User’sManual Diaphragm Seal System

EJXC80A, EJAC80E, EJXC81A, EJAC81E, EJXC50A and EJAC50E

IM 01C25W01-01EN

IM 01C25W01-01EN4th Edition

Page 2: Diaphragm Seal System EJXC80A, EJAC80E, EJXC81A, EJAC81E, … · 2019-11-20 · Flushing connection ring (High pressure side)*1 Direct Mounted Diaphragm Seal System Diaphragm Seal

Toc-1

IM 01C25W01-01EN

Diaphragm Seal SystemEJXC80A, EJAC80E, EJXC81A, EJAC81E, EJXC50A and EJAC50E

IM 01C25W01-01EN 4th Edition

4th Edition: Nov. 2019 (YK)All Rights Reserved, Copyright © 2016, Yokogawa Electric Corporation

Contents1. Introduction ............................................................................................... 1-1

Regarding This Manual ................................................................................................1-3 Trademarks ...................................................................................................................1-31.1 Safe Use of This Product .................................................................................1-41.2 Warranty .............................................................................................................1-5

2. Handling Cautions .................................................................................... 2-12.1 ModelandSpecificationsCheck .....................................................................2-12.2 Unpacking ..........................................................................................................2-22.3 Storage ...............................................................................................................2-22.4 Selecting the Installation Location ................................................................2-22.5 Pressure Connection ........................................................................................2-22.6 WaterproofingofCableConduitConnections ..............................................2-32.7 Restrictions on Use of Radio Transceivers ................................................... 2-32.8 Insulation Resistance and Dielectric Strength Test ...................................... 2-3

3. Component Names .................................................................................. 3-14. Installation ................................................................................................. 4-1

4.1 Precautions .......................................................................................................4-14.2 Mounting the Diaphragm Seals (Remote Seals) ........................................... 4-1

4.2.1 Mounting Flush type/Extended type Seals ........................................ 4-14.2.2 Mounting Inner Diaphragm Type Seals ............................................. 4-3

4.3 Mounting EJC80 and EJC81 with Remote Seal ................................ 4-34.5 Mounting EJC80 with Direct Mount Seal ................................................. 4-5

4.5.1 Mounting ............................................................................................4-54.5.2 Connecting Impulse Piping to the Transmitter ................................... 4-5

4.6 Mounting EJC50 with Direct Mount Seal ................................................. 4-74.7 Mounting EJC50 and EJC80 with Hygienic Seal .............................. 4-7

4.7.1 Hygienic Seal (Flush Type) ................................................................4-74.7.2 Hygienic Seal (Extended Type) ........................................................ 4-84.7.3 Tank Spud Mounting Method .............................................................4-8

Page 3: Diaphragm Seal System EJXC80A, EJAC80E, EJXC81A, EJAC81E, … · 2019-11-20 · Flushing connection ring (High pressure side)*1 Direct Mounted Diaphragm Seal System Diaphragm Seal

Toc-2

IM 01C25W01-01EN

4.8 Rotating Transmitter Section .........................................................................4-104.9 Changing Integral Indicator Direction ..........................................................4-104.10 Mounting the Flushing Connection Ring ..................................................... 4-11

4.10.1 Mounting to Pressure Detector Section ........................................... 4-114.10.2 Mounting to Process Flange ............................................................ 4-11

4.11 AffixingtheTeflonFilm ..................................................................................4-12

5. Operation ................................................................................................... 5-15.1 Preparation for Starting Operation .................................................................5-15.2 Zero Point Adjustment .....................................................................................5-3

5.2.1 Zero point adjustment for Absolute Pressure Diaphragm Seal System ...........................................................................................................5-4

5.3 Starting Operation ............................................................................................5-65.4 Shutting Down Operation ................................................................................5-65.5 Venting or Draining Transmitter Pressure-detector Section ....................... 5-6

5.5.1 Draining Condensate .........................................................................5-75.5.2 Venting Gas........................................................................................5-75.5.3 Draining Condensate for Flushing Connection Ring or Inner

Diaphragm Type Seal ........................................................................5-75.5.4 Venting Gas for Flushing Connection Ring or Inner Diaphragm

Type Seal ...........................................................................................5-85.6 Local Parameter Setting ...................................................................................5-8

5.6.1 Local Parameter Setting (LPS) Overview .......................................... 5-85.6.2 Activating Local Parameter Setting .................................................5-105.6.3 Parameter Setting Review ...............................................................5-105.6.4 LoopTestConfiguration ................................................................... 5-115.6.5 TagNumberConfiguration ............................................................... 5-115.6.6 PressureUnitConfiguration............................................................. 5-115.6.7 PressureLRV/URVConfiguration ...................................................5-125.6.8 DampingTimeConstantConfiguration ...........................................5-125.6.9 OutputModeConfiguration .............................................................5-125.6.10 DisplayOut1Configuration .............................................................5-125.6.11 Re-range by applying actual pressure (LRV/URV). .........................5-135.6.12 Device Information Display ..............................................................5-135.6.13 Save or Cancel.................................................................................5-135.6.14 AbortConfiguration ..........................................................................5-14

5.6.14.1 AbortConfiguration(Menu) ............................................5-145.6.14.2 AbortConfiguration(Parameter) ....................................5-14

5.6.15 Local Parameter Setting Lock ..........................................................5-145.6.16 Others ..............................................................................................5-14

Page 4: Diaphragm Seal System EJXC80A, EJAC80E, EJXC81A, EJAC81E, … · 2019-11-20 · Flushing connection ring (High pressure side)*1 Direct Mounted Diaphragm Seal System Diaphragm Seal

Toc-3

IM 01C25W01-01EN

When using the Transmitters in a Safety Instrumented Systems(SIS) application, refer to Functional Safety Manual(Document number: TI 01C25A05-01EN or TI 01C25A05-21EN for option code SLT )

6. Maintenance .............................................................................................. 6-16.1 Overview ............................................................................................................6-16.2 CalibrationInstrumentsSelection ..................................................................6-16.3 Calibration .........................................................................................................6-16.4 DisassemblyandReassembly ........................................................................6-4

6.4.1 Replacing the Integral Indicator .........................................................6-46.4.2 Replacing the CPU Board Assembly ................................................. 6-5

6.5 Replacing the Process Connector Gasket .....................................................6-56.6 DisassemblyandReassemblyofConnectionAdapterofInnerDiaphragm

Type Seal ............................................................................................................6-66.7 Troubleshooting ................................................................................................6-6

6.7.1 Basic Troubleshooting .......................................................................6-66.7.2 Troubleshooting Flowcharts ...............................................................6-76.7.3 Alarms and Countermeasures ...........................................................6-9

7. GeneralSpecifications ............................................................................ 7-1Revision Information

Page 5: Diaphragm Seal System EJXC80A, EJAC80E, EJXC81A, EJAC81E, … · 2019-11-20 · Flushing connection ring (High pressure side)*1 Direct Mounted Diaphragm Seal System Diaphragm Seal

<1. Introduction> 1-1

IM 01C25W01-01EN

1. IntroductionThank you for purchasing the DPharp Pressure transmitter.

YourTransmitterwaspreciselycalibratedatthefactorybeforeshipment.Toensurebothsafetyandefficiency,please read this manual carefully before you operate the instrument.

This manual describes the diaphragm seal system that consists of a transmitter section and a pressure detectorsection(diaphragmseal).Pleaseconfirmthemodelandsuffixcode(MScode)andthestylecodeofthe transmitter section on the product nameplate.

Pressure detector section

F0101ai

Transmitter section

with flushing connection ring

Transmitter section

Pressure detector section

Differential Pressure Diaphragm Seal System (High and low pressure remote seals)Diaphragm Seal System

Differential pressure transmitterRemote Mounted Diaphragm Seal (High pressure side)Remote Mounted Diaphragm Seal (Low pressure side)Flushing connection ring (High pressure side)*1

Flushing connection ring (Low pressure side)*1

Differential Pressure Diaphragm Seal System (Single pressure remote seal)Diaphragm Seal System

Differential pressure transmitterRemote Mounted Diaphragm Seal (High pressure side)Flushing connection ring (High pressure side)*1

Gauge/Absolute Pressure Diaphragm Seal SystemDiaphragm Seal System

Gauge/Absolute pressure transmitterRemote Mounted Diaphragm Seal (High pressure side)Flushing connection ring (High pressure side)*1

Direct Mounted Diaphragm Seal SystemDiaphragm Seal System

Differential/Gauge pressure transmitterDirect Mounted Diaphragm SealFlushing connection ring*1

*1: Specify when a flushing connection ring is required.Pressure detector section

Transmitter section

Page 6: Diaphragm Seal System EJXC80A, EJAC80E, EJXC81A, EJAC81E, … · 2019-11-20 · Flushing connection ring (High pressure side)*1 Direct Mounted Diaphragm Seal System Diaphragm Seal

<1. Introduction> 1-2

IM 01C25W01-01EN

Table1.1 TransmitterModel

Transmitter Model Style code GS No. IM No.

Transmitter section

Differentialpressuretransmitter

EJX110A S3 GS 01C25B01-01EN

IM 01C25B01-01EEJA110E S1, S2 GS 01C31B01-01EN

Gauge pressure transmitter

EJX430A S2 GS 01C25E01-01ENEJA430E S1, S2 GS 01C31E01-01ENEJX530A S2 GS 01C25F01-01EN IM 01C25F01-01EEJA530E S1, S2 GS 01C31F01-01EN

Absolute pressuretransmitter

EJX310A S2 GS 01C25D01-01EN IM 01C25B01-01EEJA310E S1, S2 GS 01C31D01-01EN

WARNING

This manual describes the hardware configurationsofthediaphragmsealsystem.

For wiring and precautions for the use in hazardous area, please refer to the users’ manual(IM) of each transmitter section as listed in table 1.1 or “EJX/EJA-E series Installation Manual”(IM 01C25A01-01E) attached to the transmitter upon shipment.

Forinformationonthesoftwareconfigurationand operation, please refer to either IM 01C25T03-01E for the BRAIN communication type, or IM 01C25T01-06EN for the HART communication type.For FOUNDATION Fieldbus protocol type, please refer to IM 01C25T02-01E. For PROFIBUS PA protocol type, please refer to IM 01C25T04-01EN.

Forthespecifications,environmentalconditions,configurationsandexternaldimensions,pleaserefertotheGeneralSpecificationslistedintheChapter 7.

To ensure correct use of this instrument, read both the hardware and software manuals thoroughly before use.

ThemanualsandGeneralSpecificationsinpdfformat are available on our website (Website address: https://www.yokogawa.com/solutions/products-platforms/field-instruments/) .

WARNING

When using the transmitters in a Safety Instrumented System application, refer to the Functional Safety Manual (Document ID: TI 01C25A05-01EN or TI 01C25A05-21EN for option code SLT) and follow the instructions and procedures described there. The document can be downloaded from the website of Yokogawa. (Website address: https://www.yokogawa.com/solutions/products-platforms/field-instruments/)

In order to satisfy the requirement of Safety Instrumented System, executing parameters setting is required. Please refer to the clause of “Setting Parameters” for setting range in the following manuals for the actual operation.

BRAIN: IM 01C25T03-01E HART: IM 01C25T01-06EN

Please also refer to the contact output setting in the same clause. After installing the transmitter, confirmthattherangeandunitissetcorrectly.Calibration of the transmitters shall be done after completing the range setting.

NOTEWhen describing the model name like EJC80, EJC81, or EJC50, it shows the applicability for both EJXC80A and EJAC80E, EJXC81A and EJAC81E, or EJXC50A and EJAC50E respectively.

Page 7: Diaphragm Seal System EJXC80A, EJAC80E, EJXC81A, EJAC81E, … · 2019-11-20 · Flushing connection ring (High pressure side)*1 Direct Mounted Diaphragm Seal System Diaphragm Seal

<1. Introduction> 1-3

IM 01C25W01-01EN

Regarding This Manual• This manual should be provided to the end

user.

• The contents of this manual are subject to change without prior notice.

• All rights reserved. No part of this manual may be reproduced in any form without Yokogawa’s written permission.

• Yokogawa makes no warranty of any kind with regard to this manual, including, but not limited to, implied warranty of merchantability and fitnessforaparticularpurpose.

• If any question arises or errors are found, or if any information is missing from this manual, please inform the nearest Yokogawa sales office.

• Thespecificationscoveredbythismanualarelimited to those for the standard type under the specifiedmodelnumberbreak-downanddonotcover custom-made instruments.

• Pleasenotethatchangesinthespecifications,construction, or component parts of the instrumentmaynotimmediatelybereflectedin this manual at the time of change, provided that postponement of revisions will not cause difficultytotheuserfromafunctionalorperformance standpoint.

• Yokogawa assumes no responsibility for this product except as stated in the warranty.

• If the customer or any third party is harmed by the use of this product, Yokogawa assumes no responsibility for any such harm owing to any defects in the product which were not predictable, or for any indirect damages.

• The following safety symbols are used in this manual:

WARNING

Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.

CAUTIONIndicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices.

IMPORTANTIndicates that operating the hardware or software in this manner may damage it or lead to system failure.

NOTEDraws attention to information essential for understanding the operation and features.

Direct current

Functional grounding terminal

CautionThis symbol indicates that the operator must refer to an explanation in the user’s manual in order to avoid the risk of injury or death of personnel or damage to the instrument.

Trademarks • ‘DPharp’, ‘EJX’, ‘EJA’, ‘FieldMate’ and ‘BRAIN

TERMINAL’ are registered trademarks of Yokogawa Electric Corporation. Company names and product names used in this material are registered trademarks or trademarks of their respective owners.

• In this manual, trademarks or registered trademarks are not marked with ™ or ®.

Page 8: Diaphragm Seal System EJXC80A, EJAC80E, EJXC81A, EJAC81E, … · 2019-11-20 · Flushing connection ring (High pressure side)*1 Direct Mounted Diaphragm Seal System Diaphragm Seal

<1. Introduction> 1-4

IM 01C25W01-01EN

1.1 Safe Use of This Product For the safety of the operator and to protect the instrument and the system, please be sure to follow this manual’s safety instructions when handling this instrument. If these instructions are not heeded, the protection provided by this instrument may be impaired. In this case, Yokogawa cannot guarantee that the instrument can be safely operated. Please pay special attention to the following points:

(a) Installation

• This instrument may only be installed by an engineer or technician who has an expert knowledge of this device. Operators are not allowed to carry out installation unless they meet this condition.

