  • DSE6110/20 MKIIAUTO START AND AUTO MAINS FAILURECONTROL MODULES

    FEATURES

    ENVIRONMENTAL TESTING STANDARDS

    ELECTRO-MAGNETIC COMPATIBILITYBS EN 61000-6-2EMC Generic Immunity Standard for the Industrial EnvironmentBS EN 61000-6-4EMC Generic Emission Standard for the Industrial Environment

    ELECTRICAL SAFETYBS EN 60950Safety of Information Technology Equipment, including Electrical Business Equipment

    TEMPERATUREBS EN 60068-2-1Ab/Ae Cold Test -30 oCBS EN 60068-2-2Bb/Be Dry Heat +70 oC

    VIBRATIONBS EN 60068-2-6Ten sweeps in each of three major axes5 Hz to 8 Hz at +/-7.5 mm, 8 Hz to 500 Hz at 2 GN

    HUMIDITYBS EN 60068-2-30Db Damp Heat Cyclic 20/55 oCat 95% RH 48 HoursBS EN 60068-2-78Cab Damp Heat Static 40 oCat 93% RH 48 Hours

    SHOCKBS EN 60068-2-27Three shocks in each of three major axes15 GN in 11 mS

    DEGREES OF PROTECTIONPROVIDED BY ENCLOSURESBS EN 60529IP65 - Front of module when installed into thecontrol panel with the optional sealing gasket.

    DSEGenset

    The DSE6110 MKII Auto StartControl Module and the DSE6120MKII Auto Mains (Utility) FailureControl Module are suitable for awide variety of single gen-setapplications.

    Monitoring engine speed, oilpressure, coolant temperature,frequency, voltage, current, powerand fuel level, the modules givecomprehensive engine andalternator protection. This isindicated on a large back-lit LCDtext display via an array of warning,electrical trip and shutdown alarmsin multiple languages.

    Electronic J1939 (CAN) and non-electronic MPU and alternatorsensing engine support for diesel,gas and petrol engines all in onevariant. With a number of flexibleinputs, outputs and protections, themodules can be easily adapted tosuit a wide range of applications.

    Through USB Communication bothmodules can be configured usingthe DSE Configuration Suite PCSoftware or through the module'sfront panel editor.

    Using the DSE Configuration SuitePC Software the controller is easyto use and configure which allowsalteration of operating parameters,sequences, timers and alarms.

    1ph2ph3phN

    1ph2ph3phN

    6 4

    PC

    VOLTS

    4

    +D +W/L

    GENERATORSENSING

    VOLTS

    USBDSENet EXPANSION

    CONFIGURABLEINPUTS

    DC OUTPUTS ANALOGUE SENSOR /DIGITAL INPUT

    EMERGENCY STOP

    DC POWER SUPPLY 8-35V

    ELECTRONICENGINES &MAGNETIC PICK-UP

    FUEL & STARTOUTPUTS(Flexible with CAN)

    CHARGEALTERNATOR

    MAINS (UTILITY) SENSING (DSE6120 MKII)

    +

    1 1

    COMPREHENSIVE FEATURE LIST TO SUIT AWIDE VARIETY OF GEN-SET APPLICATIONS

    7

    OTHER

    DSE6110/20 MKII

    1ph2ph3ph

    GENERATOR /LOAD CURRENT

    DC OUTPUT1 OF 4

    DC OUTPUT1 OF 4

    6110-03

    6110-04

    6120-03

    6120-04

    Auto Start with real time clock

    Auto start with real time clock andheated display

    Auto Mains Failure with real timeclock

    Auto Mains Failure with real timeclock and heated display

    AVAILABLE VARIANTS

    ++

    DSE2130DSE2157DSE2548

  • SPECIFICATION

    DC SUPPLYCONTINUOUS VOLTAGE RATING8 V to 35 V Continuous

    CRANKING DROPOUTSAble to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries.LEDs and backlight will not be maintained during cranking.

