DeltaV SISTM for Process Safety SystemsSmart Safety Loops. Reliable Process.

Page 2: DeltaV SISTM for Process Safety Systems

The DeltaV SISTM system helps you reliably protect your assets and improve your plant

performance. Increased safety integrity is provided by continuously monitoring the ability of sensors,

logic solvers, and final elements to perform on demand, with faults diagnosed before they cause

spurious trips. The Smart safety instrumented system (SIS) approach increases process reliability

and reduces lifecycle costs.

Page 2–DeltaV SIS system

Smart SIS, an extension of thePlantWebTM digital plantarchitecture, provides anintegrated approach to completesafety loops–from sensor, to logicsolver, to final control element. Asa key component of Emerson’sSmart SIS, the DeltaV SIS systemshuts down your plant whenneeded for safety, but keeps yourunning safely when devices fail.

The unique modular, distributedarchitecture enables you tocustom fit the system to your SISapplications. This modularity givesyou the capability to meetchanging project requirements.The DeltaV SIS architecture isflexible to help provide the safetyyou want, when you want, where you want.

Smart SISOptimized process reliability.

Modular Distributed ArchitectureFlexibility to meet your project needs.

SensorsLogic Solvers

Smart SIS

Final ControlElements

Page 3: DeltaV SISTM for Process Safety Systems

Page 3–DeltaV SIS system

As an integrated control and safetysystem (ICSS), the DeltaV SIS andDeltaV systems share the sameengineering, maintenance, andoperations environment. Allsafety-related information is easilyaccessible through familiar andintuitive applications.

The integrated but separatearchitecture meets IEC 61508 andIEC 61511 requirements forphysical separation andindependence of safety andcontrol. The DeltaV SIS systemdelivers the benefits of totalintegration and total separationwithout the tradeoffs associatedwith the two extremes.

As a stand-alone system, DeltaVSIS can easily be integrated withcontrol systems from othervendors using interfaces that arebased on open communicationstandards, such as Modbus, OPCand OPC Express Interface (Xi).

The IEC 61508-certified SISfunction blocks deliver powerfulfunctionality out of the box,simplifying the implementation ofcomplex SIS applications. Nocustom code is required toimplement common SIS tasks. Theresult is faster configuration andtroubleshooting of SIS logic.

Standard operator faceplatesautomatically provide detailedsafety information with noconfiguration. Using these SISfunction blocks can helpeliminate engineering hoursrequired to implement emergencyshutdown (ESD) systems, fire andgas systems (FGS), and burnermanagement systems (BMS).

The DeltaV SIS system is built forIEC 61511 compliance, providingstringent change management,security management, anddocumentation tools. The systemis certified by TÜV for use in safetyintegrity level (SIL) 3 applicationswithout restriction. DeltaV SIS isbuilt from the ground up to

simplify IEC 61511 compliance,eliminating your concerns relatedto proper implementation.

Integrated but SeparateIncreased visibility into your process.

Certified Function BlocksReduced engineering and complexity.

Built for IEC 61511 ComplianceSimplified safety lifecycle management.

Page 4: DeltaV SISTM for Process Safety Systems

The proven PlantWeb digital plantarchitecture helps you detectoperations, process, andequipment problems before theyeven occur, so you can move fromreactive to proactive andprofitable management.

Only Emerson ProcessManagement reliably protects yourassets by providing an integratedapproach to complete safetyloops. Improve your performanceby continuously monitoring anddiagnosing the ability of thesensors, logic solvers, and finalcontrol elements to perform ondemand as required.

Page 4–DeltaV SIS system

SmartSIS

Modular,Distributed

Architecture

Integratedbut

Separate

CertifiedFunction

Blocks

Built-inIEC 61511

Compliance

The DeltaV SIS system is IEC 61508 certified for use in SIL 3applications and provides a comprehensive solution for yourprocess safety system.

� Modular DeltaV SIS logic solver with configurable HART TM I/O

� Embedded digital field communications and integrated asset

management

� Integrated operations environment with easy access to all safety and

control information

� Intuitive function block engineering environment with integrated

change management

� Automatic event reporting of safety information

� Non-intrusive simulation for training and offline testing.

Engineering Operations

Page 5: DeltaV SISTM for Process Safety Systems

Page 5–DeltaV SIS system

Services

The integrated control andsafety system architecture

delivered by the DeltaVand DeltaV SIS systemsprovide reliability and

redundancy.