• With high process temperatures, care must be taken not to burn yourself by touching the instrument or its casing.

• Never loosen the process connector nuts when the instrument is installed in a process. This can lead to a sudden, explosive release of process fluids.

• When draining condensate from the pressure detector section, take appropriate precautions to prevent the inhalation of harmful vapors and thecontactoftoxicprocessfluidswiththeskinor eyes.

• When removing the instrument from a hazardousprocess,avoidcontactwiththefluidand the interior of the meter.

• All installation shall comply with local installation requirements and the local electrical code.

(b) Wiring

• The instrument must be installed by an engineer or technician who has an expert knowledge of this instrument. Operators are not permitted to carry out wiring unless they meet this condition.

• Before connecting the power cables, please confirmthatthereisnocurrentflowingthroughthe cables and that the power supply to the instrumentisswitchedoff.

(c) Operation

• Wait10min.afterthepoweristurnedoff,beforeopening the covers.

(d) Maintenance

• Please carry out only the maintenance procedures described in this manual. If you require further assistance, please contact the nearestYokogawaoffice.

• Care should be taken to prevent the build up of dust or other materials on the display glass and the name plate. To clean these surfaces, use a soft, dry cloth.

(e) ExplosionProtectedTypeInstrument

• Users of explosion protected type instruments shouldreferfirsttothesection“Installationofan Explosion Protected Instruments” of the IM (users’ manual) of the transmitter section.

• The use of this instrument is restricted to those who have received appropriate training in the device.

• Take care not to create sparks when accessing the instrument or peripheral devices in a hazardous location.

(f) Modification

• Yokogawa will not be liable for malfunctions or damageresultingfromanymodificationmadeto this instrument by the customer.

(g) Product Disposal

• The instrument should be disposed of in accordance with local and national legislation/ regulations.

Page 9: Diaphragm Seal System EJXC80A, EJAC80E, EJXC81A, EJAC81E, … · 2019-11-20 · Flushing connection ring (High pressure side)*1 Direct Mounted Diaphragm Seal System Diaphragm Seal

<1. Introduction> 1-5

IM 01C25W01-01EN

1.2 Warranty• The warranty shall cover the period noted on

the quotation presented to the purchaser at the time of purchase. Problems occurring during the warranty period shall basically be repaired free of charge.

• If any problems are experienced with this instrument, the customer should contact the Yokogawa representative from which this instrument was purchased or the nearest Yokogawaoffice.

• If a problem arises with this instrument, please inform us of the nature of the problem and the circumstances under which it developed,includingthemodelspecificationand serial number. Any diagrams, data and other information you can include in your communication will also be helpful.

• Thepartyresponsibleforthecostoffixingtheproblem shall be determined by Yokogawa following an investigation conducted by Yokogawa.

• The purchaser shall bear the responsibility for repair costs, even during the warranty period, if the malfunction is due to:

- Improper and/or inadequate maintenance by the purchaser.

- Malfunction or damage due to a failure to handle, use, or store the instrument in accordancewiththedesignspecifications.

- Use of the product in question in a location notconformingtothestandardsspecifiedbyYokogawa, or due to improper maintenance of the installation location.

- Failureordamageduetomodificationorrepair by any party except Yokogawa or an approved representative of Yokogawa.

- Malfunction or damage from improper relocation of the product in question after delivery.

- Reasonofforcemajeuresuchasfires,earthquakes,storms/floods,thunder/lightening, or other natural disasters, or disturbances, riots, warfare, or radioactive contamination.

Page 10: Diaphragm Seal System EJXC80A, EJAC80E, EJXC81A, EJAC81E, … · 2019-11-20 · Flushing connection ring (High pressure side)*1 Direct Mounted Diaphragm Seal System Diaphragm Seal

<2. Handling Cautions> 2-1

IM 01C25W01-01EN

2. Handling CautionsThis chapter provides important information on how to handle the transmitter. Read this carefully before using the transmitter.

WARNING

The codes of the diaphragm seal system represent a seal system type.CEandotherstandardcertificationsareacquiredfor each transmitter section.

Please refer to the designated sections of each transmitter’s users’ manual(IM) for these information as “Installation of an Explosion Protected Instrument”, “EMC conformity standards”, ”Pressure Equipment Directive(PED)” and “Safety Requirement Standards”.

Table2.1 TransmittersManualList

Diaphragm Seal System

ApplicableTransmitter Users’ Manual(IM)

EJXC80A, EJAC80E

EJX110A, EJA110E, EJX430A, EJA430E IM 01C25B01-01E

EJXC81A, EJAC81E

EJX310A, EJA310E

EJXC50A, EJAC50E

EJX530A, EJA530E IM 01C25F01-01E

The transmitters are thoroughly tested at the factory before shipment. When taking delivery of an instrument, visually check them to make sure that no damage occurred during shipment.

Also check that all the transmitter mounting hardwareshowninfigure2.1isincluded.If the transmitter is ordered without a mounting bracket or a process connector, such mounting hardware will not be included.

Mounting bracketU-bolt nut

U-bolt

Transmittermounting bolt

Process connectorProcess connector gasket

Bolt

F0201.ai

Figure 2.1 Transmitter Mounting Hardware

2.1 ModelandSpecificationsCheck

Themodelnameandspecificationsarewrittenonthe name plate attached to the case.

F0202.ai

Tag

Serial No. & Model

Figure 2.2 Name Plate

Page 11: Diaphragm Seal System EJXC80A, EJAC80E, EJXC81A, EJAC81E, … · 2019-11-20 · Flushing connection ring (High pressure side)*1 Direct Mounted Diaphragm Seal System Diaphragm Seal

<2. Handling Cautions> 2-2

IM 01C25W01-01EN

2.2 UnpackingKeep the transmitter in its original packaging to prevent it from being damaged during shipment. Do not unpack the transmitter until it reaches the installation site.

2.3 StorageThe following precautions must be observed when storing the instrument, especially for a long period.

(a) Select a storage area which meets the following conditions:• It is not exposed to rain or subject to water

seepage/leaks.• Vibration and shock are kept to a minimum.• It has an ambient temperature and relative

humidity within the following ranges.

Ambient temperature: –40* to 85°C without integral indicator –30* to 80°C with integral indicator

*–15°Cwhen/HEisspecified.Relative humidity: 0% to 100% R.H. (at 40°C)Preferred temperature and humidity: approx. 25°C and 65% R.H.

(b) When storing the transmitter, repack it carefully in the packaging that it was originally shipped with.

(c) If the transmitter has been used, thoroughly cleanthechambersinsidethecoverflangesand the diaphragm surface of high pressure-detector section, so that there is no process fluidremaininginsideoronit.Beforeplacingitin storage, also make sure that the pressure-detector section is securely connected to the transmitter section.

2.4 Selecting the Installation Location

The transmitter is designed to withstand severe environmental conditions. However, to ensure that it will provide years of stable and accurate performance, take the following precautions when selecting the installation location.

(a) Ambient Temperature Avoid locations subject to wide temperature

variationsorasignificanttemperaturegradient.If the location is exposed to direct sunlight or radiant heat from plant equipment, provide adequate shade, thermal insulation and/or ventilation.

(b) Ambient Atmosphere Do not install the transmitter in a corrosive

atmosphere. If this cannot be avoided, there must be adequate ventilation as well as measures to prevent the leaking of rain water and the presence of standing water in the conduits.

(c) Shock and Vibration Although the transmitter is designed to be

relatively resistant to shock and vibration, an installation site should be selected where this is kept to a minimum.

(d) Installation of Explosion-protected Transmitters An explosion-protected transmitter is

certifiedforinstallationinahazardousareacontainingspecificgastypes.Seesubsection2.9 “Installation of an Explosion-Protected Transmitters” of each transmitter’s manual as of table 1.1.

2.5 Pressure Connection

WARNING

• Neverloosentheflangeboltswhenaninstrument is installed in a process. The device is under pressure, and a loss of seal can result in a sudden and uncontrolled releaseofprocessfluid.

• Whendrainingtoxicprocessfluidsthathavecondensed inside the pressure detector, take appropriate steps to prevent the contact ofsuchfluidswiththeskinoreyesandtheinhalationofvaporsfromthesefluids.

• Sincetheaccumulatedprocessfluidmaybetoxic or otherwise harmful, take appropriate stepstopreventthecontactofsuchfluidswith the skin or eyes and the inhalation ofvaporsfromthesefluidsevenafterdismounting the instrument from process line for maintenance.

The following precautions must be observed in order to safely operate the transmitter under pressure.

(a) Make sure that all the process connector bolts aretightenedfirmly.

(b) Make sure that there are no leaks in the impulse piping.

(c) Never apply a pressure higher than the specifiedmaximumworkingpressure.

Page 12: Diaphragm Seal System EJXC80A, EJAC80E, EJXC81A, EJAC81E, … · 2019-11-20 · Flushing connection ring (High pressure side)*1 Direct Mounted Diaphragm Seal System Diaphragm Seal

<2. Handling Cautions> 2-3

IM 01C25W01-01EN

2.6 WaterproofingofCableConduit Connections

Apply a non-hardening sealant to the threads to waterproof the transmitter cable conduit connections.

2.7 Restrictions on Use of Radio Transceivers

IMPORTANTAlthough the transmitter has been designed to resist high frequency electrical noise, if a radio transceiver is used near the transmitter or its externalwiring,thetransmittermaybeaffectedby high frequency noise pickup. To test this, start out from a distance of several meters and slowly approach the transmitter with the transceiver while observing the measurement loop for noise effects.Thereafterusethetransceiveroutsidetherangewherethenoiseeffectswerefirstobserved.

2.8 Insulation Resistance and Dielectric Strength Test

Since the transmitter has undergone insulation resistance and dielectric strength tests at the factory before shipment, normally these tests are not required. If the need arises to conduct these tests, heed the following:

(a) Do not perform such tests more frequently than is absolutely necessary. Even test voltages that do not cause visible damage to the insulation may degrade the insulation and reduce safety margins.

(b) Never apply a voltage exceeding 500 V DC (100 V DC with an internal lightning protector) for the insulation resistance test, nor a voltage exceeding 500 V AC (100 V AC with an internal lightning protector) for the dielectric strength test.

(c) Before conducting these tests, disconnect all signal lines from the transmitter terminals. The procedure for conducting these tests is as follows:

• Insulation Resistance Test

1) Short-circuit the + and – SUPPLY terminals in the terminal box. In case of 1 to 5 V output, short-circuit the SUPPLY+, SUPPLY – and A (VOUT +) terminals.

2) Turn OFF the insulation tester. Then connect the insulation tester plus (+) lead wire to the shorted SUPPLY terminals and the minus (–) leadwire to the grounding terminal.

3) Turn ON the insulation tester power and measure the insulation resistance. The voltage shouldbeappliedasbrieflyaspossibletoverifythattheinsulationresistanceisatleast20MΩ.

4) After completing the test and being very careful not to touch exposed conductors disconnect the insulationtesterandconnecta100kΩresistorbetween the grounding terminal and the short-circuiting SUPPLY terminals. Leave this resistor connected at least one second to discharge any static potential. Do not touch the terminals while it is discharging.

• Dielectric Strength Test

1) Short-circuit the + and – SUPPLY terminals in the terminal box. In case of 1 to 5 V output, short-circuit the SUPPLY+, SUPPLY – and A (VOUT +) terminals.

2) Turn OFF the dielectric strength tester. Then connect the tester between the shorted SUPPLY terminals and the grounding terminal. Be sure to connect the grounding lead of the dielectric strength tester to the ground terminal.

3) Set the current limit on the dielectric strength tester to 10 mA, then turn ON the power and gradually increase the test voltage from ‘0’ to thespecifiedvoltage.

4) Whenthespecifiedvoltageisreached,holditfor one minute.

5) After completing this test, slowly decrease the voltage to avoid any voltage surges.

Page 13: Diaphragm Seal System EJXC80A, EJAC80E, EJXC81A, EJAC81E, … · 2019-11-20 · Flushing connection ring (High pressure side)*1 Direct Mounted Diaphragm Seal System Diaphragm Seal

<3. Component Names> 3-1

IM 01C25W01-01EN

3. Component NamesEJC80 Differential pressure transmitter

EJC80 Differential pressure transmitter

Cover flange

Diaphragm seal(high pressure side)

Diaphragm seal(low pressure side)

Capillary tube

Pressure detector section

Transmitter section*

EJC80 Pressure transmitterEJC81 Absolute Pressure transmitter

F0301.ai

Cover flange

Diaphragm seal

Pressure detector sectionWith C10FRFlushing connection ring

C10FRFlushing connection ring

Vent, drain plug

EJC50 Pressure transmitter

Diaphragm seal

Pressure detector section

Diaphragm seal (high pressure side)

Cover flange

Pressure detector section

*See figure 3.2. Transmitter section*

*See figure 3.2.

Transmitter section*

*See figure 3.2.

Transmitter section*

*See figure 3.2.

Vent, drain plugProcess connection(low pressure side)

Process connector

EJC80 Hygienic Differential pressure transmitter

Cover flange

Diaphragm seal(high pressure side)

Diaphragm seal(low pressure side)

Capillary tube

Transmitter section*

*See figure 3.2.EJC80 Hygienic pressure transmitter

Transmitter section*

*See figure 3.2.

