53

Kukdong LSHF - NEK 606 2004

Marketing Office Tel:82-2-2140-3055 Fax:82-2-2140-3098Head Office Tel:82-43-530-2000 Fax:82-43-530-2144 Pusan Office Tel:82-51-817-0295 Fax:82-51-817-0297

Hig

h V

olta

ge F

lam

e Re

tard

ant C

able

Hig

h V

olta

ge F

lam

e&

Fir

e Re

sist

ant C

able

Low

Vol

tage

Flam

e Re

tard

ant

Cable

Low

Vol

tage

Fla

me

& F

ire

Resi

stan

t Cab

leTe

chni

cal i

nfor

mat

ion

ApplicationPower circuit below 1kV, Lighting circuits, Trace heating circuits.Fixed installation power, control & lighting in both explosion risk and safe areas, generalpurposes.Maximum operating conductor temperature 90

Standard AppliedDesign guideline : IEC 60092-353Material properties : IEC 60092-351 (Insulation, HF-EPR)

IEC 60092-359 (Sheath, SHF2)Flame retardant : IEC 60332-3-22, Cate. ‘A’Halogen free properties : IEC 60754-1Low smoke properties : IEC 61034-1/2Cold properties(option) : CSA C22.2 No. 03Sunlight resistance(option) : UL 1581Mud resistance(option) : NEK 606 (2004)

0.6/1kV SINGLE CORE, ARMORED POWER CABLE (CODE : 0.6/1kV RFOU[P1], RFOU[P1/P8])

Conductor

Nominal Min. Max.sectional No. of overall area wires dia.

mm2 EA mm

No.of core

EA

1

1.0 7 1.4

1.5 7 1.7

2.5 7 2.2

4 7 2.7

6 7 3.3

10 7 4.2

16 7 5.3

25 7 6.6

35 7 7.9

50 19 9.1

70 19 11.0

95 19 12.9

120 37 14.5

150 37 16.2

185 37 18.0

240 61 20.6

300 61 23.1

Cableweightapprox

kg/km

120

135

150

180

205

270

350

535

655

825

1080

1410

1685

2020

2455

3155

3865

Conductorresistance(20 )

/km

18.2

12.2

7.56

4.70

3.11

1.84

1.16

0.734

0.529

0.391

0.270

0.195

0.154

0.126

0.1000

0.0762

0.0607

Cableratingat 45

Amp.

18

23

30

40

52

72

96

127

157

196

242

293

339

389

444

522

601

Nominaloveralldia.

mm

8.4 0.4

8.9 0.4

9.3 0.4

9.9 0.4

10.4 0.4

11.6 0.5

12.6 0.5

15.1 0.6

16.3 0.7

18.2 0.7

20.3 0.8

22.8 0.9

24.4 1.0

26.6 1.1

29.0 1.2

32.7 1.3

35.9 1.4

Thicknessof outersheath

mm

1.0

1.1

1.1

1.1

1.1

1.2

1.2

1.3

1.3

1.4

1.5

1.6

1.6

1.7

1.8

1.9

2.1

Nominaldia. overbraid

mm

6.2

6.5

6.9

7.5

8.0

9.0

10.0

12.3

13.5

15.2

17.1

19.4

21.0

23.0

25.2

28.7

31.5

Dia. ofmetal wire forbraid

mm

0.2

0.2

0.2

0.2

0.2

0.2

0.2

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

Nominaldia. over innercovering

mm

5.1

5.4

5.8

6.4

6.9

7.9

8.9

10.7

11.9

13.6

15.5

17.8

19.4

21.4

23.6

27.1

29.9

Thickness of inner covering

mm

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.2

1.2

Thickness of insulation

mm

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.2

1.2

1.4

1.4

1.6

1.6

1.8

2.0

2.2

2.4

Construction

Conductor : Circular tinned stranded copper as per IEC60228 & 60228A, Class 2Insulation : Halogen Free Ethylene Propylene Rubber (HF-EPR)as per IEC 60092-351Inner covering : Halogen-free thermosetting compoundAmour : Copper wires braid as per IEC 60092-353Outer sheath : Flame retardant, oil, abrasion, chemical andsunlight resistant.- Code-P1 : Halogen-free thermosetting compound as per IEC60092-359, SHF2

