    DSE Configuration Suite PC Software Installation & Operation ManualISSUE 1

    DEEP SEA ELECTRONICS PLC

    DSE Configuration Suite PC SoftwareInstallation & Operation Manual

    Document Number 057-151

    Author: Ashley Senior

  • 8/11/2019 Dse Configuration Suite Pc Software Installation Operation Manual Dse7310

    2/38

    DSE Configuration Suite PC Software Installation & Operation Manual

    2

    DEEP SEA ELECTRONICS PLC

    Highfield HouseHunmanbyNorth YorkshireYO14 0PH

    ENGLAND

    Sales Tel: +44 (0) 1723 890099Sales Fax: +44 (0) 1723 893303

    E-mail : [email protected] : www.deepseaplc.com

    DSE Configuration Suite PC Software Installation & Operation Manual

    Deep Sea Electronics PlcAll rights reserved. No part of this publication may be reproduced in any material form (including photocopyingor storing in any medium by electronic means or other) without the written permission of the copyright holder

    except in accordance with the provisions of the Copyright, Designs and Patents Act 1988.Applications for the copyright holders written permission to reproduce any part of this publication should beaddressed to Deep Sea Electronics Plc at the address above.

    The DSE logo is a UK registered trademarks of Deep Sea Electronics PLC.

    Any reference to trademarked product names used within this publication is owned by their respectivecompanies.

    Deep Sea Electronics Plc reserves the right to change the contents of this document without prior notice.

    Amendments List

    Issue Comments MinimumModule

    versionrequired

    MinimumConfiguration Suite

    Version required

    1 Initial release 1

    Typeface: The typeface used in this document is Arial. Care should be taken not to mistake the upper case letter I with the numeral 1. Thenumeral 1 has a top serif to avoid this confusion.

  • 8/11/2019 Dse Configuration Suite Pc Software Installation Operation Manual Dse7310

    3/38

    DSE Configuration Suite PC Software Installation & Operation Manual

    3

    TABLE OF CONTENTS

    1 DESCRIPTION ................................................................................................. 42 INSTALLATION INSTRUCTIONS ................................................................... 5

    2.1 SOFTWARE INSTALLATION ........................................................................................................... 52.1.1 MINIMUM SYSTEM REQUIREMENTS ........................................................................................................... 5

    2.1.2

    INSTALLATION .............................................................................................................................................. 52.1.3 TROUBLESHOOTING SOFTWARE INSTALLATION .................................................................................... 9

    2.1.3.1 WINDOWS 7 ....................................................................................................................................................................... 92.1.3.2 WINDOWS VISTA ............................................................................................................................................................... 92.1.3.3 WINDOWS XP .................................................................................................................................................................... 92.1.3.4 WINDOWS NT, WINDOWS MILLENIUM, WINDOWS 98, WINDOWS 95, WINDOWS 3.1 ............................................. 92.1.3.5

    APPLE MAC, WINDOWS CE, PALM OS, SMARTPHONE, PDA, ANDROID ................................................................... 9

    2.2 HARDWARE INSTALLATION ........................................................................................................ 102.3 TROUBLESHOOTING INSTALLATION ......................................................................................... 10

    3 USING THE DSE CONFIGURATION SUITE PC SOFTWARE ...................... 113.1 IF SOFTWARE UPDATES ARE AVAILABLE ................................................................................ 113.2 OPENING PAGE ............................................................................................................................. 13

    4 MENUS AND TOOLBAR ............................................................................... 144.1 TOOLBAR ....................................................................................................................................... 144.2 FILE MENU ..................................................... ........................................................... ...................... 16

    4.3

    TOOLS MENU ................................................................................................................................. 174.3.1 UPDATE FIRMWARE ................................................................................................................................... 19

    4.3.1.1

    DIRECT USB CONNECTION ........................................................................................................................................... 19

    4.3.1.2

    CONNECTION VIA DSE813 ............................................................................................................................................. 22

    4.3.2 ACCESS PERMISSIONS ...................... ..................... ..................... ..................... ...................... ................... 244.3.4 DSE8XXX SERIES PC EVENT LOG ............................................................................................................ 264.3.5 ADDRESS BOOK ......................................................................................................................................... 27

    4.3.5.1

    CREATING A NEW ENTRY ............................................................................................................................................. 27