Diaphragm seal (high pressure side)

Cover flange

Pressure detector section

Vent, drain plug

Pressure detector section

Figure 3.1 Components Name(Figures Show Flush Type Diaphragm Seals)

Page 14: Diaphragm Seal System EJXC80A, EJAC80E, EJXC81A, EJAC81E, … · 2019-11-20 · Flushing connection ring (High pressure side)*1 Direct Mounted Diaphragm Seal System Diaphragm Seal

<3. Component Names> 3-2

IM 01C25W01-01EN

HIGH LOW

H L H L

F0302.ai

H L

E D

H L

E D

YES(Write disabled)

NO(Write enabled)

Slide switch(Note 2)

Integralindicator (Note 1)

Mounting screw

Amplifier Cover

Burnout direction switch (BO) Hardware write protection switch (WR)

Burnout DirectionSwitch Position

Burnout Direction

Write ProtectionSwitch Position

Write Protection

Transmitter section

(Note 2) (Note 2)

CPU assembly

Burnout direction switch

BO H L

WR E D

Write protection switch

Range-settingswitch (Note 1)

Zero-adjustment screw

Conduit connection

External indicatorconduit connection (Note 1)

Cover flange(only for EJC80 and EJC81)

Bolt for flange(only for EJC80 and EJC81)

Note1: Asofspecifieduponordering.SeeGSfordetails.Note2: ApplicableforBRAIN/HARTcommunicationtype.Settheswitchesasshowninthefigureabovetosettheburn-outdirection

andwriteprotection.TheBurnoutswitchissettotheHsidefordelivery(unlessoptioncode/C1or/C2isspecifiedintheorder),andthehardwarewriteprotectionswitchissettoEside.Thesettingoftheswitchescanbeconfirmedviacommunication.Anexternal zero adjustment screw can only be disabled by communication. To disable the screw, set a parameter before activating the hardware write protect function. See each communication manual for details.

Figure 3.2 Component Names (Transmitter Section)

Table3.1 DisplaySymbol

Display Symbol Meaning of Display SymbolThe output signal being zero-adjusted is increasing. Besides, this symbol lights when local parameter setting is in progress.

The output signal being zero-adjusted is decreasing. Besides, this symbol lights when local parameter setting is in progress.

F0303.ai

Write protect function is enabled.

Page 15: Diaphragm Seal System EJXC80A, EJAC80E, EJXC81A, EJAC81E, … · 2019-11-20 · Flushing connection ring (High pressure side)*1 Direct Mounted Diaphragm Seal System Diaphragm Seal

<4. Installation> 4-1

IM 01C25W01-01EN

4. Installation4.1 Precautions Before installing the transmitter, read the cautionary notes in Section 2.4, “Selecting the Installation Location.” For additional information on the ambient conditions allowed at the installation location, refer to in the GS.(See Chapter 7)

IMPORTANT• When welding piping during construction,

take care not to allow welding currents to flowthroughthetransmitter.

• Do not step on this instrument after installation.

• For the EJC80 gauge transmitter, there is a small hole in the low pressure side coverflangethatisusedtomeasuretheatmospheric pressure.

The hole must not face upward. • Never loosen the four bolts securing the coverflanges(Refertofigure3.2)forEJC80 and EJC81 diaphragm seal system.

If the seal liquid leaks, the transmitter cannot be used.

• When installing diaphragm seals, process connectors or manifolds, make sure that no foreign matter has adhered to the seal surface of the gasket (or O-ring) before assembling. If foreign matter adheres, it may lead to leaks.

4.2 Mounting the Diaphragm Seals (Remote Seals)

4.2.1 MountingFlushtype/ExtendedtypeSeals

Mountthediaphragmsealsusingtheflangesasshown in Figure 4.1 Figure 4.2 shows how to mount thediaphragmsealsonatank.Thematingflange,gasket, bolts and nuts are to be procured by the customer.

NutFlangeDiaphragm

Ød

Gasket

F0401.ai

Bolt

The product is shipped withthese parts assembled.

Correctly install the diaphragm seals onthe high and low pressure sides of theprocess (The label on each diaphragm seal is marked HIGH or LOW.)

Figure 4.1 Mounting the Diaphragm Seals (Remote seal)

IMPORTANTPlease use a gasket with an inside diameter (ød) that is greater than the diameter of the diaphragm seal. If a gasket with a smaller inside diameter is used, the diaphragm may not function correctly.

C20FWC80FW

Flange size 80A(3B) 50A(2B) 40A(1 1/2B)

ød (mm) 90 61 44*

* Combination with C10FR is necessary.

Page 16: Diaphragm Seal System EJXC80A, EJAC80E, EJXC81A, EJAC81E, … · 2019-11-20 · Flushing connection ring (High pressure side)*1 Direct Mounted Diaphragm Seal System Diaphragm Seal

<4. Installation> 4-2

IM 01C25W01-01EN

IMPORTANT• When measuring the liquid level of the tank,

the minimum liquid level (zero point) must be set to a level at least 50 mm above the center of the high pressure side diaphragm seal (see Figure 4.2).

• Correctly install the diaphragm seals on the high and low pressure sides of the process, checking the label on each seal.

• To avoid measuring error duets temperature differencebetweenthetwodiaphragmseals, capillary tube must be bound together. Thecapillarytubemustbesecurelyfixedto the tank wall to prevent movement by wind or vibration. If the capillary tube is too long, loosely coil the extra tube portion (coil diameter of 300 mm or more) and secure the coiled tube with a clamp.

• During the diaphragm seal installation, ensure as far as possible that no seal liquid head pressure is applied to the diaphragm seals.

• Exercise care so as not to damage diaphragm surfaces. Since the diaphragm protrudesapprox.1mmfromtheflangesurface, do not place the pressure detector section face down on a surface as this can damage the diaphragm.

• Do not sharply bend or twist capillary tube or apply excessive stress to them.

F0402.ai

50mm minimum

Minimum liquid levelHigh

pressureside

Install the sealed diaphragm so that the shank positions downward.

Low pressure sideIMPORTANT

The transmitter should be installed as low as possible below the position where the high pressure side diaphragm seal is installed.

Install the sealed diaphragm so that the shank positions downward.

IMPORTANT

Figure 4.2 Installing the Diaphragm Seals to a Tank

Page 17: Diaphragm Seal System EJXC80A, EJAC80E, EJXC81A, EJAC81E, … · 2019-11-20 · Flushing connection ring (High pressure side)*1 Direct Mounted Diaphragm Seal System Diaphragm Seal

<4. Installation> 4-3

IM 01C25W01-01EN

4.2.2 Mounting Inner Diaphragm Type Seals

Install the seal in accordance with the Figure 4.3.Thebolts,nuts,matingflangeandgasketaretobeprocured by the customer.Position the connection adapter so that the drain/vent plugs are aligned straight up and down.

IMPORTANT• Please use the gasket whose inside

diameter is greater than the inside pipe diameter.

• Do not sharply bend or twist capillary tube or apply excessive stress to them.

• Fordifferentialpressuretransmitters,capillary tubes must be bundled together to avoid measuring error duets temperature differencebetweenthetwodiaphragmseals.

• The product is performing temperature compensation by the temperature sensor in thetransmittersection.Whenadifferenceof temperature appears between the transmitter section and capillary tube, an output error occurs.

Please use thermal insulants to decrease the effectoftemperaturedifferencebetweenthetransmitter section and capillary tube.

Mating flangeProcured by the customer

GasketProcured by the customer

Connection flange

Connection adapter

Drain/vent plug

Capillary tube

Diaphragm

Gasket

Stud bolt/nutAttached to product

Flange connection type

Adapter connection type

Mating flangeProcured by the customerGasketProcured by the customer

Connection adapterDrain/vent plug

Capillary tube

Diaphragm

Gasket

F0403.ai

Figure 4.3 Mounting Inner Diaphragm Seal

4.3 Mounting EJC80 and EJC81 with Remote Seal

Thetransmittercanbemountedonanominal50 mm (2 to inch) pipe using the mounting bracket supplied, as shown in Figure 4.4. The transmitter can be mounted on either a horizontal or a vertical pipe.

Whenmountingthebracketonthetransmitter,tighten the (four) bolts that hold the transmitter to a torque of approximately 39 N·m 4 kgf·m.

F0404.ai

U-bolt nut

Mounting bracket

Mounting bracket

50mm (2-inch) pipe

U-bolt

U-bolt

Horizontal pipe mounting

50mm (2-inch) pipe

Transmittermounting bolt

Transmittermounting bolt

U-bolt nut

Vertical pipe mounting

Figure 4.4 Transmitter Mounting

IMPORTANTWhen using the absolute pressure transmitter of M-Capsule, please care so that the sum of the head pressure and atmospheric pressure does not exceed Upper Range Limit (130 kPa abs.)

Page 18: Diaphragm Seal System EJXC80A, EJAC80E, EJXC81A, EJAC81E, … · 2019-11-20 · Flushing connection ring (High pressure side)*1 Direct Mounted Diaphragm Seal System Diaphragm Seal

<4. Installation> 4-4

IM 01C25W01-01EN

IMPORTANT

The transmitter should be installed at least 600 mm below the high pressure (HP) process connection to ensure a positive head pressure offillfluid.Payspecialattentiontovacuumapplications.If it can not be installed at least 600 mm below the HP process connection, please use the equation below:

h= × 0.102 [mm](P–P0)

ds

h: Vertical height between the HP process connection and the transmitter (mm)h≤0: Installthetransmitteratleasth(mm)

below the HP process connectionh>0: Install the transmitter at most h (mm)

above the HP process connectionP: Pressure in the tank (Pa abs)P0: Minimum working pressure limit of the

transmitter (Pa abs). See below table.[ForfillfluidcodeA,B,D,E,F,P]

Wetted parts material code

Capillary length

Process connection size code

6 9

S1 to 5 m 6790 31906 to 10 m 10030 352011 to 15 m 13310 3840

H1 to 5 m 19150 61406 to 10 m 32090 829011 to 15 m -------- 10480

T1 to 5 m 9620 36206 to 10 m 15090 421011 to 15 m -------- 4800

U1 to 5 m 9540 47506 to 10 m 14930 605011 to 15 m -------- 7360

M1 to 5 m 10910 39706 to 10 m 17380 478011 to 15 m -------- 5600

K1 to 5 m 10910 39706 to 10 m 17380 478011 to 15 m -------- 5600

V1 to 5 m 10910 39706 to 10 m -------- 478011 to 15 m -------- --------

J1 to 5 m -------- 130706 to 10 m -------- 1954011 to 15 m -------- --------

[Forfillfluidcode1,2,4]

Wetted parts material code

Capillary length

Process connection size code

6 9

S 1 to 5 m 2570 3206 to 10 m 4680 530

H 1 to 5 m 10220 20506 to 10 m 18650 3450

T 1 to 5 m 4270 5706 to 10 m 7780 960

ds:Specificgravityoffillfluid(at25°C).Fluid type and code Density*

Silicone oil (general use) A 1.07Silicone oil (general use) B 0.94 Silicone oil (low temperature use) F 0.88 Fluorinated oil (oil-prohibited use) D 1.90 to 1.92 Ethylene glycol (low temperature use) E 1.09 Propylene glycol P 1.04 Silicone oil (high temp. and high vacuum use) 1 1.07

Silicone oil (high temp. and high vacuum use) 2 1.09

Silicone oil (high vacuum use) 4 1.07 * Approximate values at a temperature of 25°C (77°F)

F0405.ai

P

Low pressure side

Highpressureside

(+)

(–)

0

h

Figure4.5 ExampleofInstallationtoTankforDifferentialPressureTransmitter (Caution on Installation)

Page 19: Diaphragm Seal System EJXC80A, EJAC80E, EJXC81A, EJAC81E, … · 2019-11-20 · Flushing connection ring (High pressure side)*1 Direct Mounted Diaphragm Seal System Diaphragm Seal

<4. Installation> 4-5

IM 01C25W01-01EN

F0406.ai

(+)

0

(–) P

h

Figure4.6 ExampleofInstallationtoTankforGauge Pressure Transmitter (Caution on Installation)

4.5 Mounting EJC80 with Direct Mount Seal

4.5.1 MountingThe transmitter is mounted on a process using its high-pressuresideflangeasshowninFigure4.7.Thematingflange,gasket,studboltsandnutsareto be procured by the customer.

F0407.ai

Gasket

Stud bolt

Nut

Figure 4.7 Transmitter Mounting

IMPORTANTPlease use a gasket with an inside diameter (ød) that is greater than the diameter of the diaphragm seal. If a gasket with a smaller inside diameter is used, the diaphragm may not function correctly. (See the table in 4.2.1.)

4.5.2 Connecting Impulse Piping to the Transmitter

The impulse piping that connects the process outputs to the transmitter must convey the process pressure accurately. If, for example, gas collects in aliquid-filledimpulseline,orthedrainofagas-filledimpulse line becomes plugged, it will not convey the pressure accurately. Since this will cause errors in the measurement output, select the proper piping methodfortheprocessfluid(gas,liquid,orsteam).Pay careful attention to the following points when routing the impulse piping and connecting the impulse piping to a transmitter.

(1) Check the High and Low Pressure Connections on the Transmitter (Figure 4.8)

The letters H and L on the capsule assembly indicate the high and low pressure sides. For liquid level measurement in an open tank, the low pressure side measures atmospheric pressure. For a closed tank, connect the impulse line to the low pressure side of the transmitter to measure the pressure in the tank.

F0408.ai

H and L appear here

Low pressureconnection

Process connector

Bolt

Figure4.8 HandLSymbolsonaCapsuleAssembly

Page 20: Diaphragm Seal System EJXC80A, EJAC80E, EJXC81A, EJAC81E, … · 2019-11-20 · Flushing connection ring (High pressure side)*1 Direct Mounted Diaphragm Seal System Diaphragm Seal

<4. Installation> 4-6

IM 01C25W01-01EN

(2) Tightening the Process Connector Mounting Bolts

After connecting the impulse line, tighten the process connector mounting bolts uniformly.

(3) Removing the Impulse Piping Connecting Port Dustproof Cap

The impulse piping connecting port of the transmitter may be covered with a plastic cap to keep out dust. This cap must be removed before connecting the line. (Be careful not to damage the threads when removing this cap. Never insert a screwdriver or other tool between the cap and port threads to remove the cap.)

(4) Impulse Piping Slope

The impulse piping must be routed with only an upward or downward slope. Even for horizontal routing, the impulse piping should have a slope of at least 1/10 to prevent condensate (or gases) from accumulating in the pipes.

(5) Preventing Freezing

Ifthereisanyriskthattheprocessfluidintheimpulse piping or transmitter could freeze, use a steam jacket or heater to maintain the temperature ofthefluid.

