Upload
others
View
2
Download
0
Embed Size (px)
Citation preview
20
CIT
Y O
F H
AM
PT
ON
OLD
H
AM
PT
ON
C
IR
CU
IT
C
OU
RT
RE
PL
AC
E H
VA
C
19-0
15
11/
12/
2019
2406 Princess Anne Road,
Virginia Beach, VA 23456Phone (757) 563-9027
Facsimile(757) 563-9028
Suite 200
COASTALE N G I N E E R I N G
RM
K
CO
MM
ONWEALTH OF VIRGIN
IA
PROFESSIONAL ENGIN
EER
RICHARD M. KLEIN
No. 027864
TH
E C
OP
YR
IG
HT
S T
O A
LL
D
ES
IG
NS
A
ND
D
RA
WIN
GS
A
RE
T
HE
P
RO
PE
RT
Y O
F C
OA
ST
AL
E
NG
IN
EE
RIN
G, P
LL
C. R
EP
RO
DU
CT
IO
N O
R U
SE
F
OR
A
NY
P
UR
PO
SE
O
TH
ER
T
HA
N T
HA
T A
UT
HO
RIZ
ED
B
Y C
OA
ST
AL
E
NG
IN
EE
RIN
G, P
LL
C IS
F
OR
BID
DE
N.
1
T-1.0
TIT
LE
SH
EE
TW
RK
RM
KPHONE: (757) 563-9027 FAX: (757) 563-9028
VIRGINIA BEACH, VA 23456
2406 PRINCESS ANNE RD, SUITE 200
CONSULTING ENGINEERS
COASTAL ENGINEERING
LOCATION MAP
NOT TO SCALE
NORTH
VICINITY MAP
NOT TO SCALE
NORTH
SITE LOCATIONHAMPTON
REPLACE HVAC
OLD HAMPTON CIRCUIT COURT
CITY OF HAMPTON
DRAWING INDEX:
SHEET NUMBER SHEET TITLE
T-1.0 TITLE SHEET
MECHANICAL
M-001MECHANICAL LEGEND, NOTES, ABBREVIATIONS
M-101 MECHANICAL1st FLOOR PLAN - DEMOLITION
M-102 MECHANICAL 2nd FLOOR PLAN - DEMOLITION
M-201 MECHANICAL 1ST FLOOR PLAN - NEW WORK
M-202 MECHANICAL 2ND FLOOR PLAN - NEW WORK
M-301 MECHANICAL DETAILS AND SCHEDULE
M-302 MECHANICAL DETAILS AND SCHEDULE
M-401 MECHANICAL SCHEDULES
M-402MECHANICAL CONTROLS, LEGEND AND NOTES
M-403 MECHANICAL CONTROLS AND DETAILS
M-404 DIAGRAM
M-601 MECHANICAL SPECIFICATIONS
ELECTRICAL
E-001ELECTRICAL LEGEND, NOTES AND ABBREVIATIONS
E-101 ELECTRICAL 1ST FLOOR PLAN - DEMOLITION POWER AND SPECIAL SYSTEMS
E-102 ELECTRICAL 2ND FLOOR PLAN - DEMOLITION POWER AND SPECIAL SYSTEMS
E-201 ELECTRICAL 1ST FLOOR PLAN - NEW WORK POWER AND SPECIAL SYSTEMS
E-202 ELECTRICAL 2ND FLOOR PLAN - NEW WORK POWER AND SPECIAL SYSTEMS
E-601 ELECTRICAL RISER DIAGRAM AND PANELBOARD SCHEDULES
E-701 ELECTRICAL SPECIFICATION
20
CIT
Y O
F H
AM
PT
ON
OLD
H
AM
PT
ON
C
IR
CU
IT
C
OU
RT
RE
PL
AC
E H
VA
C
19-0
15
11/
12/
2019
2406 Princess Anne Road,
Virginia Beach, VA 23456Phone (757) 563-9027
Facsimile(757) 563-9028
Suite 200
COASTALE N G I N E E R I N G
RM
K
CO
MM
ONWEALTH OF VIRGIN
IA
PROFESSIONAL ENGIN
EER
RICHARD M. KLEIN
No. 027864
TH
E C
OP
YR
IG
HT
S T
O A
LL
D
ES
IG
NS
A
ND
D
RA
WIN
GS
A
RE
T
HE
P
RO
PE
RT
Y O
F C
OA
ST
AL
E
NG
IN
EE
RIN
G, P
LL
C. R
EP
RO
DU
CT
IO
N O
R U
SE
F
OR
A
NY
P
UR
PO
SE
O
TH
ER
T
HA
N T
HA
T A
UT
HO
RIZ
ED
B
Y C
OA
ST
AL
E
NG
IN
EE
RIN
G, P
LL
C IS
F
OR
BID
DE
N.
2
M-001
ME
CH
AN
ICA
L L
EG
EN
D, N
OT
ES, A
BB
RE
VIA
TIO
NS
WR
K
RM
K
ABBREVIATIONS∠ ANGLE
AD ACCESS DOOR
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
APD AIR PRESSURE DROP
APPROX APPROXIMATELY
AS-1 AIR SEPARATOR MARK - SEE SCHEDULE
BD BALANCING DAMPER
BDD BACK DRAFT DAMPER
BTUH BRITISH THERMAL UNIT PER HOUR
CFH CUBIC FEET PER HOUR
CFM CUBIC FEET PER MINUTE
CHLR-1 CHILLER MARK - SEE SCHEDULE
COP COEFFICIENT OF PERFORMANCE
CP-1 CONDENSATE PUMP MARK - SEE SCHEDULE
CU-1 CONDENSING UNIT MARK - SEE SCHEDULE
CWR CHILLED WATER RETURN
CWS CHILLED WATER SUPPLY
DN DOWN
DSS-1 DUCTLESS SPLIT SYSTEM MARK - SEE SCHEDULE
EAT ENTERING AIR TEMPERATURE
EDB ENTERING DRY BULB
EMD END OF MAIN DRIP
EWB ENTERING WET BULB
EWT ENTERING WATER TEMPERATURE
ESP EXTERNAL STATIC PRESSURE
EXIST EXISTING
FD FIRE DAMPER WITH ACCESS DOOR
FDB DEGREE FAHRENHEIT DRY BULB
FF FINISHED FLOOR
FPM FEET PER MINUTE
FT FEET
FWB DEGREE FAHRENHEIT WET BULB
GA GAUGE
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
"HG INCHES OF MERCURY
HP HORSE POWER
HWC HOT WATER CONVERTER MARK - SEE SCHEDULE
HWR HOT WATER RETURN
HWS HOT WATER SUPPLY
ID INSIDE DIAMETER
KW KILOWATT
L-1 LOUVER MARK - SEE SCHEDULE
LAT LEAVING AIR TEMPERATURE
LBS/HR POUND PER HOUR
LDB LEAVING DRY BULB
LWB LEAVING WET BULB
LWT LEAVING WATER TEMPERATURE
MAX MAXIMUM
MOCP MAXIMUM OVER CURRENT PROTECTION
MIN MINIMUM
MBH THOUSAND BTU/HR
MCA MINIMUM CIRCUIT AMPS
MFS MAXIMUM FUSE SIZE
NOM NOMINAL
NO NUMBER
OA OUTSIDE AIR
OD OUTSIDE DIAMETER
PD PRESSURE DROP
PH PHASE
PSIG POUNDS PER SQUARE INCH GAGE
%RH PERCENT RELATIVE HUMIDITY
PRV PRESSURE RELIEF VALVE
RA RETURN AIR
RBJ RUN BETWEEN JOIST
RIH-1 ROOF INTAKE HOOD MARK - SEE SCHEDULE
RLA RATED LOAD AMPS
RPM REVOLUTIONS PER MINUTE
RTJ RUN THRU JOIST
SA SUPPLY AIR
SCT SATURATED CONDENSING TEMPERATURE
SEER SEASONAL ENERGY EFFICIENCY RATING
SF SQUARE FEET
SP STATIC PRESSURE
SST SATURATED SUCTION TEMPERATURE
TS TIP SPEED
T'STAT THERMOSTAT
TYP TYPICAL
UH-1 UNIT HEATER MARK - SEE SCHEDULE
VAV-1 VARIABLE AIR VOLUME UNIT AND MARK - SEE
SCHEDULE
"WC INCHES WATER COLUMN
WPD WATER PRESSURE DROP
NEW WORK NOTE MARK
SPECIFICATION (CFM NOTE)
GRILLE OR DIFFUSER MARK - SEE SCHEDULE OR
AIR HANDLING UNIT MARK - SEE SCHEDULE
EXHAUST FAN MARK - SEE SCHEDULE
PUMP MARK - SEE SCHEDULE
MOTORIZED CONTROL DAMPER
FLEXIBLE DUCT CONNECTION
MANUAL BALANCING DAMPER WITH LOCKING QUADRANT
ELBOW WITH TURNING VANES
SUBSCRIPT INDICATES EQUIPMENT BEING CONTROLLED
THERMOSTAT/SENSOR MOUNT 48" ABOVE FLOOR
FIRE DAMPER
RETURN DUCT SECTION
BUTTERFLY VALVE
BACKFLOW PREVENTER
FLOW CONTROL BALANCING VALVE WITH
PRESSURE TAPS (GPM NOTED)
PIPE SLOPE (DOWN IN ARROW DIRECTION)
PRESSURE GAUGE SHUT-OFF COCK
FLEXIBLE PIPING CONNECTION
PRESSURE REDUCING VALVE
3-WAY AUTO CONTROL VALVE
STRAINER WITH BLOW DOWN VALVE
SUPPLY DUCT SECTION
PIPE ANCHOR
DIRECTION OF FLOW
PIPE CAP
ECCENTRIC PIPE REDUCER
RELIEF VALVE
GAS SHUT-OFF COCK
THERMOMETER
AUTOMATIC AIR VENT
UNION
AHU-1
EF-1
P-1
DUCT SMOKE DETECTOR
UC
M
(AD) ACCESS DOOR
BD
MECHANICAL LEGEND
CHECK VALVE
BALL VALVE
FD
EXHAUST DUCT SECTION
FLEXIBLE DUCT CONNECTION
WITH BALANCING DAMPER
BOILER EMERGENCY SHUT-OFF SWITCH
NOTE: HEAVY LINE WEIGHT INDICATES NEW EQUIPMENT OR EQUIPMENT TO BE REMOVED, LIGHT LINE WEIGHT INDICATES EQUIPMENT WHICH IS EXISTING TO REMAIN
BLOWER COIL MARK - SEE SCHEDULEBC-1
AIR SEPARATOR MARK - SEE SCHEDULEAS-1
EXPANSION TANK MARK - SEE SCHEDULEET-1
DUCTLESS SPLIT SYSTEM MARK - SEE SCHEDULEDSS-1
DEMOLITION WORK NOTE MARK
EMERGENCY BOILER SHUT-OFF SWITCH
LOW PRESSURE SUPPLY OR RETURN DUCT WORK
UNDER CUT DOOR MIN. 1"
GENERAL NOTES
1. SCOPE OF WORK INCLUDES PROVIDING A FIRST CLASS WORKING SYSTEM IN COMPLIANCE WITH THESE
DRAWINGS AND SPECIFICATIONS, TESTED READY FOR OPERATION COMPLETE WITH LABOR, MATERIALS,
APPARATUS, TRANSPORTATION, AND TOOLS REQUIRED FOR THE INSTALLATION.
2. COORDINATE WORK WITH THAT OF OTHER TRADES AND EXISTING CONDITIONS.
3. THE CONTRACTOR SHALL BE RESPONSIBLE FOR MODIFICATIONS, CHANGES, ETC. FOR THE EQUIPMENT HE
PROVIDES, EVEN IF APPROVED AS AN EQUAL.
4. MISCELLANEOUS ITEMS NOT SHOWN ON THE PLANS BUT NECESSARY FOR A COMPLETE OPERABLE SYSTEM,
SHALL BE SUPPLIED AND INSTALLED.
5. INSTALL EQUIPMENT PER MANUFACTURER'S INSTALLATION INSTRUCTIONS. MAINTAIN ALL RECOMMENDED
CLEARANCES.
6. REMOVE EXCESS MATERIAL, SCRAP, ETC. FROM THE JOB SITE.
7. REPAIR ANY MATERIAL OR WORK WHICH HE HAS DAMAGED.
8. BALANCE AIR AND WATER SYSTEMS WITHIN ±10% OF THE VALUES INDICATED.
9. TEST THE ENTIRE SYSTEM IN ALL MODES OF OPERATION TO INSURE PROPER OPERATION.
10. FURNISH AND INSTALL ALL EQUIPMENT AND MATERIALS FOR A COMPLETE INSTALLATION IN ALL RESPECTS
READY OF INTENDED USE AND IN STRICT ACCORDANCE WITH ALL STATE AND LOCAL CODES AND
MANUFACTURER'S RECOMMENDATIONS. PAY NECESSARY FEES AND OBTAIN PERMITS. INITIATE, MAINTAIN
AND SUPERVISE ALL SAFETY PRECAUTIONS AND PROCEDURES.