    4.3.5.2

    USING AN ENTRY ............................................................................................................................................................ 28

    4.3.6 LANGUAGE EDITOR ................................................................................................................................... 294.3.6.1

    GETTING STARTED ........................................................................................................................................................ 29

    4.3.6.2

    EDITING THE STRINGS .................................................................................................................................................. 30

    4.3.6.3 UPDATING THE MODULE LANGUAGE .......................................................................................................................... 30 4.3.6.4 UPDATING THE SCADA ALARMS/EVENT LOG LANGUAGE ....................................................................................... 31

    4.3.8 DSE8XXX DATA LOG VIEWER ................................................................................................................... 334.3.9 BATCH CONVERT TO... .............................................................................................................................. 35

    4.4 HELP MENU .................................................................................................................................... 36

  • 8/11/2019 Dse Configuration Suite Pc Software Installation Operation Manual Dse7310

    4/38

  • 8/11/2019 Dse Configuration Suite Pc Software Installation Operation Manual Dse7310

    5/38

    Installation

    5

    2 INSTALLATION INSTRUCTIONS

    2.1 SOFTWARE INSTALLATION

    2.1.1 MINIMUM SYSTEM REQUIREMENTS

    Operating System Windows 7, Windows Vista, Windows XP with Microsoft .Net 4.0 frameworkMonitor 17 inch recommended (1024 x 768 resolution)Communications USB required to configure the module. DSE813 for some modules.

    NOTE: - As DSE configuration software for Windows is a 32 or 64 bit application requiringMicrosoft .net 4 framework, it will not operate on Windows 2.0, 3.0, 3.1,3.11, 95, 98 or Me.

    NOTE: - Microsoft .Net 4.0 Framework can be obtained from Microsofts website. Alternatively, itis included in the DSE Configuration Suite Software CD version which can be obtained on CD fromDeep Sea Electronics PLC or by downloading the WebSetup from the DSE website.

    NOTE: - Exit all other programs before installing the software. It is recommended that any earlierreleases of the software be uninstalled prior to installing this version.

    NOTE: - Please register online at www.deepseaplc.com Once registered you will be able todownload updates to the software to ensure that you always have access to the latest features.

    2.1.2 INSTALLATION

    Insert the Software CD into the CD-ROM drive on thePC. The CD will then Auto-run if this feature is enabledon your PC.

    Alternatively:

    Download the PC software by visiting our websitewww.deepseaplc.com.

    Once download:

    Double click on Computer Double click WebSetup

    Double click on CD-ROM Drive

    Double click CDSetup

    Click Nextto continue

  • 8/11/2019 Dse Configuration Suite Pc Software Installation Operation Manual Dse7310

    6/38

    Installation

    6

    Select Typical (only installs the common program features), Custom(allows the user to customise toinstallation)orComplete (installs all software packages) to start the installation

    Example showing the Custom installation window.Click Nextto continue.

    Click Install to begin.

  • 8/11/2019 Dse Configuration Suite Pc Software Installation Operation Manual Dse7310

    7/38

    Installation

    7

    Enter your login details for the DSE Website.Click Ok to continue.

    NOTE: - To register on our website please visit: http://www.deepseaplc.com/members/register/

  • 8/11/2019 Dse Configuration Suite Pc Software Installation Operation Manual Dse7310

    8/38

    Installation

    8

    Select the modules which are to be installed with the software.Click Update to continue.

    The installer will then either download or install the modules selected.

    Click Finish to complete the installation.

    A module with (new)indicates it has notbeen installed.

  • 8/11/2019 Dse Configuration Suite Pc Software Installation Operation Manual Dse7310

    9/38

  • 8/11/2019 Dse Configuration Suite Pc Software Installation Operation Manual Dse7310

    10/38

    Installation

    10

    2.2 HARDWARE INSTALLATION

    Ensure the Configuration Suite Software is installed on the PC as described above.The installation of the PC software also installs the DSE Controller USB and DSE813 Driver automatically.Connect the USB cable to the PC as shown below and also to the module. Connection details for the DSE813can be found in the products software manual.

    Windows detects the module when power is applied to it.You are now ready to configure or monitor the module using the Configuration Suite Software.

