Installation Manual
Multi-Split SystemCondensing Unit18,000-54,000 BtuhModels 50/60 Hz
MS-SVN005-EN
TTD/TTT
October 2012
50 Hz ModelsCooling OnlyTTD 518 ABTTD 521 AB
TTD 527 AB
TTD 530 AB
TTD 536 ABTTD 536 DB
TTT 527 ABTTT 530 ABTTT 533 ABTTT 536 ABTTT 536 DBTTT 542AB
60 Hz ModelsCooling OnlyTTD 518 A1TTD 521 A1TTD 524 A1TTD 527 A1TTD 530 A1TTD 536 A1TTD 536 D1
TTT 527 A1TTT 530 A1TTT 533 A1TTT 536 A1TTT 536 D1
TTD 524 AB
TTD 530 DB
TTD 524 DB
TTD 527 DB
TTD 533 ABTTD 533 DB
TTD 542 ABTTD 542 DBTTD 545 ABTTD 548 ABTTD 548 BBTTD 548 DB
TTD 554 ABTTD 554 DB
TTT 542DBTTT 545ABTTT 548ABTTT 548BBTTT 554ABTTT 554DB
TTD 551 AB
2 MS-SVN005-EN
General Information
© American Standard Inc. 2000
General InformationThis Installation Manual is given as aguide to good practice in theinstallation by the installer of TTD/TTTmini-split system. Installationprocedures should be performed inthe sequence that they appear in thismanual.
For installing the unit to operateproperly and reliably, it must beinstalled in accordance with theseinstructions. Also, the services of aqualified service technician should beemployed, through the maintenancecontract with a reputable servicecompany.
Read this Installation Manualcompletely before installing andoperating the system.
About this ManualCautions appear at appropriate placesin this Instruction Manual. Yourpersonal safety and the properoperation of this machine require thatyou follow them carefully.The Trane Company assumes noliability for installations or servicingperformed by unqualified personnel.All phases of the installation of this airconditioning system must conform toall national, provincial, state and localcodes.
About the UnitThese TTD/TTT units are assembled,pressure tested, dehydrated, chargedand run tested before shipment.
ReceptionOn arrival, inspect the unit beforesigning the delivery note. Specify anydamage of the unit on the deliverynote, and send a registered letter ofprotest to the last carrier of the goodswithin 72 hours of delivery. Notify thedealer at the same time.
The unit should be totally inspectedwithin 7 days of delivery. If anyconcealed damage is discovered,send a registered letter of protest tothe carrier within 7 days of deliveryand notify the dealer.
WarningWarnings are provided at appropriateplaces in this manual to indicate toinstallers, operators and servicepersonnel of potentially hazardoussituations which, if not avoided,COULD result in death or seriousinjury.
CautionCautions are provided at appropriateplaces in this manual to indicate toinstallers, operators, and servicepersonnel of potentially hazardoussituations which, if not avoided, MAYresult in minor or moderate injury ormalfunction of the unit.
Your personal safety and the properoperation of this unit require that youfollow them carefully. The TraneCompany assumes no liability forinstallations or servicing performed byunqualified personnel.
WarrantyWarranty is based on the generalterms and conditions by country. Thewarranty is void if the equipment ismodified or repaired without thewritten approval of The TraneCompany, if the operating limits areexceeded or if the control system orthe electrical wiring is modified.
Damage due to inappropriateinstallation, lack of knowledge orfailure to comply with themanufacturer’s instructions, is notcovered by the warranty obligation.If the installation does not conform tothe rules described in InstallationManual, it may entail cancellation ofwarranty and liabilities by The TraneCompany.
ImportantThis document is customer propertyand is to remain with unit. Pleaseplace in service information pack uponcompletion of work.These instructions do not cover allvariations in systems, nor do theyprovide for every possible contingencyto be met in connection withinstallation.Should further information be desiredor should particular problems arisewhich are not covered sufficiently inthis manual, the matter should bereferred to your authorized Tranedealer.