11. ALL INDICATED DUCT DIMENSIONS ARE INSIDE CLEAR DIMENSIONS.
POINT OF CONNECTION-NEW TO EXISTING AND
POINT OF DEMOLITION TERMINATION
A
100
T
AHU-1
B
HOT WATER RETURN PIPING
HOT WATER SUPPLY PIPING
GAS PIPING
CHILLED WATER SUPPLY
CHILLED WATER RETURN
CONDENSATE DRAIN
CONDENSER WATER SUPPLY
CONDENSER WATER RETURN
FIRE DAMPER WITH ACCESS DOORFD
VENTILATION RATE SCHEDULE
AREA
SERVED
OCCUPANCY
CLASSIFICATION
VENTILATION
RATE CFM /
PERSON
VENTILATION
RATE CFM /
SQFT
NUMBER OF
PERSONS
PER SPACE
SQUARE
FOOT OF
SPACE
TOTAL PER
PERSON
REQUIRED
VENTILATION
TOTAL
REQUIRED
SQUARE FOOT
VENTILATION
REQUIRED
VENTILATION
VENTILATION
PROVIDED
101 OFFICE 50.06 2 893 10 53.6 64 55
102 OFFICE 50.06 13 1503 65 90.2 155 155
104 OFFICE 50.06 5 573 25 34.4 59 60
103 OFFICE 50.06 8 446 40 26.8 67 75
203OPEN AREA
50.06 20 1686 100 101.2 201 210
FILE FILING ROOM 50.06 0 221 0 13.3 13 15
SLEEP SLEEP ROOM 50.06 2 140 10 8.4 18 20
HSO FILE HSO FILING ROOM 50.06 0 131 0 7.9 8 10
201LORI'S OFFICE
50.06 2 352 10 21.1 31 35
202 TRAINING ROOM 50.06 4 193 20 11.6 32 35
206
BREAK ROOM /KITCHEN 5
0.06 2 208 10 12.5 22 25
205 OFFICE 50.06 2 278 10 16.7 27 30
204 COPY ROOM 50.06 0 90 0 5.4 5 10
208 I.T. ROOM 50.00 0 92 0 0.0 0 -
207 TIFFANYS OFFICE 50.06 1 275 5 16.5 22 25
211 CONFERENCE ROOM 50.06 6 201 30 12.1 42 45
105OFFICE
50.06 2 310 10 18.6 29 30
ENTRYENTRY VESTIBULE
50.06 0 448 0 26.9 27 30
LABCOMPUTER LAB
50.06 1 365 5 21.9 27 30
NOTES:
1.
VENTILATION AND OCCUPANCY RATE IS BASED ON MINIMUM VENTILATION RATES;
INTERNATIONAL MECHANICAL CODE 2015, TABLE 403.3
TOTAL 724 725.00
(E) DOMESTIC HOT
WATER HEATER TO
REMAIN
(E) AIR COMPRESSOR TO
REMAIN
(E) AIR DRYER TO REMAIN
(E) JOHNSON CONTROLS
PANEL TO REMAIN
(E) AHU STARTER
(E) 4" SANITARY VENT TO
REMAIN
ROOM 101
ROOM 102
ROOM 103
ROOM 104
ROOM 105
12x5 O
A
(E) FACP TO REMAIN
(E) DIALBOX TO REMAIN
(E) DIALBOX TO REMAIN
(E) TBB TO REMAIN
(E) PANEL MDP
(E) PANEL A
(E) FAN STARTER
(E) PUMP STARTER
(E) CHILLER PUMP
STARTER
(E) PUMP
STARTER
1
12
7 6
4
21
10
5
21
8
9
11
3
8
14
16
15
17
1718
18
18
18
18
18
18
18
17
ROOM 104
12X
12
12X
12
12X
10
12X
12
12X
10
12X
10
12X812X10
12X
10
12X
8
20
20
19
19
20
19
20
19
19 20
14
14
13
18
18
2
23
22
22
20
CIT
Y O
F H
AM
PT
ON
OLD
H
AM
PT
ON
C
IR
CU
IT
C
OU
RT
RE
PL
AC
E H
VA
C
19-0
15
11/
12/
2019
2406 Princess Anne Road,
Virginia Beach, VA 23456Phone (757) 563-9027
Facsimile(757) 563-9028
Suite 200
COASTALE N G I N E E R I N G
RM
K
CO
MM
ONWEALTH OF VIRGIN
IA
PROFESSIONAL ENGIN
EER
RICHARD M. KLEIN
No. 027864
TH
E C
OP
YR
IG
HT
S T
O A
LL
D
ES
IG
NS
A
ND
D
RA
WIN
GS
A
RE
T
HE
P
RO
PE
RT
Y O
F C
OA
ST
AL
E
NG
IN
EE
RIN
G, P
LL
C. R
EP
RO
DU
CT
IO
N O
R U
SE
F
OR
A
NY
P
UR
PO
SE
O
TH
ER
T
HA
N T
HA
T A
UT
HO
RIZ
ED
B
Y C
OA
ST
AL
E
NG
IN
EE
RIN
G, P
LL
C IS
F
OR
BID
DE
N.
3
M-101
ME
CH
AN
ICA
L 1
ST
FL
OO
R P
LA
N -
DE
MO
LIT
ION
WR
K
RM
K
MECHANICAL 1ST FLOOR PLAN - DEMOLITION
SCALE: 1/4" = 1'-0"
DEMOLITION WORK NOTES:
(THIS SHEET ONLY)
REMOVE EXISTING AIR HANDLING UNIT AND ALL ASSOCIATED HARDWARE
AND CONTROLS. REMOVE EXISTING DUCT WORK AND PIPING TO THE
LIMITS REQUIRED FOR REMOVAL OF EXISTING AIR HANDLING UNIT AND
INSTALLATION OF NEW AIR HANDLING UNIT.
REMOVE EXISTING SUPPLY AIR DUCTWORK TO POINT JUST BELOW THE
MECHANICAL ROOM CEILING AS REQUIRED FOR RECONNECTION TO NEW
AIR HANDLING UNIT.
REMOVE CHWS AND CHWR WATER PIPING.
16x5 O.A. DUCT AND WALL LOUVER SHALL REMAIN.
74x48 LOUVER BLANK OFF WITH 18 GAUGE GALVANIZED SHEET METAL.
76x64 LOUVER BLANK OFF WITH 18 GAUGE GALVANIZED SHEET METAL.
REMOVE COOLING TOWER, PIPING, PUMPS, APPURTENANCES, AND
CONTROLS.
REMOVE BASE MOUNTED PUMPS, PIPING, AND APPURTENANCES AS
REQUIRED FOR INSTALLATION OF NEW PUMPS. TURN OVER EXISTING
PUMPS TO THE OWNER.
REMOVE WATER COOLED CHILLER, PIPING, AND ALL ASSOCIATED
APPURTENANCES.
COOLING TOWER CHEMICAL TREATMENT SYSTEM REMOVED BY AND
TURN OVER TO THE OWNER.
REMOVE EXPANSION TANK, PIPING, AND ALL ASSOCIATED
APPURTENANCES,
REMOVE EXISTING BOILER AND FLUE PATCH ROOF TO MATCH EXISTING.
REMOVE THE GAS LINE AS REQUIRED FOR THE BOILER REMOVAL, RETAIN
THE REMAINING PIPE AND SERVICE FOR RECONNECTION TO NEW BOILER.
REMOVE EXISTING HOT WATER UNIT HEATER AND ALL ASSOCIATED
PIPING AND HARDWARE.
REMOVE MAKE-UP WATER PIPING TO POINT INDICATED
REMOVE HWS, HWR CHWS AND CHWR PIPING TO EXISTING AIR HANDLING
UNIT.
REMOVE 1-1/2" CHWS AND 1-1/2" CHWR PIPING.
REMOVE EXISTING FAN COIL UNIT AND ALL ASSOCIATED HARDWARE; THE
EXISTING PIPING AND DUCTWORK SHALL REMAIN FOR RECONNECTION TO
NEW FAN COIL UNIT.
REMOVE EXISTING HWS, HWR, CHWS, AND CHWR PIPING FROM FAN COIL
UNITS COMPLETE.
REMOVE EXISTING SUPPLY AIR DIFFUSER AND ALL ASSOCIATED DUCT
WORK BACK TO FAN COIL UNIT.
REMOVE EXISTING SUPPLY AIR DIFFUSER AND ALL ASSOCIATED DUCT
WORK BACK TO FAN COIL UNIT.
REMOVE EXISTING COOLING TOWER DUCT WORK FROM TOWER TO
LOUVERS, BLANK OFF REMAINING LOUVERS.
REMOVE EXISTING WALL MOUNTED THERMOSTAT AND ALL ASSOCIATED
WIRING.
REMOVE EXISTING RETURN AIR DUCT FROM AIR HANDLING UNIT AS
REQUIRED FOR INSTALLATION OF NEW BLOWER COIL.
GRAPHIC SCALE1/4" = 1'-0"
0' 12'4' 8'
ROOM 201
JUDGES CHAMBERS 202
ROOM 203
COPY ROOM 204
HEARING ROOM 205
JURY ROOM 206
ATTORNEY CONFERENCE ROOM 207
ROOM 208
ROOM 209
ROOM 210
ROOM 211
14x14
24x20
24x12
18x10
10x8
12x12
12x12
10x8
10x8
10x8
10x8
10x8
12x12
10x8
JURY ROOM
1
2
1
2 22
1
2
2
2
2
2
2
2
2
2
2
2
2
1
1
1
1
1
1
1
2
2
2
1
1
2
JUDGES
LOUNGE
10x8
10x8
12x10
10x8
10x8
12x10
10x8
3
3
3
3
3
6" Ø (TYP OF 22)
10x6
12X
6
10X
8
10X
8
12X
6
10X810X8
6X6
6X4
6X4
6X6
6X4
6
5
6
5 6
5
6
4
5
8
6
6
6
6
6 5
6
5
6
6
5
6
7
7
44
4
44
8
8
4
9
9
9
10 10
10
9
10 1010
10
10
10
10
10
10
10
999
10
10
10
11
11
11
11
11
11
11
11
11
11
20
CIT
Y O
F H
AM
PT
ON
OLD
H
AM
PT
ON
C
IR
CU
IT
C
OU
RT
RE
PL
AC
E H
VA
C
19-0
15
11/
12/
2019
2406 Princess Anne Road,
Virginia Beach, VA 23456Phone (757) 563-9027
Facsimile(757) 563-9028
Suite 200
COASTALE N G I N E E R I N G
RM
K
CO
MM
ONWEALTH OF VIRGIN
IA
PROFESSIONAL ENGIN
EER
RICHARD M. KLEIN
No. 027864
TH
E C
OP
YR
IG
HT
S T
O A
LL
D
ES
IG
NS
A
ND
D
RA
WIN
GS
A
RE
T
HE
P
RO
PE
RT
Y O
F C
OA
ST
AL
E
NG
IN
EE
RIN
G, P
LL
C. R
EP
RO
DU
CT
IO
N O
R U
SE
F
OR
A
NY
P
UR
PO
SE
O
TH
ER
T
HA
N T
HA
T A
UT
HO
RIZ
ED
B
Y C
OA
ST
AL
E
NG
IN
EE
RIN
G, P
LL
C IS
F
OR
BID
DE
N.
4
M-102
ME
CH
AN
ICA
L 2
ND
FL
OO
R P
LA
N -
DE
MO
LIT
ION
WR
K
RM
K
MECHANICAL 2ND FLOOR PLAN - DEMOLITION
SCALE: 1/4" = 1'-0"
1
DEMOLITION WORK NOTES:
(THIS SHEET ONLY)
REMOVE EXISTING FAN COIL UNIT AND ALL ASSOCIATED HARDWARE;
PIPING AND DUCTWORK UNLESS OTHERWISE NOTED. REMOVE EXISTING
WALL MOUNTED THERMOSTAT AND ASSOCIATED CONTROL WIRING.
REMOVE EXISTING HWS, HWR, CHWS, AND CHWR PIPING FROM FAN COIL
UNIT COMPLETE.
RETURN AIR DUCT TO REMAIN IS RUN BELOW FLOOR IN FIRST FLOOR
CEILING SPACE (TYP).
EXISTING OUTSIDE AIR INTAKE TO REMAIN, REMOVE ASSOCIATED
DUCTWORK TO FAN COIL UNIT.
REMOVE EXISTING SUPPLY AIR DIFFUSER AND ALL ASSOCIATED DUCT
WORK BACK TO FAN COIL UNIT.
REMOVE EXISTING SUPPLY AIR DIFFUSER AND ALL ASSOCIATED DUCT
WORK BACK TO FAN COIL UNIT.
REMOVE EXISTING DUCT WORK FROM FAN COIL TO POINT INDICATED,
ABANDON REMAINING DUCT IN PLACE.
REMOVE EXISTING OUTSIDE AIR DUCT AND INTAKE FROM FAN COIL UNIT,
PATCH WALL TO MATCH EXISTING.
REMOVE EXISTING SUPPLY AIR DIFFUSER AND HARD DUCT-RUN OUT
BACK TO TRUNK DUCK, PATCH TRUNK DUCT TO MATCH EXISTING.
REMOVE EXISTING SUPPLY AIR DIFFUSER AND HARD DUCT RUN-OUT
BACK TO TRUNK DUCT, MODIFY TRUNK DUCT AS REQUIRED FOR NEW
FLEXIBLE RUN-OUT DUCT TO DIFFUSER.
REMOVE EXISTING WALL MOUNTED THERMOSTAT AND ASSOCIATED
WIRING.
2
3
GRAPHIC SCALE1/4" = 1'-0"
0' 12'4' 8'
4
5
6
7
8
9
10
11
ROOM 101
ROOM 102
ROOM 103
ROOM 104
ROOM 105
10x10
(E) DOMESTIC HOT
WATER HEATER
(E) AIR
COMPRESSOR
(E) AIR DRYER
(E) JOHNSON
CONTROLS PANEL
(E) AHU STARTER
(E) 4" SANITARY
VENT
(E) HOT WATER UNIT
HEATER
(E) FACP
(E) DIALBOX
(E) DIALBOX
(E) TBB
(E) PANEL MDP
(E) PANEL A
BC
-6
BC-7
BC-5
3
ET-15
AS-15
P-25
P-15
7
6
2
1
5 8
CHLR-1
4" HIGH CONCRETE
HOUSEKEEPING PAD TO
EXTEND 6" BEYOND UNIT
IN ALL DIRECTIONS
BOLLARD (TYP OF 17);
SEE "BOLLARD DETAIL"
SHEET M-502
ROOM 104
10x12
10x10
10x8
10x10
14x14 12x12
10x8
8x10 8x6
10
16x14BC-2
10x8
6x8
B
160
B
140
B
140
B
160
B
140
B
160
B
140
B
140
B
150
D
180
D
180
D
180
D
135
B
140
B
140
B
140
B
130
A
120
8"Ø
6"Ø
10
8x10
8x14
10x10
8"Ø
B
140
6x10
6x10
8"Ø
8"Ø8"Ø
8"Ø 8"Ø
8"Ø
8"Ø
8"Ø
8"Ø
10x6
6x6
Z
Y
6x6
10x10
Y
6x4
12
8x10
12x12
11
Z
Z
BC-1
CU-1
3/4"
3/4"
1"
3/4"
1 1/2"
1 1/4"
2 1/2"
2"
2"
1"
1 1/4"
12x6
16x12
12x10
C.O.
C.O.
