 A
8.0~40 A
8.0~40 A
5.0~50 A
10~50 A
10~50 A
Definite
Inverse
Inverse(with Reverse
Protection)
Definite
Inverse
Inverse(with Reverse
Protection)
Definite
Inverse
Inverse(with Reverse
Protection)
Pin Type
Screw Type
Tunnel Type
1) For 2CT type, just R and T phase protection is applicable.2) 2SPST becomes 1a1b when control power is on.
M C
Digital Motor Protection Relay
Deluxe Type
RemarksConnection Type Current RangeProtection Ordering TypeBasic Type
Over-currentUnder-currentPhase FailurePhase UnbalanceRestriction
Over-currentUnder-currentPhase FailurePhase UnbalanceRestrictionShort Circuit
Over-currentUnder-currentPhase FailurePhase UnbalanceRestrictionLeakage Current
0.5~6.0 A
5.0~60 A
0.5~6.0 A
5.0~60 A
0.5~6.0 A
5.0~60 A
0.5~6.0 A
5.0~60 A
0.5~6.0 A
5.0~60 A
0.5~6.0 A
5.0~60 A
Screw
Tunnel
Screw
Tunnel
Screw
Tunnel
HiMP-D06S
HiMP-D60S
HiMP-D06T
HiMP-D60T
HiMP-D06SI
HiMP-D60SI
HiMP-D06TI
HiMP-D60TI
HiMP-D06SZ
HiMP-D60SZ
HiMP-D06TZ
HiMP-D60TZ
Tunnel Unit Tunnel Extension
Connecting Cable
Display Bracket
When extension typeis selected connectingcable and displaybraket should beordered separately
High-trust Realization
The micro controller unit of HiMP series provides superiorreliability.
Real time processing and high precision.
Various Protective Features
Basic functionsOver-current / Under-current Stall / Lock Phase Loss / Phase unbalance / Reverse phaseOptional functionsEarth leakage current Short circuit current
Preliminary Alert Function
HiMP series can prevent the sudden over-current tripthrough the preliminary alert function.
HiMP series can be inspected easily due to displaying loadratio by bar-graph during operation.
Operating Time Function
Accumulated motor operation time can be displayed.Certain operating time can be set to alert, so oil exchange
point can be checked conveniently.
Digital Ampere Meter Function
HiMP series are able to check the three phase amperewithout additional ampere meter.
Display the Cause of Fault
Easy maintenance and repair
Selectable Inverse and Definite Curve
Applicable to the Inverter Control Circuit
14
Screw Unit Screw Extension
Contactor & Overload Relay
MV & LV Circuit Breaker, Contactor & Overload RelayV C
Digit
Digit 1
Digit 2
Digit 3
Digit 4
Digit 5
Digit 6
Digit 7
Digit 8?
Digit 12
H C A - - Digit 1 2 3 4 5 6 7 8 12
Description
Rated voltage
Rated current
Energizing type
Frame structure
Operating voltage
Cradle
Fuse
Accessories
Specification3.3 kV6.6 kV200 A400 AContinuously energizedLatchedFixed type without fuse holderFixed type with single fuse holderFixed type with double fuse holderDraw-out type without fuse holderDraw-out with single fuse holderDraw-out type with double fuse holderDC 110 VDC 220 VAC 110 VAC 220 VDC 125 VAC 120 VE : No shutterF : Insulation shutterM : Metal shutter, bushingT : Metal shutter, bushing with earthing switchFixed typeFuse rating
CTDAC 110 VAC 220 V
Electrical interlockFuse melting detectorPosition switch
3.3 kV / 200 VA1set 4.16 kV / 200 VA
Potential 6.6 kV / 200 VAtransformer 3.3 kV / 200 VA
2set 4.16 kV / 200 VA6.6 kV / 200 VA
Code3624CLFAJBDH123456EFMTO-
1)EFLMP123456
HCA Type
Vacuum Contactor
HYUNDAI HCA series high voltage vacuum contactors are designed and manufacturedfor frequent switchings, especially taking into account of safety and quality assurance.They are suitable for switching and controlling 3 phase motors with a squirrel cageand slipring rotor, high voltage load and resistance furnace, and a capacitor andtransformer which is of the dried or moulded type.
Qualified Standard & Approval
Standard IEC 60470NEMA ICS3
Approval ISO 18001, 14001, 9001LRS, ABS, BV, NK, KR
15
General Characteristics
1) Fuse list is available upon request.
Ordering Informations
TypeNumberof Poles
(P)Rated Current
(A)
154154154154154154187187220286286110110110110110143143143105143143143143143143187187220105143143143143143143187
Manual and
MotorCharging
RatedInsulationVoltage (V)
Rated BreakingCapacity (kA)
(500V, With Inst.)