� Ethernet network

connections

�Controllers

�Digital HART I/O and classic

field interface cards

�Modbus RTU/ASCII interface

�DeltaV SIS logic solvers

� SISNet communications

�Zone servers

�OPC servers

�Backup workstations

Digital Communications

�HART

�Modbus RTU/ASCII/TCP

� Ethernet/IP

�OPC

Maintenance Application Station

Page 6: DeltaV SISTM for Process Safety Systems

A total loop approach tosafetyEmerson’s Smart SIS is theextension of the PlantWebarchitecture to safety instru-mented systems. With integrateddigital communications and devicediagnostics from the sensor, to thelogic solver, to the final controlelement, DeltaV SIS shuts downyour plant when needed for safety,but keeps you running safely whencomponents fail.

Safety instrumented systemsperform a critical role in providingsafer, more reliable processoperations. Based on industryresearch, over 92% of all faults inSIS application occur in fieldinstruments and control elements.Therefore, it is critical to considerthe entire safety instrumentedfunction as a complete entity. As asmart solution, the DeltaV SISsystem continuously monitors the

ability of sensors, logic solvers andfinal elements to perform ondemand while diagnosing faultsbefore they cause spurious trips.Digital HART communications isthe enabler. This approachincreases process availability andreduces lifecycle costs.

Digital transparencyThe PlantWeb digital plantarchitecture enables the use ofdigital intelligence and predictivediagnostics to increase systemavailability while reducing life cyclecosts and enabling easy regulatorycompliance. Emerson products(sensors, systems, and final controlelements) are third-party certifiedto the IEC 61508 standard for usein safety-rated applications.

The DeltaV SIS systemPressure to keep your plant safe 24hours a day, 7 days a week isrelentless. Equipping your safetyinstrumented system with today’sdigital technologies is your bestpath to addressing thisrequirement. A highly reliablesafety system starts withpredictive intelligence, whichprovides a wealth of diagnosticinformation, enabling you topredict and prevent problems before they occur. The DeltaV SISsystem is a comprehensive

solution for your safety system

with the power of embedded digital communications–all day,every day.

Smart logic solverBulky logic solvers and multi-plexers can now be replaced withstate-of-the-art logic solvers thatsupport digital communications tocontinuously monitor the health ofthe entire SIF. The DeltaV SIS logicsolver, built for digital communi-cations with safety sensors andfinal control elements, uses thepower of predictive fieldintelligence to increase the overallreliability of the entire SIF. It is TÜV-certified without exception for usein SIL 1-3 safety applications asdefined by IEC 61508.

An integrated approach to the entire safety instrumented function (SIF)—from sensor, to logic solver, to final control element—shuts down when needed for safety, butkeeps you running safely when components fail.

Page 6–DeltaV SIS system

SmartSIS

Modular,Distributed

Architecture

Integratedbut

Separate

CertifiedFunction

Blocks

Built-inIEC 61511

Compliance

Smart SIS

Page 7: DeltaV SISTM for Process Safety Systems

Smart devices deliverpredictive and healthdiagnosticsBy replacing switches withtransmitters, you take the first steptoward reducing undetectedfailures. Smart transmitters havefar fewer dangerous undetectedfailures than switches. Emerson’ssmart sensors, such as Rosemount TM and Micro MotionTM

devices, go beyond detectingcomponent failures. They evaluatethe performance of the completemeasurement system, extendingdiagnostics to detect formerlyundetectable dangerous failuresoutside the physical bounds of thetransmitter–providing bothtransmitter and processdiagnostics.

The end result is greater credit forfailure-on-demand calculations,easier compliance with IEC 61511guidelines, higher safe failurefractions, less redundancy, lessproof testing and longer intervalsbetween proof tests.

Smart final elementsreduce risk FIELDVUETM digital valve controllerinstruments provide automatedperformance monitoring andtesting by enabling remote partialstroke testing while the safetyvalve is online. This keepspersonnel safely away from thevalve’s location. The FIELDVUEDVC6000 SIS for emergencyshutdown applications is third-party certified for use in SIL 3applications.

FIELDVUE instruments haveextensive diagnostics to monitortravel deviation, pressuredeviation, valve packing frictionand more. Information iscommunicated back to the DeltaVSIS system and the AMSTM DeviceManager software.

The SIL-PAC solution incorporatesEmerson’s industry-leadingactuators, digital valve controllers,solenoids, and valves to provide aSIL 3 certified valve solution:

� BettisTM G and CBA actuators

� FisherTM DVC6000 SIS controllers

� ASCOTM solenoids

� FisherTM valves.

Smart partial stroketesting extends testintervalsAutomated partial stroke testingof valves can improve safetyintegrity, reduce the number ofrisky personnel trips into the field,and extend the time betweenmandatory proof tests. Automatedpartial stroke testing results inincreased confidence that thevalve will perform on demandwhile reducing costs. Partial stroketests can be automatically initiatedby the DeltaV SIS logic solver ormanually initiated from standardoperator faceplates. The DeltaV SISsystem communicates with theDVC6000 SIS via the HARTprotocol so no additional wiring orcomponents are required toautomate partial stroke tests.Partial stroke test results areautomatically recorded in theDeltaV Event Chronicle for easydocumentation.