1 1/4"
9
13
13
9
P-3
P-4
15
14
M
11
4
16
17
5
M-201
ME
CH
AN
ICA
L 1
ST
FL
OO
R P
LA
N -
NE
W W
OR
KW
RK
RM
K
20
CIT
Y O
F H
AM
PT
ON
OLD
H
AM
PT
ON
C
IR
CU
IT
C
OU
RT
RE
PL
AC
E H
VA
C
19-0
15
11/
12/
2019
2406 Princess Anne Road,
Virginia Beach, VA 23456Phone (757) 563-9027
Facsimile(757) 563-9028
Suite 200
COASTALE N G I N E E R I N G
RM
K
CO
MM
ONWEALTH OF VIRGIN
IA
PROFESSIONAL ENGIN
EER
RICHARD M. KLEIN
No. 027864
TH
E C
OP
YR
IG
HT
S T
O A
LL
D
ES
IG
NS
A
ND
D
RA
WIN
GS
A
RE
T
HE
P
RO
PE
RT
Y O
F C
OA
ST
AL
E
NG
IN
EE
RIN
G, P
LL
C. R
EP
RO
DU
CT
IO
N O
R U
SE
F
OR
A
NY
P
UR
PO
SE
O
TH
ER
T
HA
N T
HA
T A
UT
HO
RIZ
ED
B
Y C
OA
ST
AL
E
NG
IN
EE
RIN
G, P
LL
C IS
F
OR
BID
DE
N.
NEW WORK NOTES:
(THIS SHEET ONLY)
1
CONNECT 3/4" MAKE-UP WATER TO EXISTING 3/4" BACKFLOW
PREVENTER.
1 1/2" CHWS, 1 1/2" CHWR, 1 1/4" HWS, 1 1/4" HWR AND 1 1/4" D
UP IN WALL TO ABOVE SECOND FLOOR CEILING, DEMO AND
PATCH WALL TO MATCH EXISTING.
NEW HOT WATER PUMPS MOUNT ON EXISTING HOUSE
KEEPING PAD, MODIFY AS REQUIRED. MOUNT ON EXISTING
HOUSE KEEPING PAD, MODIFY AS REQUIRED.
PROVIDE A 4" HIGH CONCRETE CHILLER PAD TO EXTEND 6"
BEYOND CHILLER IN ALL DIRECTIONS. CHILL IS LOCATED ON
EXISTING SIDE WALK AND PARTIALLY IN PARKING LOT,
ADJUST PAD THICKNESS AS REQUIRED TO SET CHILLER 4"
ABOVE SIDE WALK LEVEL. MAINTAIN ALL MANUFACTURES
RECOMMENDED CLEARANCES.
EXTEND 4" HIGH CONCRETE HOUSEKEEPING PAD AS
REQUIRED, DOWEL INTO ABANDONED COOLING TOWER PAD.
HVAC CONTROL PANEL LOCATION.
STARTER FOR CHILLED WATER PUMPS.
PROVIDE CHEMLINE 300 GALLON CHILLED WATER BUFFER
TANK, BAFFLE TYPE TANK WITH UPPER 3" FLANGED INLET
AND DISCHARGE FITTINGS. PROVIDE TANK DRAIN FITTING
WITH A 3/4" FULL PORT BALL VALVE AND HOSE CONNECTION,
SEE CHILLED WATER BUFFER TANK DETAIL SHEET M-501.
CONNECT EXISTING SUPPLY AND RETURN AIR DUCTS TO
NEW BLOWER COIL, TRANSITION AS REQUIRED.
EXPOSED DUCT WORK, RUN AS HIGH AS POSSIBLE,
COORDINATE WITH EXISTING STRUCTURE AND LIGHTS.
CLEAN AND PAINT EXISTING LOUVER, PROVIDE AN 8" DEEP
PLENUM FULL SIZE OF LOUVER, CONNECT 12"x12" OUTSIDE
AIR DUCT TO BACK OF PLENUM.
CONNECT NEW OUTSIDE AIR DUCT TO EXISTING, FIELD
VERIFY EXACT SIZE AND LOCATION, TRANSITION AS
REQUIRED.
SPILL CONDENSATE DRAIN INTO EXISTING FLOOR DRAIN,
FIELD VERIFY EXACT LOCATION.
NEW CONDENSING UNIT, PROVIDE WITH 4" HIGH CONCRETE
HOUSE KEEPING TO EXTEND 4" BEYOND UNIT IN ALL
DIRECTIONS LOCATE UNIT TO ALLOW ACCESS TO EXISTING
SIDE WALK.
HEAT TRACE ALL EXTERIOR PIPING AT 5 WATTS PER LINEAR
FOOT FOR FREEZE PROTECTION.
CONNECT NEW BOILER TO EXISTING GAS LINE FIELD VERIFY
EXACT SIZE AND LOCATION, PROVIDE MANUFACTURES
RECOMMENDED GAS TRANE
STARTER FOR HOT WATER PUMPS.
SCALE: 1/8" = 1'-0"
MECHANICAL 1ST FLOOR PLAN - NEW WORK
GRAPHIC SCALE1/4" = 1'-0"
0' 12'4' 8'
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
ROOM 201
JUDGES CHAMBERS 202
ROOM 203
COPY ROOM 204
HEARING ROOM 205
ATTORNEY CONFERENCE ROOM 207
ROOM 208
ROOM 209
ROOM 210
ROOM 211
14x14
24x20
(E) 24x14
(E) 14x14
10x8
12x12
12x12
10x8
10x8
10x8
10x8
10x8
12x12
10x8
JURY ROOM
BC
-8
BC-4
BC-9
1
1
2
2
2
BC-3
1
JUDGES
LOUNGE
(E
) 10x8
(E
) 12x10
(E
) 10x8
(E
) 12x10
10x8
6" Ø (TYP OF 22)
16x14
C
280
C
360
C
360
A
140
A
40
A
110
A
70
14x14
14x10
8x10
12x14
12x6
16x14
6x8
16x18
A
130
A
130
A
130
A
130
A
130
A
130
A
140
A
140
(E
) 12x10
(E
) 10x8
(E
) 12x10
A
140
A
140
A
130
A
130
A
130
A
130
A
130
A
130
10x6
6x8
8x6
10x10
B
160
B
160
10x8 6x8
10x6
8x6
10x610x10
10x10
A
60
A
120
A
60
B
190
A
100
BC-10
B
200
B
200
C
340
10x8 10x10
8"Ø
8"Ø
7"Ø7"Ø
7"Ø7"Ø
7"Ø
7"Ø
7"Ø
7"Ø
7"Ø
7"Ø7"Ø
7"Ø
7" Ø
10"Ø
8"Ø
8"Ø
2
8"Ø3/4"
1"
3/4"
C.O.
1 1/4"
3
DSS-1
7"Ø
10"Ø
3/4"
1 1/4"
3
1
1
1
1
7"Ø
1
11
1 1
1
1
1
1
1
(E
) 10x8
3/4" 3/4"
3
7"Ø
7"Ø
1
6"Ø
X
X
X
Y
Y
X
Y
X
Y
Y
Y
BC-11
C
400
C
400
C
400
14x14
24x12
10"Ø
10"Ø
W
3/4"
3/4"
1 1/4"
3/4"
3/4"
3/4"
1 1/2"
1"
1"
1"
3/4"
3/4"
3/4"
3/4"
6"Ø
6"Ø
6"Ø
6"Ø
6"Ø
6"Ø
1 1/4"
C.O.
10x10
6x6
6
M-202
ME
CH
AN
ICA
L 2
ND
FL
OO
R P
LA
N -
NE
W W
OR
KJA
K/
WR
K
RM
K
20
CIT
Y O
F H
AM
PT
ON
OLD
H
AM
PT
ON
C
IR
CU
IT
C
OU
RT
RE
PL
AC
E H
VA
C
19-0
15
11/
12/
2019
2406 Princess Anne Road,
Virginia Beach, VA 23456Phone (757) 563-9027
Facsimile(757) 563-9028
Suite 200
COASTALE N G I N E E R I N G
RM
K
CO
MM
ONWEALTH OF VIRGIN
IA
PROFESSIONAL ENGIN
EER
RICHARD M. KLEIN
No. 027864
TH
E C
OP
YR
IG
HT
S T
O A
LL
D
ES
IG
NS
A
ND
D
RA
WIN
GS
A
RE
T
HE
P
RO
PE
RT
Y O
F C
OA
ST
AL
E
NG
IN
EE
RIN
G, P
LL
C. R
EP
RO
DU
CT
IO
N O
R U
SE
F
OR
A
NY
P
UR
PO
SE
O
TH
ER
T
HA
N T
HA
T A
UT
HO
RIZ
ED
B
Y C
OA
ST
AL
E
NG
IN
EE
RIN
G, P
LL
C IS
F
OR
BID
DE
N.
NEW WORK NOTES:
(THIS SHEET ONLY)
1
CONNECT NEW VOLUME DAMPER AND FLEXIBLE DUCT
RUN-OUT TO EXISTING TRUNK DUCT, MODIFY EXISTING
TRUNK DUCT AS REQUIRED.
INSTALL DSS-1 ABOVE DOOR PROVIDE WITH PUMPED
CONDENSATE TO ABOVE CEILING.
CONNECT NEW OUTSIDE AIR DUCT TO EXISTING, FIELD
VERIFY EXACT SIZE AND LOCATION, TRANSITION AS
REQUIRED.
SCALE: 1/4" = 1'-0"
MECHANICAL 2ND FLOOR PLAN - NEW WORK
GRAPHIC SCALE1/4" = 1'-0"
0' 12'4' 8'
2
3
BUILDING INSULATION NOTE:
PROVIDE R-38 FOIL FACED BATT INSULATION AT BOTTOM
CHORD OF ROOF TRUSSES OVER THE ENTIRE SECOND
FLOOR AREA OF WORK INDICATED ON THE DRAWINGS.
INSULATION SHALL MEET THE REQUIREMENTS FOR NON
COMBUSTIBLE CONSTRUCTION. ATTACH BATTS TO BOTTOM
CHORD OF TRUSSES WITH GALVANIZED STAPLES AND A
MECHANICAL.
7
M-301
ME
CH
AN
ICA
L D
ET
AIL
S A
ND
SC
HE
DU
LE
JAK
/W
RK
RM
K
20
CIT
Y O
F H
AM
PT
ON
OLD
H
AM
PT
ON
C
IR
CU
IT
C
OU
RT
RE
PL
AC
E H
VA
C
19-0
15
11/
12/
2019
2406 Princess Anne Road,
Virginia Beach, VA 23456Phone (757) 563-9027
Facsimile(757) 563-9028
Suite 200
COASTALE N G I N E E R I N G
RM
K
CO
MM
ONWEALTH OF VIRGIN
IA
PROFESSIONAL ENGIN
EER
RICHARD M. KLEIN
No. 027864
TH
E C
OP
YR
IG
HT
S T
O A
LL
D
ES
IG
NS
A
ND
D
RA
WIN
GS
A
RE
T
HE
P
RO
PE
RT
Y O
F C
OA
ST
AL
E
NG
IN
EE
RIN
G, P
LL
C. R
EP
RO
DU
CT
IO
N O
R U
SE
F
OR
A
NY
P
UR
PO
SE
O
TH
ER
T
HA
N T
HA
T A
UT
HO
RIZ
ED
B
Y C
OA
ST
AL
E
NG
IN
EE
RIN
G, P
LL
C IS
F
OR
BID
DE
N.
CHILLED WATER BUFFER TANK DETAIL
NO SCALE
3-LEG STANDS
1/2" THERMAL
INSULATION
BAFFLE PLATE
6" OUTLET
BYPASS AIR
VENT
6" INLET
BUTTERFLY
VALVE (N.O.)
BUTTERFLY
VALVE (N.O.)
