15
SUB-CHAPTER: I.4 SECTION : I.4.2 PAGE : 1 / 15 UK-EPR FUNDAMENTAL SAFETY OVERVIEW VOLUME 2: DESIGN AND SAFETY CHAPTER I: AUXILIARY SYSTEMS 2. VENTILATION SYSTEMS FOR THE NUCLEAR AUXILIARY BUILDING AND THE FUEL BUILDING 2.1. ROLE OF THE SYSTEMS 2.1.1. Functional role of the systems The DWN ventilation system for the Nuclear Auxiliary Building (BAN) and its extension, the DWK ventilation system for the Fuel Building (BK) at operate continuously. They are designed for the following purposes: to keep the ambient conditions within limits prescribed for correct operation of equipment and/or staff in normal operation (air supply and filtering, heating/refrigeration/humidity) to ensure during normal operation that contamination is contained at source to avoid it spreading from potentially contaminated areas to potentially less contaminated areas. to limit the concentration of aerosols and radioactive gases in the atmosphere. to keep a negative pressure in the BAN [Nuclear Auxiliary Building] and the BK [Fuel Building] compared to the outside pressure. Furthermore, the DWN system is designed for the following: to ensure the conditioning, extraction and filtering of air supplied and taken in by DWK to ensure the operational extraction and filtering of the air taken in by DWL (see Chapter I.4.6) to ensure during plant outage, the conditioning, extraction and filtering of the air from the purging ventilation system of the containment: high-capacity EBA [CSVS] (see Chapter I.4.5) during the operation of the plant, to ensure the conditioning and discharge to the stack of the air from the blowdown ventilation system of the containment: low-capacity EBA [CSVS] (see Chapter I.4.5) to limit the radioactivity of the air discharged to the stack during normal operation to isolate the air intake and the extraction from the BAN [Nuclear Auxiliary Building] in the event of an earthquake. In addition, the DWK system prevents condensation on the walls of the rooms that are in contact with the outside and more specifically on the walls of the fuel handling hall.

FUNDAMENTAL SAFETY OVERVIEW SECTION : I.4.2 UK-EPR VOLUME 2

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: FUNDAMENTAL SAFETY OVERVIEW SECTION : I.4.2 UK-EPR VOLUME 2

SUB-CHAPTER: I.4 SECTION : I.4.2

PAGE : 1 / 15 UK-EPR

FUNDAMENTAL SAFETY OVERVIEW VOLUME 2: DESIGN AND SAFETY

CHAPTER I: AUXILIARY SYSTEMS

2. VENTILATION SYSTEMS FOR THE NUCLEAR AUXILIARY BUILDING AND THE FUEL BUILDING

2.1. ROLE OF THE SYSTEMS

2.1.1. Functional role of the systems

The DWN ventilation system for the Nuclear Auxiliary Building (BAN) and its extension, the DWK ventilation system for the Fuel Building (BK) at operate continuously. They are designed for the following purposes:

− to keep the ambient conditions within limits prescribed for correct operation of equipment and/or staff in normal operation (air supply and filtering, heating/refrigeration/humidity)

− to ensure during normal operation that contamination is contained at source to avoid it spreading from potentially contaminated areas to potentially less contaminated areas.

− to limit the concentration of aerosols and radioactive gases in the atmosphere.

− to keep a negative pressure in the BAN [Nuclear Auxiliary Building] and the BK [Fuel Building] compared to the outside pressure.

Furthermore, the DWN system is designed for the following:

− to ensure the conditioning, extraction and filtering of air supplied and taken in by DWK

− to ensure the operational extraction and filtering of the air taken in by DWL (see Chapter I.4.6)

− to ensure during plant outage, the conditioning, extraction and filtering of the air from the purging ventilation system of the containment: high-capacity EBA [CSVS] (see Chapter I.4.5)

− during the operation of the plant, to ensure the conditioning and discharge

to the stack of the air from the blowdown ventilation system of the containment: low-capacity EBA [CSVS] (see Chapter I.4.5)

− to limit the radioactivity of the air discharged to the stack during normal operation

− to isolate the air intake and the extraction from the BAN [Nuclear Auxiliary Building] in the event of an earthquake.

In addition, the DWK system prevents condensation on the walls of the rooms that are in contact with the outside and more specifically on the walls of the fuel handling hall.

