COMMERCIALwww.braycommercialdivision.com ATT-1
½”-1½” - Pressure Independent Control Valve - Modulating control valve, dynamic balancing valve and differential pressure control valve in one body. Field adjustable, self-balancing, dynamic flow control valves that are pressure independent, two-way and modulating to accept analog signal inputs. Each valve has an adjustable maximum flow rate setting to enable flow limitation and balancing to the coil or zone that the valve is controlling.
Advantages of Bray ATT Valves -
1. Installation costs - up to 60% fewer valves are required. Due to the automatic balancing of each heat exchanger, no other differential pressure control valves or balancing valves are required. This simplifies installation, reduces installed costs, and improves accuracy and reliability.
2. Operating costs - Minimizes pumping, heating and cooling costs by eliminating overflow through the coil and by reducing pressure drop.
3. The location of the Bray ATT automatic balancing valve does not require lengths of pipe before or after the valve.
Flow rate can be changed on demand without removing the cartridge from the valve body
The valve will always use full stroke of the control element offering the 100% authority for any of its 41 flow settings
Features and Benefits
• Field Adjustable, up to 41 different flow rates in one and the same cartridge
• 100% Authority Pressure Independent
Allows for coil isolation• Built-In Isolation Ball Valve (Body Style C and D)
Allows for verifying operating differential pressure across the valve
For ease of installation and wide selection of end fittings
• Optional Pressure/Temperature Measurement Ports
• Female-by-Female Threaded (Body Style B)• Double Union End Connection, Threaded or Sweat (Body Style C and D)
11/13/13
- System Types: - Media:
Fan Coil, VAV Reheat Coils, Hot Water, Chilled Water,
Chilled Beams and Air Handling Units 50/50 Glycol Solutions.
COMMERCIAL ATT SeriesAdjustable PIC Valves
2 Way • 1/2”- 1-1/2” • ATT - AutoTouch Terminal
Body Style B
Body Style C & D
COMMERCIALwww.braycommercialdivision.comATT-2
ATT - Valve SpecificationsBody Style B, C, D 1/2” – 1-1/2”
Hot Water, Chilled Water, 50/50 Glycol Solutions
Valve Body Pressure Rating Water
Maximum
Technical SpecificationsService
Operational ∆P
Operational ∆P
Pressure rating: 360 psi / (25 Bar)
Close-Off PressureMaximum
Minimum
(H Cartridge) 58 psid / (4 Bar)(L & M Cartridge) 87 psid / (6 Bar)
(M Cartridge) 4.4 psid / (0.3 Bar)(H Cartridge) 2.3 psid / (0.16 Bar)
(L Cartridge) 2.3 psid / (0.16 Bar)
58 psid / (4 Bar)
AmbientTemperature Rating 34˚ to 122˚ F (1˚ to 50˚ C)
Leakage
(Body “B” Only) Fixed female NPT or BSP, or Sweat(Body “C, D” Only) Union End Connection in Brass Alloy, NPT or BSP
Body
Ball Valve (Body “C, D” Only)
Materials
Forged Brass ASTM CuZn40Pb2
Chemically Nickel Plated Brass Ball
Cartridge
Diaphragm
Brass alloy NPT (Body Style C & D only)
Disclaimer - The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Bray office. Bray, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
POM (Polyoxymethylene) - with Stainless Steel trim
Hydrogenated Acrylonitrile-Butadiene-Rubber
O-Rings
Union End Connections
EPDM
(L Cartridge) 0.1 to 3.3 GPM, (32.0 to 757 L/hr)(M Cartridge) 0.3 to 4.9 GPM, (64 to 1110 L/hr)(H Cartridge) 3.8 to 20.4 GPM, (865 to 4630 L/hr)
Flow Rate Range
End Connections
Minimum MediaTemperature Rating
248°F (120°C)Maximum MediaTemperature Rating ATT Body Style C, D
Valve BodyOnly
Weights (lbs.)
1/2”– 1” (Body C) 1.9lb., 0.87kg
1”– 1-1/2“ (Body D) 4.7lb., 2.14kg
ANSI / FCI 70-2 2006 (R1982) / IEC 60534-4 Class - Class IV- < 0.01%
212°F (100°C) ATT Body Style B
1/2” (Body B) 1.2lb., 0.55kg
3/4” (Body B) 1.3lb., 0.59kg
1“ (BSP Only) (Body B) 1.4lb., 0.64kg
1” (Body B) 4.1lb., 1.86kg.