Asset management helpsincrease plantavailabilityAMS Suite™: Intelligent DeviceManager enables you to monitorand maintain field devices.Intelligent device diagnosticinformation allows staff to respondquickly and prevent unexpecteddowntime. Automatic docu-mentation provides completedevice maintenance records.

� Enables safer plants� Increased availability� Reduced lifecycle cost� Simplified regulatory compliance

Key Benefits

� IEC 61508 certified sensors, logic solvers,and final elements

� Integrated asset management from AMSSuite

� Integrated digital device diagnosticsensures reliability� Extended health diagnostics

detect device failures� Device alerts enable quick action� Inherent SIS signal status propagation� HART PV vs. analog value comparison� Automatic partial stroke testing� Automated proof testing

� Integrated documentation tools

Key Features

Page 7–DeltaV SIS system

Services

Page 8: DeltaV SISTM for Process Safety Systems

The unique, modular distributedarchitecture enables you tocustom fit the system for your SISapplications. Modularity gives youthe flexibility to meet changingproject requirements. The DeltaVSIS architecture is flexible to helpprovide the safety you want, whenyou want, where you want.

Applications that require safetyinstrumented systems to reducerisk come in all sizes andtopologies. You need anSIS offering that can handle thesmallest to the largest applicationand one that has the flexibility toaddress widely distributedarchitectures. The modular SIF-based DeltaV SIS architecturedelivers the capability to meetchanging project requirements.

Flexible architectureWhether you have an isolatedboiler or a large ESD application,the DeltaV SIS system scales tohelp provide the safety coverageyou require for your SIL 1, 2 and 3applications. Unlike otherapproaches, the modular logicsolver hardware scales in sizes of16 configurable I/O. This meansyou automatically add memoryand logic solver processing everytime you add I/O. The days ofrunning out of memory orprocessing power are over.

A SIF-based approachThe DeltaV SIS architecture allowsyou to concentrate on the designof each SIF–each logic solver is acontainer for a small number ofSIFs and there can be nounplanned interaction betweenthem. This is very different from

the traditional approach wherehundreds of SIFs are all placed in asingle safety PLC and the effect ofchanging a single register or theaddition of a SIF could affect all ofthe logic. The DeltaV SISarchitecture isolates SIFs,eliminates single points of failure,and simplifies change manage-ment. For complex applications,which require multiple SIFs actingon the same final element, inputdata is shared among multiplelogic solvers so that cause andeffect logic can easily beimplemented in a single SISmodule.

Given this flexibility, the DeltaV SISsystem is ideally suited for allsafety applications up to SIL 3:from small burner managementapplications to large ESD and fireand gas applications.

Flexible to provide the safety you want, when you want, where you want.

Page 8–DeltaV SIS system

SmartSIS

Modular,Distributed

Architecture

Integratedbut

Separate

CertifiedFunction

Blocks

Built-inIEC 61511

Compliance

SISNet Domains can be used to distribute SIS applications throughout your plant.

Page 9: DeltaV SISTM for Process Safety Systems

Page 9–DeltaV SIS system

� Increased engineering flexibility� Increased overall reliability� Isolated failures–no single point of failure� Isolation of changes and maintenance� Adding new SIFs does not affect existing

SIFs’ logic, scan rate, or execution� Custom fit for applications� Can implement centralized or decentralized� SIL 3 certified without restriction� No repair time required for degraded mode� Fits any size application

Key Benefits

� A SIF-based approach to logic solving� Modular logic solver with configurable I/O� Scalable from 16 to 30,000 I/O� Flexible redundancy� SIL 3 rating for simplex and redundant SLS� Deterministic scan rate� Remote I/O capability� Expandable online� SIL 3 certified SISNet communications� Up to 62 km distances between nodes

Key Features

Services

SLS 1508 logic solverKey features of the SLS 1508 logicsolver include:� SIL 3 certified by TÜV�24V DC redundant power�dual-modular redundant logic

processing�dual-voting on output channels�16 channels per logic solver� configurable HART I/O for AI,

AO, DI, and DO� line fault detection on all I/O�50ms execution� -40° to 70°C temperature rating

(compliant with NAMUR NE 21temperature rating)

� ISA G3 (corrosive environmentrating)

� I/O published locally every scanon redundant peer-to-peer links

�data integrity checking everyscan

�online logic modification.

Redundant logic solverYou can increase the availability ofyour SIS loops with a redundantpair of SLS logic solvers. Key features include:�quad-modular redundant logic

processing�quad-voting on output channels� separate power� same input data for each logic

solver� continuously drives output

channels if a redundant partnerfails

� automatic online proof testing� in-situ hardware and software

upgrades.