Page 2: FUNDAMENTAL SAFETY OVERVIEW SECTION : I.4.2 UK-EPR VOLUME 2

SUB-CHAPTER: I.4 SECTION : I.4.2

PAGE : 2 / 15 UK-EPR

FUNDAMENTAL SAFETY OVERVIEW VOLUME 2: DESIGN AND SAFETY

CHAPTER I: AUXILIARY SYSTEMS

2.1.2. Safety role of the systems

The general safety requirements are given in Chapter I.4.0 and the specific requirements are given below:

The safety roles of the DWN system are as follows:

− to isolate the air inlet and extraction to and from the BAN [Nuclear Auxiliary Building] in the event of an earthquake.

− to extract the air (HEPA and iodine filtration included)

The safety roles of the DWK system are as follows:

− to automatically isolate the pool hall air supply and extraction system in the event of a fuel handling accident in this hall (PCC-4)

− to automatically isolate the pool bay air supply and extraction system adjacent to the equipment hatch in the event of a fuel handling accident in the Reactor Building (PCC-4)

− to automatically isolate of the air supply and extraction system adjacent to the emergency airlock in the event of a fuel handling accident in the Reactor Building (PCC-4)

− to automatically isolate the pool hall air supply and extraction system in the event of failure of the two main line of the fuel pool cooling system (RRC-A)

N.B.: In the first case, containment is achieved by the DWL extraction system; for fuel handling accidents in the Reactor Building, containment is achieved by the low-capacity EBA [CSVS] system. In the last case, the containment is static.

2.2. DESIGN BASES

Air-supply conditions

The air-supply characteristics of the DWN system in design conditions are as follows:

− Summer: 20°C

− Winter : 22°C

The design conditions (temperature and humidity) are defined in Chapter I.4.1.

Auxiliary fluids

During the summer, the blown air is cooled by cooling coils supplied by the DER chilled water system (see Chapter I.4.11)

During the winter, the blown air is heated by heating coils supplied by the SEL electrically-produced hot water system (see Chapter I.4.16).

Page 3: FUNDAMENTAL SAFETY OVERVIEW SECTION : I.4.2 UK-EPR VOLUME 2

SUB-CHAPTER: I.4 SECTION : I.4.2

PAGE : 3 / 15 UK-EPR

FUNDAMENTAL SAFETY OVERVIEW VOLUME 2: DESIGN AND SAFETY

CHAPTER I: AUXILIARY SYSTEMS

Conditions in rooms:

Air flows in the rooms are calculated taking account of both the minimum air renewal rate and the use of equipment and lighting.

Temperatures to be maintained in the rooms are given in I.4.1 TAB 1.

The minimum temperatures are only guaranteed when the ventilation system is operating normally.

Minimum air renewal rates:

Air renewal rates are given in Chapter I.4.1.

2.3. DESCRIPTION, CHARACTERISTICS OF EQUIPMENT

A diagram of all ventilation systems in the BAN [Nuclear Auxiliary Building], BK [Fuel Building], BAS [safeguard building] and BR [Reactor Building] buildings is provided in I.4.2 FIG 1.

The flow rates are given for information only and remain to be validated by detailed studies.

DWN (See I.4.2 FIG 2 to I.4.2 FIG 4 ):

The DWN comprises an air supply plant, an extraction plant with permanent filtering on HEPA filter, an iodine extraction plant, an air supply duct network, an extraction duct network and a vent stack.

The air supply plant includes the following:

− an external air inlet on the wall of the Nuclear Auxiliary Building with a protective grid and a rain barrier

− a concrete air intake plenum

− three trains of 33% capacity mounted in parallel, each equipped with the following:

. an automatic isolation damper

. a pre-heating coil supplied by the hot water system (SEL)

. a 2-stage filtering system

. a cooling coil supplied with chilled water (DER)

. a heating coil supplied by the hot water system (SEL)

− a concrete plenum, fitted with humidifiers

− four redundant 50%-capacity fans installed in parallel

The extraction network comprises seven independent sub-networks

Page 4: FUNDAMENTAL SAFETY OVERVIEW SECTION : I.4.2 UK-EPR VOLUME 2

SUB-CHAPTER: I.4 SECTION : I.4.2

PAGE : 4 / 15 UK-EPR

FUNDAMENTAL SAFETY OVERVIEW VOLUME 2: DESIGN AND SAFETY

CHAPTER I: AUXILIARY SYSTEMS

− One for each of the six cells of the BAN [Nuclear Auxiliary Building], BK [Fuel Building] and BAS [safeguard building]: cells no.1, 2 and 3 for the BAN [Nuclear Auxiliary Building], cells no. 4 and 5 for the BK [Fuel Building] and cell no. 6 for the mechanical parts of the four BAS [safeguard buildings]