1-1/4” (Body B) 3.7lb., 1.68kg
-4°F (-20°C)
COMMERCIALwww.braycommercialdivision.com ATT-3
ATT - Valve Specifications ATT - Actuator Specifications
ATT Actuators FN.0.2 FN.0.4 FN.1.2
Supply voltage 24V AC/DC ±10%, 50/60 Hz
Motor Bi-directional synchronous
(2-position / 3-point floating)
Power consumption
Input Impedance
3VA 3VA 3VA, 5VA peaks
Control signalAnalog 0(2)-10V DC
DigitalAnalog 0(2)-10V DC
Position output 0(2)-10V DC - 0(2)-10V DC
Failsafe function No No Yes
>30kΩ - >30kΩ
Auto stroke Yes No Yes
Operation time 50 Hz: 90 seconds 50 Hz: 90 Seconds 50 Hz: 45 Seconds
Actuation force 50 lbf, 225N ±5% 50 lbf, 225N ±5% 50 lbf, 225N ±5%
Ambient temperature -0.4°F to +122°F
Humidity rating <95% Non Condensing
Protection IP54, class II
Cable 4 wires 22 AWG halogenfree cable, 3.2 feet
3 wires 22 AWG halogenfree cable, 3.2 feet
4 wires 22 AWG halogenfree cable, 3.2 feet
Weight 0.55 lbs 0.55 lbs 0.66 lbs
FN.0.2 & FN.0.4 Series FN.1.2 Series
Auto Stroke OptionWith the auto stroke option activated, the actuator will make one full cycle every 24 hours, if the actuator constantly has been in fully open or fully closed position during the previous 24 hours.
This operation will clear up any possible impurities accumulated in the valve, and re-calculate the end positions.
COMMERCIALwww.braycommercialdivision.comATT-4
ATT - Piping Diagrams
ATT - Actuator Wiring
RETURN
SUPPLY
COIL
RETURN
Shown with Optional PT Ports
SUPPLY
COIL
Notes: Valve diameter should Never exceed pipe diameter Mount the ATT valves to the return side of the coil. 20 mesh strainer should be installed on the supply side of each coil using the ATT valve.
Blac
k
Power 24V AC/DC
Ground/common
Gre
en
Whi
te
Feedback signal0(2)-10V DCInput signal
0(2)-10V DC
Red
FN.0.4 Series Actuator
FN.0.2 & FN.1.2 Series Actuators
Blac
k
Power 24V AC/DC
Ground/common
Whi
te
Red
OpenClose
FN.0.4 Actuator FN.0.4 Actuator
FN.0.4 ActuatorFN.0.4 Actuator
FN.0.2 / FN.1.2 Actuator
2-Position, Normally Closed
Blac
k
Power 24V AC/DC
Ground/common
Whi
te
Red
Open Close
2-Position, Normally Open
Blac
k
Power 24V AC/DC
Ground/common
Whi
te
Red
OpenStop
Close
3-Point-Floating, Normally Closed
Blac
k
Power 24V AC/DC
Ground/common
Whi
te
Red
OpenStop
Close
3-Point-Floating, Normally Open
COMMERCIALwww.braycommercialdivision.com ATT-5
Valve model: C, DShown with
FN.0.4, FN.0.2 Actuator
B
A E
Note * Add end connection length to body length.Note ** Weight does not include end connections or actuator.Note *** For valve body.
ModelNumber
ValveModel
ValveSize
CartridgeSize
BodyTappings
A BFC
(FN.0.4 & FN.0.2)
D(FN.1.2)
End connections E** ***Weight
(lbs.)Cv
(GPM)NPTfemale
NPTmale Sweat
ATT-B-050-X-X/Act.
ATT-B-075-X-X/Act.
ATT-B-100-X-X/Act.
ATT-B-100-X-X/Act.
ATT-B-125-X-X/Act.
ATT-C-050-X-X/Act.
ATT-C-075-X-X/Act.
ATT-C-100-X-X/Act.
ATT-D-100-X-X/Act.
ATT-D-125-X-X/Act.
ATT-D-150-X-X/Act.
B
1/2”
1/4”
1/4”
1/4”
3.23
1.22 5.12 5.71 N/A N/A N/A
1.2
3.03/4” 3.70 1.31”
BSP Only 4.02 1.4
1” H(1-1/2”dia.) 5.04 1.85 6.02 6.50 N/A N/A N/A
4.114.5
1 1/4” 3.7
C
1/2”
L & M (3/4”dia.)