6"6"
TO CHILLER, SEE PLANS
FOR CONTINUATION
FROM HWS, SEE PLANS
FOR CONTINUATION
3/4" DRAIN, WITH FULL
PORT BALL VALVE AND
HOSE CONNECTION
HORIZONTAL BLOWER COIL UNIT DETAIL
NOT TO SCALE
AIR HANDLING UNIT
FLEXIBLE DUCT CONNECTION (TYP)
FINISHED FLOOR
P-TRAP, EZ-TRAP INC. SERIES 200
WITH CLEAR TRAP AND FLOAT
SWITCH, PROVIDE EACH WITH A
CLEANING BRUSH AND BRUSH CLAMP
CONDENSATE DRAIN SEE
PLANS FOR CONTINUATION
RA PLENUM FULL
SIZE OF UNIT RA
OPENING
RA DUCT SEE PLANS FOR
SIZE AND ORIENTATION
HWS & HWR PIPING
SEE PLANS FOR SIZE
CHR & CHR PIPING,
SEE PLANS FOR SIZE
TRANSITION AS REQUIRED
SA DUCT SEE PLANS FOR SIZE
AND CONTINUATION
2" DEEP GALVANIZED STEEL DRAIN
PAN TO EXTEND 4" BEYOND UNIT
AND VALVES IN ALL DIRECTIONS
FLOAT SWITCH IN AUXILIARY
DRAIN PAN TO SHUT DOWN UNIT
UPON ACTIVATION
CAULK
CAULK
IMBED IN SEALANT
CLIP ANGLES (TYP)
BIRDSCREEN
(TYP)
WITH EXPANSION SHIELDS
STAINLESS STEEL BOLTS
IMBED IN SEALANT
DRAWINGS
VARIES, SEE ARCHITECTURAL
WALL CONSTRUCTION
NOT TO SCALE
TYPICAL LOUVER DETAIL
SUSPEND FROM
STRUCTURE WITH
1
4
"
THREADED ROD (TYP OF 4)
VIBRATION ISOLATOR (TYP
OF 4)
(CONCRETE WALL)
PIPE SLEEVE EXTERIOR WALL
NO SCALE
PIPE
PIPE SLEEVE
BACK-UP MATERIAL
MINERAL WOOD
INSTALLATION
PLASTIC WATER PROOF
CEMENT
EXISTING
CONCRETE
WALL
4" BRICK FACE
HEAT TRACE
CHILLER PIPING DETAILNO SCALE
F
AIR COOLED CHILLER
THERMOMETER (TYP)
PRESSURE GAUGE WITH VALVE COCK
2 - POSITION AUTOMATIC CHILLER VALVE
AUTOMATIC AIR VENT
FLEXIBLE PIPING CONNECTION (TYP)
BUTTERFLY TYPE
CHILLER ISOLATION
VALVE (TYP OF 2)
FLOW CONTROL
BALANCING VALVE WITH
PRESSURE TAPS
FLOW SWITCH
BASE MOUNTED, CLOSED COUPLED CENTRIFUGAL PUMP
3/4" DRAIN VALVE W/ HOSE CONNECTION
1/4"
PRESSURE GAUGE 0-120 PSIG RANGE
MOTOR
PUMP
*
*
BUTTERFLY VALVE (TYPICAL)
VIBRATION ISOLATOR (TYPICAL)
CHECK VALVE
* STRAIGHT LENGTHS OF UNOBSTRUCTED PIPE WITHOUT INLINE APPURTENANCES SHALL
BE INSTALLED UP/DOWN STREAM OF FLOW CONTROL BALANCING VALVE PER MFG.'S
INSTALLATION INSTRUCTIONS
CONCENTRIC
REDUCER
(TYPICAL)
GLOBE OR
NEEDLE VALVE
(TYPICAL)
PRESSURE
GAUGE
0-120
RANGE
STRAINER WITH
BLOW DOWN
FLOW CONTROL BALANCING VALVE SIZED
PER MANUFACTURER'S RECOMMENDATION
GROUT IN PUMP BASE WHEN REQUIRED BY
MANUFACTURER'S INSTALLATION INSTRUCTIONS
ANCHOR PUMP TO EXISTING INERTIA BASE,
MODIFY BASE AS REQUIRED TO ACCEPT NEW
PUMP OR PROVIDE A NEW INERTIA BASE
MIN. STRAIGHT PIPE 5 X DIA. SUCTION
OR USE SUCTION DIFFUSER
ELECTRIC UNIT HEATER MOUNTING DETAIL
NOT TO SCALE
4" HOUSEKEEPING PAD
TO EXTEND 6" BEYOND
UNIT IN ALL DIRECTIONS
EXTERIOR WALL
THREADED BOLT
AND LOCKNUT
WALL BRACKET
FASTEN WALL BRACKET
TO WALL WITH 1/2"Ø
BOLTS (TYP OF 2)
SWIVEL BRACKET
UNIT HEATER
GRILLE REGISTER & DIFFUSER SCHEDULE
MARK
MANUFACTURER/
MODEL
TYPE SERVICE
NECK SIZE
INCHES
APD
"WC
NOISE
CRITERIA
(NC)
MATERIALS REMARKS
A
ANEMOSTAT / E
SERIES
SQR-CONE
ADJUSTABLE
CEILING
SUPPLY
6"Ø .02 15 ALUMINUM1, 2, 3
B
ANEMOSTAT / E
SERIES
SQR-CONE
ADJUSTABLE
CEILING
SUPPLY
8"Ø .02 15 ALUMINUM1, 2, 3
C
ANEMOSTAT / E
SERIES
SQR-CONE
ADJUSTABLE
CEILING
SUPPLY
10"Ø .02 15 ALUMINUM1, 2, 3
D ANEMOSTAT
SUPPLY
GRILLE
DUCT
SUPPLY
- .02 15 ALUMINUM1, 2, 3
W
ANEMOSTAT/
MODEL 30
LOUVERED
RETURN
CEILING
RETURN
24X24 .02 20 ALUMINUM1, 3, 4
X
ANEMOSTAT/
MODEL 30
LOUVERED
RETURN
CEILING
RETURN
6X6 .02 20 ALUMINUM1, 3, 4
Y
ANEMOSTAT/
MODEL 30
LOUVERED
RETURN
CEILING
RETURN
12X12 0.02 20 ALUMINUM1, 3, 4
Z
ANEMOSTAT/
MODEL 30
LOUVERED
RETURN
CEILING
RETURN
16X16 0.02 20 ALUMINUM1, 3, 4
NOTES:
1 FOR LAY-IN MOUNT APPLICATION.
24-WAY BLOW, ADJUSTABLE DISTRIBUTION HORIZONTAL TO VERTICAL
3 COLOR TO BE WHITE.
445° DEFLECTION, BLADES PARALLEL TO SHORT SIDE.
8
M-502
ME
CH
AN
ICA
L D
ET
AIL
S A
ND
SC
HE
DU
LE
JAK
RM
K
20
CIT
Y O
F H
AM
PT
ON
OLD
H
AM
PT
ON
C
IR
CU
IT
C
OU
RT
RE
PL
AC
E H
VA
C
19-0
15
11/
12/
2019
2406 Princess Anne Road,
Virginia Beach, VA 23456Phone (757) 563-9027
Facsimile(757) 563-9028
Suite 200
COASTALE N G I N E E R I N G
RM
K
CO
MM
ONWEALTH OF VIRGIN
IA
PROFESSIONAL ENGIN
EER
RICHARD M. KLEIN
No. 027864
TH
E C
OP
YR
IG
HT
S T
O A
LL
D
ES
IG
NS
A
ND
D
RA
WIN
GS
A
RE
T
HE
P
RO
PE
RT
Y O
F C
OA
ST
AL
E
NG
IN
EE
RIN
G, P
LL
C. R
EP
RO
DU
CT
IO
N O
R U
SE
F
OR
A
NY
P
UR
PO
SE
O
TH
ER
T
HA
N T
HA
T A
UT
HO
RIZ
ED
B
Y C
OA
ST
AL
E
NG
IN
EE
RIN
G, P
LL
C IS
F
OR
BID
DE
N.
NOTE:
BACKFILL, CONCRETE, REINFORCING STEEL, AND ANCHOR
BOLTS ARE SHOWN FOR REFERENCE ONLY.
NOTE:
4'-0"
(TYP. 4 SIDES)
8"
1'-0"
3"
12" MIN.
2 #4 BARS CONT.
FINISH GRADE
1" CHAMFER - TYP.SLOPE 1"
6" REINFORCED CONCRETE SLAB
3"
NO SCALE
CONCRETE PAD DETAIL
REMOVE EXISTING TOP SOIL WITHIN AREA OF NEW CONCRETE SLAB. CONCRETE SLAB SHALL MATCH
EXISTING SLAB ON THE EAST SIDE OF THE MECHANICAL ROOM. SLAB SHALL BE 8'-0" x 12'-0"±.
6x6 6/6 WELDED WIRE
FABRIC
ELEVATION TO MATCH
EXISTING SLAB ON EAST
SIDE OF MECHANICAL ROOM
6" CONCRETE PAD AT MECHANICAL
UNIT
FACE OF
EXISTING
BUILDING
8" COMPACTED
FILL - MIN.
1/2" PREMOLDED EXPANSION
JOINT MATERIAL
NO SCALE
BOLLARD DETAIL
BOLLARD PAINT TRAFFIC YELLOW
FINISHED GRADE
GALVANIZED ANCHOR
BOLTS & HEX NUTS
CONCRETE BASE AND
REINFORCING STEEL
UNDISTURBED SOIL,
OR SELECT BACKFILL,
COMPACTED
NO SCALE
6"
EQUIPMENT PAD DETAIL
DRILL HOLES IN EXIST CONCRETE
SLAB AND GROUT IN #5 REBARS 6"
LONG AT 12" OC AROUND
PERIMETER OF NEW PUMP PAD
EXIST CONCRETE SLAB
NEW CONCRETE PUMP PAD, TO
EXTEND 4" BEYOND PUMP BASE
#4 REBAR AT 8" OC
NEW EQUIPMENT
ANCHOR BOLTS
SYSTEM POINT LIST
SYSTEM POINT
DESCRIPTION
ANALOGBINARY SYSTEM FEATURES
NOTES:
CGAF3PTS.XLS
INPUT OUTPUT INPUT OUTPUT ALARMS PROGRAMS
(CH-1) HOT
WATER SYSTEM
TE
MP
ER
AT
UR
E
PR
ES
SU
RE
RH
KW
GP
M
CF
M
PP
M
PE
RC
EN
T
PE
RC
EN
T R
LA
SE
TP
OIN
T
AM
PS
DD
C
SE
TP
OIN
T A
DJ.
ST
AT
US
ST
AT
US
O
N/O
FF
FILT
ER
S
TA
TU
S
ST
AT
US
O
PE
N/C
LS
D.
FA
ULT
ALA
RM
OF
F / O
N
OP
EN
/ C
LO
SE
D
LO
CK
OU
T
EN
AB
LE
/ D
IS
AB
LE
HIG
H A
NA
LO
G
LO
W A
NA
LO
G
BIN
AR
Y
PR
OO
F
SE
NS
OR
F
AIL
FLO
W F
AIL
CO
MM
. F
AIL
DIA
GN
OS
TIC
S
TIM
E S
CH
ED
ULIN
G
DE
MA
ND
LIM
IT
IN
G
OP
T. S
TA
RT
/ S
TO
P
RE
SE
T
EV
EN
T P
RO
GR
AM
DD
C
ALA
RM
IN
ST
RU
CT
MA
IN
T. W
K. O
RD
ER
RU
N T
IM
E
EX
P. M
ES
SA
GE
SE
T B
AC
K / S
ET
U
P
NIG
HT
P
UR
GE
TE
NA
NT
B
ILLIN
G
CH
ILLE
R S
EQ
UE
NC
IN
G
TO
TA
LIZ
IN
G
TIM
ED
O
VE
RR
ID
E
CH
ILLE
R S
TA
RT
S
CHILLER X X X X X X X
CHILLED WATER RETURN X X X X
CHILLED WATER SUPPLY X X X X X
CURRENT LIMIT X X
CHILLED WATER SETPOINT X X
UNIT CURRENT X X X X
COND. REFRIG X X X X
EVAP REFRIG. X X X X
CW PUMP X X TYP. OF 2
GAS FIRED WATER BOILER SCHEDULE
MARK
MANUFACTURER/
MODEL
GAS
PRESSURE
IN/WC
INPUT
BTUH
OUTPUT
BTUH
LWT
°F
EWT °F
AIR INLET/
OUTLET
FLOW GPM PD FT H2O
ELECTRICAL SERVICE
REMARKS
VOLTS PH AMPS
B-1 APEX / 425C 11399,000 375,000
160 135.3 4"Ø 21.8 7.9 120 1 71, 2, 3, 4
1.ELECTRONIC IGNITION, CONDENSING HYDRONIC BOILER, PROVIDE WITH MODULATION CONTROLS PROVIDING A 5 TO 1 TURN DOWN
2. PROVIDE CPVC EXHAUST AND INTAKE VENT PIPING AND TERMINATION FITTINGS WITH SCREENS IN ACCORDANCE WITH MANUFACTURES RECOMMENDATIONS
3. PROVIDE GAS TRAIN PER MANUFACTURES RECOMMENDATIONS.
4.
PROVIDE WITH INTERNAL CONTROLS TO MAINTAIN 160 BUILDING SUPPLY WATER TEMPERATURE. (ADJUSTABLE).
NO SCALE
DIRECT VENT THROUGH WALL DETAIL.
NO SCALE
PIPE
HEAT TRACE INSTALLATION DETAIL
PIPE INSULATION
HEAT TRACE, INSTALL
AND STRAP TO PIPE PER
MANUFACTURERS
RECOMMENDATIONS FOR
ACTUAL PIPE DIAMETER.
CORRUGATED ALUMINUM
JACKET, SEAL ALL SEAMS
WEATHER TIGHT.
CONTINUOUS
VAPOR/WEATHER SEAL
VENT TERMINAL
COUPLING WITH SCREEN
12IN. MIN ABOVE GRADE
+ HIGHEST ANTICIPATED
SNOW LEVEL
RECOMMENDED
SPACING 36IN.
12 IN. MIN.
24IN. MAX
TO WALL
(TYP)
COMBUSTION AIR TERMINAL
90° ELBOW WITH SCREEN
9
M-401
ME
CH
AN
ICA
L S
CH
ED
UL
ES
WR
K
RM
K
20
CIT
Y O
F H
AM
PT
ON
OLD
H
AM
PT
ON
C
IR
CU
IT
C
OU
RT
RE
PL
AC
E H
VA
C
19-0
15
11/
12/
2019
2406 Princess Anne Road,
Virginia Beach, VA 23456Phone (757) 563-9027
Facsimile(757) 563-9028
Suite 200
COASTALE N G I N E E R I N G
RM
K
CO
MM
ONWEALTH OF VIRGIN
IA
PROFESSIONAL ENGIN
EER
RICHARD M. KLEIN
No. 027864
TH
E C
OP
YR
IG
HT
S T
O A
LL
D
ES
IG
NS
A
ND
D
RA
WIN
GS
A
RE
T
HE
P
RO
PE
RT
Y O
F C
OA
ST
AL
E
NG
IN
EE
RIN
G, P
LL
C. R
EP
RO
DU
CT
IO
N O
R U
SE
F
OR
A
NY
P
UR
PO
SE
O
TH
ER
T
HA
N T
HA
T A
UT
HO
RIZ
ED
B
Y C
OA
ST
AL
E
NG
IN
EE
RIN
G, P
LL
C IS
F
OR
BID
DE
N.