Rated MakingCapacity (kA)
(500V, With Inst.)Charging
Mechanism
63080010001250160020002500320040005000630063080010001250160020002500320063080010001250160020002500320040005000630800100012501600200025003200
AC1000
AC1000
AC1000
AC1000
HiAN06HiAN08HiAN10HiAN12HiAN16HiAN20HiAN25HiAN32HiAN40HiAN50HiAN63HiAS06HiAS08HiAS10HiAS12HiAS16HiAS20HiAS25HiAS32HAT06HAT08HAT10HAT12HAT16HAT20HAT25HAT32HAT40HAT50HAS06HAS08HAS10HAS12HAS16HAS20HAS25HAS32
3, 4
3, 4
2, 3, 4
2, 3, 4
707070707070858510012012050505050506565655065656565656585851005065656565656585
All HYUNDAIs ACB has the function of N phase close before R, S & T and N phase open after R, S & T in accordance with IEC 60947-2.
HAT Type
HAS Type
Designed for industrial and marine application, HYUNDAI ACB is built with innovatedstructure, increased protection, and reliable performance.
Qualified Standard & Approval
Standard IEC 60947-2EN 60947-2AS 3972-2NEMA PUB NO. SG3ANSI C37.13GOST-R 50030.2-99 9GOST-R 50030.1-2000
Approval ISO 18001, 14001, 9001CE (Community European / TU
..V Rheinland)
GOST-RCCCKR, GL, LR, ABS, BV, NK
Air Circuit Breaker
16
A C B
HiAN Type
HiAS Type
APR (ACB Protection Relay) Characteristics for HiAN Type
OCR (Over Current Relay) Characteristics for HAT Type
Application Type Protective Function Indicating Function
General Feeder
Generator
APR-1L-AL
APR-1L-ASAPR-1L-AM
APR-1L-GLAPR-1L-GSAPR-1L-GMAPR-2L-GS
APR-1D-GMAPR-1S-ALAPR-1S-AS
APR-2S-AS
AL
AL
AL
AL
AL
AL
AL
AL
AL
AL
AL
ASASAS
ASASASAS
ASASAS
AS
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AP
AP
AP
AP
AP
AP
AP
AP
AGAGAGAG
AG
MCRMCR
MCRMCRMCR
MCR
MCR
NP
NP
NP
NP
NP
IU
IU
IU
IUt
IUt
CP / I
CP / I
CP / I
CP / I
CP / I
CP / I
LED
LED
LED
LED
LED
LED
LED
LED
AL Adjustable Long Time Delay TripAS Adjustable Short Time Delay TripAI Adjustable Instantaneous TripAP Adjustable Pre-trip AlarmAG Adjustable Ground Fault Trip
MCR Making Current Release Function
NP Neutral Phase Protection Function
IU Integrated Indicating Operation LED & Contact1a contact makes the signal during 40 ms when aprotective function operates.Insulation level from earth is 1500 V.
IUt Integrated Indicating Operation LED & Contact2a contacts make the signal until the RESET buttonis pushed when protective function operates.Insulation level from earth is 1500 V.
CP / I Individual Indicationg Operation Contact 2a contactsmake the signal until the RESET button is pushedwhich protective function operates.Insulation level from earth is 1500 V.
LED Individual Indicating Operation LED.Each LED indicates until the RESET button ispushed which protective function operates.
Application Type Protective Function Indicating Function
General Feeder
Generator
AOR-1L-AL
AOR-1L-ASAOR-1L-GLAOR-1L-GS
AOR-1L-AMAOR-1L-GM
AOR-1L-GM(Digital Display Type)
AOR-1S-ALAOR-1S-AS
AL
AL
AL
AL
AL
AL
AL
AL
AL
AS
ASASAS
ASAS
AS
ASAS
AI
AI
AI
AI
AI
AI
AI
AI
AI
AP
AP
AP
AP
AP
AP
AGAG
AG
AG
MCR
MCRMCRMCR
MCR
IU
IU
IU
IU
IU
IU
CP / I
CP / I
CP / ICP / I
CP / I
CP / I
Protective Function Indicating Function
17
MV & LV Circuit Breaker, Contactor & Overload Relay
HVG TypeHVF Type
Vacuum Circuit Breaker
18
HYUNDAI VCB garners superior reputation with its extended life expectancy, easymaintenance, and excellent performance for industrial facilities, power plants,and marine vessels.