H(1-1/2”dia.)
L & M (3/4”dia.) 4.80 1.30 5.12 5.71
0.87 0.99 0.79
1.9 3.03/4” 0.87 0.99 0.79
1” N/A 1.54 0.87
D
1”
6.61 1.62 6.02 6.50
1.38 1.57 1.34
4.7 14.51 1/4” 1.38 1.57 1.46
1 1/2” 1.57 1.65 N/A
Valve model: C, DShown with
FN.1.2 Actuator
B
A E
Valve model: BShown with
FN.0.4, FN.0.2 Actuator
C, D† C, D† C, D†FFF
B
A
ATT - Valve/Actuator Dimensions
ATT - Strainer Dimensions
ATT - Piping Diagrams
ATT - Actuator Wiring
Notes: Valve diameter should Never exceed pipe diameter Mount the ATT valves to the return side of the coil. 20 mesh strainer should be installed on the supply side of each coil using the ATT valve.
Dimensions may vary, depending on the actuator. Dimensions are shown for the largest spring return actuator currently available.Dimensions are shown in inches and are approximate.
A
C
B
1/2” 3.9 1.1 2.3
3/4” 3.9 1.1 2.3
1”
2”
5.3 1.3 2.6
7.7 1.9 3.71 1/4”
7.5 1.9 3.71 1/2”
15
20
25
32
40
50 9.5 1.6 4.3
A B CConnection
in. mm
COMMERCIALwww.braycommercialdivision.comATT-6
Dynamic Flow Rate Limiter
The diaphragm reacts to the system and
regulates the pressure differential across the actuated control valve orifice to maintain its
flow rate.
Changing the setting will not affect the stem height as the setting merely turns the inner bottom part of the cartridge sideways.
At any setting the stem height will remain the same providing full stroke.
Indicates Flow DirectionIndicates Pressure Changes
Dynamic Balancing of Flow
Cartridge Adjustment
with Key
FlowFlow
Rotates with Key to adjust Flow
Adjustment
The AutoTouch Terminal (ATT) is set to 1 of 41 settings of maximum flows with the adjustment key.
Turn the adjustment key to numerals 1 through 5 with the decimals appearing in red.
Flow Rate can be changed on demandwithout removing the cartridgefrom the valve body.
Full Stroke Modulation100% authority guaranteed.
ATT - How it Works Principle of Operation
The function of the ATT
valve is best described as
three functions in one. The
first valve regulates the
pressure differential across
the second valve by means
of a rolling diaphragm
element counteracted by
a spring. The second valve
is a calibrated variable
orifice device adjusted by
the actuator (similar to
a standard modulating
control valve).
Go to the following web
address to see a video
demonstration:
www.
braycommercialdivision.
com/att.mov
COMMERCIALwww.braycommercialdivision.com ATT-7
ATT - How it Works ATT - Flow Rate Table
(L) Cartridge (M) Cartridge (H) Cartridge2.3-58 psid (.16-4 bar)*
High Flow(Black O-Ring)
2.3-29 psid (.16-2 bar)Low Flow
(Green O-Ring)
4.4-58 psid (.30-4 bar)Medium Flow(Black O-Ring)
SETTING GPM l/hr GPM l/hr GPM l/hr1 0.1 32.0 0.3 64 3.8 865