    2.3 TROUBLESHOOTING INSTALLATION

    Occasionally USB devices are disabled by the Windows operating system, the following procedure will re-enable the device in these instances.

    Disconnect the Deep Sea Electronics Controller from the USB port. Wait a moment, then reconnectand try again. If you still encounter problems then :

    Try another USB cable. If you dont have one, its the same type of cable as usually used between aPC and a USB printer (Type A to Type B). If you still encounter problems then :

    Disconnect the Deep Sea Electronics Controller. Shutdown, then restart the PC. Reconnect theinterface, and then try again. If you continue to experience problems then :

    Check the USB port with another device (for instance a mouse, printer or digital camera).

  • 8/11/2019 Dse Configuration Suite Pc Software Installation Operation Manual Dse7310

    11/38

    Using the DSE Configuration Suite PC Softwar

    11

    3 USING THE DSE CONFIGURATION SUITE PC SOFTWARE

    To run the Configuration Suite Software for Windows program click the Windows start button

    or depending upon your version of Windows.

    Then select All Programs - DSE Configuration Suite - DSE Configuration Suite

    3.1 IF SOFTWARE UPDATES ARE AVAILABLE

    After a short delay to load the application, the splash screen is shown, after which the screen willdisplay the following:-

    If there is an internet connection and updates are available, this window will be displayed.Click Update Now to begin the procedure.

  • 8/11/2019 Dse Configuration Suite Pc Software Installation Operation Manual Dse7310

    12/38

    Using the DSE Configuration Suite PC Software

    12

    Select the type of software update required. Example showing Custom UpdateClick Update to continue.

    The software will then download the selected updates.

    A module with (update available)indicates there are updatesavailable for that specific module

  • 8/11/2019 Dse Configuration Suite Pc Software Installation Operation Manual Dse7310

    13/38

    Using the DSE Configuration Suite PC Software

    13

    3.2 OPENING PAGE

    If there are not updates or they have been completed, the initial start up screen will be displayed. This is theinitial start-up screen and can be disabled by checking the box Hide this screen at start-up.The screen prompts the user to select between the three main uses for the software:

    Creating a new configuration. Select the module type under Create new configuration. This allows

    you to create a configuration for the latest module version. Use File | Convert to...to convert theconfiguration to suit an earlier module version or use Tools | Update firmwareto update an earliermodule to the latest firmware version.

    Editing a configuration previously saved to disk or flash memory device. Select the configuration fileeither from the Open recent configurationarea or by clicking Open a configuration fileand browsingto the file.

    Reading and changing the configuration of a connected module. Click Read configuration from amodule.The file is read from a currently connected controller and is available for editing in theConfiguration Suite.

    Alternatively you can ignore this screen and continue to use the program in the background. Once you make aconnection or load/create a configuration, the start-up screen will disappear.

  • 8/11/2019 Dse Configuration Suite Pc Software Installation Operation Manual Dse7310

    14/38

    4 MENUS AND TOThe menu and toolbar are located

    4.1 TOOLBAR

    The toolbar contains the most usecommands. Not all options are ap

    Creat

    Open

    Save ta newPrint t

    Previe

    Send

    Read

    AllowsdescriAllowsSCADwhere

    Allowsfrom a

    Menus and Toolbar

    14

    LBAR

    at the top of the screen:

    commands from the menus and is often a quicker wlicable to all DSE controllers.a new configuration file

    an existing file from disk or flash memory device

    he currently open file to the location it was loaded frofile, you are prompted to enter a filename.

    he currently open configuration file

    w what the configuration file will look like on the page

    he currently open configuration settings to the controll

    he settings out of the connected controller for viewing

    the user to create an Address Book of connects. Forption see the section entitled Address Book else whethe user to log all the events from any module conne

    A. For a complete description see the section entitledin this document.

    the user to mute any alarms that have been receivedsuitably configured controller.

    oltages are shown as phase to phase voltages in the

    oltages are shown as phase to neutral voltages in the

    y of accessing these

    previously. If this is

    after printing.

    er

    / editing

    a completere in this document.ted to the PC via

    Event Log else

    by telephone modem

    onfiguration editor

    configuration editor

  • 8/11/2019 Dse Configuration Suite Pc Software Installation Operation Manual Dse7310

    15/38

    Menus and Toolbar

    15

    Select the communication method. The choices present are dependent upon yourPCs configuration. Any modem connections added to the address book are alsoselected here.

