Upload
others
View
26
Download
0
Embed Size (px)
Citation preview
DSE6110/20AUTO START & AUTO MAINS FAILURECONTROL MODULES
DSEGenset
®
1ph2ph3phN
1ph2ph3ph
1ph2ph3phN
6 4
PC
VOLTS
3
++
DEUTZISUZUPERKINSCATERPILLARMTUVOLVOCUMMINSSCANIA
D +W/L
GENERATOR SENSING
VOLTSCURRENT
USBPORT
CONFIGURABLEINPUTS
DC OUTPUTS ANALOGUESENDERS
EMERGENCY STOP
DC POWER SUPPLY 8-35V
ELECTRONICENGINES ORMAGNETIC PICK-UP
FUEL & CRANKOUTPUTS(Flexible with CAN)
CHARGEALTERNATOR
MAINS (UTILITY) SENSINGDSE6120 ONLY
ISSUE 2
+
1 1
DC OUTPUTS
+
COMPREHENSIVE FEATURE LIST TO SUIT AWIDE VARIETY OF GEN-SET APPLICATIONS
7
OTHER
DSE6110/20
The DSE6110 is an Auto StartControl Module and the DSE6120is an Auto Mains (Utility) FailureControl Module suitable for a widevariety of single gen-setapplications.
Monitoring speed, frequency,voltage, current, oil pressure,coolant temperature and fuel level,the modules will display warnings,shutdown and engine statusinformation on the back-lit LCDscreen and illuminated LED.
Both modules offer electronic(CAN) and non-electronic (magneticpick-up/alternator sensing) engineversions and offer a number offlexible inputs, outputs and engineprotections so the system can beeasily adapted to suit a wide rangeof application demands.
The modules can be easilyconfigured using the DSEConfiguration Suite PC software.Selected front panel editing is alsoavailable.
FEATURES
ENVIRONMENTAL TESTING STANDARDS
ELECTRO-MAGNETIC COMPATIBILITYBS EN 61000-6-2EMC Generic Immunity Standard for the Industrial EnvironmentBS EN 61000-6-4EMC Generic Emission Standard for the Industrial Environment
ELECTRICAL SAFETYBS EN 60950Safety of Information Technology Equipment, including Electrical Business Equipment
TEMPERATUREBS EN 60068-2-1Ab/Ae Cold Test -30 oCBS EN 60068-2-2Bb/Be Dry Heat +70 oC
VIBRATIONBS EN 60068-2-6Ten sweeps in each of three major axes5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn
HUMIDITYBS EN 60068-2-30Db Damp Heat Cyclic 20/55 oC@ 95% RH 48 HoursBS EN 60068-2-78Cab Damp Heat Static 40 oC@ 93% RH 48 Hours
SHOCKBS EN 60068-2-27Three shocks in each of three major axes15 gn in 11 mS
DEGREES OF PROTECTIONPROVIDED BY ENCLOSURESBS EN 60529IP65 - Front of module when installed into thecontrol panel with the optional sealing gasket.
DEEP SEA ELECTRONICS PLC UKHighfield House, Hunmanby Industrial Estate, Hunmanby YO14 0PHTELEPHONE +44 (0) 1723 890099 FACSIMILE +44 (0) 1723 893303EMAIL [email protected] WEBSITE www.deepseaplc.com
DEEP SEA ELECTRONICS INC USA3230 Williams Avenue, Rockford, IL 61101-2668 USATELEPHONE +1 (815) 316 8706 FACSIMILE +1 (815) 316 8708EMAIL [email protected] WEBSITE www.deepseausa.com
Registered in England & Wales No.01319649VAT No.316923457
055-069/10/11 (4)
KEY FEATURES• Back-lit text LCD display• Front panel editing• LED and LCD alarm indication• Power Save mode• CAN and Magnetic Pick-up/Alt.
versions available (specify onordering)
• PC and front panelconfiguration
• 6 Digital inputs• 3 Analogue inputs• 6 Outputs (4 configurable on
Magnetic Pick-up/Alt., 6configurable on CAN version)
• Configurable timers and alarms• Alternative configuration • Event Log (10)• Remote Start input• 3 Phase generator monitoring
• Current Monitoring and protection• 3 Phase Mains (Utility)
monitoring (DSE6120 only)• Test button (DSE6120 only)• Battery voltage monitoring• Engine pre-heat• Hours counter• Comprehensive shutdown or
warning on fault condition
KEY BENEFITS• Automatically transfers between
mains (utility) and generatorpower (DSE6120 only)
• Hours counter provides accurateinformation for monitoring andmaintenance periods
• User-friendly set-up and buttonlayout
• Multiple engine parameters aremonitored simultaneously
• Module can be configured tosuit individual applications
• Compatible with a wide rangeof CAN engines
• Tier 4 engine support• Uses DSE Configuration Suite
PC software for simplifiedconfiguration
• IP65 rating (with optionalgasket) offers increasedresistance to water ingress
• Licence-free PC software
RELATED MATERIALSTITLE PART NO’SDSE6110 Installation Instructions 053-059DSE6120 Installation Instructions 053-060DSE6100 Quick Start Guide 057-102DSE6100 Operator Manual 057-095DSE6100 Configuration Suite PC Manual 057-096
SPECIFICATION
DC SUPPLYCONTINUOUS VOLTAGE RATING8 V to 35 V Continuous
CRANKING DROPOUTSAble to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries.LEDs and backlight will not be maintained during cranking.
MAXIMUM OPERATING CURRENT178 mA at 12 V, 95 mA at 24 V
MAXIMUM STANDBY CURRENT88 mA at 12 V, 50 mA at 24 V
CHARGE FAIL/EXCITATION RANGE0 V to 35 V
MAINS (UTILITY) DSE6120 ONLYVOLTAGE RANGE15 V - 333 V AC (L-N)
FREQUENCY RANGE3.5 Hz to 75 Hz
OUTPUTSOUTPUT A (FUEL)2 A DC at supply voltage
OUTPUT B (START)2 A DC at supply voltage
AUXILIARY OUTPUTS C,D,E & F2 A DC at supply voltage
GENERATORVOLTAGE RANGE 15 V - 333 V AC (L-N)
FREQUENCY RANGE3.5 Hz to 75 Hz
MAGNETIC PICK UPVOLTAGE RANGE+/- 0.5 V to 70 V
FREQUENCY RANGE10,000 Hz (max)
DIMENSIONSOVERALL215 mm x 158 mm x 42 mm 8.5” x 6.2” x 1.6”
PANEL CUT-OUT182 mm x 137 mm7.2” x 5.4”
MAXIMUM PANEL THICKNESS8 mm0.3”
STORAGE TEMPERATURE RANGE-40 oC to +85 oC
DSE6110/20AUTO START & AUTO MAINS FAILURECONTROL MODULES
®
DSEGenset
DSE6110
DSE6120
Deep Sea Electronics Plc maintains a policy of continuous development and reserves the right to changethe details shown on this data sheet without prior notice. The contents are intended for guidance only.