    MAXIMUM OPERATING CURRENT100 mA at 12 V, 105 mA at 24 V

    MAXIMUM STANDBY CURRENT60 mA at 12 V, 55 mA at 24 V

    MAXIMUM SLEEP CURRENT40 mA at 12 V, 35 mA at 24 V

    GENERATOR & MAINS (UTILITY)VOLTAGE RANGE15 V to 415 V AC (Ph to N)26 V to 719 V AC (Ph to Ph)

    FREQUENCY RANGE3.5 Hz to 75 Hz

    INPUTSDIGITAL INPUTS A to FNegative switching

    ANALOGUE INPUT AConfigurable as:Negative switching digital input0 V to 10 V4 mA to 20 mA0 to 240 ANALOGUE INPUTS B to DConfigurable as:Negative switching digital input0 to 480 OUTPUTSOUTPUT A (FUEL)10 A short term, 5 A continuous, at supply voltage

    OUTPUT B (START)10 A short term, 5 A continuous, at supply voltage

    AUXILIARY OUTPUTS C, D, E & F2 A DC at supply voltage

    DIMENSIONSOVERALL216 mm x 158 mm x 43 mm8.5 x 6.2 x 1.5

    PANEL CUT-OUT184 mm x 137 mm7.2 x 5.3

    MAXIMUM PANEL THICKNESS8 mm0.3

    STORAGE TEMPERATURE RANGE-40 C to +85 C-40 F to +185 F

    OPERATING TEMPERATURE RANGENON HEATED DISPLAY VARIANT-30C to +70C-22 F to +158 F

    HEATED DISPLAY VARIANT-40 C to +70 C-40 F to +158 F

    OPTIONAL PARTS

    PART PART NUMBERIP65 Gasket 020-521

    DEEP SEA ELECTRONICS PLC UKHighfield House, Hunmanby Industrial Estate, Hunmanby YO14 0PHTELEPHONE +44 (0) 1723 890099 FACSIMILE +44 (0) 1723 893303EMAIL [email protected] WEBSITE www.deepseaplc.com

    DEEP SEA ELECTRONICS INC USA3230 Williams Avenue, Rockford, IL 61101-2668 USATELEPHONE +1 (815) 316 8706 FACSIMILE +1 (815) 316 8708EMAIL [email protected] WEBSITE www.deepseausa.com

    055-191/08/14 (1)

    RELATED MATERIALSTITLE PART NOSDSE6110/20 MKII Installation Instructions 053-173DSE6110/20 MKII Operator Manual 057-226DSE6110/20 MKII Configuration Suite PC Manual 057-224

    Registered in England & Wales No.01319649VAT No.316923457

    Deep Sea Electronics Plc maintains a policy of continuous development and reserves the right to changethe details shown on this data sheet without prior notice. The contents are intended for guidance only.

    DSEGenset

    DSE6110/20 MKIIAUTO START AND AUTO MAINS FAILURECONTROL MODULES

    FEATURES

    DSE6110 MKII

    DSE6120 MKII

    KEY FEATURES Large back-lit text display Multiple display languages Heated display option available DSENet expansion compatible Data logging facility Fully configurable via PC usingUSB communication

    Front panel configuration Efficient power save mode 3 phase generator sensing 3 phase mains (utility) sensing(DSE6120 MKII only)

    Generator/load powermonitoring (kW, kV A, kV Ar, pf)

    Generator/load currentmonitoring and protection

    Breaker control via fasciabuttons

    Fuel and start outputs,configurable when using CAN

    4 configurable DC outputs 4 configurable analogue/digitalinputs

    Support for 0 to10 V & 4 to 20 mA oil pressure sensors

    6 configurable digital inputs Configurable staged loadingoutputs

    CAN, MPU and alternator speedsensing in one variant

    3 engine maintenance alarms Engine speed protection Engine hours counter Engine pre-heat Engine run-time scheduler Engine idle control for starting &stopping

    Fuel pump control Real time clock Battery voltage monitoring Start on low battery voltage Configurable remote start input 1 alternative configuration Comprehensive warning,electrical trip or shutdownprotection upon fault condition

    LCD and LED alarm indication Customisable informationscreens

    Configurable event log (100)

    KEY BENEFITS Automatically transfers betweenmains (utility) and generator(DSE6120 MKII only)

    Increased input and outputexpansion capability viaDSENet

    Hours counter provides accurateinformation for monitoring andmaintenance periods

    User-friendly set-up and buttonlayout for ease of use

    Multiple parameters aremonitored simultaneously whichare clearly displayed on a largeback-lit text display via multiplelanguages

    The module can be configuredto suit a wide range ofapplications

    Compatible with a wide range ofCAN engines including Tier 4

    Uses DSE Configuration SuitePC Software for simplifiedconfiguration

    Licence-free PC software IP65 rating (with optional gasket)offers increased resistance towater ingress