- Code-P1/P8 : Halogen-free & Mud resistance thermosettingcompound as per IEC 60092-359, SHF Mud

Identification of color

Insulation1 : Grey

Outer sheath : BlackNote) Any other colors purchaser required

IEC 60332-3-22 : Flame retardant, Cate ‘A’IEC 60754-1 : Halogen free, 0.5%IEC 61034-1/2 : Smoke densityCSA C22.2 No.03 : Cold bend, 40

Cold impact, 35UL 1581 : Sunlight resistanceNEK 606 : Mud resistance

Page 5: Att-4 Lv Cable Epr Epr Gswb Shf-2

Marketing Office Tel:82-2-2140-3055 Fax:82-2-2140-3098Head Office Tel:82-43-530-2000 Fax:82-43-530-2144 Pusan Office Tel:82-51-817-0295 Fax:82-51-817-029754

Kukdong LSHF - NEK 606 2004

ApplicationPower circuit below 1kV, Lighting circuits, Trace heating circuits.Fixed installation power, control & lighting in both explosion risk and safe areas, generalpurposes.Maximum operating conductor temperature 90

Standard AppliedDesign guideline : IEC 60092-353Material properties : IEC 60092-351 (Insulation, HF-EPR)

IEC 60092-359 (Sheath, SHF2)Flame retardant : IEC 60332-3-22, Cate. ‘A’Halogen free properties : IEC 60754-1Low smoke properties : IEC 61034-1/2Cold properties(option) : CSA C22.2 No. 03Sunlight resistance(option) : UL 1581Mud resistance(option) : NEK 606 (2004)

0.6/1kV DOUBLE CORE, ARMORED POWER CABLE (CODE : 0.6/1kV RFOU[P1], RFOU[P1/P8])

Conductor

Nominal Min. Max.sectional No. of overall area wires dia.

mm2 EA mm

No.of core

EA

2

1.0 7 1.4

1.5 7 1.7

2.5 7 2.2

4 7 2.7

6 7 3.3

10 7 4.2

16 7 5.3

25 7 6.6

35 7 7.9

50 19 9.1

70 19 11.0

95 19 12.9

120 37 14.5

150 37 16.2

185 37 18.0

240 61 20.6

300 61 23.1

Cableweightapprox

kg/km

245

270

320

440

525

685

895

1295

1630

2085

2795

3780

4560

5500

6675

8605

10510

Conductorresistance(20 )

/km

18.2

12.2

7.56

4.70

3.11

1.84

1.16

0.734

0.529

0.391

0.270

0.195

0.154

0.126

0.1000

0.0762

0.0607

Cableratingat 45

Amp.

15

20

26

34

44

61

82

108

133

167

206

249

288

331

377

444

511

Nominaloveralldia.