− One for the High-capacity EBA [CSVS] in the BR [Reactor Building]

The continuous extraction plant equipped with THE [HEPA] filters includes the following components:

− seven metal chambers mounted in parallel, each including a pre-filter and a HEPA filter

− a concrete plenum

− four redundant fans installed in parallel, each providing 50% capacity

− a shared concrete duct to the vent stack

The iodine filter includes the following elements:

− a concrete plenum

− trains mounted in parallel, each equipped with the following:

. an automatic closing damper

. an electric heater

. an iodine trap

− a concrete plenum

− four redundant “booster” fans mounted in parallel each providing 50% capacity or 33% if high-capacity EBA [CSVS] is operating

The vent stack is installed on the reinforced structure of the Reactor Building, at the connection between the Fuel Building and the BAN [Nuclear Auxiliary Building]. Other ventilation systems are directly connected to the stack. These are the low-capacity EBA [CSVS], the DWL, the DWB, the DWW, the DWQ and the EDE [AVS].

DWK (see I.4.2 FIG 5):

The DWK comprises an air supply duct network and an extraction duct network.

The air supply duct network is connected to the DWN main air-supply duct.

The extraction duct network comprises two separate networks that correspond to cells no. 4 and 5. These two networks are connected to the DWN extraction plant upstream of the filtering chambers.

Characteristics shared by the DWN and the DWK:

Electrical convection heaters are installed in “boron” rooms; fan coil heaters are used to heat large volume rooms.

Page 5: FUNDAMENTAL SAFETY OVERVIEW SECTION : I.4.2 UK-EPR VOLUME 2

SUB-CHAPTER: I.4 SECTION : I.4.2

PAGE : 5 / 15 UK-EPR

FUNDAMENTAL SAFETY OVERVIEW VOLUME 2: DESIGN AND SAFETY

CHAPTER I: AUXILIARY SYSTEMS

The fume chambers and the sampling glove boxes are filtered by specific REN [NSS] iodine filters (see Chapter I.3.1). The specific REN [NSS] extraction fans are connected to the DWN (or the DWK) extraction ducts.

The thermal flow rates and heat exchange rates will be confirmed by detailed studies.

2.4. OPERATING CONDITIONS

2.4.1. Normal operation of the plant

The systems are used when the plant is in operation or shutdown.

Plant operation

The DWN system operates permanently.

The air supply rate is a constant 79,000 m³/hr, distributed as follows:

− 47,500 m3/hr to the BAN [Nuclear Auxiliary Building]

− 31,500 m3/hr to the BK [Fuel Building]

When the air supply of the small-capacity EBA [CSVS] of the BR [Reactor Building] is open (5,000 m³/hr), this air supply rate goes to 84,000 m3/hr. The extraction rate is 120,000 m³/hr, distributed as follows:

− 60,000 m3/hr from the BAN [Nuclear Auxiliary Building]

− 40,000 m3/hr from the BK [Fuel Building]

− 20,000 m3/hr from the entire controlled zone of the four BAS [safeguard building]

The DWN fan flow rate is adjusted by speed modulation.

Plant outage

During outage of the plant, the air-supply and extraction plants provide the ventilation described above simultaneously and 30,000 m3/hr purging in the Reactor Building (provided by high-capacity EBA [CSVS] + low-capacity EBA [CSVS]).

The air-supply rate is then 109,000 m3/hr and the extraction rate is 145,000 m3/hr.

When the equipment hatch and the two airlocks are open, dampers located at the level of the air extraction from the emergency airlock and the personal airlock are closed and extraction is performed by the BR [Reactor Building] ventilation system.

The DWN fan flow rate is adjusted by speed modulation.

Presence of iodine in the rooms in the BAN [Nuclear Auxiliary Building], the BK [Fuel Building] or the BAS [safeguard building] in normal operation.

In this situation, the cells affected (a maximum of three) are processed by iodine filtering.