BLOWER COIL UNIT SCHEDULE
MARK
MANUFACTURER/
MODEL
FAN DATA
COOLING DATA (EWT: 42.0°F) HEATING DATA (EWT: 160.0°F)
ELECTRICAL SERVICE
REMARKS
NORMAL
CFM
DESIGN
ESP
OA
CFM
ESP
'WC
FAN
RPM
MOTOR
HP
TOTAL
MBH
SENSIBLE
MBH
EAT LAT
WPD
FT
WATER
FLOW
GPM
TOTAL
MBH
EAT
°FDB
LAT
°FDB
WPD
FT
WATER
FLOW
GPM
VOLTS PH
MOCP
AMPS
°FDB °FWB °FDB °FWB
BC-1 TRANE/BCVDO72E2 2220 NOTE 2 220 .5 ECM 1 72.43 60.78 79.00 64.80 54.02 58.85 1.99 9.62 84.0 65.0 100.0 0.24 3.37 208 3 152, 3, 4, 5, 6
BC-2 TRANE/BCHD072E2 1470 NOTE 1 210 .5 ECM 1 44.87 38.79 79.10 65.10 55.11 55.01 0.84 5.96 55.80 65.0 100.0 0.38 4.79 208 1 151, 3, 4, 5, 6
BC-3 TRANE/ BCHD024E2 430 NOTE 1 80 .45 ECM .5 14.15 11.30 79.60 11.30 55.75 55.55 1.61 1.88 9.33 65.0 85.0 0.19 0.52 208 1 151, 3, 4, 5, 6
BC-4 TRANE/BCHD036E2 1360 NOTE 1 100 .4 ECM 1 38.92 33.32 78.60 64.90 56.39 55.51 4.46 5.17 51.77 65.0 100.0 1.09 1.87 208 1 151, 3, 4, 5, 6
BC-5 TRANE/BCHD012E2 350 NOTE 1 30 .4 ECM .5 10.01 9.10 78.20 64.20 54.95 54.80 0.87 1.33 13.51 65.0 100.0 2.71 2.19 208 1 151, 3, 4, 5, 6
BC-6 TRANE/BCHD018E2 420 NOTE 1 60 .35 ECM .5 14.93 11.83 79.00 65.10 53.21 53.08 2.34 1.95 15.83 65.0 100.0 2.34 1.95 208 1 151, 3, 4, 5, 6
BC-7 TRANE/BCHD012E2 540 NOTE 1 70 .4 ECM .5 20.68 15.48 79.90 66.00 53.22 52.95 1.58 2.75 20.00 65.0 100.0 1.93 1.53 208 1 151, 3, 4, 5, 6
BC-8 TRANE/BCHD012E2 360 NOTE 1 35 .35 ECM .5 9.82 8.52 79.00 65.0 57.0 54.98 .84 1.31 12.30 65.0 100.0 1.49 1.60 208 1 151, 3, 4, 5, 6
BC-9 TRANE/BCHD012E2 340 NOTE 1 45 .3 ECM .5 13.68 10.05 79.00 65.90 53.51 53.22 1.68 1.82 13.59 65.0 100.0 1.05 1.27 208 1 151, 3, 4, 5, 6
BC-10 TRANE/BCHD012E2 400 NOTE 1 30 .3 ECM .5 13.78 11.53 78.00 64.10 53.09 52.96 1.70 1.83 15.98 65.0 100.0 2.48 1.83 208 1 151, 3, 4, 5, 6
BC-11 TRANE/BCHD036 1200 NOTE 1 30 .3 ECM 1 29.8 29.17 77.5 62.5 54.74 53.91 2.58 3.81 45.36 65.0 100.0 0.78 1.56 208 1 151, 3, 4, 5, 6
NOTES:
1. HORIZONTAL BLOWER COIL, PROVIDE WITH UNIT MOUNTED POLYMER DRAIN PAN.
2. VERTICAL BLOWER COIL, PROVIDE WITH UNIT MOUNTED POLYMER DRAIN PAN.
3. PROVIDE WITH UNIT MOUNTED CONTROLS FOR STAND ALONE OPERATION.
4. PROVIDE WITH FILTER SECTION AND MERV 8 FILTERS.
5. PROVIDE WITH WALL MOUNTED THERMOSTAT.
6. PROVIDE WITH 3-WAY MODULATING CONTROL VALVES ON HOT AND CHILLED WATER COILS.
AIR SEPARATOR/EXPANSION TANK SCHEDULE
AIR SEPARATOR EXPANSION TANK
REMARKS
MARK
MANUFACTURER/
MODEL
PIPE
SIZE
(IN)
PRESSURE
DROP
(FT)
MARK
MANUFACTURER/
MODEL
ACCEPTANCE
VOLUME
(GALS)
SYSTEM
VOLUME
(GALS)
MAX
TEMP
(°F)
MIN
TEMP
(°F)
FULL
PRESSURE
PSIG
AS-1
BELL AND
GOSSET R-2
2"
1.8
ET-1
BELL AND
GOSSETT / B-35LA
10.0 560 100 40 20
3
AS-2
BELL AND
GOSSET IAS-1 1/2
1 1/2"
3.0
ET-2
BELL AND
GOSSETT / B100LA
4.95 220 165 40 20
1,2
NOTES:
1 INLINE.
2 PROVIDE WITH AUTOMATIC AIR VENT.
CIRCULATING PUMP SCHEDULE
MARK
MANUFACTURER/
MODEL
TYPE
WATER
FLOW
GPM
HEAD
FT
MOTOR
RPM EFFICIENCY
MOTOR STARTER
REMARKS
HP VOLTS PH SIZE TYPE
P-1
BELL AND
GOSSET/SERIES
1510 1.25AD
BASE
MOUNTED
37.4 38.4 1 208 3 1559 57.8 00 11, 2, 3, 4
P-2
BELL AND
GOSSET/SERIES
1510 1.25AD
BASE
MOUNTED
37.4 38.4 1 208 3 1559 57.8 00 11, 2, 3, 4
P-3
BELL AND
GOSSET/SERIES
1510
BASE
MOUNTED
21.8 30.6 0.75 208 3 1616 51.0 00 11, 2, 3, 4
P-4
BELL AND
GOSSET/SERIES
1510
BASE
MOUNTED
21.8 30.6 0.75 208 3 1616 51.0 00 11, 2, 3, 4
NOTES:
1 BASE MOUNTED SPLIT COUPLED PUMP.
2 NON-OVERLOADING.
3 PROVIDE WITH SUCTION DIFFUSER.
4 PROVIDE WITH MOTOR STARTER.
AIR COOLED CHILLER SCHEDULE
MARK
MANUFACTURER/
MODEL
CAPACITY
WATER
FLOW
GPM
EWT
°F
LWT
°F
WPD
FT
OA
TEMP
°F
UNLOADING
STEPS %
ELECTRIC SERVICES
REFRIGERANT
TYPE
REMARKS
TOTAL
RLA
MCA MOP VOLTS PHASE
ACC-1 TRANE / CGAM026 26 37.4 57.0 42.0 6.0 95.0 2 114.4 131 125 208 3 410A1,2,3,4,5
NOTES:
1 SINGLE POINT ELECTRICAL CONNECTION
2 HIGH EFFICIENCY UNIT
3 PROVIDE CHILLER WITH FULL POWER QUALITY SAFETIES, INCLUDING OVERCURRENT, UNDER CURRENT, OVER VOLTAGE, UNDER VOLTAGE, PHASE LOSS, AND POWER SURGE / DROP
PROTECTION.
4 PROVIDE WITH LOW AMBIENT CONTROLS FOR OPERATION DOWN TO 20°F
5 PROVIDE WITH BARREL HEATERS FOR FREEZE PROTECTION.
ELECTRIC UNIT HEATER SCHEDULE
MARK
MANUFACTURER/
MODEL
CFM MBH WATTS
EAT
°F
LAT
°F
VOLTS PHASE AMPS REMARKS
EUH-1 MARKEL/FIFS105N 400 17.1 5000 55.0 95.0 208 1 24.11, 2, 3
NOTES:
1 PROVIDE WITH MANUFACTURERS WALL MOUNTING BRACKET.
2 PROVIDE WITH MANUFACTURERS REMOTE LINE VOLTAGE WALL MOUNTED THERMOSTAT.
3 PROVIDE WITH AUTOMATIC RESET HIGH LIMIT CONTROLS.
DUCTLESS SPLIT SYSTEM SCHEDULE
INDOOR UNIT
MARK
MANUFACTURER/
MODEL
FAN DATA COOLING CAPACITY HEATING CAPACITY ELECTRIC HEATER
REMARKS
AIR
FLOW
CFM
OA
CFM
MOTOR
WATTS
TOTAL
MBH
SENSIBLE
MBH
EAT
TOTAL
MBH
EAT
°FDB
LAT
°FDB
KW MBH
NO.
STAGES
°FDB °FWB
DSS-1
MITSUBISHI/
NTYWST090A112A
360 - 30 9.0 7.4 80.0 67.0 - - - - - -1, 2, 3, 4, 5
NOTES:
1 PROVIDE WITH WIRED WALL MOUNTED STAND ALONE THERMOSTAT.
2 PROVIDE WITH UNIT MOUNTED CONDENSATE PUMP.
3PROVIDE FOR SINGLE POINT CONNECTION, FED FROM OUT DOOR UNIT.
4 WALL MOUNTING HARDWARE.
5 AT 17° F
DUCTLESS SPLIT SYSTEM SCHEDULE
OUTDOOR UNIT
MARK
MANUFACTURER/
MODEL
SERVES MIN SEER MIN EER REFRIGERANT TYPE
ELECTRIC SERVICE
REMARKS
MCA MOCP VOLTS PHASE
CU-1
MITSUBISHI/
NTYSST090A112A
DSS-1 24.60 15.40 R410A 7 15 208 11, 2, 3
NOTES:
1 AT 17° F
2 SINGLE POINT CONNECTION.
3 PROVIDE WITH REFRIGERANT LINE KIT DESIGNED AND SIZED BY THE MANUFACTURER FOR ACTUAL DISTANCE AND ELEVATION CHANGES.
DS
S-1
RM
K12/19/2019
10
M-402
ME
CH
AN
ICA
L C
ON
TR
OL
S, L
EG
EN
D A
ND
NO
TE
SW
RK
RM
K
20
CIT
Y O
F H
AM
PT
ON
OLD
H
AM
PT
ON
C
IR
CU
IT
C
OU
RT
RE
PL
AC
E H
VA
C
19-0
15
11/
12/
2019
2406 Princess Anne Road,
Virginia Beach, VA 23456Phone (757) 563-9027
Facsimile(757) 563-9028
Suite 200
COASTALE N G I N E E R I N G
RM
K
CO
MM
ONWEALTH OF VIRGIN
IA
PROFESSIONAL ENGIN
EER
RICHARD M. KLEIN
No. 027864
TH
E C
OP
YR
IG
HT
S T
O A
LL
D
ES
IG
NS
A
ND
D
RA
WIN
GS
A
RE
T
HE
P
RO
PE
RT
Y O
F C
OA
ST
AL
E
NG
IN
EE
RIN
G, P
LL
C. R
EP
RO
DU
CT
IO
N O
R U
SE
F
OR
A
NY
P
UR
PO
SE
O
TH
ER
T
HA
N T
HA
T A
UT
HO
RIZ
ED
B
Y C
OA
ST
AL
E
NG
IN
EE
RIN
G, P
LL
C IS
F
OR
BID
DE
N.
CHW SYSTEM CONTROL DIAGRAM
NOT TO SCALE
BLOWER COIL (2 THROUGH 10) UNIT CONTROL DIAGRAM
SEQUENCE OF OPERATIONS
CHILLED WATER SYSTEM CONTROL:
DURING THE OCCUPIED MODE, WHENEVER THE OUTSIDE AIR TEMPERATURE RISES TO THE SETPOINT OF THE DDC CONTROLLER, THE DDC CONTROLLER
SHALL ENABLE THE MAIN CHILLED WATER PUMP. ONCE FLOW HAS BEEN PROVEN THROUGH THE EVAPORATOR, THE DDC CONTROLLER SHALL ENABLE THE
CHILLER. ONCE THE CHILLER IS DISABLED, THE CHILLER WILL CONTINUE TO RUN THE CHILLED WATER PUMP UNTIL REFRIGERANT PRESSURES ARE IN THE
CHILLER'S LIMIT TO DISABLE FLOW.
THE DDC CONTROLLER SHALL MONITOR CHILLER CURRENT DRAW, EVAPORATOR TEMPERATURE AND CONDENSER TEMPERATURE ON THE CHILLER.
WHENEVER ANY OF THE ABOVE THREE VARIABLES REACHES SETPOINT, THE DDC CONTROLLER SHALL RESET THE LEAVING THE WATER SUPPLY SETPOINT
AND UNLOAD THE COMPRESSOR AND IF NECESSARY DE-ENERGIZE THE CHILLER. PID CONTROL SHALL BE UTILIZED FOR THE ABOVE SEQUENCE.
THE DDC CONTROLLER SHALL SELECT A DIFFERENT CHILLED WATER PUMP WEEKLY TO ACT AS THE MAIN, INDEXING THE OTHER PUMP AS A STANDBY.
WHENEVER THE DDC CONTROLLER SENSES THAT THE LEAD PRIMARY CHILLED WATER PUMP HAS LOST FLOW, THE DDC CONTROLLER, AFTER A TIME
DELAY (ADJUSTABLE), SHALL START THE STANDBY PUMP AMD DISABLE THE FAILED PUMP.
HOT WATER SYSTEM CONTROL:
ON A FALL IN OUTSIDE AIR TEMPERATURE TO THE SETPOINT OF THE DDC CONTROLLER OR WHENEVER HEAT IS REQUIRED, THE DDC CONTROLLER SHALLENERGIZE THE LEAD HOT WATER PUMP AND ENABLE BOILER
THE DDC CONTROLLER SHALL SELECT A DIFFERENT HOT WATER PUMP WEEKLY TO ACT AS THE LEAD, INDEXING THE OTHER PUMP AS A STANDBY.WHENEVER THE DDC CONTROLLER SENSES THAT THE MAIN HOT WATER PUMP HAS LOST FLOW, THE DDC CONTROLLER, AFTER A TIME DELAY(ADJUSTABLE), SHALL START THE STANDBY PUMP AND DISABLE THE LEAD HOT WATER PUMP.
BC-1 CONTROL:
THE DDC CONTROLLER SHALL ENERGIZE THE UNIT THROUGH ITS OPTIMIZATION PROGRAM FOR MORNING WARM-UP. DURING MORNING WARM-UP, THE
OUTSIDE AIR DAMPER SHALL REMAIN FULLY CLOSED, THE RETURN AIR DAMPER SHALL BE FULLY OPEN, AND THE HOT WATER VALVE SHALL BE FULLY OPEN
TO THE COIL.
AT OCCUPANCY TIME, THE DDC CONTROLLER SHALL OPEN THE MINIMUM OUTSIDE AIR DAMPER CLOSING THE RETURN AIR DAMPER A PROPORTIONAL
AMOUNT.