    USB To connect via USBdirectly to the controller, select USB:

    If there are more than one controller connected via USB, select which moduleyou wish to communicate with:

    Modem To connect via Modem, select your modem connection from the list:

    Then click Modem Settingsbox to enter the number to dial.

    Alternatively you can select an entry in the address book.

    DialDial the number currently entered into the ModulePhone Numbersetting.

    Hang-up Close the phone connection.

    Answer modeThe Configuration Suite goes into Answer Modeawaiting a connection from a remote module.

    TCP/IP connection To connect via Ethernet, select TCP/IP connection:

    Then click TCP/IPSettingsin the toolbar.You must consult your networkadministrator for help in selecting thesesettings.They must match the settings of thecontroller you wish to communicate with.

    RS485 / RS232 To connect to a module via RS232or RS485, select your comport from the list :

    Then click Serial Settingsto configure the RS485 Port :Enable 485 :Enable or Disable the RS485port connection in the PC.

    86x Support :Enables a longercommunication time-out

    Slave ID:The modbus slave ID you wish tocommunicate with.

    Baud Rate:The baud rate you wish toconnect at.

  • 8/11/2019 Dse Configuration Suite Pc Software Installation Operation Manual Dse7310

    16/38

    Menus and Toolbar

    16

    4.2 FILE MENU

    Create a new configuration file. You are prompted to select what kind ofmodule you want to create the configuration for.The settings of the new configuration file match the factory settings for thechosen module type.

    You can only select to create a configuration file for the latest version ofcontroller. If you want to create a configuration for an earlier version ofcontroller, you can use Convert to...to make your configuration suitable for theearlier controller or use Tools | Update firmwareto update the earlier moduleto the latest version.

    Open an existing file from disk or flash memory device.

    Close the currently open file.

    Save the currently open file to the location it was loaded from previously. If thisis a new file, you are prompted to enter a filename.Save the currently open file, under a new name. You will be prompted to entera filename.

    Send the currently open configuration settings to the controller.

    Read the settings out of the connected controller for viewing / editing.

    Read the settings from the connected controller and convert to the currentlyselected configuration type.Read the settings from a modules configuration file on disk or flash memorydevice and convert to the currently selected configuration type.Convert the currently loaded configuration file to suit another module type oranother module version.

    Print the currently open configuration file.

    Preview what the configuration file will look like on the page after printing.

    Select printer type and printer settings.

    Exit the software. If the currently open file has changed since it was lastsaved, you will be prompted to save it.

  • 8/11/2019 Dse Configuration Suite Pc Software Installation Operation Manual Dse7310

    17/38

    Menus and Toolbar

    17

    4.3 TOOLS MENU

    Options Opens the Settingsscreen containing customisation options for the DSEConfiguration Suite.

    Logo insert Only available when currently viewing the Module section of theconfiguration.

    This allows the user to create Logo Inserts for certain DSE modules tocustomise the controller to suit the generator manufacturer.

    Text Insert Only available when currently viewing the Module section of theconfiguration.

    This allows the user to create Text Inserts for the configurable LEDs on thecertain DSE modules.

    Changefont

    Changebackgroundcolour

    Reset fontand colourchanges

    Print thisinsert card

    Load an imageinto the logoinsert program

    Print thislogo insertcard

    File/folder

    location

    Browse to change

    file/folder location

    Check forupdates

    Press ok tosave changes

  • 8/11/2019 Dse Configuration Suite Pc Software Installation Operation Manual Dse7310

    18/38

    Menus and Toolbar

    18

    Annunciator text insert Only available when currently viewing the DSE2548 configurations in theExpansion | 2548 Annunciator Modulessection of the configuration.

    This allows the user to create Text Inserts for the DSE2548 ExpansionAnnunciator modules

    Update Firmware Allows the user to update the firmware (internal software) of the DSEcontroller. For a complete description see the section entitled UpdateFirmware elsewhere in this document.

    Access Permissions See the section headed Access Permissions after this table.Alarms Allows the user to mute any alarms that have been received by telephone

    modem from a suitably configured controller.

    Manage curves Allows the management (editing or deleting) of custom sensor curvesEvent Log Allows the user to log all the events from any module connected to the PC

    via SCADA. For a complete description see the section entitled EventLog else where in this document.