Qualified Standard & Approval
Standard IEC 62271-100, 60056ESB 150ANSI C37KSC 4611
Approval ISO 18001, 14001, 9001KR, GL
TypeRated
Voltage(kV)
AppliedStandard Type
WithstandVoltage (kV)
Power-frequency/ Impulse
RatedBreaking
Current(kA)Rated Current (A)
400 630 1250 2000 2500 3150
50
25
31.5
40
25
31.5
40
40
25
31.5
40
12.5
25
25
8
12.5
20
25
20 / 60
28 / 75
50 / 125
70 / 170
19 / 60
38 / 95
20 / 60
7.2
12
24 / 25.8
36
4.76
36 / 9515
17.5
7.2
ANSIIECIECIEC
IECIECIEC
ANSIIECIEC
IECIECIECIEC
IECIECIEC
IEC
HVF137?
HVF114?
HVF115?
HVF116?
HVF214?
HVF215?
HVF216?
HVF336?
HVF314?
HVF315?
HVF316?
HVF611?
HVF614?
HVF714?
HVG109?
HVG101?HVG113?HVG114?
Type number in the square ?shall be listed as shown in the line for the rated current : 1 600 / 630A 2 1200 / 1250A 4 2000A 6 2500A7 3000 / 3150A 9 400A
HVF Type
HVG Type
IEC 62271-100
V C B
TypeRated
Voltage(kV)
AppliedStandard Type
WithstandVoltage (kV)
Power-frequency/ Impulse
RatedBreaking
Current(kA)Rated Current (A)
400 630 1250 2000 2500 3150
25
31.5
40
25
31.5
40
50
12.5
25
31.5
40
31.5
40
50
25
31.5
40
50
25
31.5
40
50
25
31.5
40
12.5
16
20
25
20
25
50 / 125
20 / 60
28 / 75
50 / 125
80 / 150
19 / 60
20 / 60
28 / 75
36 / 95
20 / 60
7.2
12
24
38
4.76
7.2
12
15
7.2
IEC
IECIECIEC
IECIECIECIEC
IECIECIEC
ANSIANSIANSI
IECIEC
IEC / ESBIEC
IECIECIEC
IECIECIEC
IEC / ANSIIECIECIEC
IEC / ESBIECIEC
HVF104?
HVF105?
HVF106?
HVF204?
HVF205?
HVF206?
HVF207?
HVF601?
HVF604?
HVF605?
HVF606?
HVF705?
HVF706?
HAF107? -3
HAF104? -4
HAF105? -4
HAF116? -3
HAF117? -3
HAF154? -4
HAF175? -4
HAF176? -3
HAF177? -3
HAF234? -4
HAF235? -4
HAF236? -3
HAF611? -4
HAF612? -4
HAF613? -4
HAF614? -4
HVG103?HVG104?
Type number in the square ?shall be listed as shown in the line for the rated current : 1 600 / 630A 2 1200 / 1250A 4 2000A 6 2500A7 3000 / 3150A 9 400A
HAF Type(3AF Type)
HVF Type
HVG Type
IEC 60056
24
(25.8)
HVF Type HAF Type
19
MV & LV Circuit Breaker, Contactor & Overload Relay
HHIS-WC-LE-A39-05, 2007.3 Designed by Design Korea
www.hyundai-elec.com
Head Office 1 Jeonha-dong, Dong-gu, Ulsan, Korea Tel. 82-52-202-8101~8 Fax. 82-52-202-8100
Seoul 140-2, Gye-dong, Jongno-gu, Seoul, Korea(Sales & Marketing) Tel. 82-2-746-7510, 7589 Fax. 82-2-746-7648Orlando 3452 Lake Lynda Drive, Suite 170, Orlando, Florida 32817, U.S.A.
Tel. 1-407-249-7350 Fax.1-407-275-4940
London 2nd Floor, The Triangle, 5-17 Hammersmith Grove London, W6 0LG, UKTel. 44-20-8741-0501 Fax. 44-20-8741-5620
Tokyo 8th Fl., Yurakucho Denki Bldg.1-7-1, Yuraku-cho, Chiyoda-gu, Tokyo 100-0006, JapanTel. 81-3-3212-2076, 3215-7159 Fax. 81-3-3211-2093
Cairo Apartment No. 503, 5th Fl., Bldg. No. 7 Block 2, 9th Division, El-nasr Road, New Maadi, Cairo, EgyptTel. 20-2-520-0148~9 Fax. 20-2-754-7528
Sofia 1271, Sofia 41, Rojen Blvd. BulgariaTel. 359-2-803-3200 Fax. 359-2-803-3203
Yangzhong Lianzhong Avenue, Xinba Scientific and Technologic Zone, Yangzhong City, Jiangsu 212212, ChinaTel. 86-511-842-0666, 0500 Fax. 86-511-842-0668, 0231
Recyled paper used for environmental protection.