NOTEAfter completing the connections, close the valves on the process pressure taps (main valves), the valves at the transmitter (stop valves), and the impulse piping drain valves, so that condensate, sediment, dust and other extraneous material cannot enter the impulse piping.

(6) ImpulsePipingConnectionExamples

Figure 4.9 shows examples of typical impulse piping connections. Before connecting the transmitter to the process, study the transmitter installation location, the process piping layout, andthecharacteristicsoftheprocessfluid(corrosiveness,toxicity,flammability,etc.),etc.andmake appropriate changes and additions to the connectionconfigurations.

F0409.ai

Pipe (opened to atmosphereat low pressure side)

Open Tank

Closed Tank

Tap valve

Union or flange

Vent plug

Tee

Drain valve

Drain plug

Figure4.9 ImpulsePipingConnectionExamples

Page 21: Diaphragm Seal System EJXC80A, EJAC80E, EJXC81A, EJAC81E, … · 2019-11-20 · Flushing connection ring (High pressure side)*1 Direct Mounted Diaphragm Seal System Diaphragm Seal

<4. Installation> 4-7

IM 01C25W01-01EN

4.6 Mounting EJC50 with Direct Mount Seal

The transmitter is mounted on a process using its high-pressuresideflangeasshowninFigure4.10.Thematingflange,gasket,studboltsandnutsareto be procured by the customer.

F0410.ai

Gasket

Stud bolt

Nut

Figure 4.10 Transmitter Mounting

IMPORTANTPlease use a gasket with an inside diameter (ød) that is greater than the diameter of the diaphragm seal. If a gasket with a smaller inside diameter is used, the diaphragm may not function correctly. (See the table in 4.2.1.)

4.7 Mounting EJC50 and EJC80 with Hygienic Seal

4.7.1 Hygienic Seal (Flush Type)Theflushdiaphragmtypeismountedonaprocesstank as shown in Figure 4.11.

1) Fit the gasket into the gasket slot and attach it to the transmitter .

2) With the gasket attached, mount the transmitter onto the sleeve.

3) Use the clamp to secure the connecting section in position.

F0411.ai

*: The customer should prepare the mating gasket and clamp, They are also available from Yokogawa; if required, please order them separately. Refer to Table 4.2.

Tank

Sleeve

Gasket* (Optional)

Clamp* (Optional)

Tank

Sleeve

Gasket* (Optional)

Diaphragm seal

Clamp* (Optional)

Figure 4.11 Mounting Hygienic Seal (Flush Type)

Page 22: Diaphragm Seal System EJXC80A, EJAC80E, EJXC81A, EJAC81E, … · 2019-11-20 · Flushing connection ring (High pressure side)*1 Direct Mounted Diaphragm Seal System Diaphragm Seal

<4. Installation> 4-8

IM 01C25W01-01EN

4.7.2 HygienicSeal(ExtendedType)The extended diaphragm type is mounted on a process tank as shown in Figure 4.12.

1) Fit the O-ring into the O-ring slot of the transmitter.

2) With the O-ring attached, mount the transmitter onto the tank spud.

3) Use the clamp to secure the connecting section in position.

F0412.ai

*: The customer should prepare the mating O-ring, clamp, and tank spud. They are also available from Yokogawa; if required, please order them separately. Refer to Table 4.1 and 4.2.

Tank

Tank spud* (sold separately)

O-ring* (Optional)

Clamp* (Optional)

Diaphragm seal

O-ring* (Optional)

Clamp* (Optional)

Tank

Tank spud* (sold separately)

Figure4.12 MountingHygienicSeal(ExtendedType)

For the installation of a tank spud, read the following section very carefully.

4.7.3 Tank Spud Mounting MethodA tank spud is used to joint a tank and an extended diaphragm type of level transmitter.It is imperative for sanitary use that the contact parts of the transmitter and the tank are securely andtightlysealedinordertoavoidtheprocessfluidspoutingandthedecompositionbystagnantfluid.The construction of the tank spud using a O-ring eliminates the clearance between the contact parts and ensures the tightness.

F0413.ai

Tank spud

in Tank

(A)

Transmitter body

O-ring

Tank spud(Detail of A)

Tank

ISO Clamp

Transmitter side

Welding

Figure 4.13 Details of Transmitter Mounting

WeldingWhen welding a tank spud to a tank, take great care not to change its shape by heat. The deformation of the shape eventually makes a dead space between the transmitter and the tank spud, resulting in the processfluidspoutingandthedecompositionthecouplingbystagnantfluid.

Mounting PositionSet the center of the tank spud to a level at least 50mm above the minimum liquid level (zero point).

IMPORTANT• Clean thoroughly the tank after the welding

the tank spud to the hole on a tank.• Besurethatthesurfaceisfinishedsmoothly

by using a grinder except the hole is made by the machinery cutting.

Page 23: Diaphragm Seal System EJXC80A, EJAC80E, EJXC81A, EJAC81E, … · 2019-11-20 · Flushing connection ring (High pressure side)*1 Direct Mounted Diaphragm Seal System Diaphragm Seal

<4. Installation> 4-9

IM 01C25W01-01EN

Mounting DirectionFit the tank spud onto the tank so that the drain outlet faces downward. Then carry out the temporary welding at four points outside the spud, making sure to keep the boundary of the inside surfaceofthetankwallandspudflat.Also,setthespud vertical against the tank wall, in order for the transmitter to be installed correctly.

F0414.ai

Tank spud

Minimam liquid level

50mm

Drain hole

Tank

Welding

Center of tank spud

Figure 4.14 Mounting Tank Spud

Welding method and Cautions• Welding work should start with the inside of

tank, then continue to outside.• Before starting the welding work, cool the

welding part with dry ice and so on. The welded part should be cooled down one welding part after another.

• Set the welding heat level as low as possible to avoid the deformation of the spud.

• Since the tank spud materials used are SUS304, SUS316, and SUS316L, use the welding stick material as follows; Covered arc welding: D316L Tig or Mig welding: Y316L

• Take care not to damage the O-ring sealing part.

Finishing Welding SurfaceMake sure that all the welded parts are ground smoothandflatinawaythatnodustisstucktothesurface.

[Special Tools for Tank Spud Welding]

Yokogawa provides special tools exclusively designed for the tank spud welding to make the installationeasilyandeffectively.Thesetoolscanbe ordered separately.• Cooling tool.....reduces the strain on the spud

during welding process.For extension length L = 52 mm: Part No. 1J833A063-31For extension length L = 102 mm: Part No. 1J833A063-32

• Strain check gauge.....determines whether the transmitter can be mounted.For extension length L = 52 mm: Part No. 1J833A063-41For extension length L = 102 mm: Part No. 1J833A063-42

Table4.1 TankSpudmodelcode

Model SuffixCode DescriptionTS . . . . . . . . . . Tank spud

Extension length

-E . . . . . . . .

-F . . . . . . . .

-J . . . . . . . .

-K . . . . . . . .

-G . . . . . . . .

-H . . . . . . . .

2 inch (50 mm) for ISO101.6 Clamp

4 inch (100 mm) for ISO101.6 Clamp

2 inch (50 mm) for ISO76.1 Clamp

4 inch (100 mm) for ISO76.1 Clamp

2 inch (50 mm) for ISO51 Clamp

4 inch (100 mm) for ISO51 Clamp

Material U. . . . . . .V . . . . . . .W . . . . . .

304 SST316 SST316L SST

Welding part plate thickness

A. . . . . .B. . . . . .C. . . . . .

16 mm12 mm8 mm

for ISO101.6for ISO76.1

D. . . . . .E . . . . . .F . . . . . .

16 mm12 mm8 mm

for ISO51

*: For the overview of the tank spud, refer to Subsection 4.7.3.

Page 24: Diaphragm Seal System EJXC80A, EJAC80E, EJXC81A, EJAC81E, … · 2019-11-20 · Flushing connection ring (High pressure side)*1 Direct Mounted Diaphragm Seal System Diaphragm Seal

<4. Installation> 4-10

IM 01C25W01-01EN

Table4.2 Mountingtool,Gasket,ando-ring

Item Part No. DescriptionClamp G9726AE

G9726ABG9726AD

for ISO101.6 clampfor ISO51 clampfor ISO76.1 clamp

Gasket F9500DZF9500DXF9500DY

for ISO101.6 clampfor ISO51 clampfor ISO76.1 clamp

O-ring F9271QKF9357ELF9995CB

for ISO101.6 clampfor ISO51 clampfor ISO76.1 clamp

*: Observe the condition of the gasket when unscrewing the clamp. If the gasket is worn away or changed its shape, it must be replaced with new one.

F0415.ai

Figure 4.15 Clamp Overview

4.8 Rotating Transmitter SectionThe transmitter section can be rotated to any desired position. Note that there is a stopper which prevents the transmitter from being rotated more than 360°.

1) Using the Allen wrench, remove the two setscrews securing the transmitter section to the capsule assembly.

2) Rotate the transmitter section slowly to the desired position.

3) Tighten the two setscrews to a torque of 1.5 N·m 15 kgf·cm.

WARNING

Inthecaseoftheexplosion-proof/flameprooftype transmitter, do not rotate the transmitter part in the hazardous area while the transmitter is energized.

IMPORTANTDo not rotate the transmitter section more than the above limit.

F0416.ai

Set screw

Transmitter section

Stopper

Figure 4.16 Rotating Transmitter Section

4.9 Changing Integral Indicator Direction

IMPORTANT• AlwaysturnOFFpowerandshutoffand

release pressures before disassembly. • For changing the integral indicator direction,

the transmitter must be removed to a non-hazardous area.

An integral indicator can be installed in the following three directions, Refer to subsection 6.4 for attaching and removing the integral indicator.

F0417.ai

Figure 4.17 Integral Indicator Direction

Page 25: Diaphragm Seal System EJXC80A, EJAC80E, EJXC81A, EJAC81E, … · 2019-11-20 · Flushing connection ring (High pressure side)*1 Direct Mounted Diaphragm Seal System Diaphragm Seal

<4. Installation> 4-11

IM 01C25W01-01EN

4.10 Mounting the Flushing Connection Ring

4.10.1 Mounting to Pressure Detector Section

Theflushingconnectionringismountedtothepressure detector section as shown in Figure 4.18.

Atthefactoryshipment,theflushingconnectionringis enclosed with the diaphragm seal section without being tightly attached to the pressure detector section with screw, bolt/nut or welding. Therefore, when taking it out, please handle it with care not to damage the diaphragm with ring holders or vent/drainplugsoftheflushingconnectionring.

F0418.ai

Pressure-detector section

Vent/Drain plug

Ring

Ring holder

Spiral gasket

View from pressure detector section side

Groove for installingspiral gasket

Figure 4.18 Mounting to Pressure Detector Section

(1) Mount the ring holder on the ring and loosely tighten the mounting screws.

(2) Place the spiral gasket in the ring groove. With theringcorrectlyalignedandflushwiththefaceof the pressure detector, securely tighten each ring holder’s mounting screws.

(3) Position the ring so that the vent/drain plugs are aligned straight up and down.

4.10.2 Mounting to Process FlangeTighten the bolts to completely close the gap between the ring and the pressure detector section.

Thematingflange,gasket,studboltsandnutsareto be procured by the customer.

F0419.ai

Ring

Diaphragm

Pressure-detector section

Gasket

Mating flangeSpiral gasket

Figure 4.19 Mounting to Process Flange

Page 26: Diaphragm Seal System EJXC80A, EJAC80E, EJXC81A, EJAC81E, … · 2019-11-20 · Flushing connection ring (High pressure side)*1 Direct Mounted Diaphragm Seal System Diaphragm Seal

<4. Installation> 4-12

IM 01C25W01-01EN

IMPORTANT• Confirmthatthereisnogapbetweentheringandtheprocess-detectorsectionaftertheyaremountedontheprocessflange.Agapcanleadtoasudden,explosivereleaseofprocessfluids.

• When mounting or removing the ring, take care not to tilt the pressure detector downward as the ring canslipoffandcauseinjury.

• When re-mounting the ring, use the new spiral gasket as shown in below table.

Table4.3 SpiralGasketforPressureDetectorSectionSide*

Hoop material/Parts No.Gasket size Specifications SUS316 SUS316L Hastelloy C-276

ø100×ø120×t4.5 For 3-inch General use F9350SV F9350SW F9990BRø100×ø120×t4.5 For 3-inch High temperature use F9990BK F9990BN --------ø100×ø120×t4.5 For 3-inch Oil-prohibited use** F9970XF F9970XG --------ø70×ø90×t4.5 For 2-inch General use F9350ST F9350SU F9990BQø70×ø90×t4.5 For 2-inch High temperature use F9990BJ F9990BM --------ø70×ø90×t4.5 For 2-inch Oil-prohibited use** F9970XD F9970XE --------ø60×ø75×t4.5 For 1 1/2-inch General use F9346ZH F9970XA F9990BPø60×ø75×t4.5 For 1 1/2-inch High temperature use F9990BH F9990BL --------ø60×ø75×t4.5 For 1 1/2-inch Oil-prohibited use** F9970XB F9970XC --------

*: Filler materials General use, oil-prohibited use : PTFE High temperature use : inorganic paper**: For oil-prohibited use (Option code: /K31, /K35)

4.11 AffixingtheTeflonFilmTheFEPTeflonoptionincludesateflonfilmandfluorinatedoil.Beforemountingthetransmittertotheprocessflange,affixtheteflonfilmasfollows:

IMPORTANT1) Position the diaphragm so that the

diaphragm is in a upward position.2) Pourthefluorinatedoilonthediaphragm

and gasket area covering it completely and evenly. Be careful not to scratch the diaphragm or change the its shape.

3) Affixtheteflonfilmoverthediaphragmandgasket area.

4) Next, carefully inspect the cover and try to identify any entrapped air between thediaphragmandtheteflonfilm.Theair must be removed to ensure optimum performance. If air pockets are present, use yourfingerstoremovetheairbystartingat the center of the diaphragm and work your way out. However, do not lay too much stress on the diaphragm, as it may cause a deform of the diaphragm.

5) PositionthegasketontheTeflonfilm.6) Mount the transmitter onto the process

flange.

Teflon film

DiaphragmFluorinated oil

[PART No. : F9145YN]

Gasket area

PART No.