The flexible, modular SLS 1508 logic solvers can be installed inredundant pairs for increased process availability.

Simplex SLS Redundant SLS

Page 10: DeltaV SISTM for Process Safety Systems

As an integrated control and safetysystem, DeltaV and DeltaV SISprovide increased visibility intoyour process. DeltaV SIS isintegrated with the DeltaVsystem’s engineering,maintenance and operationsenvironment. All safety-relatedinformation is easily accessiblethrough familiar and intuitiveapplications. The integrated butseparate architecture meets IEC61511 requirements for physicalseparation and independence ofsafety and control. The DeltaV SISsystem delivers the benefits oftotal integration and totalseparation without the tradeoffsassociated with the two extremes.

Architecturallyindependent safetysystemThe DeltaV SIS power supplies,communication channels,hardware and real-time operatingsystems are physically separateand independent of the controlsystem, maintaining theseparation required by IEC 61508and IEC 61511 standards. Thissystem automatically monitors,controls and collects safety-related data.

OperationsThe operator interfaceprovides a powerfulenvironment for safetyoperation, with built-infeatures for easyinformation access.Alarm management,operator navigation,standard faceplatesand detail displaysprovide a consistentand intuitive operatingenvironment.

To more effectivelyoperate your plant,operators have one commonoperating environment for boththe basic process control system(BPCS) and SIS when using theDeltaV control system. Thisintegrated operator interfaceincludes alarm handling, timesynchronization, user security anddevice health monitoring.

Should an emergency stop berequired for the application, twomechanisms may be used. Youmay hard-wire a physicalemergency shutdown mushroombutton to the input of a logicsolver. You may also soft-wire anemergency shutdown and displayit on an SIS graphic on theoperator station. To comply with

IEC 61511, the DeltaV SIS systemrequires a repeat confirmation onthe emergency shutdown actionbefore it will take effect–avoidingan accidental shutdown.

EngineeringThe DeltaV SIS system gives youthe benefits of drag-and-dropfunction block configuration,comprehensive security andexplorer-based software forintuitive project implementation.The engineering software allowsyou to manage all aspects of yoursystem configuration, includinghardware configuration, controlstrategies, built-in changemanagement and history.

Delivers the benefits of total integration and total separation without the tradeoffs

associated with the two extremes.

Page 10–DeltaV SIS system

Integrated operations, engineering and maintenance.

Separate control and safety.

SmartSIS

Modular,Distributed

Architecture

Integratedbut

Separate

CertifiedFunction

Blocks

Built-inIEC 61511

Compliance

Page 11: DeltaV SISTM for Process Safety Systems

Page 11–DeltaV SIS system

The DeltaV SIS system maintainsproper security on safety logicsoftware and makes themanagement of required safetylogic modifications easier.

For DeltaV BPCS users, theintegrated configurationenvironment simplifies andstreamlines the engineering effort.This integrated approacheliminates time-wasting, difficult-to-maintain data mapping andhandshaking logic that is commonwith disparate systems.Additionally, non-intrusivesimulation allows forcomprehensive testing of safetylogic before installation.

MaintenanceTo manage change and maintaincompliance over time, the DeltaVSIS system provides compre-hensive version control and audittrail functionality for requiredengineering modifications.Electronic signatures ensureproper authorization for onlinechanges. To support compliancedocumentation requirements, acomprehensive history of plantsafety events are automaticallyrecorded. AMS Device Managerprovides detailed diagnosticinformation to diagnose deviceproblems quickly and correctly. Italso documents and archivesinstrument configurations andchanges, as well as healthinformation and alarms.

Connecting to existingBPCSNo matter what DCS or PLC youare using as your basic processcontrol system, you can increaseyour plant’s availability using theadvanced diagnostics in Emerson’sSmart SIS solution.

Modbus integrationModbus RTU and Modbus TCP canbe used to integrate the DeltaV SISsystem and your BPCS. Modbusbrings the advantage of familiarityto most users, as well as thecomfort of decades of provenreliability.

OPC Xi and OPC The DeltaV SIS system can connectwith your non-DeltaV BPCS viaOPC or OPC Xi. All operating andevent information is available toyour operator interfaces andhistory collection software as partof an integrated solution.

OPC Express Interface (Xi) is a newdata communications interfacedeveloped by many diverseprocess automation suppliers.OPC Xi connectivity providessecure, robust, firewall-friendlydata access to real-time andhistorical process data, as well asreal-time alarm and event data.

The OPC communicationsstandard has served the processindustry well for over a decade. Itsupports access to real-time andhistorical data, as well as alarm andevent data.