    Address Book Allows the user to create an Address Book of connections. For a completedescription see the section entitled Address Book else where in thisdocument.

    Language Editor Allows the editing of the text displayed by the module. For a completedescription see the section entitled Language Editor elsewhere in thisdocument.

    Data Log Viewer Allows the user to view previously logged data from a DSE module. For a

    complete description see the section entitled Data Log Viewer elsewherein this document.

    Batch Convert To... Allows the user to update a large quantity of configuration files to the latestversion. For a complete description see the section entitled Batch ConvertTo... elsewhere in this document.

    Backup Module Allows the user to backup up the connected modules configuration file andSCADA settings.

    Restore Module Allows the user to restore a previous configuration file and SCADA settingsto the connected module.

    Changefont

    Change

    backgroundcolour

    Reset fontand colour

    changes

    Print thisinsert card

    Load an imageinto the logoinsert program

  • 8/11/2019 Dse Configuration Suite Pc Software Installation Operation Manual Dse7310

    19/38

    Menus and Toolbar

    19

    4.3.1 UPDATE FIRMWARE

    Selecting Update Firmwareinitiates the update wizard:

    4.3.1.1 DIRECT USB CONNECTION

    Click the exitbutton if you dontwant to update your module.

    Click nextto continue.

    Hint: Stopping the update processonce it begins could leave themodule inoperable! If this occurs,simply run the update wizard againand let it complete correctly.

    Ensure the modules supply andUSB cable are removed, and

    then click nextto continue.

    Click nextto continue.

    Select the device type

  • 8/11/2019 Dse Configuration Suite Pc Software Installation Operation Manual Dse7310

    20/38

    Menus and Toolbar

    20

    Click to select the firmware updatefile.

    Then click nexttocontinue.

    If the file you attempt to send to themodule is not compatible with thecurrently connected module, theupdate cannot continue.In this example an attempt wasmade to send a DSE8660 firmwarefile to a DSE8610 module!

    Ensure the USB cable is connected before themodules power supply. It will be automaticallydetected and the update process will begin.

  • 8/11/2019 Dse Configuration Suite Pc Software Installation Operation Manual Dse7310

    21/38

    Menus and Toolbar

    21

    The update is now in progress and willtake under one minute.

    During this phase:

    DO NOT DISCONNECT THE USBCONNECTION

    DO NOT TURN OFF YOUR PC

    DO NOT REMOVE POWERFROM THE CONTROLLER

    The update is now complete.

    The module will automatically restartwith the updated firmware (internalsoftware program).

    It is now safe to disconnect the USBlead and power down the module oryour PC.

    Click OKto continue.

  • 8/11/2019 Dse Configuration Suite Pc Software Installation Operation Manual Dse7310

    22/38

    Menus and Toolbar

    22

    4.3.1.2 CONNECTION VIA DSE813

    Then click nexttocontinue.

    Select the COM Port of theDSE813 uses.

    Click to select the firmware updatefile.

    Then click nextto beginthe firmware upgrade.

    If the wrong COM port has been selected,or the DSE813 in not connected properlythe u date will not be in

    Hint: You can find the COM Port numberout from Windows Device Manager | Ports(COM & LPT)

  • 8/11/2019 Dse Configuration Suite Pc Software Installation Operation Manual Dse7310

    23/38

    Menus and Toolbar

    23

    The update is now in progress and willtake around three minutes to complete.

    During this phase:

    DO NOT DISCONNECT THEDSE813 INTERFACE

    DO NOT TURN OFF YOUR PC

    The update is now complete.

    It is now safe to disconnect theDSE813 interface from the module andyour PC.

    Click OKto continue.

  • 8/11/2019 Dse Configuration Suite Pc Software Installation Operation Manual Dse7310

    24/38

    Menus and Toolbar

    24

    4.3.2 ACCESS PERMISSIONS

    Access permissions is an advanced Administration option to allow OEMS to setup the Configuration Suitesoftware to limit access for certain users.For instance, the generator OEM can install the software on the End Users PC and then setup multipleusernames to limit the customers access to only those functions that the OEM requires for the end user.An example of this is to give only SCADA access to a user requiring monitoring, or to give access to read andwrite configuration files, but not to edit a configuration file.