��������������� � ������� �������� ��
MS-SVN005-EN 3
Contents
2
10
11
12
4
5
6
7
8
9
14
18
General Information
Valid System Combinations
Installation Requirements
Location and Preparation of Units
Connection of Refrigerant Tubing
Condensate Drain Piping
System Evacuation and Purging
Electrical Installation
Matching Table
Wiring Diagram
Dimensional Data
Note
��������������� � ������� �������� ��
4 MS-SVN005-EN
Valid System Combinations
��������������� � ������� �������� ��
MS-SVN005-EN 5
Installation Requirements
Table 2
1. Copper TubingCopper tubing, fittings andinsulation to interconnect thesuction (S) (wide tube) and liquid(L) (narrow tube) refrigerant linesbetween the indoor and outdoorunits can be purchased locally.It is necessary to purchase thefollowing items:
- Purchase equal lengths of bothtubes and insulation required.Cut the appropriate tube lengths,30 to 40 cm (12 to 16 in.) longeron each one to deepen vibrationbetween units. Wall thickness ofcopper tube should be 0.8 mm(0.0314 in.).Both tubes must be wellinsulated with proper insulationmaterials.
- The length of wiring willdetermine the wire size. Seelocal codes, refer to section ofelectrical installation.
2. Additional Materials- Saddles or clamps to hold
refrigerant tubing.- Insulated clamps or staples
for connecting wire.See local codes.
- Refrigeration oil and tape(armored).
- Putty or similar filter.
*On Cooling Mode
Indoor Unit 512 518
O.D. O.D. O.D.Item mm (in.) mm (in.) mm (in.)
Deoxidizied Annealed (L *) 6.35 (1/4) 6.35 (1/4) 6.35 (1/4)
Copper Tube (S *) 9.52 (3/8) 12.7 (1/2) 12.7 (1/2)
Foamed Polyethylene Diameter: According Diameter: According Diameter: Accordingto O.D. of copper tube to O.D. of copper tube to O.D. of copper tube
Insulation Thickness: No less than Thickness: No less than Thickness: No less than8 mm (0.3 in) 8 mm (0.3 in) 8 mm (0.3 in)
Insulated Copper Wire Length required to make Length required to make Length required to makeelectrical wiring electrical wiring electrical wiring
507-509
��������������� � ������� �������� ��
6 MS-SVN005-EN
Location and Preparation of Units
1. Choose a place as cool as possible.The place should be well ventilatedand the inlet air should not hotterthan the outside temperature (max45OC or 113OF).
2. Avoid the vicinity of heat sources,exhaust fan, etc.
3. Avoid direct sunlight, provideawnings if necessary.
4. The unit should be set on a levelreinforced concrete pad to avoidthe effect humidity. The minimumheight of the concrete pad shouldbe 100 mm. (4"). Unit shall be fixedsecurely to the concrete pad withbolts (not supplied) to preventabnormal noise and vibration.
5. The concrete pad must bepositioned a minimum of 200 mm.(8") from any well and surroundingshrubbery.
6. Minimum clearance on the inlet airside of the unit must be 250 mm.(10") : 1200 mm. (48") on thedischarge air side of the unit and250 mm. (10") on the tubing sideof the unit (Figure 1).
7. When the unit is mounted on a roof,be sure the roof will carry the unit’sweight. Vibration isolation isrecommended to preventtransmission to the buildingstructure.
NoteThe Multi-Split System (Outdoor) Unitshould be installed as close to theindoor units as possible.
Figure 1
Air Discharge Air Inlet
200 mm (10")1,200 mm (48")
250 mm (10")250 mm (10")
��������������� � ������� �������� ��
MS-SVN005-EN 7
Connection of Refrigerant Tubing
Table 3
Tube Diameter Tightening Torquemm. in. kg - cm lbs - in.