Services

� Simplified architecture with no mapping ofdata

� Integrated engineering, maintenance andoperations environment

� Time synchronization and event collection� Security management with SIS locks� Advanced alarm management� Change management including version

control, audit trail and electronic signatures� Integrated, non-intrusive ICSS simulation

for testing and operator training

Key Integration Features

� Reduced safety lifecycle costs� Equipment and installation costs� Engineering and maintenance costs

� Reduced training costs� Easier regulatory compliance� Robust security� Increased visibility into the process

Key Benefits

� Built-in IEC 61511 compliance� Separate hardware for control and safety� Separate power for control and safety� Separate control and safety networks� Gateway between SIS and control network

provides firewall protection

Key Separation Features

Page 12: DeltaV SISTM for Process Safety Systems

No custom code is required toimplement common SIS tasks withthe IEC 61508 certified functionblocks, providing fasterconfiguration and troubleshootingof SIS logic. Standard operatorfaceplates automatically providedetailed safety information withno configuration. Using thesefunction blocks can help eliminateengineering hours previouslyneeded to implement ESD, FGS,and BMS applications. Thecertified function blocks deliverpowerful functionality out of thebox, simplifying the imple-mentation of complex SISapplications.

Intuitive safety softwarefunctionsThe DeltaV SIS system provides afull palette of smart safetyfunction blocks certified by TÜVfor safety applications. Specialblocks like MooN voter blocks withbypass management reduce whatused to be pages and pages of

ladder logic or custom programming to engineer, test,and commission into a simpledrag-and-drop configuration activity. Using standard functionblocks instead of customprogramming makes it easy forengineers to troubleshoot andmaintain logic, even if they did notcreate it.

Other capabilities that make thecertified DeltaV SIS softwareintuitive include:�built-in sequence of events

handler with automatic first-outtrapping

�built-in maintenance bypasses � easy compliance to IEC 61511

standard�non-intrusive simulation�built-in alarm management per

EEMUA 191 standard� standard operator faceplates

automatically provide safetyinformation with noconfiguration.

Status handlingInput processing provides statushandling with no need for customcode and different options areavailable. For example, voterblocks can automatically degradevoting when an input value is bad.With integrated HART I/O, devicediagnostic information isautomatically presented tooperations with no additionalconfiguration.

Provides powerful functionality out of the box, simplifying the implementation of complex

SIS applications.

Page 12–DeltaV SIS system

SmartSIS

Modular,Distributed

Architecture

Integratedbut

Separate

CertifiedFunction

Blocks

Built-inIEC 61511

Compliance

Page 13: DeltaV SISTM for Process Safety Systems

Sequence of eventsBuilt-in sequence of eventshandler, with automatic first-outtrapping, eliminates hours ofengineering while reducing testingand simplifying maintenance.

Voter function blocksVoter function blocks provideadvanced features like built-inbypass and deviation alarms toimprove plant availability. Thevoting is configured using radiobuttons and check boxes withextendable blocks ensuring thesame approach is takenthroughout the configuration,regardless of the application size.

Voter blocks include advancedfeatures such as maintenance andstartup bypasses with a variety ofoptions to meet your applicationneeds.

Cause and effectfunction blocksTraditional SIS projectrequirements are typically detailedusing cause-and-effect matrices(CEM). Once approved, these areoften translated into logicdiagrams and ultimately intoladder logic of the selectedsupplier. No more. With the CEMfunction block, the cause-and-effect diagrams can be deployeddirectly in the logic solver, enablingfast configuration and reducedtesting. The CEM table executes asit is presented. Documentation iseasy, since the CEM configurationis the logic that executes.

CEM function blocks includeadvanced functionality, including astate machine for each effect tohandle trip status, resetting andforcing of outputs.

State transition and stepsequencer functionblocksFunction blocks for statetransitions and step sequencingprovide powerful functionality outof the box for BMS applications.These function blocks convertwhat is typically a verycomplicated set of custom logicinto a simple, intuitiveconfiguration task that is easy toimplement, troubleshoot andmaintain. Templates can becreated and re-used for multipleBMS applications.

Standard design templates makeconfiguring operator graphics easyfor voter, CEM, state transition andstep sequencer function blocks.Status information is automaticallypresented to the operator withoutmapping data tags or creatingcustom templates or faceplates.