ON A RISE IN SPACE TEMPERATURE TO THE HEATING SETPOINT OF THE DDC CONTROLLER, THE DDC CONTROLLER SHALL MODULATE THE HOT WATER
REHEAT VALVE CLOSED TO THE COIL. ON A FURTHER RISE IN SPACE THE DDC CONTROLLER SHALL MODULATE THE OUTSIDE AIR DAMPER OPEN CLOSING
THE RETURN AIR DAMPER A PROPORTIONAL AMOUNT FOR FREE COOLING. WHENEVER THE SETTING OF THE MIXED AIR TEMPERATURE LOW LIMIT IS
REACHED, THE DDC CONTROLLER SHALL MODULATE THE OUTSIDE AIR DAMPER CLOSED TO ITS PRESET MINIMUM POSITION OPENING THE RETURN AIR
DAMPER A PROPORTIONAL AMOUNT. WHENEVER THE OUTSIDE AIR TEMPERATURE RISES ABOVE THE SETPOINT OF THE DDC CONTROLLER, THE DDC
CONTROLLER SHALL DISABLE THE ECONOMIZER CONTROL. ON A CONTINUED RISE IN SPACE TEMPERATURE, THE DDC CONTROLLER SHALL MODULATE THE
CHILLED WATER VALVE OPEN TO THE COIL.
WHENEVER THE SETTING OF THE FREEZESTAT IS REACHED, THE FREEZESTAT SHALL DE-ENERGIZE THE SUPPLY AIR FAN, CLOSE THE OUTSIDE AIR DAMPER,
AND OPEN THE HOT WATER AND CHILLED WATER VALVES.
ON DETECTION OF PRODUCTS OF COMBUSTION, THE SMOKE DETECTOR SHALL STOP THE UNIT SUPPLY AIR FAN AND CLOSE THE OUTSIDE AIR DAMPER.
DURING THE UNOCCUPIED MODE, THE BLOWER COIL UNIT UNIT SHALL BE CYCLED AT A REDUCED HEATING SETPOINT AND A RAISED COOLING SETPOINT.
(BC-2 THROUGH BC-10) BLOWER COIL UNIT CONTROL:
THE DDC CONTROLLER SHALL ENERGIZE THE UNIT THROUGH ITS OPTIMIZATION PROGRAM FOR MORNING WARM-UP. DURING MORNING WARM-UP, THE
OUTSIDE AIR DAMPER SHALL REMAIN FULLY CLOSED, THE RETURN AIR DAMPER SHALL BE FULLY OPEN, AND THE HOT WATER VALVE SHALL BE FULLY OPEN
TO THE COIL.
AT OCCUPANCY TIME, THE DDC CONTROLLER SHALL OPEN THE MINIMUM OUTSIDE AIR DAMPER CLOSING THE RETURN AIR DAMPER A PROPORTIONAL
AMOUNT.
ON A RISE IN SPACE TEMPERATURE TO THE HEATING SETPOINT OF THE DDC CONTROLLER, THE DDC CONTROLLER SHALL MODULATE THE HOT WATER VALVE
CLOSED TO THE COIL. ON A FURTHER RISE IN SPACE THE DDC CONTROLLER SHALL MODULATE THE CHILLED WATER VALVE OPEN TO THE COIL.
WHENEVER THE SETTING OF THE FREEZESTAT IS REACHED, THE FREEZESTAT SHALL DE-ENERGIZE THE SUPPLY AIR FAN, CLOSE THE OUTSIDE AIR DAMPER,
AND OPEN THE HOT WATER AND CHILLED WATER VALVES.
ON DETECTION OF PRODUCTS OF COMBUSTION, THE SMOKE DETECTOR SHALL STOP THE UNIT SUPPLY AIR FAN AND CLOSE THE OUTSIDE AIR DAMPER.
DURING THE UNOCCUPIED MODE, THE BLOWER COIL UNIT UNIT SHALL BE CYCLED AT A REDUCED HEATING SETPOINT AND A RAISED COOLING SETPOINT.
OUTSIDE AIRO.A.
FLSOAD
P-1
RA
SA
TYP
AI1
AO1
CSR
BI1
ANALOG INPUT POINT
FLOW SENSOR
CURRENT SENSING RELAY
DIGITAL INPUT
ANALOG OUTPUT POINT
SUPPLY AIR
TYPICAL
OUTSIDE AIR DAMPER
PUMP DESIGNATION AND MARK
RETURN AIR
HWR
HWS
CONTROLS LEGEND
HOT WATER RETURN (HWR)
HOT WATER SUPPLY (HWS)
STATIC PRESSURE SENSOR
MOTOR STARTER
SMOKE DETECTOR
THERMOSTAT
TEMPERATURE SENSOR
T
TS
SP
SD
DIFFERENTIAL PRESSURE SENSOR
DAMPER MOTOR ACTUATOR
CURRENT TRANSDUCER
FREEZE STAT
LIMIT SWITCHLS
FS
CT
DIGITAL OUTPUT
DPS
BO1
DM
AIR HANDLING UNIT AND MARKAHU
NOT TO SCALE
BLOWER COIL 1 UNIT CONTROL DIAGRAM
NOT TO SCALE
11
M-403
ME
CH
AN
ICA
L C
ON
TR
OL
S A
ND
DE
TA
ILS
WR
K
RM
K
20
CIT
Y O
F H
AM
PT
ON
OLD
H
AM
PT
ON
C
IR
CU
IT
C
OU
RT
RE
PL
AC
E H
VA
C
19-0
15
11/
12/
2019
2406 Princess Anne Road,
Virginia Beach, VA 23456Phone (757) 563-9027
Facsimile(757) 563-9028
Suite 200
COASTALE N G I N E E R I N G
RM
K
CO
MM
ONWEALTH OF VIRGIN
IA
PROFESSIONAL ENGIN
EER
RICHARD M. KLEIN
No. 027864
TH
E C
OP
YR
IG
HT
S T
O A
LL
D
ES
IG
NS
A
ND
D
RA
WIN
GS
A
RE
T
HE
P
RO
PE
RT
Y O
F C
OA
ST
AL
E
NG
IN
EE
RIN
G, P
LL
C. R
EP
RO
DU
CT
IO
N O
R U
SE
F
OR
A
NY
P
UR
PO
SE
O
TH
ER
T
HA
N T
HA
T A
UT
HO
RIZ
ED
B
Y C
OA
ST
AL
E
NG
IN
EE
RIN
G, P
LL
C IS
F
OR
BID
DE
N.
VALVE MANUFACTURER RECOMMENDATIONS
HOSE CONNECTION
DRAIN VALVE WITH
UNION (TYP)
HOT WATER COIL PIPING DETAIL
NOT TO SCALE
COIL
BALL VALVE (TYP)
BALANCING VALVE WITH PRESSURE TAPS
HWS
STRAINER
HWR
VENT
THERMOMETER RANGE 100° -250° F (TYP)
PSIG PRESSURE GAUGE RANGE 0-20 PSI (TYP)
3-WAY CONTROL VALVE
MIN DISTANCE PER BALANCING
VALVE MANUFACTURER RECOMMENDATIONS
GREATER THAN AHU TOTAL STATIC PRESSURE
HOSE CONNECTION
DRAIN VALVE WITH
UNION (TYP)
CHILLED WATER COIL PIPING DETAIL
NOT TO SCALE
TRAP DEPTH TO BE 1"
DRAIN PAN IN AHU
COIL
BALL VALVE (TYP)
BALANCING VALVE WITH PRESSURE TAPS
CHS
STRAINER
CHR
VENT
THERMOMETER RANGE 30° -100° F (TYP)
PSIG PRESSURE GAUGE RANGE 0-20 PSI (TYP)
2-WAY CONTROL VALVE
MIN DISTANCE PER BALANCING
SYSTEM POINT LIST
SYSTEM POINT
DESCRIPTION
ANALOGBINARY SYSTEM FEATURES
NOTES:
CGAF3PTS.XLS
INPUT OUTPUT INPUT OUTPUT ALARMS PROGRAMS
(CH-1) CHILLED
WATER SYSTEM
TE
MP
ER
AT
UR
E
PR
ES
SU
RE
RH
KW
GP
M
CF
M
PP
M
PE
RC
EN
T
PE
RC
EN
T R
LA
SE
TP
OIN
T
AM
PS
DD
C
SE
TP
OIN
T A
DJ.
ST
AT
US
ST
AT
US
O
N/O
FF
FILT
ER
S
TA
TU
S
ST
AT
US
O
PE
N/C
LS
D.
FA
ULT
ALA
RM
OF
F / O
N
OP
EN
/ C
LO
SE
D
LO
CK
OU
T
EN
AB
LE
/ D
IS
AB
LE
HIG
H A
NA
LO
G
LO
W A
NA
LO
G
BIN
AR
Y
PR
OO
F
SE
NS
OR
F
AIL
FLO
W F
AIL
CO
MM
. F
AIL
DIA
GN
OS
TIC
S
TIM
E S
CH
ED
ULIN
G
DE
MA
ND
LIM
IT
IN
G
OP
T. S
TA
RT
/ S
TO
P
RE
SE
T
EV
EN
T P
RO
GR
AM
DD
C
ALA
RM
IN
ST
RU
CT
MA
IN
T. W
K. O
RD
ER
RU
N T
IM
E
EX
P. M
ES
SA
GE
SE
T B
AC
K / S
ET
U
P
NIG
HT
P
UR
GE
TE
NA
NT
B
ILLIN
G
CH
ILLE
R S
EQ
UE
NC
IN
G
TO
TA
LIZ
IN
G
TIM
ED
O
VE
RR
ID
E
CH
ILLE
R S
TA
RT
S
CHILLER X X X X X X X
CHILLED WATER RETURN X X X X
CHILLED WATER SUPPLY X X X X X
CURRENT LIMIT X X
CHILLED WATER SETPOINT X X
UNIT CURRENT X X X X
COND. REFRIG X X X X
EVAP REFRIG. X X X X
CW PUMP X X TYP. OF 2
SYSTEM POINT LIST
SYSTEM POINT
DESCRIPTION
ANALOGBINARY SYSTEM FEATURES
NOTES:
CVAHU35PTS.XLS
INPUT OUTPUT INPUT OUTPUT ALARMS PROGRAMS
(AHU-1)
COURT
ROOM AIR
HANDLING
UNIT
TE
MP
ER
AT
UR
E
PR
ES
SU
RE
RH
KW
GP
M
CF
M
CO
2 P
PM
PE
RC
EN
T
PE
RC
EN
T R
UN
SE
TP
OIN
T
DD
C
SE
TP
OIN
T A
DJ.
ST
AT
US
ST
AT
US
O
N/O
FF
FILT
ER
S
TA
TU
S
FA
ULT
OV
ER
RID
E
CA
NC
EL
OF
F / O
N
OP
EN
/ C
LO
SE
D
LO
CK
OU
T
EN
AB
LE
/ D
IS
AB
LE
HIG
H A
NA
LO
G
LO
W A
NA
LO
G
BIN
AR
Y
PR
OO
F
SE
NS
OR
F
AIL
FLO
W F
AIL
CO
MM
. F
AIL
DIA
GN
OS
TIC
S
TIM
E S
CH
ED
ULIN
G
DE
MA
ND
LIM
IT
IN
G
OP
T. S
TA
RT
/ S
TO
P
RE
SE
T
EV
EN
T P
RO
GR
AM
DD
C
ALA
RM
IN
ST
RU
CT
MA
IN
T. W
K. O
RD
ER
RU
N T
IM
E
EX
P. M
ES
SA
GE
SE
T B
AC
K / S
ET
U
P
NIG
HT
P
UR
GE
TE
NA
NT
B
ILLIN
G
CH
ILLE
R S
EQ
UE
NC
IN
G
TO
TA
LIZ
IN
G
TIM
ED
O
VE
RR
ID
E
SUPPLY AIR X X X X
SUPPLY FAN X X X
MIXED AIR X X X X
REHEAT VALVE X
CW VALVE X
RETURN DAMPER X
OUTSIDE AIR
DAMPER X
LOW LIMIT X X X
SPACE X X X X X X X X
RETURN AIR X X X
OA ELECTRIC HEAT X UH-1
SYSTEM POINT LIST
SYSTEM POINT
DESCRIPTION
ANALOGBINARY SYSTEM FEATURES
FCU6PTS.XLS
INPUT OUTPUT INPUT OUTPUT ALARMS PROGRAMS
(BC-1
THROUGH
BC-10)
BLOWER COIL
UNITS
TE
MP
ER
AT
UR
E
PR
ES
SU
RE
RH
KW
GP
M
CF
M
PP
M
PE
RC
EN
T
PE
RC
EN
T R
UN
SE
TP
OIN
T
DD
C
SE
TP
OIN
T A
DJ.
ST
AT
US
ST
AT
US
O
N/O
FF
FILT
ER
S
TA
TU
S
FA
ULT
OV
ER
RID
E
CA
NC
EL
OF
F / O
N
OP
EN
/ C
LO
SE
D
LO
CK
OU
T
EN
AB
LE
/ D
IS
AB
LE
HIG
H A
NA
LO
G
LO
W A
NA
LO
G
BIN
AR
Y
PR
OO
F
SE
NS
OR
F
AIL
FLO
W F
AIL
CO
MM
. F
AIL
DIA
GN
OS
TIC
S
TIM
E S
CH
ED
ULIN
G
DE
MA
ND
LIM
IT
IN
G
OP
T. S
TA
RT
/
ST
OP
RE
SE
T
EV
EN
T P
RO
GR
AM
DD
C
ALA
RM
IN
ST
RU
CT
MA
IN
T. W
K.
OR
DE
R
RU
N T
IM
E
EX
P. M
ES
SA
GE
SE
T B
AC
K / S
ET
UP
NIG
HT
P
UR
GE
TE
NA
NT
B
ILLIN
G
CH
ILLE
R
SE
QU
EN
CIN
G
TO
TA
LIZ
IN
G
TIM
ED
O
VE
RR
ID
E
N
O
T
E
S
:
SUPPLY AIR X X X X
SUPPLY FAN X X X
REHEAT VALVE X
CW VALVE X
OA DAMPER X
LOW LIMIT X X
SPACE X X X X X X X X
GENERAL NOTES:
Mar-02
12
M-404
DIA
GR
AM
WR
K
RM
K
20
CIT
Y O
F H
AM
PT
ON
OLD
H
AM
PT
ON
C
IR
CU
IT
C
OU
RT
RE
PL
AC
E H
VA
C
19-0
15
11/
12/
2019
2406 Princess Anne Road,
Virginia Beach, VA 23456Phone (757) 563-9027
Facsimile(757) 563-9028
Suite 200
COASTALE N G I N E E R I N G
RM
K
CO
MM
ONWEALTH OF VIRGIN
IA
PROFESSIONAL ENGIN
EER
RICHARD M. KLEIN
No. 027864
TH
E C
OP
YR
IG
HT
S T
O A
LL
D
ES
IG
NS
A
ND
D
RA
WIN
GS
A
RE
T
HE
P
RO
PE
RT
Y O
F C
OA
ST
AL
E
NG
IN
EE
RIN
G, P
LL
C. R
EP
RO
DU
CT
IO
N O
R U
SE
F
OR
A
NY
P
UR
PO
SE
O
TH
ER
T
HA
N T
HA
T A
UT
HO
RIZ
ED
B
Y C
OA
ST
AL
E
NG
IN
EE
RIN
G, P
LL
C IS
F
OR
BID
DE
N.