F9347XA

F9347YA*1

Prosess Flange size

3 inch (80mm)

2 inch (50mm)

F0420.ai

*1: F9347YD when Diaphragm Material code is "H" and Sealing Face Material code is "S."

Figure4.20 AffixingtheTeflonFilm

Page 27: Diaphragm Seal System EJXC80A, EJAC80E, EJXC81A, EJAC81E, … · 2019-11-20 · Flushing connection ring (High pressure side)*1 Direct Mounted Diaphragm Seal System Diaphragm Seal

<5. Operation> 5-1

IM 01C25W01-01EN

5. Operation5.1 Preparation for Starting

OperationThis section describes the operation procedure for the EJC80differentialpressuretransmitterasshown in Figure 5.1 when measuring liquid level in a closed tank, and EJC80differentialpressureor gauge pressure transmitter as shown in Figure 5.2 or 5.3 or EJC50 as shown in Figure 5.4 when measuring liquid level or pressure in a tank.(a) Confirmthatthereisnoleakintheconnecting

partofeachdiaphragmsealmountingflange.(b) Turn ON power and connect the communicator. Open the terminal box cover and connect

the communicator to the SUPPLY + and – terminals.

(c) Usingthecommunicator,confirmthatthetransmitter is operating properly. Check parameter values or change the setpoints as necessary.

See IM 01C25T03-01E (BRAIN communication) or IM 01C25T01-06EN (HART communication) for communicator operation. If the transmitter is equipped with an integral indicator,itsindicationcanbeusedtoconfirmthat the transmitter is operating properly.

F0501.ai

Closed tank

Transmitter mounting pipe50mm (2 inches)

Capillary tube

Differential pressuretransmitter

Diaphragm seal(high pressure side)

Diaphragm seal(low pressure side)

Figure 5.1 Liquid Level Measurement in a Closed Tank

Closed tankCapillary tube

Differential pressuretransmitter

Diaphragm seal

F0502.ai

Figure 5.2 Liquid Level Measurement in a Closed Tank

F0503.ai

Transmitter mounting pipe50mm (2 inches)

Capillary tube

pressure transmitter

Diaphragm seal(high pressure side)

Figure 5.3 Pressure Measurement

Page 28: Diaphragm Seal System EJXC80A, EJAC80E, EJXC81A, EJAC81E, … · 2019-11-20 · Flushing connection ring (High pressure side)*1 Direct Mounted Diaphragm Seal System Diaphragm Seal

<5. Operation> 5-2

IM 01C25W01-01EN

F0504.ai

Open TankOpen Tank

Figure 5.4 Liquid Level Measurement

ConfirmingthatTransmitterisOperatingProperly

Using the BT200

IMPORTANT• Analog output may change temporally in

connecting with BRAIN terminal due to aninitialcurrentflowedtoit.Topreventcommunicationsignalaffectingtheuppersystem, it is recommended to install a low-passfilter(approximately0.1s).

• Communication signal is superimposed on analog output signal. It is recommended tosetalow-passfilter(approximately0.1s) to the receiver in order to reduce the outputeffectfromcommunicationsignal.Beforeonline-communication,confirmthatcommunicationsignaldoesnotgiveeffectonthe upper system.

• If the wiring system is faulty, ‘communication error’ appears on the display.

• If the transmitter is faulty, ‘SELF CHECK ERROR’ appears on the display.

communication error

PARAM C60:SELF CHECK ERROR

Communication error (Faulty wiring)

Self-diagnostic error(Faulty transmitter)

DATA DIAG PRNT ESC

F0505.ai

Using the integral indicator

• If the wiring system is faulty, the display stays blank.

• If the transmitter is faulty, an error code is displayed.

Self-diagnostic error on the integral indicator(Faulty transmitter) F0506.ai

NOTEIf any of the above errors are indicated on the display of the integral indicator or the communicator, refer to subsection 6.6.3 for corrective action.

Verify and Change Transmitter Parameter Setting and Values

The parameters related to the following items are setatfactoryasspecifiedbythecustomer.

• Calibration range• Integral indicator display• Output mode• Software damping (optional)

Other parameters like following are shipped with the default setting.

• Low-cut• Process alarm setting• Static pressure range• Signal characterizer• Write protection Toconfirmorchangethevalues,seeIM01C25T01-06EN, 01C25T03-01E, 01C25T02-01E or 01C25T04-01EN.

Page 29: Diaphragm Seal System EJXC80A, EJAC80E, EJXC81A, EJAC81E, … · 2019-11-20 · Flushing connection ring (High pressure side)*1 Direct Mounted Diaphragm Seal System Diaphragm Seal

<5. Operation> 5-3

IM 01C25W01-01EN

5.2 Zero Point AdjustmentAfter completing preparations for operating the transmitter, adjust the zero point.

Zero point adjustment can be done by turning the transmitter’s zero-adjustment screw or by using the communicator. This section describes the procedure for the zero-adjustment screw. For the communicator procedure, see the communication manual.

IMPORTANTDonotturnoffthepowertothetransmitterimmediately after performing a zero point adjustment.Poweringoffwithin30secondsofperforming this procedure will return the zero point to its previous setting.

NOTEBefore performing this adjustment, make sure that the external zero adjustment function has NOT been disabled by a parameter setting.

To check the output signal, use a digital multimeter, calibrator, or communicator.

(1) WhenyoucanobtainLowRangeValuefrom actual measured value of 0% (0 kPa, atmospheric pressure);

Zero-adjustmentscrew cover

F0507.ai

The zero-adjustment screw is located inside the cover.

Use a slotted screwdriver to turn the zero-adjustment screw. Turn the screw clockwise to increase the output or counterclockwise to decrease the output. The zero point adjustment can be made with a resolution of 0.01% of the setting range. The degree of zero adjustments varies with the screw turning speed; turn the screw slowly to makeafineadjustment,quicklytomakearoughadjustment.

When adjusting the transmitter zero point, the liquid level in a tank does not have to be set to the low limit (0%) of the measuring range; use a digital manometer or a glass gauge to match the transmitter output signal with the actual measured value.

(2) WhenyoucannotobtainLowRangeValuefrom actual measured value of 0%;

Adjust the transmitter output to the actual measured value obtained by a digital manometer or a glass gauge.

[Example]

The measuring range of 50 to 250 kPa; the actual measured value of 130 kPa.

130–50250–50

Actual measured value= x100=40.0%(=10.4mA)

Turn the screw to match the output signal to the actual measured value.

Page 30: Diaphragm Seal System EJXC80A, EJAC80E, EJXC81A, EJAC81E, … · 2019-11-20 · Flushing connection ring (High pressure side)*1 Direct Mounted Diaphragm Seal System Diaphragm Seal

<5. Operation> 5-4

IM 01C25W01-01EN

5.2.1 ZeropointadjustmentforAbsolutePressure Diaphragm Seal System

In the case of the Absolute Pressure Diaphragm Seal System, because a head pressure is caused bythefillfluidinthecapillary,itisbasicallyrecommended to perform zero adjustment after installing the transmitter in the process and with decompressing the process pressure to vacuum pressure.However,ifitisdifficulttomaketheprocess pressure to the zero state after installation, there are a couple of applicable methods. Select the most suitable method according to the situation.

Timing Process pressure Outline

a After installation

Vacuum pressure

Decompressing the process pressure to the vacuum pressure standard and adjust the zero to it. Accurate measurement can be expected.

b After installation

Atmospheric pressure

Performing adjustment to atmospheric pressure. Measuring atmospheric pressure with a digital manometer and adjust the output to it.

c Before installation

Atmospheric pressure

Performing zero adjustment with using calculated head pressure. This procedure is performed via Communication. Select when neither ‘a’ nor ‘b’ can be applied. Errors for zero point may be caused when there’s a gap between the installation position used for calculation and the actual installation position.

(a) Decompressing the process pressure to the vacuum pressure standard and adjust the zero to it.

F0513.ai

Internal pressure: vacuum pressure

Adjustment is performed after installation under vacuum pressure. Make the process pressure to the vacuum pressure.Follow the procedures of “(1) When you can obtain Low Range Value from actual measured value of 0%” to adjust zero point to the vacuum pressure.You can also perform adjustment via communication with using a parameter “J11:P ZERO ADJ.” for BRAIN communication type, “Auto Lower pt” at “Pres trim” for HART communication type, or “CAL POINT LO” parameter for FOUNDATIONfieldbustype.Pleaserefertoeachcommunication manual.

Page 31: Diaphragm Seal System EJXC80A, EJAC80E, EJXC81A, EJAC81E, … · 2019-11-20 · Flushing connection ring (High pressure side)*1 Direct Mounted Diaphragm Seal System Diaphragm Seal

<5. Operation> 5-5

IM 01C25W01-01EN

(b) Performing adjustment to atmospheric pressure.

F0514.ai

Internal pressure: atmospheric pressure

Adjustment is performed after installation under atmospheric pressure.Measure the atmospheric pressure with a highly accurate digital manometer, and perform adjustment by following the procedures of “(2) When you cannot obtain Low Range Value from actual measured value of 0%.”You can also perform adjustment by setting the measured atmospheric value to the parameter “J11:P ZERO ADJ.” for BRAIN communication type, “Auto Lower pt” at “Pres trim” for HART communication type, or “CAL POINT LO” parameter for FOUNDATIONfieldbustype.Pleaserefereachcommunication manual.

NOTEWhen entering the atmospheric pressure, set all the available number under decimal point as much as possible to minimize errors. If you round the number, it may lead to the errors. [Example]Whensettingspanis20kPa,ifthemeasured atmospheric pressure is “97.25 kPa” and set it as “97.3 kPa”, error of 0.05 kPa (0.25% at 20 kPa) may be caused.

(c) Performing zero adjustment with using calculated head pressure.

Adjustment is performed before installation under atmospheric pressure.Use the following equation to calculate the head pressure.

Head pressure = h (mm) × ds × 9.80665 × 10-3 (kPa)

h: Vertical height between the HP process connection and the connection of remote seal oncoverflange.

ds:Specificgravityoffillfluid(at25°C). See table in the clause 4.3.

F0515.ai

h

Set the calculated value to “J15: P ZERO DEV” for BRAIN communication type, “Manual Lower Pt” for HART communication type, or “CAL_DEVIATION_LO” for FOUNDATIONfieldbustype.Thevalueshould be negative, as the head pressure shall be subtracted from the atmospheric pressure. If a value of the adjustment in the past are already existing in the parameter, add that value to make the new adjustment value.

[Example]Calculated head pressure is 50 kPa, and adjustmentvaluein“J15”is−0.04kPa;

−50+(−0.04)=−50.04(kPa)Set“−50.04”to“J15”parameterasanewadjustment value.

Page 32: Diaphragm Seal System EJXC80A, EJAC80E, EJXC81A, EJAC81E, … · 2019-11-20 · Flushing connection ring (High pressure side)*1 Direct Mounted Diaphragm Seal System Diaphragm Seal

<5. Operation> 5-6

IM 01C25W01-01EN

5.3 Starting OperationAfter completing the zero point adjustment, follow the procedure below to start operation.

1) Confirmtheoperatingstatus.Iftheoutputsignalexhibitswidefluctuations(hunting)duetoperiodic variation in the process pressure, use the communicator to dampen the transmitter outputsignal.Confirmthehuntingusingareceiving instrument or the integral indicator, and set the optimum damping time constant.

2) Afterconfirmingtheoperatingstatus,performthe following:

IMPORTANT• Remove the communicator from the terminal box,andconfirmthatnoneoftheterminalscrews are loose.

• Close the terminal box cover and the amplifiercover.Screweachcoverintightlyuntil it will not turn further.

• There are two covers that must be locked on the ATEX Flameproof type transmitters. An Allen head bolt (shrouding bolt) under the edge of each cover is used to lock the cover. When the shrouding bolt is driven counterclockwise with an Allen wrench, the bolt rotates upward and locks the cover. (See page6-4.)Afterlockingthecovers,confirmthat they are secure and cannot be opened by hand.

• Tighten the zero-adjustment cover mounting screwtofixthecoverinposition.

5.4 Shutting Down OperationTurnoffthepower.

NOTEWhenever shutting down the transmitter for a long period, detach the transmitter from the tank.

5.5 Venting or Draining Transmitter Pressure-detector Section

If condensate (or gas) collects in the transmitter pressure-detector section, the measured pressure maybeinerror.Ifitisnotpossibletoconfigurethepiping for self-draining (or self-venting) operation, you will need to loosen the drain (vent) screw on the transmitter to completely drain (vent) any stagnated liquid (gas).

However,sincedrainingcondensateorbleedingoffgas gives the pressure measurement disturbance, this should not be done when the loop is in operation.

WARNING

Since the accumulated liquid (or gas) may be toxic or otherwise harmful, take appropriate care to avoid contact with the body, or inhalation of vapors.

Page 33: Diaphragm Seal System EJXC80A, EJAC80E, EJXC81A, EJAC81E, … · 2019-11-20 · Flushing connection ring (High pressure side)*1 Direct Mounted Diaphragm Seal System Diaphragm Seal

<5. Operation> 5-7

IM 01C25W01-01EN

5.5.1 Draining Condensate1) Gradually open the drain plug and drain the

transmitter pressure-detector section. (See Figure 5.5)

2) When all accumulated liquid is completely removed, close the drain plug.

3) Tighten the drain plug to a torque of 34 to 39 N·m 3.5 to 4 kgf·m.

5.5.2 Venting Gas1) Gradually open the vent screw to vent gas from

the transmitter pressur-detector section. (See Figure 5.5)

2) When the transmitter is completely vented, close the vent screw.

3) Tighten the vent screw to a torque of 10 N·m 1 kgf·m.

F0508.ai

When you loosen the drain plug or the vent screw, the accumulated liquid (or gas) will be expelled in the direction of the arrow.

Vent screwDrain plug

Figure 5.5 Draining/Venting the Transmitter

5.5.3 Draining Condensate for Flushing Connection Ring or Inner Diaphragm Type Seal

1) Gradually open the drain screw to drain from theflushingconnectionring.

2) Whentheflushingconnectionringortheconnection adapter of the inner diaphragm type seal is completely drained, close the drain screw.

3) Tighten the drain screw to a torque of 10 N·m 1 kgf·m.