Page 13–DeltaV SIS system

Services

� Powerful, intuitive, out-of-the-boxfunctionality

� Intuitive drag-and-drop function blockinterface

� Inherent status propagation and statushandling

� Built-in overrides and deviation alarms� Automatic degraded voting when device

failures are detected� Built-in sequence of events handler with

automatic first-out trapping� Powerful state transition and step sequence

function blocks for BMS

Key Features

� Implement complex logic in a singlemodule, eliminating pages of customprogramming

� No custom code needed to implementcommon tasks

� Simplified configuration andtroubleshooting of logic

� Consistent approach throughout SISapplications

� Significantly reduce engineering hoursrequired to implement ESD, FGS and BMSapplications

� Rich function block information� No concerns for migration to future

releases

Key Benefits

Page 14: DeltaV SISTM for Process Safety Systems

The DeltaV SIS system is built forIEC 61511 compliance, providingstringent change management,security management anddocumentation tools. It is certifiedfor use in SIL 3 applicationswithout restriction. The system isbuilt from the ground up tosimplify regulatory compliance–eliminating your concerns relatedto proper implementation.

Change ManagementIncreasingly stringent regulationsrequire manufacturers to providecomprehensive documentation oftheir process. DeltaVConfiguration Audit Trail is apowerful tool that tracks changesand manages revision informationfor any item in the configurationdatabase, including SIS items. Thisapplication creates and maintainsa change history for configurationitems, such as modules, SISmodules, phases, operations, unitprocedures, user accounts andoperator graphics–makingregulatory compliance simpler.

Protected composite templates For reduced complexity in globalengineering and IEC 61508compliance, the DeltaV SIS systemincludes protected compositetemplates. Templates, such ascertified safety logic, are createdon a ‘master’ DeltaV SIS systemand then distributed to

engineering centers forimplementation. Thetemplates are protected frommodification by only allowingchanges to occur on the mastersystem.

Easy to track changesComprehensive version controlof a configuration item isautomatically tracked andupdated. The new version istime-stamped and a historycomment can be recordedwhen the item is checked backin. Embedded reporting toolsgive engineers the ability toprint configuration changehistories for any item in theconfiguration database.By keeping detailed historicalinformation on configurationitems, the system automaticallymaintains quality data forregulatory compliancerequirements andtroubleshooting.

Ensure authorized configurationchangesThe DeltaV SIS security systemgives you the ability to grantprivileges to individual users. Itemsmay be checked out for editingonly by approved users.

Ensure compliance duringoperation with ElectronicSignaturesTo support compliancerequirements for online changes,the DeltaV SIS system uses anelectronic signature functionalitydesigned to meet the life scienceindustry’s stringent requirements.Any actions taken can beconfigured to require aconfirmation in which the user’sname and password is needed toexecute, as well as an additionalverifying user name and passwordif required.

Built from the ground up to simplify regulatory compliance, eliminating your concerns

related to proper implementation.

Page 14–DeltaV SIS system

SmartSIS

Modular,Distributed

Architecture

Integratedbut

Separate

CertifiedFunction

Blocks

Built-inIEC 61511

Compliance

The DeltaV SIS system is built for IEC 61511 compliance.

Page 15: DeltaV SISTM for Process Safety Systems

Page 15–DeltaV SIS system

Services

SecurityAdaptable User ManagerWith the role-based user access,you have complete flexibility todefine the security structure tomatch your operating philosophy.

A separate set of locks and keys isprovided for control and safety.Through a single sign-on, you candefine groups of users and assignthem privileges. For example, onegroup may be able to change onlycontrol operating parameters,while another may be able tochange safety parameters. Andyou can limit a user to particularareas of the plant–providing youwith peace of mind that only theappropriate people are makingdecisions affecting your plant.

Easy security managementWhen you make changes tosystem users and their privileges inDeltaV User Manager, the changesare immediately applied across allDeltaV and AMS applications andWindows security is automaticallyupdated.

Built for securityThe DeltaV system was developedwith system security as a keydesign criterion. To safeguard yourassets and ensure proper access,the system delivers these securitycapabilities:�DeltaV controllers have been

hardened to mitigate specific,well-documented securitythreats.

�Workstation hardening disablesunused operating systemservices and disables CDROM

and USB ports to prevent theintroduction of viruses andmalware.

� The DeltaV Flexlock securityapplication creates a secureworkstation desktop to preventunauthorized access outside ofthe DeltaV operationsenvironment.

�DeltaV Smart Switches provideauto lockdown to preventunauthorized networkconnections on switch ports.

�Unauthorized network devicescannot participate in DeltaVcommunications, becauseDeltaV devices areauthenticated as part of systemconfiguration.

� Physical access to localequipment is not required forroutine maintenanceprocedures andtroubleshooting becausesystem diagnostics are doneover the network using DeltaVand AMS Device Managerworkstations.

SyncadeTM SuiteSyncade Smart OperationsManagement suite extends thevalue of PlantWeb by providingelectronic manufacturing controlthat optimizes plant-wide workprocesses and increasesproductivity. Safety workflow,such as proof-testing, is guided,verified, and documented for easyregulatory compliance.