6.35 (1/4) 150 - 200 (130 - 170)
9.52 (3/8) 350 - 400 (300 - 340)
12.70 (1/2) 500 - 550 (430 - 470)
1. The principal concerns inrefrigeration tubing are:
- Uniform oil return to thecompressor.
- Pressure drops and their effect onsystem capacity.
- Tube routing and isolation to avoidline breakage, vibration and soundtransmission. Regarding this, theinterconnecting refrigerant linesshould be simple and shorter asmuch as possible.
2. Flare ConnectionsThe units reported in this manualemploy the flare method tointerconnect refrigerant tubes betweenindoor and outdoor units (Figure 2).- The tube end of all refrigerant tubes
should be flared, the tube shouldbe cut and deburred. Be sure nocopper scraps fall in to the tube.
- Be sure to fit a cap to the open endof the tube to keep it free of dustand moisture.
- Avoid bending the tube. If it isnecessary, bend it gently, with aradius of more than 3 or 4 cm.(1 1/2 in. or 1 5/8 in.)
- Cut approximately 30 to 50 cm.(12 in. to 20 in.) longer thanestimated tubing length.
- Before flaring remember to fitthe nut.
- Ream with tube end downwardto avoid copper scraps insidethe tube.
- Remove the flare caps on thetube end.
- Connect the tubes by aligningthe centers of both flares and turnthe flare nuts by hand 3 or 4 turns(Figure 3).
3. Insulate both lines, liquid (narrowtube) and suction (wide tube), toprevent heat loss and wet floor due todripping of chilled condensation.Apply proper insulation material,minimum thickness should be 8 mm(1/3 in.) (Figure 4).
NoteDo not try to bend the tube afterinstallation.
4. Finish with armoring tape.Also see section of condensate drainpiping.
NoteApply refrigeration oil on flare andunion surfaces before connectingthem. This will reduce refrigerantleakage.
- Check the tubing connections andrefrigerant lines before applyingspecified torque. Fasten flare nutsas recommended below.
Figure 4
Figure 3
Figure 2
Electrical Connection
Service Port
Valve Cap TubeConnection(Flare)
Liquid Line System # 1
Gas Line System # 1
Liquid Line System # 2
Gas Line System # 2
Liquid Line System # 3
Gas Line System # 3
Union Flare nut
Insulation Thickness
Min. 8 mm Min. 8 mm (1/3 in.)
��������������� � ������� �������� ��
8 MS-SVN005-EN
Condensate Drain Piping
Figure 5
Drain
1. The drain hose should comestraight down the wall to a levelwhere runoff will not stain the wall.
2. There should be no traps and avoidputting the end of the hose in water.
3. To avoid damage to the floor orfurniture when the drain hose isplaced in the room, insulate thehose with foamed polyethyleneor equivalent.
4. After completing refrigerant lines,wining and drain connection, bindthe tubing, wining and drain pipe(check if local codes permit it) intoa bundle by using tape at 100 or200 mm (4 in. or 8 in.) intervals.Make sure the drain tube is at thebottom of the bundle (Figure 5).
��������������� � ������� �������� ��
MS-SVN005-EN 9
System Evacuation and Purping
The outdoor unit is factory charged.Unit nameplate charge is the totalrequired system charge with 7.5meters of interconnecting lines. Sincethe outdoor unit will not have to beevacuated unless charge has beencompletely lost, leave the suction andliquid shut-off valves closed.
1. Upon completion of installation,evacuate the refrigerant lines andindoor coil (Figure 6).
2. Evacuate unit until the gauge reads350 microns or evacuate at leastone hour for one system.
3. Close off valve to vacuum pumpand observe the micron gauge. Ifgauge pressure rised above 500microns in one (1) minute, thenevacuation is incompleted orsystem is leaking.
- Attach appropriate hose frommanifold gauge to suction andliquid line valves service ports.
- Attached center hose of mainfoldgauges to vacuum pump.