    Create a new user type

    Select Edit,then Newto createa new user

  • 8/11/2019 Dse Configuration Suite Pc Software Installation Operation Manual Dse7310

    25/38

    Menus and Toolbar

    25

    This example shows a new userthat is able to view, read and

    write configurations but is notable to edit the configuration.

    When you exit this window youare asked if you want to savethese changes and thenprompted to enter the passwordfor this user.

  • 8/11/2019 Dse Configuration Suite Pc Software Installation Operation Manual Dse7310

    26/38

    Menus and Toolbar

    26

    4.3.4 DSE8XXX SERIES PC EVENT LOG

    The PC event log is provided to maintain a log of alarms of DSE8XXX controllers that have been connected tothe SCADA section of the software.This event log is intended to maintain a log of alarms from modules that have dialled in when the station isunattended.

    Export PC Event Logas either a PDF orExcel spreadsheet

    Clear andcreate a newPC Event Log

    Events taken fromDSE8XXX modulesand stored on the PC

  • 8/11/2019 Dse Configuration Suite Pc Software Installation Operation Manual Dse7310

    27/38

    Menus and Toolbar

    27

    4.3.5 ADDRESS BOOK

    The Address Book(Tools | Address Book) is included to allow the user to create and store address entries tomake connection to a defined module with ease. An obvious use for this facility is to allow the user to create andstore address entries for modules which are connected with modems to make communication without enteringthe information into the software multiple times.

    4.3.5.1 CREATING A NEW ENTRY

    To create a new Address Bookentry, click on the Address Bookicon or go to (Tools | Address Book).

    Availablecommunication ports

    The user can choose to create a newAddress Book entry, open an existingone for editing or delete an old one.

    Click the column headingsto sort them into order.

    Select the port to communicatewith module.

    Enter the address details, if an identicalname is used multiple times, a number will

    be automatically added after each entry.

    Enter the modules PIN number ifconfigured to allow access. If themodule does not have a PIN numberconfi ured, leave as shown.

    Configure the communicationparameters.

    To save the address entry,

    press the Ok button.

  • 8/11/2019 Dse Configuration Suite Pc Software Installation Operation Manual Dse7310

    28/38

    Menus and Toolbar

    28

    4.3.5.2 USING AN ENTRY

    The new entry can now be selectedby double clicking with the leftmouse button or using the Connectvia drop down menu

    If the user has multipleAddress Book entries, the last5 used will be shown in theConnect via drop downmenu.

  • 8/11/2019 Dse Configuration Suite Pc Software Installation Operation Manual Dse7310

    29/38

    Menus and Toolbar

    29

    4.3.6 LANGUAGE EDITOR

    The Language editor(Tools | Language Editor) is included to allow the user to tailor the text for some DSEcontrollers to suit their own requirements. An obvious use for this facility is to allow the user to change the entiremodule text to another language. Other uses include changing some wording to better reflect the customersapplication. For instance Shutdown can be renamed to Critical Alarm and Warning can be changed toPrompt Alarm.

    4.3.6.1 GETTING STARTED

    To start a new translation, go to the File menu. The user can choose tocreate a new module translation or SCADA/event log translation (Modulealarm strings) or open an existing one for editing.

    The text strings are grouped together to make finding aparticular string easier.

    A summary shows how many strings do not have textentered, and if any are incorrect (are too long to display onthe module screen) these will be shown as errors.

    Give the new text file a name, for instance the name of thelanguage you are translating it to.

  • 8/11/2019 Dse Configuration Suite Pc Software Installation Operation Manual Dse7310

    30/38

    Menus and Toolbar

    30

    4.3.6.2 EDITING THE STRINGS

    4.3.6.3 UPDATING THE MODULE LANGUAGE

    Click the + symbol to open up thatsection and view/modify the textstrings. Click to close this group

    Click the column headings to sortthe strings into alphabetical order

    Enter the new text intothe Translation column.

    A tick shows that the textfits onto the display.A cross means the text istoo long for the display.

    When youre ready to test your new text file in the connected module, send i t using thebutton provided.Remember you must select this new language file in the modules display configuration

    editor. You can also upload language files to the module using the SCADA |LANGUAGES section of the Configuration Suite Software.