AMS SuiteWhen maintenance functions areperformed, AMS Device Managerautomatically records activity in

the Audit Trail for a completehistory. AMS Suite provides integrated device configurationand security to reduce lifecyclecosts. QuickCheck allows for easierinterlock verification. Additionally,Meridium APM software can beseamlessly integrated with AMSSuite in real-time to easily verifyproof-testing compliance. AMSSuite allows you to operate withconfidence.

� IEC 61511 compliance is enforced byengineering tools, with no restrictions

� Change management of safety logic andfield device configuration/calibration

� Integrated security for competencymanagement

� Secure write mechanism provides repeatconfirmation for online changes

� Automatic logging of events and diagnosticfaults

� Non-intrusive simulation for testing andoperator training

Key Features

� Simplified regulatory compliance� Standardized designs� Reduced engineering effort� Reduced lifecycle costs� Robust security

Key Benefits

Page 16: DeltaV SISTM for Process Safety Systems

Safety applications are designed toprotect your plant and personnelfrom hazardous conditions andprovide a rapid and coordinatedoperational response toemergency situations, ensuringmaximum uptime for your plant.

The DeltaV SIS system provides ahigh level of reliability andavailability through redundantarchitecture design, includingredundant networks, logic solversand I/O. The system automaticallymonitors, controls and collectssafety-related data for ESD, FGSand BMS applications.

Prevent incidents fromoccurring

The DeltaV SIS system can be usedfor emergency shutdownapplications to prevent hazardoussituations from occurring, and caninitiate the shutdown of a plant,unit, or piece of equipment should

it be required. Sensors are used todetect certain conditions, and theDeltaV SIS logic solver isconfigured to meet your safetyrequirements to take the finalelements (valves, pumps) to a safe state.

The combination of sensor, logicsolver and final element form asafety instrumented function (SIF).Each SIF is designed to prevent aspecific hazard from occurring byreducing a certain amount of risk.This risk reduction equates to asafety integrity level (SIL). TheDeltaV SIS system provides SIL 3

reliability in compliance with IEC 61508 and IEC 61511 internationalstandards, and in addition hasmany innovations: repeatconfirmation built in to theoperator graphics, version control that can be defined by SIL level,powerful voting functionality anda very flexible cause and effectmatrix (CEM) function block that isintuitive and easy to use.

Ensures maximum uptime for your plant.

Page 16–DeltaV SIS system

SmartSIS

Modular,Distributed

Architecture

Integratedbut

Separate

CertifiedFunction

Blocks

Built-inIEC 61511

Compliance

Emergency Shutdown System

Emergency Response Layer

Passive Protection Layer

Active Protection Layer

Safety Layer

Process Control Layer

Process Control Layer

SIS

BPCS

Plant andEmergency

Response

Containment,Dike/Vessel

Fire and GasSystem

EmergencyShutdown

System

OperatorIntervention

Trip level alarm

Process alarm

Process value Normal behavior

Emergency shutdown

Operator intervention

Mitigate

Prevent

Incident

Emergency Response Layer

Passive Protection Layer

Active Protection Layer

Safety Layer

Process Control Layer

Process Control Layer

Page 17: DeltaV SISTM for Process Safety Systems

Page 17–DeltaV SIS system

Mitigate theconsequences of eventswhen they occur

IEC 61511 recognizes fire and gassystems (FGS) as mitigative SISsystems. The major focus of a FGSis to mitigate an incident AFTER ithas occurred. This is done to gaintime for people to evacuate thearea, contain the incident fromescalating and allow emergencyresponse teams to assess and dealwith the incident. By monitoringprocess areas where fire, build upof a potentially flammable gas ortoxic gases may occur, the DeltaVSIS system can be configured todetect these hazardous events,alert personnel and initiate timelyactions in order to minimize theconsequences of an incident.

Fire and gas systems are usuallystand alone systems that takeactions when required. Withtoday’s technology, manycompanies utilize an integratedapproach and interface the FGSwith the ESD system to initiateplant shutdown if hazardousevents occur.

The integrated system can alertpersonnel in a fast, accurate andstructured way, giving employeestime to decide what course ofaction to take while bringing theplant to a pre-determined state.

Permit the system tooperate when safe

The DeltaV SIS system can be usedfor burner management system(BMS) applications, a safetysolution for control andmonitoring of burner units.Through proper sequencing andinterlocks, the DeltaV SIS BMSapplication allows the burnerunit(s) to go safely through allrelevant states, from start-up tooperation and shutdown whenneeded. If so required (usuallydependent on the size of theburner unit), the DeltaV SIS systemcan also be configured to provideautomated leak testing of the gasvalves. Using specially developedfunction blocks, the DeltaV SISBMS solution is highly flexible andeasy to maintain and monitor.