mm

12.3 0.5

12.9 0.5

13.7 0.5

15.6 0.6

16.8 0.7

18.8 0.8

21.0 0.8

25.0 1.0

27.6 1.1

31.2 1.2

35.8 1.4

41.2 1.6

44.8 1.8

49.2 2.0

53.8 2.2

61.0 2.4

67.0 2.7

Thicknessof outersheath

mm

1.2

1.2

1.2

1.3

1.4

1.4

1.5

1.7

1.8

1.9

2.1

2.3

2.4

2.6

2.7

3.0

3.2

Nominaldia. overbraid

mm

9.7

10.3

11.1

12.8

13.8

15.8

17.8

21.4

23.8

27.2

31.4

36.4

39.8

43.8

48.2

54.8

60.4

Dia. ofmetal wire forbraid

mm

0.2

0.2

0.2

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.4

0.4

0.4

0.4

0.4

0.4

Nominaldia. over innercovering

mm

8.6

9.2

10.0

11.2

12.2

14.2

16.2

19.8

22.2

25.6

29.8

34.4

37.8

41.8

46.2

52.8

58.4

Thickness of inner covering

mm

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.2

1.2

1.4

1.4

1.4

1.6

1.6

Thickness of insulation

mm

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.2

1.2

1.4

1.4

1.6

1.6

1.8

2.0

2.2

2.4

Construction

Conductor : Circular tinned stranded copper as per IEC60228 & 60228A, Class 2Insulation : Halogen Free Ethylene Propylene Rubber (HF-EPR)as per IEC 60092-351Cabling (with filler)Inner covering : Halogen-free thermosetting compoundAmour : Copper wires braid(screen) as per IEC 60092-353Outer sheath : Flame retardant, oil, abrasion, chemical andsunlight resistant.- Code-P1 : Halogen-free thermosetting compound as per IEC60092-359, SHF2

- Code-P1/P8 : Halogen-free & Mud resistance thermosettingcompound as per IEC 60092-359, SHF Mud

Identification of color

Insulation2 : Grey, Black

Outer sheath : BlackNote) Any other colors purchaser required

IEC 60332-3-22 : Flame retardant, Cate ‘A’IEC 60754-1 : Halogen free, 0.5%IEC 61034-1/2 : Smoke densityCSA C22.2 No.03 : Cold bend, 40

Cold impact, 35UL 1581 : Sunlight resistanceNEK 606 : Mud resistance

RFCU

= with galvanized steel wire braid

Page 6: Att-4 Lv Cable Epr Epr Gswb Shf-2

Marketing Office Tel:82-2-2140-3055 Fax:82-2-2140-3098Head Office Tel:82-43-530-2000 Fax:82-43-530-2144 Pusan Office Tel:82-51-817-0295 Fax:82-51-817-029756

Kukdong LSHF - NEK 606 2004

ApplicationPower circuit below 1kV, Lighting circuits, Trace heating circuits.Fixed installation power, control & lighting in both explosion risk and safe areas, generalpurposes.Maximum operating conductor temperature 90

Standard AppliedDesign guideline : IEC 60092-353Material properties : IEC 60092-351 (Insulation, HF-EPR)

IEC 60092-359 (Sheath, SHF2)Flame retardant : IEC 60332-3-22, Cate. ‘A’Halogen free properties : IEC 60754-1Low smoke properties : IEC 61034-1/2Cold properties(option) : CSA C22.2 No. 03Sunlight resistance(option) : UL 1581Mud resistance(option) : NEK 606 (2004)

0.6/1kV THREE CORE, ARMORED POWER CABLE (CODE : 0.6/1kV RFOU[P1], RFOU[P1/P8])

Conductor

Nominal Min. Max.sectional No. of overall area wires dia.

mm2 EA mm

No.of core

EA

3

1.0 7 1.4

1.5 7 1.7

2.5 7 2.2

4 7 2.7

6 7 3.3

10 7 4.2

16 7 5.3

25 7 6.6

35 7 7.9

50 19 9.1

70 19 11.0

95 19 12.9

120 37 14.5

150 37 16.2

185 37 18.0

240 61 20.6

300 61 23.1

Cableweightapprox

kg/km

280

320

420

510

610

830

1100

1560

2000

2620

3580

4700

5750

6960

8560

10940

13490

Conductorresistance(20 )

/km

18.2

12.2

7.56

4.70

3.11

1.84

1.16

0.734

0.529

0.391

0.270

0.195

0.154

0.126

0.1000

0.0762

0.0607

Cableratingat 45

Amp.