Page 6: FUNDAMENTAL SAFETY OVERVIEW SECTION : I.4.2 UK-EPR VOLUME 2

SUB-CHAPTER: I.4 SECTION : I.4.2

PAGE : 6 / 15 UK-EPR

FUNDAMENTAL SAFETY OVERVIEW VOLUME 2: DESIGN AND SAFETY

CHAPTER I: AUXILIARY SYSTEMS

This state may be preceded by a transient start-up of iodine filtering (see Chapter D.3), the main consequence of which is to cause filtering at half-flow in all rooms (six cells) (only one of the main extraction and air supply fans remains in operation).

The unaffected cells are then directed to normal extraction.

The DWN fan flow rate is adjusted by speed modulation.

2.4.2. Accident conditions

Fuel handling accident in the BK [Fuel Building]

In this case, the air supply in the zone to be contained is isolated by closing the sealing dampers. The extraction via the DWK is isolated and directed to the DWL system equipped with a HEPA and iodine filter which extracts only from the zones subject to potential leaks.

Fuel handling accident in the BR [Reactor Building]

The air supply and the extraction used during plant outages (EBA [CSVS] high capacity system), and the EBA [CSVS] low capacity system air supply, are closed. The air supply and extraction (DWK) for the equipment area of the BK [Fuel Building] in front of the equipment hatch, are automatically closed.

The air supply in the areas facing the emergency airlock and the personal airlock are automatically closed.

Containment is ensured by the EBA [CSVS] low-capacity system equipped with a HEPA filter and iodine filter.

Use of the RIS [SIS] in the BAS [safeguard building] in the event of LOCA.

In this case, RIS [SIS] leaks may lead to an iodine activity level that is incompatible with discharge through the iodine filters in the DWN system. Discharge is thus preventively performed using the DWL system filters.

The DVL normal air supply (see Chapter I.4.7) and extraction (DWN) to/from the mechanical BAS [safeguard building] controlled areas are automatically closed.

2.4.3. Transient states of the systems

Transient start-up of iodine filtration

In the event of iodine being released in the rooms of the BAN [Nuclear Auxiliary Building], the BK [Fuel Building] or the controlled areas of the BAS [safeguard building], and if the affected cell is not identified, the extraction from the six cells is diverted automatically to iodine filtering, by start-up of two iodine extraction fans at full capacity, and shutdown of one of the two operating extraction, air-supply fans.

In this configuration, the extraction from all rooms is processed with iodine filtering. The air supply and extraction is operated at half capacity.

Page 7: FUNDAMENTAL SAFETY OVERVIEW SECTION : I.4.2 UK-EPR VOLUME 2

SUB-CHAPTER: I.4 SECTION : I.4.2

PAGE : 7 / 15 UK-EPR

FUNDAMENTAL SAFETY OVERVIEW VOLUME 2: DESIGN AND SAFETY

CHAPTER I: AUXILIARY SYSTEMS

2.4.4. Other operating conditions of the systems

Loss of the hot water system (SEL)

When a signal is generated indicating that the air temperature is too low after the pre-heating coils, the fans are automatically stopped and the dampers at the air inlet are automatically closed to prevent freezing of equipment.

Failure of the two main fuel pool cooling trains (BK [Fuel Building])

The DWK isolating dampers in the fuel handling hall are closed.

Fire in an iodine filter

When a fire is detected, the operator is informed, the dampers located upstream and downstream of the iodine filter (which are flame arresters and designed to prevent smoke from spreading) are closed and the fan is automatically stopped.

2.5. PRELIMINARY SAFETY ANALYSIS

2.5.1. Compliance with regulations

To follow.

2.5.2. Compliance with functional criteria

DWN and DWK contribute to limiting radioactive releases.

The air extracted is filtered by HEPA filters and iodine traps (in the event of iodine detection) before being discharged to the stack, in compliance with Chapter I.4.0.2.

2.5.3. Compliance with design requirements

2.5.3.1. Safety classification

Compliance of design and production of materials and equipment with requirements of the classification rules are detailed in Chapter C.2.2.

2.5.3.2. Redundancy

The DWN and DWK systems are not required to meet the single failure criterion.

Only the dampers of the F1A-classified DWK system meet the SFC and therefore have redundancy.

2.5.3.3. Qualification

Equipment is qualified in accordance with the requirements described in Chapter C.7.

Page 8: FUNDAMENTAL SAFETY OVERVIEW SECTION : I.4.2 UK-EPR VOLUME 2

SUB-CHAPTER: I.4 SECTION : I.4.2

PAGE : 8 / 15 UK-EPR

FUNDAMENTAL SAFETY OVERVIEW VOLUME 2: DESIGN AND SAFETY

CHAPTER I: AUXILIARY SYSTEMS

Station blackout

Loss of grid supply (LOOP)

2.5.3.5. Emergency electrical supplies

The fallback position required for each actuator in the event of loss of instrumentation and control will be examined at a later date.