F0509.ai

Drain screw

When you loosen the drain screw, the accumulated liquid(or gas) will be expelled in the direction of the arrow.

Figure 5.6 Draining for Flushing Connection Ring

F0510.ai

Drain screw

When you loosen the drain screw, the accumulated liquid(or drain) will be expelled in the direction of the arrow.

Figure 5.7 Draining for Inner Diaphragm Type Seal

Page 34: Diaphragm Seal System EJXC80A, EJAC80E, EJXC81A, EJAC81E, … · 2019-11-20 · Flushing connection ring (High pressure side)*1 Direct Mounted Diaphragm Seal System Diaphragm Seal

<5. Operation> 5-8

IM 01C25W01-01EN

5.5.4 Venting Gas for Flushing Connection Ring or Inner Diaphragm Type Seal

1) Gradually open the vent screw to vent gas from theflushingconnectionring.

2) Whentheflushingconnectionringortheconnection adapter of the inner diaphragm type seal is completely vented, close the vent screw.

3) Tighten the vent screw to a torque of 10 N·m 1 kgf·m.

F0511.ai

Vent screw

When you loosen the vent screw, the accumulated liquid(or drain) will be expelled in the direction of the arrow.

Figure 5.8 Venting for Flushing Connection Ring

F0512.ai

Vent screw

When you loosen the vent screw, the accumulated liquid(or gas) will be expelled in the direction of the arrow.

Figure 5.9 Venting for Inner Diaphragm Type Seal

5.6 Local Parameter Setting

WARNING

The local push button on the integral indicator must not be used in a hazardous area. When it is necessary to use the push button, operate it in a non- hazardous location.

IMPORTANT• Donotturnoffthepowertothetransmitter

immediately after performing parameter setting.Poweringoffwithin30secondsofperforming this procedure will return the parameter to its previous setting.

• The parameter of Ext SW must be“Enabled” toperformthisconfiguration.Seetheuser’smanual IM 01C25T (HART/BRAIN) for the setting procedure.

• The Local Parameter Setting function is available with HART or BRAIN communication type.LCD update will be slower at low ambient temperature, and it is recommended to use LPS function at temperatures above -10 degrees C.

5.6.1 Local Parameter Setting (LPS) Overview

Parameterconfigurationbytheexternaladjustmentscrew and push button (integral indicator code E)offerseasyandquicksetupforparametersofLoop test, Tag number, Unit, LRV, URV, Damping, Output mode (linear/square root), Display out 1, and Re-range by applying actual pressure (LRV/URV) and Device Information. There is no effectonmeasurementsignal(analogoutputorcommunication signal) when Local Parameter Setting is carried out.

Page 35: Diaphragm Seal System EJXC80A, EJAC80E, EJXC81A, EJAC81E, … · 2019-11-20 · Flushing connection ring (High pressure side)*1 Direct Mounted Diaphragm Seal System Diaphragm Seal

<5. Operation> 5-9

IM 01C25W01-01EN

F0517.ai

Integral indicator

Push-button

Figure5.11 Range–SettingSwitch(pushbutton)

F0518.ai

screw

push

push

push

push

push

push

Save/Cancel the value

Save/Cancel the value

Save/Cancel the value

Save/Cancel the value

Save/Cancel the value

Save/Cancel the value

Save/Cancel the value

Save/Cancel the value

Save/Cancel the value

7. Output Mode

3. Press Unit

2. Tag Number*

*

*

*

*

*

*

4. Press LRV

5. Press URV

8. Display Out1

9. LRV-Apply Press

10. URV-Apply Press

6. Damping Time

Select Output mode

Select Press unit

Edit Tag number

Edit Press LRV

Edit Press URV

Edit Display Out1

Set LRV

Set URV

Edit Damping time

ProcessMeasurement

Display Zero adjustment

9, 10 : Re-range by applying actual pressure

ProcessMeasurement

Display

11. Device Information

Run/Cancel1. Loop Test***

Select Output Current

Activate LPS mode

**

*: Theseparameterconfigurationsareavailablewiththesoftwarerevision(SOFTREV)2.03orlater. Softwarerevisioncanbecheckedviaafieldcommunicator(HART/BRAIN)orDTM.PleaserefertoIM01C25T01forHARTparameter “Software rev” and IM 01C25T03 for BRAIN “SOFT REV.”

**:Thisparatmeterconfigurationisavailablewiththesoftewarerevision(SOFTREV)3.01orlater.***:Thisparatmeterconfigurationisavailablewiththesoftewarerevision(SOFTREV)5.01orlater.

External adjustmentscrew cover

F0516ai

Figure5.10 ExternalAdjustmentScrew

Page 36: Diaphragm Seal System EJXC80A, EJAC80E, EJXC81A, EJAC81E, … · 2019-11-20 · Flushing connection ring (High pressure side)*1 Direct Mounted Diaphragm Seal System Diaphragm Seal

<5. Operation> 5-10

IM 01C25W01-01EN

5.6.2 Activating Local Parameter SettingPress the push button on the integral indicator to activate the Local Parameter Setting mode. The transmitter will exit automatically from the Local Parameter Setting mode if no operation is carried out for 10 minutes.

5.6.3 Parameter Setting ReviewCurrent setting value for the below parameters are shown sequentially by each press of the push button.Loop test, Tag number, Unit, LRV, URV, Damping, Output mode (linear/square root), Display out 1, Re-range by applying actual pressure (LRV/URV) and Device Information.

F0519.ai

push

push

push

push

push

push

push

push

push ProcessMeasurement

Display

*

push

push

ProcessMeasurement

Display

1. Loop Test

2. Tag Number

3. Press Unit

4. Press LRV

5. Press URV

6. Damping Time

7. Output Mode (Transfer function)

8. Display Out1

9. LRV-Apply Press

10. URV-Apply Press

11. Device Information

*: [Softwarerevision:2.03]Upto6charactersareshowninthebottomline.Toreviewafterthe7thcharacter,turntheexternaladjustment screw and press the push button six times or more.

[Softwarerevision:3.01orlater]Thedisplayautomaticallyscrollstoshowallthecharacters.

Toconfigureeachparametervalue,turntheexternaladjustmentscrewoneachparameterscreenafteractivating the Local Parameter Setting mode.

TocanceltheLocalParameterSettingconfiguration,pleasereferto5.6.13SaveorCanceland5.6.14AbortConfiguration.

Page 37: Diaphragm Seal System EJXC80A, EJAC80E, EJXC81A, EJAC81E, … · 2019-11-20 · Flushing connection ring (High pressure side)*1 Direct Mounted Diaphragm Seal System Diaphragm Seal

<5. Operation> 5-11

IM 01C25W01-01EN

5.6.4 LoopTestConfigurationLooptestconfigurationcanbechagedasbelow.Outputcurrentvalue(4mA,12mAor20mA)forLooptestcan be selected by turning the external adjustment screw.

[Available loop test]

4mA: 0% output12mA: 50% output20mA: 100% output

Select by the push button or turning the extemal adjustment scerw

F0520.ai

screw

push

Select by the push button

Blinking Blinking

Run ?/Cancel ?

5.6.5 TagNumberConfigurationTag Number is edited by turning the external adjustment screw. Up to 8 alphanumeric characters for HART or 16 alphanumeric characters for BRAIN can be set.

F0521.ai

screw

push

Change the first Character Go to the next Character

Set all other characters in the same way

Blinking Blinking

Save ?/Cancel ?

5.6.6 PressureUnitConfigurationPressure unit for the below table can be changed as below. By turning the external adjustment screw, user can scroll between the various available pressure units.

F0522.ai

screw

push

Select by the push button

Blinking Blinking

Save ?/Cancel ?

[Available pressure units]

kPa bar inH2O@4degC(39.2degF)Torr mbar inH2O@20degC(68degF)atm g/cm2 inHgMPa kg/cm2 ftH2O@4degC(39.2degF)hPa Pa ftH2O@20degC(68degF)mmHg mmH2O@4degC(39.2degF)psi mmH2O@20degC(68degF)

In addition to the above units, mmAq@4degC, mmAq@20degC, mmWG@4degC and mmWG@20degC are available for BRAIN communication type.

Page 38: Diaphragm Seal System EJXC80A, EJAC80E, EJXC81A, EJAC81E, … · 2019-11-20 · Flushing connection ring (High pressure side)*1 Direct Mounted Diaphragm Seal System Diaphragm Seal

<5. Operation> 5-12

IM 01C25W01-01EN

5.6.7 PressureLRV/URVConfigurationPressure LRV and URV can be set. The number for each digit is changed by turning the external adjustment screwandsetbypressingthepushbutton.Pleasereferto5.6.8DampingTimeConstantConfigurationforhow to change the numerical value. When the setting is out of the limit, an alarm will be generated.

5.6.8 DampingTimeConstantConfigurationThedampingtimeconstantfortheamplifierassemblycanbeset.QuickResponseParameterisautomaticallyset to ON when the damping time constant is set to less than 0.5 seconds. Damping time constant is rounded offtotwodecimalplaces.

F0523.ai

screw

Change the first digit

Set all other characters in the same way

Setting range: 0.00 to 100.00 (seconds)

Blinking Blinking Blinking

Save ?/Cancel ?

push

Go to the next Character

5.6.9 OutputModeConfigurationPressure Output Mode (Linear or Sq root) can be selected by turning the external adjustment screw. Please referto5.6.6PressureUnitConfigurationforhowtoselectandsettheenumeratedvalue.

5.6.10DisplayOut1ConfigurationDisplay Out1 can be selected by turning the external adjustment screw. Please refer to 5.6.6 Pressure Unit Configurationforhowtoselectandsettheenumeratedvalue.

Page 39: Diaphragm Seal System EJXC80A, EJAC80E, EJXC81A, EJAC81E, … · 2019-11-20 · Flushing connection ring (High pressure side)*1 Direct Mounted Diaphragm Seal System Diaphragm Seal

<5. Operation> 5-13

IM 01C25W01-01EN

5.6.11 Re-rangebyapplyingactualpressure (LRV/URV).

This feature allows the lower and upper range values to be setup with the actual input applied.

F0524.ai

Follow the procedure below to change the LRV and URV settings.

[Example]

Rerange LRV to 0 and URV to 3 MPa.

1) Connect the transmitter and apparatus as shown in Figure 6.1 and warm it up for at least fiveminutes.

2) Press the push-button. The integral indicator then displays “LRV.SET.”

3) Apply a pressure of 0 kPa (atmospheric pressure) to the transmitter. (Note 1)

4) Turn the external adjustment screw in the desired direction. The integral indicator displays the output signal in %. (Note 2)

5) Adjust the output signal to 0% (1 V DC) by rotating the external adjustment screw. Press the push button to save the value. Doing so completes the LRV setting. (Note 3)

6) Press the push-button. The integral indicator then displays “URV.SET.”

7) Apply a pressure of 3 MPa to the transmitter. (Note 1)

8) Turn the external adjustment screw in the desired direction. The integral indicator displays the output signal in %. (Note 2)

9) Adjust the output signal to 100% (5 V DC) by rotating the external adjustment screw. Press the button to save the value.Doing so completes the URV setting.

10) Press the push-button. The transmitter then switches back to the normal operation mode with the measurement range of 0 to 3 MPa.

Note 1: Wait until the pressure inside the pressure-detector section has stabilized before proceeding to the next step.

Note 2: If the pressure applied to the transmitter exceeds the previous LRV (or URV), the integral indicator may display error number “AL.30” (In this case, the output signal percent and “AL.30” are displayed alternately every two seconds). Although “AL.30” is displayed, you may proceed to the next step. However, should any other error number be displayed, take the appropriate measure in reference to , “Errors and Countermeasures” in each communication manual.

Note 3 : Changing the lower range value (LRV) also automatically changes the upper range value (URV), keeping the span constant. New URV=previous URV+(new LRV–previous LRV)

5.6.12 Device Information DisplayModel name, communication protocol, device revision and software revision are displayed repeatedly.

5.6.13 Save or CancelAt the end of each parameter setting, select “Save” or “Cancel” by the external adjustment screw and press the push button to save or cancel the configuration.

Save? Saved

Save or Cancel

Cancel? Canceled

screw

F0525.ai

push

push

After parameter

setting

Page 40: Diaphragm Seal System EJXC80A, EJAC80E, EJXC81A, EJAC81E, … · 2019-11-20 · Flushing connection ring (High pressure side)*1 Direct Mounted Diaphragm Seal System Diaphragm Seal

<5. Operation> 5-14

IM 01C25W01-01EN

5.6.14AbortConfiguration

5.6.14.1AbortConfiguration(Menu)Hold down the push button for over 2 seconds to exit the Local Parameter Setting mode.

Hold down the button for over 2 seconds

Proccess Value

Process Measurement Display

Process Measurement Display

1. Loop Test

2. Tag Number

3. Press Unit

4. Press LRV

5. Press URV

11. Device Information

F0526.ai

Jum

p to

the

norm

al m

ode

:

:

5.6.14.2AbortConfiguration(Parameter)Toexittheconfigurationwhileeditingthevalue,hold down the button for over 2 seconds and select “Save” or “Cancel.”

F0527.ai

Return to parameter review window

Save or Cancel?Push for Over 2 seconds

Tag editing (3rd Character)

5.6.15 Local Parameter Setting LockTo disable parameter changes by the Local ParameterSettingtherearethreedifferentways.

Locked featuresCommunication ParameterExt SW =disable(EXT ZERO ADJ = disable)

• External Zero Adjustment

• Local Parameter SettingCommunication ParameterWrite Protect = On(WRT PROTECT = Yes)

• Local Parameter Setting• All Communication

Parameters *Hardware write protection switch on CPU assembly = D (Disable)

• Local Parameter Setting • All Communication

Parameters **External Zero Adjustment is unlocked.

The above parameter setting is carried out by usingfieldcommunicatororDTM.Seetheuser’smanual IM 01C25T (HART/BRAIN) for the setting procedure.Reviewing local parameter setting by push button on the integral indicator is available at any time even when the Local Parameter Setting is locked.