12

16

21

28

36

50

67

89

110

137

169

205

237

272

311

365

421

Nominaloveralldia.

mm

12.7 0.5

13.4 0.5

15.0 0.6

16.2 0.6

17.5 0.7

19.9 0.8

22.2 0.9

26.1 1.0

29.3 1.2

33.5 1.3

38.4 1.5

43.5 1.7

47.7 1.9

52.4 2.1

57.9 2.3

65.0 2.6

71.9 2.9

Thicknessof outersheath

mm

1.2

1.2

1.3

1.3

1.4

1.5

1.6

1.7

1.8

2.0

2.2

2.3

2.5

2.7

2.9

3.1

3.4

Nominaldia. overbraid

mm

10.2

10.9

12.3

13.5

14.6

16.8

18.9

22.8

25.4

29.5

34.0

38.9

42.6

46.9

52.0

58.7

64.9

Dia. ofmetal wire forbraid

mm

0.2

0.2

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.4

0.4

0.4

0.4

0.4

0.4

0.4

Nominaldia. over innercovering

mm

9.1

9.8

10.7

11.9

13.0

15.2

17.3

21.0

24.0

27.8

31.9

36.8

40.6

44.9

50.0

56.7

63.0

Thickness of inner covering

mm

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.2

1.2

1.2

1.4

1.4

1.6

1.6

1.8

Thickness of insulation

mm

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.2

1.2

1.4

1.4

1.6

1.6

1.8

2.0

2.2

2.4

Construction

Conductor : Circular tinned stranded copper as per IEC60228 & 60228A, Class 2Insulation : Halogen Free Ethylene Propylene Rubber (HF-EPR)as per IEC 60092-351Cabling (with filler)Inner covering : Halogen-free thermosetting compoundAmour : Copper wires braid(screen) as per IEC 60092-353Outer sheath : Flame retardant, oil, abrasion, chemical andsunlight resistant.- Code-P1 : Halogen-free thermosetting compound as per IEC60092-359, SHF2

- Code-P1/P8 : Halogen-free & Mud resistance thermosettingcompound as per IEC 60092-359, SHF Mud

Identification of color

Insulation3 : Grey, Black, Red 3phase3G : Grey, Black, Green/Yellow stripe

1phase, neutral & protectiveearth

Outer sheath : BlackNote) Any other colors purchaser required

IEC 60332-3-22 : Flame retardant, Cate ‘A’IEC 60754-1 : Halogen free, 0.5%IEC 61034-1/2 : Smoke densityCSA C22.2 No.03 : Cold bend, 40

Cold impact, 35UL 1581 : Sunlight resistanceNEK 606 : Mud resistance

RFCU

= with galvanized steel wire braid

Page 7: Att-4 Lv Cable Epr Epr Gswb Shf-2

89

Kukdong LSHF - NEK 606 2004

Marketing Office Tel:82-2-2140-3055 Fax:82-2-2140-3098Head Office Tel:82-43-530-2000 Fax:82-43-530-2144 Pusan Office Tel:82-51-817-0295 Fax:82-51-817-0297

Hig

h V

olta

ge F

lam

e Re

tard

ant C

able

Hig

h V

olta

ge F

lam

e&

Fire

Res

ista

nt C

able

Low

Vol

tage

Fla

me

Reta

rdan

t Cab

leLo

w V

olta

ge F

lam

e &

Fire

Res

ista

nt C

able

Tech

nica

l inf

orm

atio

n

ApplicationPower circuit below 1kV, Motor Power circuit for PWM AC Drives.Fixed installation power in both explosion risk and safe areas, general purpose.Maximum operating conductor temperature 90

Standard AppliedDesign guideline : IEC 60092-353Material properties : IEC 60092-351 (Insulation, HF-EPR)

IEC 60092-359 (Sheath, SHF2)Flame retardant : IEC 60332-3-22, Cate. ‘A’Halogen free properties : IEC 60754-1Low smoke properties : IEC 61034-1/2Cold properties(option) : CSA C22.2 No. 03Sunlight resistance(option) : UL 1581Mud resistance(option) : NEK 606 (2004)