In general, the instrumentation and control processing is installed in the same electrical division as the controlled actuators.

2.5.3.4. Instrumentation and control

The DWN system is not backed up, except for the heating in the Boron B1 rooms (7000 ppm borated water safety system).

The fans are shut down.

For the DWK system: Maintenance must be performed when fuel handling is not taking place.

The isolation dampers used in the event of a fuel handling accident in the BK [Fuel Building] or in the BR [Reactor Building] are supplied from the uninterruptible supplies and are automatically closed in the event of LOOP. A static containment is ensured.

Systems are not backed up in the event of station blackout.

2.5.3.6. Hazards

See I.4.2 TAB 1 and I.4.2 TAB 2

2.6. TESTS, INSPECTIONS AND MAINTENANCE

2.6.1. Tests

The safety functions are subject to periodic tests.

2.6.2. Inspections and maintenance

For the DWN system: Maintenance should preferably be carried out during power operation since the DWN is more challenged during shutdown states. (EBA [CSVS] operation).

See I.4.2 FIG 1 to FIG 5

2.7. FLOW DIAGRAMS

Page 9: FUNDAMENTAL SAFETY OVERVIEW SECTION : I.4.2 UK-EPR VOLUME 2

SUB-CHAPTER: I.4

SECTION : I.4.2 FUNDAMENTAL SAFETY OVERVIEW

UK-EPR VOLUME 2: DESIGN AND SAFETY CHAPTER I: AUXILIARY SYSTEMS

TABLE : 1 PAGE : 9 / 15

I.4.2 TAB 1: SUMMARY TABLE FOR THE PROTECTION OF THE DWN SYSTEM AGAINST HAZARDS

Internal hazards Protection required in principle

General protection Specific protection introduced in the design of the system

Rupture of piping - - Failures of tanks, pumps and valves

- -

Internal missiles - - Dropped Loads - - Internal explosion - - Fire - Fire dampers around the iodine traps (to limit

the spread of the fire) Internal flooding

No

- -

External hazards Protection required in principle

General protection Specific protection introduced in the design of the system

Earthquake No, except for dampers on the air inlets

- SC1 for dampers on the air inlets

Aircraft crash no - - External explosion no - - External flooding no - - Snow and wind no - - Extreme cold no - Heating for protection of systems of the BAN

[Nuclear Auxiliary Building] Electromagnetic interference

no - -

Page 10: FUNDAMENTAL SAFETY OVERVIEW SECTION : I.4.2 UK-EPR VOLUME 2

SUB-CHAPTER: SECTION : I.4.2 FUNDAMENTAL SAFETY OVERVIEW I.4 UK-EPR VOLUME 2: DESIGN AND SAFETY

CHAPTER I: AUXILIARY SYSTEMS TABLE : 2 PAGE :10 / 15

I.4.2 TAB 2: SUMMARY TABLE FOR THE PROTECTION OF THE DWK SYSTEM AGAINST HAZARDS

Internal hazards Protection required in principle

General protection Specific protection introduced in the design of the system

Rupture of piping Physical separation of redundant equipment - Failures of tanks, pumps and valves

Physical separation of redundant equipment -

Internal missiles Physical separation of redundant equipment - Dropped Loads Physical separation of redundant equipment - Internal explosion Physical separation of redundant equipment - Fire Fire sectorisation in the BK [Fuel Building] - Internal flooding

No loss of more than one trainof the isolation dampers

Physical separation of redundant equipment -

External hazards Protection required in principle

General protection Specific protection introduced in the design of the system

Earthquake Installation in the BK [Fuel Building] SC1 for the classified parts Aircraft crash Installation in the BK [Fuel Building] -

External explosion Installation in the BK [Fuel Building] No (no air inlet) External flooding Installation in the BK [Fuel Building] - Snow and wind Installation in the BK [Fuel Building] - Extreme cold Installation in the BK [Fuel Building] Heating for protection of systems of the BK