5.6.16 Others• DifferencebetweenBRAINandHART

HART BRAIN

Tag NumberUp to 8 characters can be set

Up to 16 characters can be set

Output Mode(Linear/Sq root)

“TRNS.FC” shown on the integral indicator

“OUT.MOD” shown on the integral indicator

• The degree of adjustment depends on the speed of turning the adjustment screw. Turn the screwslowlyforfinetuningandturnthescrewfast for quick tuning.

Page 41: Diaphragm Seal System EJXC80A, EJAC80E, EJXC81A, EJAC81E, … · 2019-11-20 · Flushing connection ring (High pressure side)*1 Direct Mounted Diaphragm Seal System Diaphragm Seal

<6. Maintenance> 6-1

IM 01C25W01-01EN

6. Maintenance6.1 Overview

WARNING

Sincetheaccumulatedprocessfluidmaybetoxic or otherwise harmful, take appropriate care to avoid contact with the body or inhalation of vapors when draining condensate or venting gas from the transmitter pressure-detector section and even after dismounting the instrument from the process line for maintenance.

Maintenance of the transmitter is easy due to its modular construction. This chapter describes the procedures for calibration, adjustment, and the disassembly and reassembly procedures required for component replacement.

Transmitters are precision instruments. Please carefully and thoroughly read the following sections for information on how to properly handle them while performing maintenance.

IMPORTANT• As a rule, maintenance of this transmitter

should be done in a shop that has all the necessary tools.

• The CPU assembly contains sensitive parts that can be damaged by static electricity. Take precautions such as using a grounded wrist strap when handling electronic parts or touching the board circuit patterns. Also be sure to place the removed CPU assembly into a bag with an antistatic coating.

6.2 CalibrationInstrumentsSelection

Table 6.1 lists the instruments that can be used to calibrate a transmitter. When selecting an instrument, consider the required accuracy level. Exercise care when handling these instruments to ensuretheymaintainthespecifiedaccuracy.

6.3 CalibrationUse the procedure below to check instrument operation and accuracy during periodic maintenance or troubleshooting.

1) Connecttheinstrumentsasshowninfigure6.1a and 6.1b and warm up the instruments for atleastfiveminutes.

IMPORTANT• To adjust the transmitter for highest

accuracy, make adjustments with the power supply voltage and load resistance including leadwire resistances set close to the conditions under which the transmitter is installed.

• If the measurement range 0% point is 0 kPa or shifted in the positive direction (suppressed zero), the reference pressure shouldbeappliedasshowninthefigure. If the measurement range 0% point is shifted in the negative direction (elevated zero), the reference pressure should be applied using a vacuum pump.

2) Apply reference pressures of 0%, 50%, and 100% of the measurement range to the transmitter.Calculatetheerrors(differencesbetween digital voltmeter readings and reference pressures) as the pressure is increased from 0% to 100% and is decreased from100%to0%,andconfirmthattheerrorsare within the required accuracy.

Page 42: Diaphragm Seal System EJXC80A, EJAC80E, EJXC81A, EJAC81E, … · 2019-11-20 · Flushing connection ring (High pressure side)*1 Direct Mounted Diaphragm Seal System Diaphragm Seal

<6. Maintenance> 6-2

IM 01C25W01-01EN

Table6.1 InstrumentsRequiredforCalibration

Name Yokogawa-recommended Instrument RemarksPower supply Model SDBT or SDBS distributor 4 to 20 mA DC signalLoad resistor Model2792standardresistor[250Ω±0.005%,3W]

Loadadjustmentresistor[100Ω±1%,1W]Voltmeter Model 2501 A digital multimeter

Accuracy(10VDCrange):±(0.002%ofrdg+1dgt)Digital manometer

Model MT220 precision digital manometer1) For 10 kPa class Accuracy:±(0.015%ofrdg+0.015%ofF.S.). . . . for 0 to 10 kPa ±(0.2%ofrdg+0.1%ofF.S.) . . . . . . . . for -10 to 0 kPa2) For 130 kPa class Accuracy:±0.02%ofrdg . . . . . . . . . . . . . . . . . . . . for 25 to 130 kPa ±5digits . . . . . . . . . . . . . . . . . . . . . . . . . for 0 to 25 kPa ±(0.2%ofrdg+0.1%ofF.S.) . . . . . . . . for -80 to 0 kPa3) For 700 kPa class Accuracy:±(0.02%ofrdg+3digits) . . . . . . . . . . . for 100 to 700 kPa ±5digits . . . . . . . . . . . . . . . . . . . . . . . . for 0 to 100 kPa ±(0.2%ofrdg+0.1%ofF.S.) . . . . . . . . for -80 to 0 kPa4) For 3000 kPa class Accuracy:±(0.02%ofrdg+10digits) . . . . . . . . . . for 0 to 3000 kPa ±(0.2%ofrdg+0.1%ofF.S.) . . . . . . . . for -80 to 0 kPa5) For 130 kPa abs class Accuracy:±(0.03%ofrdg+6digits) . . . . . . . . . . . for 0 to 130 kPa abs

Select a manometer having a pressure range close to that of the transmitter.

Pressure generator

Model 7674 pneumatic pressure standard for 200 kPa 2 kgf/cm2, 25 kPa 2500 mmH2O

Accuracy:±0.05%ofF.S.

Requires air pressure supply.

Dead weight gauge tester 25 kPa 2500 mmH2OAccuracy:±0.03%ofsetting

Select the one having a pressure range close to that of the transmitter.

Pressure source

Model 6919 pressure regulator (pressure pump)Pressure range: 0 to 133 kPa 1000 mmHg

Prepare the vacuum pump for negative pressure ranges.

Note: The above table contains the instruments capable of performing calibration to the 0.2% level. Since special maintenance and management procedures involving traceability of each instrument to higher-level standards are required for calibration to the 0.1% orhigherlevel,theremaybedifficultiesincalibrationtothislevelinthefield.Forcalibrationtothe0.1%level,contactYokogawarepresentativesfromwhichtheinstrumentwaspurchasedorthenearestYokogawaoffice.

Page 43: Diaphragm Seal System EJXC80A, EJAC80E, EJXC81A, EJAC81E, … · 2019-11-20 · Flushing connection ring (High pressure side)*1 Direct Mounted Diaphragm Seal System Diaphragm Seal

<6. Maintenance> 6-3

IM 01C25W01-01EN

F0601.ai

P

P

V

Mating calibration flange

Load resistance, 250Ω

Model MT220precision digital manometer

High pressure sidediaphragm seal

Rc RLoad adjustmentresistance, 100Ω

Digital voltmeter

Powersupply

E

Low pressure side diaphragm seal

Model 7674 pneumaticpressure standards

Pressure source

Supply pressure

If a pressuregenerator is used:

If a pressure sourceand a manometerare combined:

PC/FieldMate

Figure 6.1a EJXC80A/EJAC80E Instrument Connections (4 to 20 mA output)

F0602.ai

P

P

V

Reference pressure

Load resistance, 250Ω

MT220 precision digital manometer

Rc RLoad adjusting resistance100Ω Digital voltmeter

Powersupply

E

7674 pneumatic pressure standard

Pressure source

Supply pressure

PC/FieldMate

When using a pressure source with a digital manometer

When using a pressure generator

Figure6.1b EJXC50A/EJAC50EInstrumentConnections(4to20mAoutput)

Page 44: Diaphragm Seal System EJXC80A, EJAC80E, EJXC81A, EJAC81E, … · 2019-11-20 · Flushing connection ring (High pressure side)*1 Direct Mounted Diaphragm Seal System Diaphragm Seal

<6. Maintenance> 6-4

IM 01C25W01-01EN

6.4 DisassemblyandReassembly

This section describes procedures for disassembly and reassembly for maintenance and component replacement.

AlwaysturnOFFpowerandshutoffandreleasepressures before disassembly. Use proper tools for all operations. Table 6.2 shows the tools required.

Table6.2 ToolsforDisassemblyandReassembly

Tool Quantity RemarksPhillips screwdriver

1 JIS B4633, No. 2

Slotted screwdriver

1

Allen wrenches 3 JIS B4648 One each, nominal 3, 4 and 2.5 mm Allen wrenches

Wrench 1 Widthacrossflats,17mmTorque wrench 1Adjustable wrench

1

Socket wrench 1 Widthacrossflats,16mmSocket driver 1 Widthacrossflats,5.5mmTweezers 1

CAUTIONPrecautions for ATEX Flameproof Type Transmitters• Flameproof type transmitters must be, as

a rule, removed to a non-hazardous area for maintenance and be disassembled and reassembled to the original state.•Ontheflameprooftypetransmittersthetwo

covers are locked, each by an Allen head bolt (shrouding bolt). When a shrouding bolt is driven clockwise by an Allen wrench, it is going in and cover lock is released, and then the cover can be opened.

When a cover is closed it should be locked by a shrouding bolt without fail. Tighten the shrouding bolt to a torque of 0.7 N·m 7 kgf·cm.

Shrouding Bolt

Shrouding Bolt F0603.ai

Figure 6.2 Shrouding Bolts

6.4.1 Replacing the Integral Indicator

CAUTIONCautions for Flameproof Type TransmittersUsers are prohibited by law from modifying the constructionofaflameprooftypetransmitter.This would invalidate the agency approval for the use of the transmitter in a rated area. It follows that the user is prohibited from using aflameprooftypetransmitterwithitsintegralindicator removed, or from adding an integral indicatortoatransmitter.Ifsuchmodificationisabsolutely required, contact Yokogawa.

This subsection describes the procedure for replacinganintegralindicator.(Seefigure6.3)

Removing the Integral Indicator

1) Remove the cover.2) While supporting the integral indicator with one

hand, loosen its two mounting screws.3) Dismount the LCD board assembly from the

CPU assembly. When doing this, carefully pull the LCD board

assembly straight forward so as not to damage the connector pins between it and the CPU assembly.

Attaching the Integral Indicator

1) Align both the LCD board assembly and CPU assembly connectors and engage them.

2) Insert and tighten the two mounting screws.3) Replace the cover.

F0604.ai

Pressforward

Output terminal cable

Zero-adjustmentscrew pin

Slide switch

Boss Zero-adjustmentscrew

Integralindicator

Mounting screwAmplifier Cover

CPU assemblyBracket(for zero-adjustmentscrew pin)

LCD board assembly

Figure 6.3 Removing and Attaching LCD Board AssemblyandCPUAssembly

Page 45: Diaphragm Seal System EJXC80A, EJAC80E, EJXC81A, EJAC81E, … · 2019-11-20 · Flushing connection ring (High pressure side)*1 Direct Mounted Diaphragm Seal System Diaphragm Seal

<6. Maintenance> 6-5

IM 01C25W01-01EN

6.4.2 ReplacingtheCPUBoardAssemblyThis subsection describes the procedure for replacingtheCPUassembly.(Seefigure6.3)

RemovingtheCPUAssembly

1) Remove the cover. If an integral indicator is mounted, refer to subsection 6.4.1 and remove the indicator.

2) Turn the zero-adjustment screw to the position (where the screw head slot is horizontal) as showninfigure6.3.

3) Disconnect the output terminal cable (cable with brown connector at the end). When doing this, lightly press the side of the CPU assembly connector and pull the cable connector to disengage.

4) Useasocketdriver(widthacrossflats,5.5mm)to loosen the two bosses.

5) Carefully pull the CPU assembly straight forward to remove it.

6) Disconnecttheflatcable(cablewithwhiteconnector at the end) that connects the CPU assembly and the capsule.

NOTEBe careful not to apply excessive force to the CPU assembly when removing it.

MountingtheCPUAssembly

1) Connecttheflatcable(withwhiteconnector)between the CPU assembly and the capsule.

2) Connect the output terminal cable (with brown connector).

NOTEMake certain that the cables are free of pinching between the case and the CPU assembly edge.

3) Align and engage the zero-adjustment screw pin with the groove on the bracket on the CPU assembly. Then insert the CPU board assembly straightontothepostintheamplifiercase.

4) Tighten the two bosses. If the transmitter is equipped with an integral indicator, refer to subsection 6.4.1 to mount the indicator.

NOTEConfirmthatthezero-adjustmentscrewpinisplaced properly in the groove on the bracket prior to tightening the two bosses. If it is not, the zero-adjustment mechanism will be damaged.

5) Replace the cover.

6.5 Replacing the Process Connector Gasket

This section describes the procedure for replacing the process connector gasket. (See Figure 6.4)

1) Loosen the two bolts and remove the process connector.

2) Replace the process connector gasket.3) Mount the process connector. Tighten the bolts

securely and uniformly to a torque of 39 to 49 N·m 4 to 5 kgf·m, and verify that there are no pressure leaks.

F0609.ai

Process connector gasket

Process connector

Bolt

Figure 6.4 Replacing the Process Connector Gasket

Page 46: Diaphragm Seal System EJXC80A, EJAC80E, EJXC81A, EJAC81E, … · 2019-11-20 · Flushing connection ring (High pressure side)*1 Direct Mounted Diaphragm Seal System Diaphragm Seal

<6. Maintenance> 6-6

IM 01C25W01-01EN

6.6 DisassemblyandReassemblyofConnectionAdapter of Inner Diaphragm Type Seal

• Removing the connection adapter, exercise care so as not to damage the diaphragm surfaces.(Seefigure4.3)

• When re-mounting the connection adapter, use the new gasket as shown in the table.

• Install the connection adapter, and use a torque wrench to tighten the four bolts uniformly to a torque of 59N·m.

• After the pressure detector section has been reassembled, a leak test must be performed to verify that there are no pressure leaks.

Part No. DescriptionF9270AM For general use F9270AM-A For oil-prohibited useF9994CA For high temperature useF9300AS For special materialF9300AT For special material and oil-prohibited

useF9994CC For high temperature and oil-prohibited

use

6.7 TroubleshootingIf any abnormality appears in the measured values, usethetroubleshootingflowchartbelowtoisolateand remedy the problem. Since some problems havecomplexcauses,theseflowchartsmaynotidentifyall.Ifyouhavedifficultyisolatingorcorrecting a problem, contact Yokogawa service personnel.

6.7.1 BasicTroubleshootingFirst determine whether the process variable is actually abnormal or a problem exists in the measurement system.

If the problem is in the measurement system, isolate the problem and decide what corrective action to take.