0.6/1kV THREE CORE+THREE EARTH, ARMORED POWER CABLE (Code : 0.6/1kV RFOU-EMC, RFOU-EMC ‘MR’)

Construction

Conductor : Circular tinned stranded copper as per IEC 60228& 60228A, Class 2Insulation : Halogen Free Ethylene Propylene Rubber (HF-EPR) asper IEC 60092-351Cabling (with filler)Inner covering : Halogen-free thermosetting compoundAmour(screen) : Cu/PS tape & Copper wire braid combination100% shield screen.Outer sheath : Flame retardant, oil, abrasion, chemical andsunlight resistant.- Halogen-free thermosetting compound as per IEC 60092-359,SHF2

- ’MR’ : Halogen-free & Mud resistance thermosettingcompound as per IEC 60092-359, SHF Mud

Identification of color

Insulation3 : Grey, Black, RedEarth : Green or Green/Yellow stripe

Outer sheath : BlackNote) Any other colors purchaser required

Technical specification

VoltagesRated AC and DC voltage Uo/U(Um) ; 0.6/1(1.2)kVMax. permissible periodic peak voltage : 2kVAC test voltage : 5kVeff (Standard test voltage 3.5kV/5min)Min. bending radius : 6 cable outside diameterMax. permissible tensile load : 50N/mm2(sum of cross-section of all conductors in mm2)Permissible operation with conductor earth fault in non-earthed networks ; max. eight hours, but notmore than 125hours within a period of one year.

IEC 60332-3-22 : Flame retardant, Cate ‘A’IEC 60754-1 : Halogen free, 0.5%IEC 61034-1/2 : Smoke densityCSA C22.2 No.03 : Cold bend, 40

Cold impact, 35UL 1581 : Sunlight resistanceNEK 606 : Mud resistanceEMC : Electromagnetic Compatibility

Conductor

Nominal Min. Max.sectional No. of overall area wires dia.

mm2 EA mm

No.of core

EA

3+3E

25 7 6.66 7 3.3

35 7 7.910 7 4.2

50 19 9.110 7 4.2

70 19 11.016 7 5.3

95 19 12.925 7 6.6

120 37 14.525 7 6.6

150 37 16.235 7 7.9

185 37 18.035 7 7.9

240 61 20.650 19 9.1

300 61 23.150 19 9.1

Cableweightapprox

kg/km

1775

2375

2860

3950

5390

6330

7780

9315

12005

14395

Conductorresistance(20 )

/km

0.7343.11

0.5291.84

0.3911.84

0.2701.16

0.1950.734

0.1540.734

0.1260.529

0.10000.529

0.07620.391

0.06070.391

Cableratingat 45

Amp.

89

110

137

169

205

237

272

311

365

421

Nominaloveralldia.

mm

28.6 1.1

32.7 1.3

33.9 1.4

38.8 1.6

44.3 1.8

48.0 1.9

52.7 2.1

58.2 2.3

65.5 2.6

72.1 2.9

Thicknessof outersheath

mm

1.8

1.9

2.0

2.2

2.4

2.5

2.7

2.9

3.2

3.4

Nominaldia. overbraid

mm

24.8

28.7

29.7

34.2

39.3

42.8

47.1

52.2

58.9

65.1

Dia. ofmetal wire forbraid

mm

0.3

0.3

0.3

0.4

0.4

0.4

0.4

0.4

0.4

0.4

Nominaldia. over innercovering

mm

23.2

27.1

28.1

32.2

37.3

40.8

45.1

50.2

56.9

63.1

Thickness of inner covering

mm

1.0

1.2

1.2

1.2

1.4

1.4

1.4

1.6

1.6

1.8

Thickness of insulation

mm

1.21.0

1.21.0

1.41.0

1.41.0

1.61.2

1.61.2

1.81.2

2.01.2

2.21.4

2.41.4