NoteUnnecessary switching of hoses andcomplete evacuation of all linesleading to sealed system can beaccomplished by placing a “T” inmanifold center hose and connectingbranch hose to cylinder of R-22.
NoteEvacuate unit 2 and 3 in the samemanner explained above.This completes system evacuationwith a vacuum pump and the airconditioner is ready for actualoperation.
Figure 6
Indoor Unit 3
Indoor Unit 2
Indoor Unit 1
System # 3System # 2System # 1
Service Port System #3
Suction Line System #3
Liquid Line System #3
Suction Pressure
Liquid Pressure
Vacuum Pump
Cylinder of R-22
��������������� � ������� �������� ��
10 MS-SVN005-EN
Electrical Installation
Wiring and grounding must complywith national and local codes.
WiringImportant Safeguards:- Check the unit nameplate for
electrical rating. Be sure wiring isaccording to local codes and wiringsystem diagram.
- A power supply disconnect and acircuit breaker for overcurrentprotection should be provided inthe exclusive line.
- Connect all units electrically withground.
- Wiring should not touch refrigeranttubing, compressor or movingparts.
- The manufacturer will have noresponsibility for the problemscaused by unauthorized change inthe internal wiring.
- Connect wiring firmly.- Use recommended wire length
and size.
Note- Each country has their own field
wiring rules and regulations. Besure the installation complies withlocal electrical codes.
- Nameplate ratings on indoor unitsare for “one-to-one” systeminstallations only.
Checking the system before start up
Once the unit is installed, a check ofthe system is recommended beforestarting the units.- Check that field connections are
correctly made.- Check that units are correctly
installed and there is no tool ordebris near or on top of the unit.
- Check the tubing and theconnections for leaks.
- Check that unit has a properground wiring.
- Check for proper voltage and fusesize.
- Check electrical wire size used is asspecified.
- Check all field wiring for tightconnection.
- Make sure that electrical wiresinside the unit do not contact withrefrigerant pipes.
- Start the system and carefullyobserve operation.
��������������� �� ������� �������� ��
MS-SVN005-EN 11
Matching Table
��������������� �� ������� �������� ��
12 MS-SVN005-EN
Wiring Diagram
Models50 Hz
TTD518-542/TTT527-542 CONDENSING UNIT220-240/1/50 Hz, 200-240/1/60 Hz
WIRING DIAGRAM
��������������� �� ������� �������� ��
CF
FC
1. LOW VOLTAGE WIRING TO BE 18 AWG MINIMUM
2. POWER WIRING AND GROUDING OF EQUIPMENT
3. USE COPPER CONDUCTORS ONLY
NOTES
CPR1,2,3
FAN MTR
MS1,2
CR1,2,3
LEGEND
COLOR CODE
MUST COMPLY WITH LOCAL CODES
INDOOR UNIT
APPLIES TO UNIT WITH 3 COMPRESSORS