This transmitter is equipped with a self-diagnostic function which will be useful in troubleshooting, and the transmitter equipped with an integral indicator will show an alarm code as a result of self-diagnosis. See subsection 6.7.3 for the list of alarms. See also each communication manual.

Abnormalities appear in measurement.

: Areas where self-diagnostic offers support

Is process variableitself abnormal?

Inspect theprocess system.

Isolate problem inmeasurement system.

Does problem exist inreceiving instrument?

Check/correctenvironmental conditions.

Inspect receiver.

Check transmitter.

Check/correct operatingconditions.

Measurement system problem

F0605.ai

YES

NO

NO

YES

Environmental conditions

Operating conditions

Transmitter itself

Figure 6.5 Basic Flow and Self-Diagnostics

Page 47: Diaphragm Seal System EJXC80A, EJAC80E, EJXC81A, EJAC81E, … · 2019-11-20 · Flushing connection ring (High pressure side)*1 Direct Mounted Diaphragm Seal System Diaphragm Seal

<6. Maintenance> 6-7

IM 01C25W01-01EN

6.7.2 TroubleshootingFlowcharts

Connect communicator and check self-diagnostics.

Does the self-diagnosticindicate problem location?

Contact Yokogawa service personnel.

F0606.ai

The following sorts of symptoms indicate that transmitter may not be operating properly.Example : • There is no output signal. • Output signal does not change even though process variable is known to be varying. • Output value is inconsistent with value inferred for process variable.

Is power supplypolarity correct?

Are powersupply voltage and load

resistance correct?

Check/correct polarity at each terminal from power supply to the terminal box.

Fix pressure leaks, paying particularattention to connections for impulsepiping,pressure-detector section, etc.

Fully close equalizing valve, and fullyopen high pressure and low pressurevalves.

Check rated voltage and load resistance.

Find/correct broken conductor or wiring error.

Are valves opened orclosed correctly?

Is there any pressure leak?

Is therecontinuity through the

transmitter loop wiring?Do the loop numbers

match?

YES

NO

YES

NO

NO

YES

NO

NO

YES

YES

NO

YES

Refer to error message summary in Subsection 6.7.3 or in each communication manual to take actions.

Connect BRAIN TERMINAL and check self-diagnostics.

Does the self-diagnostic indicate problem

location?

Contact Yokogawa service personnel.F0607.ai

Is power supplypolarity correct?

Are valves opened or closed correctly?

Refer to error message summary in each communication manual to take actions.

YES

NO

NO

YES Check/correct polarity at each terminal from power supply to the terminal box.

Fix pressure leaks, paying particularattention to connections for impulsepiping, pressure-detector section, etc.

Fully open the low pressure valve.

NO

YES

YES

NO

Adjust the zero point.

NO

YES

Is there any pressure leak?

Is zero point adjusted correctly?

Output travels beyond 0% or 100%.

Page 48: Diaphragm Seal System EJXC80A, EJAC80E, EJXC81A, EJAC81E, … · 2019-11-20 · Flushing connection ring (High pressure side)*1 Direct Mounted Diaphragm Seal System Diaphragm Seal

<6. Maintenance> 6-8

IM 01C25W01-01EN

Connect BRAIN TERMINAL and check self-diagnostics.

Contact Yokogawa service personnel.

F0608.ai

Are valves opened orclosed correctly?

Refer to error message summary in each communication manual to take actions.

Check rated voltage and load resistance.

Provide lagging and/or cooling, or allowadequate ventilation.

Refer to Section 6.2 when selectinginstruments for calibration.

Fully open the low pressure valve.

Adjust the output.

Is transmitterinstalled where there is

marked variation intemperature?

Is output adjusted correctly?

Large output error.

Does the self-diagnostic indicate problem

location?

Are power supplyvoltage and load resistance

correct?

Were appropriateinstruments used for

calibration?

YES

NO

YES

NO

NO

YES

NO

YES

NO

YES

NO

YES

Page 49: Diaphragm Seal System EJXC80A, EJAC80E, EJXC81A, EJAC81E, … · 2019-11-20 · Flushing connection ring (High pressure side)*1 Direct Mounted Diaphragm Seal System Diaphragm Seal

<6. Maintenance> 6-9

IM 01C25W01-01EN

6.7.3 Alarms and Countermeasures

Table6.3 AlarmMessageSummary

Indicator Cause Output Operationduring Error Countermeasure

NoneAL. 01CAP. ERR

Sensor problem. Outputs the signal (Hold, High, or Low) set with parameter.

Replace capsule when error keeps appearing even after restart.

Capsule temperature sensor problem.Capsule EEPROM problem.

AL. 02AMP. ERR

Amplifiertemperaturesensorproblem.

Outputs the signal (Hold, High, or Low) set with parameter.

Replaceamplifier.

AmplifierEEPROMproblem.Amplifierproblem.

AL. 10PRESS

Input is outside measurement range limit of capsule.

Outputs high range limit value or low range limit value.

Check input or replace capsule when necessary.

AL. 11ST. PRSS

Static pressure exceeds limit. Continues to operate and output.

AL. 12CAP. TMP

Capsule temperature is outside range (–50 to 130°C).

Use heat insulation or make lagging to keep temperature within range.AL. 13

AMP. TMPAmplifiertemperatureisoutsiderange (–50 to 95°C)

AL. 30RANGE

Output is outside upper or lower range limit value.

Outputs high range limit value or low range limit value.

Check input and range setting, and change them as needed.

AL. 31SP. RNG

Staticpressureexceedsspecifiedrange.

Continues to operate andoutput.

AL. 35 *1

P. HIInputpressureexceedsspecifiedthreshold.

Check input.

AL. 36 *1

P. LOAL. 37 *1

SP. HIInput static pressure exceeds specifiedthreshold.

AL. 38 *1

SP. LOAL. 39 *1

TMP. HIDetected temperature exceeds specifiedthreshold.

AL. 40 *1

TMP. LOAL. 50P. LRV

Specifiedvalueisoutsideofsettingrange.

Holds output immediately before error occurred.

Check setting and change them as needed.

AL. 51P. URVAL. 52P. SPNAL. 53P. ADJ

Continues to operate and output. Check input.

AL. 54SP. RNG

Continues to operate and output holding static pressure in %.

Check setting and change them as needed.

AL. 55SP. ADJ

Continues to operate and output. Check input.

AL. 60SC. CFG

Specifiedvaluesorsettingstodefinesignalcharacterizerfunctiondo not satisfy the condition.

Check setting and changethem as needed.

AL. 79OV. DISP

Displayed value exceeds limit.

*1: These alarms may appear only when process alarm function is activated.

Page 50: Diaphragm Seal System EJXC80A, EJAC80E, EJXC81A, EJAC81E, … · 2019-11-20 · Flushing connection ring (High pressure side)*1 Direct Mounted Diaphragm Seal System Diaphragm Seal

<7.GeneralSpecifications> 7-1

IM 01C25W01-01EN

7. GeneralSpecificationsPleaserefertothefollowingGeneralSpecificationslistforthespecifications,model,suffixandoptioncodes,and external dimensions of each product. Forthespecificationsspecifictothediaphragmsealsystem,refertotheGeneralSpecificationofdiaphragmseal system(GS 01C25W01-01EN.)Forthosespecificationswhicharecommonwiththeoriginaltransmitters,refertotheGeneralofeachtransmitter(EJ110, EJ310, EJ430, and EJ530.)TheGeneralSpecificationscanbedownloadedfromthewebsiteofYokogawa.Website address: https: //www.yokogawa.com/solutions/products-platforms/field-instruments/

GeneralSpecificationsListModel Document Title Document No.

EJX110A DifferentialPressureTransmitter GS 01C25B01-01ENEJX120A DifferentialPressureTransmitter GS 01C25B03-01ENEJX130A DifferentialPressureTransmiter GS 01C25B04-01ENEJX210A FlangeMountedDifferentialPressureTransmitter GS 01C25C01-01ENEJX310A Absolute Pressure Transmitter GS 01C25D01-01ENEJX430A Gauge Pressure Transmitter GS 01C25E01-01ENEJX440A Gauge Pressure Transmitter GS 01C25E02-01ENEJX510A, EJX530A Absolute and Gauge Pressure Transmitters GS 01C25F01-01ENEJX610A, EJX630A Absolute and Gauge Pressure Transmitters GS 01C25F05-01ENEJX118A DiaphragmSealedDifferentialPressureTransmitter GS 01C25H01-01ENEJX118A DiaphragmSealedDifferentialPressureTransmitter(InnerDiaphragmtype) GS 01C25H01-11ENEJX438A Diaphragm Sealed Gauge Pressure Transmitter GS 01C25J03-01ENEJX438A Diaphragm Sealed Gauge Pressure Transmitter (Inner Diaphragm type) GS 01C25J03-11ENEJX115A Low Flow Transmitter GS 01C25K01-01ENEJX910A Multivariable Transmitter GS 01C25R01-01ENEJX930A Multivariable Transmitter GS 01C25R04-01ENEJXC50A, EJXC40A, EJAC50E, C20FE, C20FW, C10FR, EJXC80A, EJAC80E, C81FA, C82FA, C81FD, C82FD, C30SW, C30SE, C80FW, C80FE, EJXC81A, EJAC81E, C70SE, C70SW

Diaphragm Seal System GS 01C25W01-01EN

EJXC40A Digital Remote Sensor GS 01C25W05-01ENEJX110A, EJX130A DifferentialPressureTransmitterHighDampingCapsule(OptionCode:/HD) GS 01C25V01-01ENEJX110A DifferentialPressureTransmittersHighDampingCapsule(General)

(Option Code: /HD2) GS 01C25V02-01EN

EJX-A, EJA-E ExplosionProtectedTypeandMarineCertificateType GS 01C25A20-01ENEJA110E DifferentialPressureTransmitter GS 01C31B01-01ENEJA120E DifferentialPressureTransmitter GS 01C31B03-01ENEJA130E DifferentialPressureTransmitter GS 01C31B04-01ENEJA210E FlangeMountedDifferentialPressureTransmitter GS 01C31C01-01ENEJA310E Absolute Pressure Transmitter GS 01C31D01-01ENEJA430E Gauge Pressure Transmitter GS 01C31E01-01ENEJA440E Gauge Pressure Transmitter GS 01C31E02-01ENEJA510E, EJA530E Absolute Pressure Transmitter and Gauge Pressure Transmitter GS 01C31F01-01ENEJA118E DiaphragmSealedDifferentialPressureTransmitter GS 01C31H01-01ENEJA118E DiaphragmSealedDifferentialPressureTransmitter(InnerDiaphragmtype) GS 01C31H01-11ENEJA438E Diaphragm Sealed Gauge Pressure Transmitter GS 01C31J03-01ENEJA438E Diaphragm Sealed Gauge Pressure Transmitter (Inner Diaphragm type) GS 01C31J03-11ENEJA115E Low Flow Transmitter GS 01C31K01-01ENEJAC60E, EJA560E Hygienic Adapter System (Fluidless Type)

Hygienic Gauge Pressure Transmitter (Fluidless Type) GS 01C31Y01-01EN

EJA110E, EJA130E DifferentialPressureTransmitterHighDampingCapsule(OptionCode:/HD) GS 01C31V01-01ENEJA110E DifferentialPressureTransmittersHighDampingCapsule(General)

(Option Code: /HD2) GS 01C31V02-01EN

Ifyoucannotfinditonourwebsite,pleasecontactYOKOGAWAoffice.

Page 51: Diaphragm Seal System EJXC80A, EJAC80E, EJXC81A, EJAC81E, … · 2019-11-20 · Flushing connection ring (High pressure side)*1 Direct Mounted Diaphragm Seal System Diaphragm Seal

i

IM 01C25W01-01EN

Revision Information Title : Diaphragm Seal System EJXC80A, EJAC80E, EJXC81A, EJAC81E, EJXC50A and EJAC50E Manual No. : IM 01C25W01-01EN

Edition Date Page Revised Item1st June 2016 — New publication2nd Dec. 2016

1-13-13-2

4-1 to 4-95-15-46-3

6-5 to 6-67-1 to 7-95

Delete sections 1.3, 2.9 to 2.12, and chapter 5.(Those contents are to be referred to each transmitter’s manual from this edition.) Add model EJXC80A, EJAC80E, C80FW, C80FE, C81FA, C82FA, C81FD, C82FD, C30SW, and C30SE.1. Add outline of the series of products and document list.3. Add EJC80. Changethefigure3.2.

Add 4.2 to 4.5 and 4.7.5.1AddfigureofEJC80.Add 5.5.6.2AddfigureofEJC80.Add 6.5 and 6.6.ReflectGS01C25W01-01EN(2).

3rd Oct. 2018

1-1 to 1-22-1

3-1 to 3-24-14-34-7

4-94-104-12

5-1 to 5-25-4 to 5-5

6-67-1 to 7-112

Add EJC81 Absolute Diaphragm Seal System. Add Combination Type (Direct-mount and Remote- mount) and Hygienic Type for EJC80 Diaphragm System. Add EJC8C Modify BT200 screen image.1. Add Absolute Diaphragm Seal System. Add style S2 of EJA-E series.2. Add EJC81 and EJ310.3. Add EJC81.4.1 Add EJC81.4.3 Add EJC81 to the title and add descriptions to IMPORTANT. 4.7 Add EJC80. 4.7.1and4.7.2Addfigureofhygienicremoteseal.4.7.3 Add ISO51 clamp in Table 4.1 and 4.2.4.8 Modify description for rotation. Add WARNING.4.10.2 Correct parts No. in Table 4.3 (9900 > 9990)4.11 Add *1 in Figure 4.20.5.1 Add Figure 5.2 and 5.4.5.2.1 Add subsection “Zero point adjustment for Absolute Pressure Diaphragm

Seal System.”6.6 Add parts number for high temperature and oil-prohibited use.7.Addspecifications.

4th Nov. 2019 1-2

4-1

4-45-87-1

1. Change NOTE to WARNING. Update contents. Update the contents of WARNING for SIS.

4.1 Add items in IMPORTANT.4.2.1 Add table for ød.4.3Addfillfluiddensitytable.5.6 Update the descriptions for LPS.7.DeleteStandardSpecificationsandaddguidetoGS.