    The Mimiccolumn shows how it willappear on the module display.Take care that the text fits correctlyin the green box. You may need toabbreviate your translation if it doesnot fit into the space allowed.

  • 8/11/2019 Dse Configuration Suite Pc Software Installation Operation Manual Dse7310

    31/38

    Menus and Toolbar

    31

    4.3.6.4 UPDATING THE SCADA ALARMS/EVENT LOG LANGUAGE

    NOTE: - The SCADA text file is only applicable to the PC that it has been selected on.

    NOTE: - The SCADA text file will be used until the user configures it back to default (leaving the filelocation blank) or selecting another file.

    NOTE: - The SCADA text file only affects the alarms page and the event log in the SCADA section.

    When youre ready to test your new text file for the SCADA alarms and event log, savethe file with an appropriate name, e.g. the name of the language you are translating it to,to a folder on your computer you know the location of.

    When you have saved the new text file for the SCADA alarms, go to the Optionspage(Tools | Options) and click the Browse button for SCADA Module alarm translations tolocate the new text file. When you have selected the new text file for the SCADA alarms,press the Ok button to save the changes.

  • 8/11/2019 Dse Configuration Suite Pc Software Installation Operation Manual Dse7310

    32/38

    Menus and Toolbar

    32

    An example of auser configuredSCADA alarmstring for Fail to

    Stop

    An example ofa defaultSCADA alarmstring for Fail

    to Stop

    An example ofa defaultevent logstring for Fail

    to Stop

    An example of auser configuredevent log string

    for Fail to Stop

  • 8/11/2019 Dse Configuration Suite Pc Software Installation Operation Manual Dse7310

    33/38

    Menus and Toolbar

    33

    4.3.8 DSE8XXX DATA LOG VIEWER

    The Data Log Viewer (Tools | Data Log Viewer) is included to allow the user to view saved data which has beenlogged by a DSE module. An obvious use for this facility is to allow the user to gather information for faultdiagnostic or creating a report.

    An example of loggeddata from the module

    Data segmentsdownloaded fromthe module

    Download progress persegment from the module

    Data segment beingdownloaded from the module

    Zoom slider

    Navigation sliders

    To view the logged data, press the Read from Controller icon if the data is being logged tothe modules internal memory. If the data is being logged to an external memory device,plug the external device into your computer and press the Open Icon and locate the data.

  • 8/11/2019 Dse Configuration Suite Pc Software Installation Operation Manual Dse7310

    34/38

    Menus and Toolbar

    34

    Click the + symbol to open up the data.Click the symbol to close to minimise the data

    Click the + symbol to increase the resolutionin the Y axisClick the symbol to decrease the resolutionin the Y axis

    Click to hide the data on thegraph. When the data is hiddenthe text will be in italics.

    Data which has been logged by themodule and waiting to be downloaded

    Data which has been logged by themodule and is currently downloading

    Once the data has downloaded from the module, save the file with anappropriate name, e.g. the name of the site the generator is based,to a folder on your computer you know the location of.

  • 8/11/2019 Dse Configuration Suite Pc Software Installation Operation Manual Dse7310

    35/38

    Menus and Toolbar

    35

    4.3.9 BATCH CONVERT TO...

    The Batch Convert To... (Tools | Batch Convert To...) is included to allow the user to convert a large batch of pre-existing module configuration files to the latest version with ease.

    Select the type ofconfiguration file to convertthe pre-existing files to.

    Add single configurationfile to be converted.

    Add multiple configuration filescontained within a folder.

    Configuration fileswaiting to be converted.

    Add filename suffix to the newconverted configuration files

    Click Startto begin theconversion process.

  • 8/11/2019 Dse Configuration Suite Pc Software Installation Operation Manual Dse7310

    36/38

    Menus and Toolbar

    36

    4.4 HELP MENU

    Check for UpdatesIf an internet connection is available, the software will check for any updates todownload.Shows the version number of the configuration suite

    A tick shows that the configuration filehas been converted.A cross shows that the configurationfile has not been converted.

    Current configuration file beingconverted.

  • 8/11/2019 Dse Configuration Suite Pc Software Installation Operation Manual Dse7310

    37/38

    37

    This page is intentionally left blank

  • 8/11/2019 Dse Configuration Suite Pc Software Installation Operation Manual Dse7310

    38/38