COMPRESSOR MOTOR CONTACTOR # 1,2,3
COMPRESSOR RUN CAPACITOR # 1,2,3
HI-WALL
1
2
1
2
1
2
RELAY CONTACT NORMALLY OPEN
FACTORY WIRINGFIELD WIRING
IDENTIFIED TERMINAL
TERMINAL BOARD BY OTHERTERMINAL BOARD BY FACTORY
OUTDOOR UNIT
INDOOR UNIT 2
INDOOR UNIT 1
INDOOR UNIT 3
CONCEALED
C1
C2
C1
C2
C1
C2
E
F
B
A
C
D
CONVERTIBLE,
BLACKBROWNGRAYORANGEREDWHITEYELLOW
CAPACITOR
COIL
BLUE
FAN MOTORFAN CONTACTOR
FAN CAPACITORCOMPRESSOR # 1,2,3
JUNCTIONTERMINAL
E MS3 F
220-240V/1ph/50Hz200-240V/1ph/60Hz
GRBRBLK
ORRD
YLWH
D
B
BL
BLK
BLK
BLK
CR3
220-240V/1ph/50Hz200-240V/1ph/60Hz
200-240V/1ph/60Hz220-240V/1ph/50Hz
MS2
BLRD
MS1
CPR2
CPR3
RD
CR2
RD
BLRD
CPR1
BLRDCR1
RD
G
BLK
N
MTRFANRD
BRRDCF
RD RD
C
A
RD
RD
RD
MS2-1
MS3-1
MS1-1
RD
RD
MS1-2RD
MS2-2
MS3-2
RD
L
FROM INDOOR UNIT 3
FROM INDOOR UNIT 2
FROM INDOOR UNIT 1
[
[
[
POWER SUPPLY220-240V/1ph/50Hz
200-240V/1ph/60Hz
TTD518ABTTD521ABTTD524ABTTD524DBTTD527ABTTD527DBTTD530ABTTD530DBTTD533ABTTD533DBTTD536ABTTD536DBTTD542ABTTD542DB
TTT527ABTTT530ABTTT533ABTTT536ABTTT536DBTTT542ABTTT542DB
Models60 Hz
TTD518A1TTD521A1TTD524A1TTD524D1TTD527A1TTD527D1TTD530A1TTD530D1TTD533A1TTD533D1TTD536A1TTD536D1TTD542A1TTD542D1
TTT527A1TTT530A1TTT533A1TTT536A1TTT536D1TTT542A1TTT542D1
TTT521AB TTT521A1
MS-SVN005-EN 13
Wiring Diagram
CF
FC
1. LOW VOLTAGE WIRING TO BE 18 AWG MINIMUM
2. POWER WIRING AND GROUDING OF EQUIPMENT
3. USE COPPER CONDUCTORS ONLY
NOTES
CPR1,2,3
FAN MTR
MS1,2
CR1,2,3
LEGEND
COLOR CODE
WIRING DIAGRAM220-240/1/50 Hz, 200-240/1/60 Hz
TTD545-554/TTT545-554 CONDENSING UNIT
MUST COMPLY WITH LOCAL CODES
INDOOR UNIT
APPLIES TO UNIT WITH 3 COMPRESSORS
COMPRESSOR MOTOR CONTACTOR # 1,2,3
COMPRESSOR RUN CAPACITOR # 1,2,3
HI-WALL
1
2
1
2
1
2
RELAY CONTACT NORMALLY OPEN
FACTORY WIRINGFIELD WIRING
IDENTIFIED TERMINAL
TERMINAL BOARD BY OTHERTERMINAL BOARD BY FACTORY
OUTDOOR UNIT
INDOOR UNIT 2
INDOOR UNIT 1
INDOOR UNIT 3
CONCEALED
C1
C2
C1
C2
C1
C2
E
F
B
A
C
D
CONVERTIBLE,
BLACKBROWNGRAYORANGEREDWHITEYELLOW
CAPACITOR
COIL
BLUE
FAN MOTORFAN CONTACTOR
FAN CAPACITORCOMPRESSOR # 1,2,3
JUNCTIONTERMINAL
E MS3 F
220-240V/1ph/50Hz200-240V/1ph/60Hz
GRBRBLK
ORRD
YLWH
D
B
BL
220-240V/1ph/50Hz200-240V/1ph/60Hz
200-240V/1ph/60Hz220-240V/1ph/50Hz
MS2
MS1
C
A
FROM INDOOR UNIT 3
FROM INDOOR UNIT 2
FROM INDOOR UNIT 1
[
[
[
��������������� �� ������� �������� ��
Models50 Hz
TTD545ABTTD548ABTTD548BBTTD548DBTTD551ABTTD554AB
TTT545ABTTT548ABTTT548DBTTT554ABTTT554DB
Models60 Hz
TTD545A1TTD548A1TTD548B1TTD548D1TTD554A1TTD554D1
TTT545A1TTT548A1TTT548D1TTT554A1TTT554D1
TTD554DB
14 MS-SVN005-EN
Dimensional Data
��������������� �� ������� �������� ��
ModelTTT521
DIMENSIONAL DATA
14.1713.0
14.1714
.17
1.93
13.0
(360
.0)
(330
.0)
(49.