[Fuel Building] Electromagnetic interference

No loss of more than one train of the isolation dampers

Installation in the BK [Fuel Building] -

Page 11: FUNDAMENTAL SAFETY OVERVIEW SECTION : I.4.2 UK-EPR VOLUME 2

SUB-CHAPTER: I.4

SECTION : I.4.2 FUNDAMENTAL SAFETY OVERVIEW

UK-EPR VOLUME 2: DESIGN AND SAFETY CHAPTER I: AUXILIARY SYSTEMS

FIGURE : 1 PAGE :11 / 15

I.4.2 F1 GENERAL ARRANGEMENT

DW

N f iltr at io n ab so lu e/

DW

N he pa fi ltr ati on

FPFPFPFPFPFPFA FA FA FA FA FA

4x50%DWN filtration iode/DWN iodine filtration

3400

2x10

0%

3400

3400 DWL

5000

5000

DVL

Div 1

EBA Low Capacity Circuit/EBA Petit débit

EBA High Capacity Circuit/EBA Grand débit50

00

2500

0

BR/RB

4x50

%3x

33%

FP FP FP

BK/FB

CELL4CELL5

DWN air neuf/DWN air supply

21

CELL6

BAS1/ SAB1

PI

PI

PI

FA FA

FP FPPIPI

BAN/NAB

CELL1

CELL2

CELL3

3

5

4EVF

PI

FPFA

2500

0

4x50%

7

6

EBA Low Capacity Circuit/ EBA Petit débit

EBA H

igh Capacity C

ircuit/EBA

grand débit

E BA

Low

Cap

aci t y

Circ

uit /

EBA

Pet it

déb

it

DVL

Div 2

DVL

Div 3

DVL

Div 4

BAS2/ SAB2

BAS3/ SAB3

BAS4/ SAB4

BAS2/ SAB2

DWK

DWNDWN

1 Hall manutention combustible (appartient à cell 5) / Fuel handling hall (which is part of cell 5)

2 Hall manutention et stockage materiel (appartient à cell 4) / Hall in front of equipement hatch (which is part of cell 4)

3 Zone de travail et de désassemblage (appartient à cell 3) / Disassembly & hot workshop zone (which is part of cell 3)

4 Zone accessible tranche en puissance / Service compartments, accessible during plant operation

Zone circuit primaire inaccessible tranche en puissance / Primary circuit compartments, inaccessible during plant operation

5

6 Sas secours / Emergency Airlock

7 Sas personnel / Personal Airlock

SCHEMA D' ENSEMBLE / GENERAL ARRANGEMENT DRAWING FIG 1

2x100%

FAFP

PI

FAFP

PI

Page 12: FUNDAMENTAL SAFETY OVERVIEW SECTION : I.4.2 UK-EPR VOLUME 2

SUB-CHAPTER: I.4

SECTION : I.4.2 FUNDAMENTAL SAFETY OVERVIEW

UK-EPR VOLUME 2: DESIGN AND SAFETY CHAPTER I: AUXILIARY SYSTEMS

FIGURE : 2 PAGE :12 / 15

I.4.2 FIG 2: DWN Functional Flow Diagram

Page 13: FUNDAMENTAL SAFETY OVERVIEW SECTION : I.4.2 UK-EPR VOLUME 2

SUB-CHAPTER: I.4

SECTION : I.4.2 FUNDAMENTAL SAFETY OVERVIEW

UK-EPR VOLUME 2: DESIGN AND SAFETY CHAPTER I: AUXILIARY SYSTEMS

FIGURE : 3 PAGE :13 / 15

I.4.2 FIG 3: DWN Functional Flow Diagram

Page 14: FUNDAMENTAL SAFETY OVERVIEW SECTION : I.4.2 UK-EPR VOLUME 2

SUB-CHAPTER: I.4

SECTION : I.4.2 FUNDAMENTAL SAFETY OVERVIEW

UK-EPR VOLUME 2: DESIGN AND SAFETY CHAPTER I: AUXILIARY SYSTEMS

FIGURE : 4 PAGE :14 / 15

I.4.2 FIG 4: DWN Functional Flow Diagram

Page 15: FUNDAMENTAL SAFETY OVERVIEW SECTION : I.4.2 UK-EPR VOLUME 2

SUB-CHAPTER: I.4

SECTION : I.4.2 FUNDAMENTAL SAFETY OVERVIEW

UK-EPR VOLUME 2: DESIGN AND SAFETY CHAPTER I: AUXILIARY SYSTEMS

FIGURE : 5 PAGE :15 / 15

I.4.2 FIG 5: DWK Functional Flow Diagram