2"
3/4"
CHR
SEE SCHEDULE
AIR SEPARATOR
EXPANSION
TANK
FINISHED FLOOR
CHR
SET AT 26 PSIG
SET AT 45 PSIG
FLOOR DRAIN
3/4", ROUTE TO
3/4" DOMESTIC
WATER MAKE UP
3/4"
CHEMICAL SHOT
5 GALLON
FEED TANK
CHR
PROVIDE DRAIN
WITH THREATED
HOSE BIBB
PAD (TYP)
EQUIPMENT
CONCRETE
CHILLER
AIR COOLED
THERMOMETER (TYP)
PRESSURE GAUGE WITH
VALVE COCK
CONNECTION (TYP)
FLEXIBLE PIPING
VALVE WITH PRESSURE TAPS
FLOW CONTROL BALANCING
FLOW SWITCH
VALVE
2 - POSITION AUTOMATIC CHILLER
NOTE: PROVIDE STRAIGHT LENGTHS OF
UNOBSTRUCTED PIPE UP AND DOWNSTREAM OF
BALANCE VALVES PER MANUFACTURER'S
RECOMMENDATIONS.
GROUT
FLOOR FLANGE
SUCTION
DIFFUSER
(TYPICAL)
ELBOW SUPPORT
(TYPICAL)
BLOW DOWN
STRAINER WITH
GLOBE OR
NEEDLE VALVE
3/4" DRAIN VALVE W/ HOSE CONNECTION (TYPICAL)
MANUFACTURER'S INSTALLATION INSTRUCTIONS (TYPICAL)
SUCTION OR USE SUCTION DIFFUSER (TYPICAL)
MIN. STRAIGHT PIPE 5 X DIA.
1/4"
ANCHOR PUMP TO 4" THICK
THAN PUMP IN BOTH DIMENSIONS (TYPICAL)
CONCRETE BASE. BASE IS 3" LARGER
GROUT IN PUMP BASE WHEN REQUIRED BY
PRESSURE GAUGE 60 PSIG RANGE (TYPICAL)
MOTOR (TYPICAL)
COUPLING GUARD (TYPICAL)
PUMP (TYPICAL)
*
*
BUTTERFLY VALVE (TYPICAL)
VIBRATION ISOLATOR (TYPICAL)
FLOW CONTROL BALANCING VALVE SIZED
CHECK VALVE (TYPICAL)
PER MANUFACTURER'S RECOMMENDATION
F
CHR
CHS
(TYPICAL)
(TYPICAL)
(TYPICAL)
(TYPICAL)
CHS
CH
R
CH
R
(TYPICAL)
CHILLED WATER PIPING DIAGRAM
NOT TO SCALE
BUTTERFLY VALVE (TYP)
FULL PORT BALL
VALVE (TYP)
PRESSURE
GAUGE 0-60 PSI
RANGE
(TYPICAL)
2" 2"
AUTOMATIC AIR VENT
HOT WATER PIPING DIAGRAM
*
*
HW
S
HW
S
HWS
2"
20
CIT
Y O
F H
AM
PT
ON
OLD
H
AM
PT
ON
C
IR
CU
IT
C
OU
RT
RE
PL
AC
E H
VA
C
19-0
15
11/
12/
2019
2406 Princess Anne Road,
Virginia Beach, VA 23456Phone (757) 563-9027
Facsimile(757) 563-9028
Suite 200
COASTALE N G I N E E R I N G
RM
K
CO
MM
ONWEALTH OF VIRGIN
IA
PROFESSIONAL ENGIN
EER
RICHARD M. KLEIN
No. 027864
TH
E C
OP
YR
IG
HT
S T
O A
LL
D
ES
IG
NS
A
ND
D
RA
WIN
GS
A
RE
T
HE
P
RO
PE
RT
Y O
F C
OA
ST
AL
E
NG
IN
EE
RIN
G, P
LL
C. R
EP
RO
DU
CT
IO
N O
R U
SE
F
OR
A
NY
P
UR
PO
SE
O
TH
ER
T
HA
N T
HA
T A
UT
HO
RIZ
ED
B
Y C
OA
ST
AL
E
NG
IN
EE
RIN
G, P
LL
C IS
F
OR
BID
DE
N.
13
M-601
ME
CH
AN
ICA
L S
PE
CIF
ICA
TIO
NS
WR
K
RM
K
MECHANICAL SPECIFICATIONS:
1. GENERAL
1.1. GENERAL REQUIREMENTS:
1.1.1. REQUIREMENTS UNDER DIVISION ONE AND THE GENERAL AND SUPPLEMENTARY CONDITIONS OF THESE
SPECIFICATIONS SHALL BE A PART OF THIS SECTION. EACH CONTRACTOR SHALL BECOME THOROUGHLY
ACQUAINTED WITH ITS CONTENTS AS TO REQUIREMENTS THAT AFFECT THIS DIVISION OR SECTION. THE WORK
REQUIRED UNDER THIS SECTION INCLUDES MATERIAL, EQUIPMENT, APPLIANCES, TRANSPORTATION, SERVICES,
AND LABOR REQUIRED TO COMPLETE THE ENTIRE SYSTEM AS REQUIRED BY THE DRAWINGS AND SPECIFICATIONS.
1.1.2. THE SPECIFICATIONS AND DRAWINGS FOR THE PROJECT ARE COMPLEMENTARY, AND PORTIONS OF THE WORK
DESCRIBED IN ONE, SHALL BE PROVIDED AS IF DESCRIBED IN BOTH. IN THE EVENT OF DISCREPANCIES, NOTIFY
THE ENGINEER AND/OR OWNER AND REQUEST CLARIFICATION PRIOR TO PROCEEDING WITH THE WORK INVOLVED.
1.2. INSPECTION OF THE SITE:
1.2.1. PRIOR TO SUBMITTING BID, THE CONTRACTOR SHALL VISIT THE SITE OF THE PROPOSED WORK AND BECOME
FULLY INFORMED AS TO THE CONDITIONS UNDER WHICH THE WORK IS TO BE DONE. FAILURE TO DO SO WILL NOT
BE CONSIDERED SUFFICIENT JUSTIFICATION TO REQUEST OR OBTAIN EXTRA COMPENSATION OVER AND ABOVE
THE CONTRACT PRICE.
1.3. MATERIAL AND WORKMANSHIP:
1.3.1. PROVIDE NEW MATERIAL, EQUIPMENT, AND APPARATUS UNDER THIS CONTRACT UNLESS OTHERWISE STATED
HEREIN, OF BEST QUALITY NORMALLY USED FOR THE PURPOSE IN GOOD COMMERCIAL PRACTICE, AND FREE FROM
ANY DEFECTS. MODEL NUMBERS LISTED IN THE SPECIFICATIONS OR SHOWN ON THE DRAWINGS ARE NOT
NECESSARILY INTENDED TO DESIGNATE THE REQUIRED TRIM, WRITTEN DESCRIPTIONS OF THE TRIM GOVERN
MODEL NUMBERS.
1.3.2. WORK PERFORMED UNDER THIS CONTRACT SHALL PROVIDE A NEAT AND "WORKMANLIKE" APPEARANCE WHEN
COMPLETED, TO THE SATISFACTION OF THE ARCHITECT AND ENGINEER. WORKMANSHIP SHALL BE THE FINEST
POSSIBLE BY EXPERIENCED MECHANICS. INSTALLATIONS SHALL COMPLY WITH APPLICABLE CODES AND LAWS.
1.3.3. THE COMPLETE INSTALLATION SHALL FUNCTION AS DESIGNED AND INTENDED WITH RESPECT TO EFFICIENCY,
CAPACITY, NOISE LEVEL, ETC. ABNORMAL NOISE CAUSED BY VIBRATING EQUIPMENT, PIPING, DUCTS, AIR DEVICES,
AND SQUEAKS IN ROTATING COMPONENTS WILL NOT BE ACCEPTABLE. IN GENERAL, MATERIALS AND EQUIPMENT
SHALL BE OF COMMERCIAL SPECIFICATION GRADE IN QUALITY. LIGHT DUTY AND RESIDENTIAL TYPE EQUIPMENT
WILL NOT BE ACCEPTABLE.
1.3.4. REMOVE FROM THE PREMISES WASTE MATERIAL PRESENT AS A RESULT OF WORK, INCLUDING CARTONS, CRATING,
PAPER, STICKERS, AND/OR EXCAVATION MATERIAL NOT USED IN BACKFILLING, ETC. CLEAN EQUIPMENT INSTALLED
UNDER THIS CONTRACT TO A NEW AND CLEAN CONDITION AT THE TERMINATION OF WORK.
1.3.5. REPAIR OR REPLACE PUBLIC AND PRIVATE PROPERTY DAMAGED AS A RESULT OF WORK PERFORMED UNDER THIS
CONTRACT TO THE SATISFACTION OF OWNER, ENGINEER AND AUTHORITIES HAVING JURISDICTION.
1.3.6. MISCELLANEOUS ITEMS NOT SHOWN ON THE PLANS BUT NECESSARY FOR A COMPLETE OPERABLE SYSTEM, SHALL
BE SUPPLIED AND INSTALLED.
1.3.7. CONTRACTOR SHALL FURNISH AND INSTALL ALL EQUIPMENT AND MATERIALS FOR A COMPLETE INSTALLATION IN
ALL RESPECTS READY OF INTENDED USE AND THE STRICT ACCORDANCE WITH STATE AND LOCAL CODES AND
MANUFACTURER'S RECOMMENDATIONS. PAY NECESSARY FEES AND OBTAIN PERMITS. INITIATE, MAINTAIN AND
SUPERVISE ALL SAFETY PRECAUTIONS AND PROCEDURES.
1.3.8. EQUIPMENT AND MATERIALS SHALL BE OF THE TYPE, SIZE AND MANUFACTURERS INDICATED ON THE DRAWINGS
OR AN APPROVED EQUIVALENT.
1.3.9. THE CONTRACTOR SHALL SUPPLY AND INSTALL THE MATERIALS AND EQUIPMENT COVERED BY THE PLANS AND
SPECIFICATIONS TO THE OWNER COMPLETE AND IN FIRST CLASS CONDITION IN EVERY RESPECT. HE SHALL
GUARANTEE THAT THE MATERIAL, EQUIPMENT, AND WORKMANSHIP SUPPLIED AND INSTALLED BY HIM SHALL BE
ENTIRELY FREE FROM DEFECTS AND THAT HE WILL REPAIR OR REPLACE AT HIS OWN EXPENSE, ANY MATERIALS,
EQUIPMENT, AND WORKMANSHIP IN WHICH DEFECTS ARE FOUND.
1.4. COORDINATION:
1.4.1. COORDINATE WORK WITH THAT OF OTHER TRADES SO THAT THE VARIOUS COMPONENTS OF THE SYSTEMS WILL
BE INSTALLED AT THE PROPER TIME, WILL FIT THE AVAILABLE SPACE, AND WILL ALLOW PROPER SERVICE ACCESS
TO THOSE ITEMS REQUIRING MAINTENANCE. COMPONENTS WHICH ARE INSTALLED WITHOUT REGARD TO THE
ABOVE SHALL BE RELOCATED AT NO ADDITIONAL COST TO THE OWNER.
1.4.2. UNLESS OTHERWISE INDICATED, THE CONTRACTOR WILL PROVIDE CHASES AND OPENINGS IN BUILDING
CONSTRUCTION REQUIRED FOR THE INSTALLATION OF THE SYSTEMS SPECIFIED HEREIN. MECHANICAL
CONTRACTOR SHALL FURNISH THE GENERAL CONTRACTOR WITH THE INFORMATION WHERE CHASES AND
OPENINGS ARE REQUIRED. COORDINATE HE WORK OF THE OTHER TRADES ENGAGED IN THE CONSTRUCTION OF
THE PROJECT, AND EXECUTE WORK IN A MANNER AS TO NOT INTERFERE WITH OR DELAY THE WORK OF OTHER
TRADES.
1.4.3. FIGURED DIMENSIONS SHALL BE TAKEN IN PREFERENCE TO SCALE DIMENSIONS. THE CONTRACTOR SHALL TAKE
HIS OWN MEASUREMENTS AT THE BUILDING, AS VARIATIONS MAY OCCUR. THE CONTRACTOR WILL BE HELD
RESPONSIBLE FOR ERRORS THAT COULD HAVE BEEN AVOIDED BY PROPER CHECKING AND INSPECTION.
1.4.4. PROVIDE MATERIALS WITH TRIM THAT WILL PROPERLY FIT THE TYPES OF CEILING, WALL, OR FLOOR FINISHES
ACTUALLY INSTALLED. MODEL NUMBERS LISTED IN THE SPECIFICATIONS OR SHOWN ON THE DRAWINGS ARE NOT
INTENDED TO DESIGNATE THE REQUIRED TRIM.
1.4.5. MECHANICAL CONTRACTOR SHALL SUBMIT SHOP DRAWINGS FOR DUCTWORK LAYOUT TO THE CONSTRUCTION
PROJECT MANAGER FOR OWNER APPROVAL PRIOR TO INSTALLATION.
1.4.6. CONTRACTOR TO SUBMIT 6 SETS (OWNER WILL RETURN 3 SETS NOTED WITH ACTION TAKEN)SPECIFICATIONS AND
DETAIL FOR EQUIPMENT AND FABRICATED MATERIALS FOR OWNER'S APPROVAL PRIOR TO ISSUING PURCHASE
ORDER. OWNER'S APPROVAL DOES NOT RELIEVE CONTRACTOR OF ANY RESPONSIBILITY FOR PERFORMANCE AND
OPERATION.