1.1 0.3 75.8 0.6 142 4.5 10101.2 0.5 116 0.9 209 5.1 11601.3 0.7 153 1.2 268 5.7 13001.4 0.8 188 1.4 319 6.3 14301.5 1.0 220 1.6 366 6.9 15701.6 1.1 250 1.8 408 7.5 17001.7 1.2 278 2.0 446 8.0 18201.8 1.3 304 2.1 482 8.6 19401.9 1.5 329 2.3 516 9.1 20602.0 1.6 352 2.4 549 9.6 21802.1 1.7 374 2.6 580 10.1 22902.2 1.7 396 2.7 611 10.6 24002.3 1.8 416 2.8 641 11.0 25102.4 1.9 435 3.0 671 11.5 26102.5 2.0 453 3.1 700 11.9 27102.6 2.1 471 3.2 728 12.4 28102.7 2.2 488 3.3 756 12.8 29002.8 2.2 504 3.5 783 13.2 30002.9 2.3 520 3.6 810 13.6 30903.0 2.4 535 3.7 835 14.0 31803.1 2.4 549 3.8 860 14.4 32603.2 2.5 563 3.9 883 14.7 33503.3 2.5 577 4.0 906 15.1 34303.4 2.6 590 4.1 927 15.5 35103.5 2.7 602 4.2 946 15.8 35903.6 2.7 614 4.3 965 16.1 36703.7 2.8 626 4.3 982 16.5 37403.8 2.8 637 4.4 998 16.8 38203.9 2.9 649 4.5 1010 17.1 38904.0 2.9 659 4.5 1020 17.4 39604.1 3.0 670 4.6 1040 17.7 40304.2 3.0 681 4.6 1050 18.1 41004.3 3.0 691 4.7 1060 18.4 41704.4 3.1 701 4.7 1070 18.7 42404.5 3.1 711 4.7 1080 19.0 43004.6 3.2 721 4.8 1080 19.2 43704.7 3.2 730 4.8 1090 19.5 44404.8 3.3 740 4.8 1100 19.8 45004.9 3.3 749 4.9 1100 20.1 45705.0 3.3 757 4.9 1110 20.4 4630
Accuracy: Greatest of either +/- 10% of controlled flow rate or +/- 5% of maximum flow rate.* At setting 2.6
A micrometer setting of 3.4 as illustrated above corresponds to a max flow rate of:
2.6 GPM - (L) Cartridge4.1 GPM - (M) Cartridge15.5 GPM - (H) Cartridge
Use the special designedkey for micrometer setting.
O-Ring
Key
O-Ring
COMMERCIALwww.braycommercialdivision.comATT-8
ATT - Model Number
FN.0.2NFP2.4M050BATTSample Part NumberSizes (in/(mm)) Isolation Ball Valve Cartridge
B 1/2(15), 3/4(20), 1(25)
L,M
B 1(25), 1-1/4(32) H
C1/2(15), 3/4(20), 1(25), 1 1/4(32)
-
-
L,M
D 1(25), 1-1/4(32), 1-1/2(40) H
in.SIZE
CODE
STYLE
CODE
mm
050 1/2 15
075 3/4 20
100 1 25
125 1-1/4 32
150 1-1/2 40Pressure range, ∆P(psi) Flow rate(GPM)
L Low Flow 2.3-29 psi, .16-2 bar 0.141-3.31
M Medium Flow 4.4-58 psi, .30-4 bar 0.282-4.89
H High Flow 2.3-58 psi, .16-4 bar 3.81-20.4
Description NF NPT female threads
NFP NPT female threads with pressure/temperature plugs
NM NPT male threads
NMP NPT male threads with pressure/temperature plugs
SW Sweat termination
SWP Sweat termination with pressure/temperature plugs
BF BSP female threads
BFP BSP female threads with pressure/temperature plugs
BM BSP male threads
BMP BSP male threads with pressure/temperature plugs
Body Style(see body style configurationchart below)
Valve Size
Flow Rate
Cartridge
Connection/Port Code
Actuator
0.1 to
20.4
FN.0.2 24V Modulating
FN.0.4 24V 3-Point Floating
FN.1.2 24V Modulating (with feedback signal)
Reference the previously listed Flow Rate Table and select the desiredflow rate GPM that is listed for the cartridge that you are using.
NPT Male
BodyType
NPT Female
BSP Male
BSP Female Sweat
Union Ends
Sizes(in. mm)
Pressure/Temp Ports
IsolationBall ValveCartridge
Body StyleConfig-urations
L,M
L,M
L,M
B 1/2 (15),3/4 (20)1(25)*
H
H
1 (25),1-1/4 (32)
* 1” utilizing the L & M cartridge available as BSP only
1/2 (15),3/4 (20)
1 (25),1-1/4 (32),1-1/2 (40)
1 (25)
B
C
C
D
See Body Style Con�guration Chart Below
(Union Ends standard on Body C & D)
*Example: Medium Flow Cartridge, 1/2", body style B, 2.4 GPM, Female NPT with PT ports with FN.0 actuator ATT-B-050-M-2.4-NFP/FN.02
Additional Example: High Flow Cartridge, 32mm, body style D, 1300 l/hr, male BSP threads with PT ports.ATT-D-125-H-5.7-BMP/FN.02