0)0.78 (20.0)
1.93
(49
.0)
SLOTS 10.0 x 25.0(MM.)
(360.0)
(330.0)(360.0)
POWER SUPPLYØ1-3/16 (30.0 MM.)
(82.0)
1.85
(47
)
1.18 (30.0)
42.0 (1068.0)
SYSTEM 1
SYSTEM 2
SYSTEM 3
15.1
1 (3
84.0
0)
3.59
(91
.0)
5.95
(15
1.0)
10.6
7 (2
71.0
)13
.03
(331
.0)
15.3
9 (3
91.0
)
17.8
7 (4
54.0
)31
.3 (
795.
0)
8.30
(21
1.0)
3.22
13.66 (347.00)
42.0 (1068.0)
44.41 (1128.00)
SUCTION
REFRIG. LINE DIA.
MODEL
LIQUID
SYSTEM # 1
LIQUID
REFRIG. LINE DIA. SYSTEM # 2
REFRIG. LINE DIA.
LIQUID SUCTION SUCTION
SYSTEM # 3
1/2 (12)
1/2 (12)TTT536D10E
TTT536A10ETTT536AB0ETTT536A100TTT536AB00
1/4 (6)
1/4 (6)
TTT533A10ETTT533AB0E
TTT527A10E
TTT530AB0ETTT530A10E
TTT527AB0E
1/4 (6)
1/4 (6)
1/4 (6) 3/8 (9)
3/8 (9)
3/8 (9)
1/4 (6)
1/4 (6)
1/2 (12)
3/8 (9)1/4 (6)
1/4 (6) 1/2 (12)
3/8 (9)
1/4 (6)
1/4 (6)
1/4 (6)3/8 (9)
3/8 (9)
1/2 (12)
1/4 (6)
1/4 (6)
1/4 (6)
1/2 (12)
1/2 (12)
3/8 (9)
TTD527AB0ETTD527A10E
1/2 (12)TTD536AB0E
TTD530AB00TTD536A100
TTD536A10E
1/4 (6) -1/2 (12)1/4 (6) -
1/2 (12)TTD536AB0E
TTD536AB00TTD536A100
TTD536A10E
1/4 (6) -1/2 (12)1/4 (6) -
5/8 (16)TTD536D10ETTD536D100
3/8 (9) -1/2 (12)1/4 (6) -
1/2 (12)1/4 (6) 1/2 (12)1/4 (6) - -
TTD536D100TTD536D10E
TTT536D10E
2) DIMENSIONS : INCHES (MILIMETERS) 1 IN. = 25.40 MM.NOTE
3) THE ABOVE MODELS UTILIZE ROTARY COMPRESSORS.MAR 8,04 REV : C
OUTDOOR UNIT
LIQUID VALVESUCTION VALVE
AIR FLOW DIRECTION
MOUNTING DETAIL
OUTLINE DRAWING
TM
1) SUCTION AND LIQUID VALVES ARE FLARE TYPE CONNECTIONS
MS-SVN005-EN 15
Dimensional Data
��������������� �� ������� �������� ��
ModelTTD527TTD530TTD533TTD536TTD539TTD542
TTT527TTT530TTT533TTT536TTT539TTT542
16 MS-SVN005-EN
Dimensional Data
��������������� �� ������� �������� ��
ModelTTD518TTD521TTD524
MS-SVN005-EN 17
��������������� �� ������� �������� ��
Dimensional Data
ModelTTD545TTD548TTD551TTD554
TTT545TTT548TTT554
18 MS-SVN005-EN
Note
��������������� �� ������� �������� ��
MS-SVN005-EN 19
Note
��������������� �� ������� �������� ��
��������������� �� ������� �������� ��
Oct 2007
Oct 2012