Services

Burner Management System

Fire and Gas System

Page 18: DeltaV SISTM for Process Safety Systems

Emerson is an industry leader inproviding services throughout thelifecycle of your operations, nomatter where on the globe youoperate.

Managing risk withglobal standardsCompanies that correctly plan forand manage the operational risksinherent to industrial processesavoid exposure to productionoutages, equipment damage,environmental incidents, injury topersonnel and loss of life. Theinternational community hasdeveloped standards for theevaluation and design of safetyfunctions. The IEC 61511 standardis aimed directly at total processplant operations and covers thewhole safety lifecycle of thesystem from concept to operation and maintenance, to decommissioning.

Certified safety processEmerson utilizes a FunctionalSafety Management System asdefined by the IEC 61511standard. This TÜV-certifiedsystem covers:�Management of functional

safety� Safety lifecycle structure and

planning�Verification�Design and engineering of SIS � Installation, commissioning and

validation�Maintenance and modification.

Emerson Certified FunctionalSafety Experts utilize this processand their expertise with the latestsafety technologies and practicesto help clients define andimplement their safety systems.Our processes are consistent withthe most stringent demands forprotection, risk reduction andreliability.

Certified safety expertsIEC 61511 requires personnel andorganizations to be competentand qualified to carry out safetyactivities.

Emerson is the first safety systemsprovider to develop TÜV-certifiedprocedures in alignment with IEC61511. In addition, all employeesinvolved with safety systemsengineering and development arerequired to complete extensivesafety training and Emersoncertification.

Many of our engineers andtechnologists have also completeda rigorous competencyqualification for system designengineers known as the CertifiedFunctional Safety Expert (CFSE)exam. This certification requiresexperience in the SIS field, as wellas successful completion of acomprehensive examination.

Reducing failures fromthe startIEC 61511 defines a process tohelp reduce random hardwarefailures and reduce systemicfailures. Having CFSE expertsinvolved early in the lifecycleprocess helps reduce faults causedby poor specifications or poorengineering.

Reduce engineering and maintenance costs.

Page 18–DeltaV SIS system

SmartSIS

Modular,Distributed

Architecture

Integratedbut

Separate

CertifiedFunction

Blocks

Built-inIEC 61511

Compliance

Page 19: DeltaV SISTM for Process Safety Systems

Differentiated safetyservices throughout thesafety lifecycleEmerson provides solutions withcertified hardware, software, andengineering services needed tomeet the requirements of thesafety system lifecycle. Emersonhas extensive global coverage formain automation contractor(MAC) services–providing a singlesource for all of your safety projectneeds. These services include allaspects of your automationproject from front endengineering design (FEED)onward. Emerson can provide aturnkey solution for your projectthat includes equipment selection,commissioning services, andimplementation and operationalcapabilities.

ANALYSISAs part of pre-project planning,FEED is early design work doneafter conceptual business planningand prior to detailed design. Oncethe safety integrity levels (SIL) ofthe safety instrument functions(SIF) are defined, Emerson cancompile your safety requirementspecification (SRS). We also offerSIS functional safety consulting tohelp you design the safety loopand select the components that are needed.

IMPLEMENTATIONEmerson project services forapplication software follow ourTÜV-certified processes andprovide documented verificationof all design, implementation, andtesting activity. Each step of theprocess is reviewed anddocumented to help ensurecompliance with IEC 61511.

OPERATIONEmerson’s SureServiceTM programoffers an array of support servicesdesigned to help you achieve yourbusiness objectives, reduce youroperating and service costs, andkeep your systems running at peakperformance. These supportservices include:�Guardian Support� Emergency Onsite Service� Express Module Replacement� Critical Data Backup� Local Spares Management� Functional Safety Maintenance

and Proof Testing� Power and Grounding Integrity � Security Assessment�Alarm Management� SIS Modification� Extended Software Support� Premier Service.

Emerson–a partner youcan trustFor over 100 years, Emerson hasbeen a global leader in providingprocess automation solutions witha commitment to total quality,plant safety, and dedication tomeeting customer expectations.We can help you operate yourplant safely, reliably, and moreefficiently–giving you peace of mind.

Page 19–DeltaV SIS system

Services

Globally, Emerson can help you with IEC 61511 Safety Life Cycle management.

Page 20: DeltaV SISTM for Process Safety Systems

Emerson Process Management12301 Research Blvd.Research Park Plaza, Building IIIAustin, TX 78759

www.EmersonProcess.com/DeltaVSIS

The contents of this publication are presented for informational purposes only, and while every effort has been made toensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the productsor services described herein or their use or applicability. All sales are governed by our software licensing agreement andterms and conditions, which are available upon request. We reserve the right to modify or improve the designs orspecifications of our product and services at any time without notice.