1.5. ORDINANCES AND CODES:
1.5.1. WORK PERFORMED UNDER THIS CONTRACT SHALL, AT A MINIMUM, BE IN CONFORMANCE WITH APPLICABLE
NATIONAL, STATE AND LOCAL CODES HAVING JURISDICTION. EQUIPMENT FURNISHED AND ASSOCIATED
INSTALLATION WORK PERFORMED UNDER THIS CONTRACT SHALL BE IN STRICT COMPLIANCE WITH CURRENT
APPLICABLE CODES ADOPTED BY THE LOCAL AUTHORITY HAVING JURISDICTION INCLUDING ANY AMENDMENTS
AND STANDARDS AS SET FORTH BY THE NATIONAL FIRE PROTECTION ASSOCIATION (NFPA), UNDERWRITERS
LABORATORIES (UL), OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION (OSHA), AMERICAN SOCIETY OF
MECHANICAL ENGINEERS (ASME), AMERICAN SOCIETY OF HEATING, REFRIGERATION, AND AIR CONDITIONING
ENGINEERS (ASHRAE), AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI), AMERICAN SOCIETY OF TESTING
MATERIALS (ASTM), AND OTHER NATIONAL STANDARDS AND CODES WHERE APPLICABLE. WHERE THE CONTRACT
DOCUMENTS EXCEED THE REQUIREMENTS OF THEIR REFERENCED CODES, STANDARDS, ETC., THE CONTRACT
DOCUMENTS SHALL TAKE PRECEDENCE.
1.5.2. PROCURE AND PAY FOR PERMITS AND LICENSES REQUIRED FOR THE ACCOMPLISHMENT OF THE WORK HEREIN
DESCRIBED. WHERE REQUIRED, OBTAIN, PAY FOR AND FURNISH CERTIFICATES OF INSPECTION TO THE OWNER.
THE CONTRACTOR WILL BE HELD RESPONSIBLE FOR VIOLATIONS OF THE LAW.
1.6. PROTECTION OF EQUIPMENT AND MATERIALS:
1.6.1. STORE AND PROTECT FROM DAMAGE EQUIPMENT AND MATERIALS DELIVERED TO JOB SITE. COVER WITH
WATERPROOF, TEAR-RESISTANT, HEAVY TARP OR POLYETHYLENE PLASTIC AS REQUIRED TO PROTECT FROM
PLASTER, DIRT, PAINT, WATER, OR PHYSICAL DAMAGE. EQUIPMENT AND MATERIAL THAT HAS BEEN DAMAGED BY
CONSTRUCTION ACTIVITIES WILL BE REJECTED, AND MECHANICAL CONTRACTOR IS OBLIGED TO FURNISH NEW
EQUIPMENT AND MATERIAL OF A LIKE KIND AS APPROVED BY OWNER.
1.6.2. KEEP PREMISES ROOM CLEAN FROM FOREIGN MATERIAL CREATED DURING WORK PERFORMED UNDER THIS
CONTRACT. PIPING, EQUIPMENT, ETC., SHALL HAVE A NEAT AND CLEAN APPEARANCE AT THE TERMINATION OF
THE WORK.
1.6.3. PLUG OR CAP OPEN ENDS OF DUCTWORK AND PIPING SYSTEMS WHILE STORED OR INSTALLED DURING
CONSTRUCTION WHEN NOT IN USE TO PREVENT THE ENTRANCE OF DEBRIS INTO THE SYSTEMS.
1.7. OPERATION AND MAINTENANCE INSTRUCTIONS:
1.7.1. COMPILE A COMPLETE BROCHURE OF FIXTURES, MATERIALS, AND EQUIPMENT FURNISHED AND INSTALLED ON
THIS PROJECT. INCLUDE OPERATIONAL AND MAINTENANCE INSTRUCTIONS, MANUFACTURER'S CATALOG SHEETS,
WIRING DIAGRAMS, PARTS LISTS, APPROVED SHOP DRAWINGS, AND DESCRIPTIVE LITERATURE FURNISHED BY THE
MANUFACTURER. INCLUDE AN INSIDE COVER SHEET THAT LISTS THE PROJECT NAME, DATE, OWNER, ARCHITECT,
ENGINEER, GENERAL CONTRACTOR, SUBCONTRACTOR, AND AN INDEX OF CONTENTS.
1.7.2. SUBMIT COPIES OF LITERATURE BOUND IN APPROVED BINDERS TO THE ARCHITECT AND OWNER AT THE
TERMINATION OF THE WORK. PAPER CLIPS, STAPLES, RUBBER BANDS, AND MAILING ENVELOPES ARE NOT
CONSIDERED APPROVED BINDERS. FINAL APPROVAL OF MECHANICAL WILL BE WITHHELD UNTIL THIS EQUIPMENT
BROCHURE IS DEEMED COMPLETE BY THE ARCHITECT, ENGINEER, AND OWNER.
1.8. WARRANTIES:
1.8.1. WARRANT EACH SYSTEM AND EACH ELEMENT THEREOF AGAINST ALL DEFECTS DUE TO FAULTY WORKMANSHIP,
DESIGN OR MATERIAL FOR A PERIOD OF 12 MONTHS OF DATE OF SUBSTANTIAL COMPLETION (COMPRESSORS IN
AIR CONDITIONING AND REFRIGERATION EQUIPMENT WITH A 60 MONTH WARRANTY), UNLESS SPECIFIC ITEMS ARE
NOTED TO CARRY A LONGER WARRANTY IN THE CONSTRUCTION DOCUMENTS OR MANUFACTURER'S STANDARD
WARRANTY EXCEEDS 12 MONTHS. REMEDY ALL DEFECTS, OCCURRING WITHIN THE WARRANTY PERIOD(S), AS
STATED IN THE GENERAL CONDITIONS AND DIVISION 1.
1.8.2. WARRANTIES SHALL INCLUDE LABOR AND MATERIAL. MAKE REPAIRS OR REPLACEMENTS WITHOUT ANY
ADDITIONAL COSTS TO THE OWNER.
1.8.3. PERFORM THE REMEDIAL WORK PROMPTLY, UPON WRITTEN NOTICE FROM THE ENGINEER OR OWNER.
1.8.4. AT THE TIME OF SUBSTANTIAL COMPLETION, DELIVER TO THE OWNER ALL WARRANTIES, IN WRITING AND
PROPERLY EXECUTED, INCLUDING TERM LIMITS FOR WARRANTIES EXTENDING BEYOND THE ONE YEAR PERIOD,
EACH WARRANTY INSTRUMENT BEING ADDRESSED TO THE OWNER AND STATING THE COMMENCEMENT DATE AND
TERM.
1.9. CUTTING AND PATCHING:
1.9.1. PERFORM CUTTING OF WALLS, FLOORS, CEILINGS, ETC., AS REQUIRED TO INSTALL WORK UNDER THIS SECTION.
OBTAIN PERMISSION FROM THE ARCHITECT PRIOR TO CUTTING. DO NOT CUT OR DISTURB STRUCTURAL MEMBERS
WITHOUT PRIOR APPROVAL FROM THE ARCHITECT. CUT HOLES AS SMALL AS POSSIBLE. PATCH WALLS, FLOORS,
ETC., AS REQUIRED BY WORK UNDER THIS SECTION. PATCHING SHALL MATCH THE ORIGINAL MATERIAL AND
CONSTRUCTION. REPAIR AND REFINISH AREAS DISTURBED BY WORK TO THE CONDITION OF ADJOINING SURFACES
IN A MANNER SATISFACTORY TO THE ARCHITECT.
1.10. ROUGH-IN:
1.10.1. COORDINATE WITHOUT DELAY ROUGH-IN WITH GENERAL CONSTRUCTION. CONCEAL PIPING AND CONDUIT
ROUGH-IN EXCEPT IN UNFINISHED AREAS AND WHERE OTHERWISE SHOWN.
1.10.2. RUN ALL PIPING AND DUCTWORK NEAT AND PARALLEL TO THE BUILDING STRUCTURE UNLESS OTHERWISE NOTED.
1.11. STRUCTURAL STEEL:
1.11.1. STRUCTURAL STEEL USED FOR PIPE SUPPORTS, EQUIPMENT SUPPORTS, ETC., SHALL BE NEW, CLEAN, AND
CONFORM TO ASTM DESIGNATION A-36.
1.11.2. SUPPORT EQUIPMENT AND PIPING FROM THE BUILDING STRUCTURE. DO NOT SUPPORT EQUIPMENT FROM
CEILINGS, OTHER PLUMBING, MECHANICAL,FIRE PROTECTION, OR ELECTRICAL COMPONENTS, AND OTHER
NON-STRUCTURAL ELEMENTS.
1.12. ACCESS DOORS:
1.12.1. PROVIDE ACCESS DOORS IN CEILINGS AND WALL WHERE INDICATED OR REQUIRED FOR ACCESS TO CONCEALED
VALVES, DAMPERS, AND EQUIPMENT INSTALLED UNDER THIS SECTION. PROVIDE CONCEALED HINGES,
SCREWDRIVER-TYPE LOCK, ANCHOR STRAPS; MANUFACTURED BY MILCOR, ZURN, TITUS OR EQUAL. OBTAIN
ARCHITECT'S APPROVAL OF TYPE, SIZE, LOCATION, AND COLOR BEFORE ORDERING.
1.13. PENETRATIONS:
1.13.1. SEAL FLOOR, EXTERIOR WALL AND ROOF PENETRATIONS WATER AND WEATHER TIGHT WITH APPROPRIATE
NON-SHRINK, NON-HARDENING COMMERCIAL CONSTRUCTION SEALANT. SEAL ROOF PENETRATIONS WITH 4
POUND PER SQUARE FOOT LEAD FLASHING. PROVIDE A SLEEVE, AND SEAL NON-FIRE-RATED FLOOR AND WALL
PENETRATIONS WITH FIBERGLASS PACKING AND SILICONE CAULK (FOR ACOUSTICAL INSULATION).
1.13.2. COORDINATE FIRE RATING REQUIREMENTS AND LOCATIONS WITH THE ARCHITECTURAL DRAWINGS OR EXISTING
BUILDING CONDITIONS AND RATINGS. SEAL PENETRATIONS OF FIRE-RATED ASSEMBLIES WITH 3M # CP-25 FIRE
BARRIER CAULK (PROVIDE THICKNESS AND METHOD AS REQUIRED AND RECOMMENDED BY MANUFACTURER) TO
MAINTAIN THE FIRE RESISTANCE RATING OF FIRE-RATED ASSEMBLIES.
1.13.3. SEAL EXTERIOR WALL PENETRATIONS BELOW GRADE WITH CASE IRON WALL PIPES AND MODULAR MECHANICAL
SLEEVE SEALS, MANUFACTURED BY THUNDERLINE/LINK SEAL, CALPICO, INC, METRAFLEX OR APPROVED EQUAL.
1.13.4. PROVIDE SLEEVE FOR HORIZONTAL PIPE PASSING THROUGH OR UNDER FOUNDATION. SLEEVES SHALL BE CAST
IRON SOIL PIPE TWO NOMINAL PIPE SIZES LARGER THAN THE PIPE SERVED. SEAL WATER-TIGHT WITH SILICON
CAULK.
2. HEATING, VENTILATION, AND AIR CONDITIONING
2.1. DUCTWORK:
2.1.1. PROVIDE ANY DUCTWORK NECESSARY FOR A COMPLETE INSTALLATION OF HVAC SYSTEMS (INCLUDING EXHAUST
SYSTEMS AND MAKE-UP AIR SYSTEMS). ALL DUCTWORK IDENTIFICATION AND INSTALLATION TO ADHERE TO
SMACNA STANDARDS AND ALL GOVERNING CODES.
2.1.2. DUCTWORK SHALL BE GALVANIZED STEEL, CONSTRUCTED AND INSTALLED AS RECOMMENDED BY SMACNA AND
INSULATED WITH 2" THICK FIBERGLASS DUCT WRAP WITH FOIL VAPOR BARRIER JACKET. SHEET METAL GAUGES
SHALL BE IN ACCORDANCE WITH SMACNA. FLEXIBLE DUCTWORK SHALL BE FACTORY INSULATED WITH VAPOR
BARRIER JACKET.
2.1.3. DUCTWORK CONNECTIONS TO AIR DEVICES MUST BE MADE WITH HARD PIPE ELBOWS, COVERED WITH SLEEVE
INSULATION. FLEX DUCT MUST NOT BE UTILIZED FOR A 90 DEGREE CONNECTION TO AN AIR DEVICE.
2.1.4. BALANCING DAMPERS WITH DOUBLE LOCKING QUADS SHALL BE PROVIDED IN ALL ROUND DUCT TAKE-OFFS FROM
THE MAIN TRUNKS, UNLESS OTHERWISE NOTED ON PLANS.
2.1.5. A MAXIMUM OF 7'-0" OF FLEX DUCT MAY BE USED FOR FINAL CONNECTION OF SUPPLY AIR DIFFUSERS AND GRILLES.
2.1.6. FLEX DUCT MUST BE PROPERLY SUPPORTED WITH ONE INCH STRAPS AND CUT TO PROPER LENGTH TO PREVENT
SAGGING.
2.1.7. FLEX DUCT SHALL BE OWENS-CORNING FOIL-BACK HIGH QUALITY U/L APPROVED. PLASTIC WRAPPED FLEX DUCT IS
NOT ACCEPTABLE. FLEXIBLE DUCTWORK MAYBE USED FOR RUN-OUTS TO AIR DISTRIBUTION DEVICES AS
INDICATED BUT SHALL NOT BE USED IN NON-ACCESSIBLE, CONCEALED SPACES.
2.1.8. RIGID DUCT SHALL BE USED FOR RETURN EXHAUST AND MAKE-UP AIR.
2.2. INSULATION:
2.2.1. SUPPLY AND RETURN DUCTWORK INSIDE THE BUILDING SHALL BE INSULATED WITH 2" THICK EXTERIOR
FIBERGLASS DUCT WRAP WITH A VAPOR BARRIER, SEAL ALL JOINTS AND LAPS TO MAINTAIN VAPOR BARRIER.
2.2.2. SUPPLY AND RETURN DUCTWORK OUTSIDE THE BUILDING SHALL BE INSULATED WITH 2" LINER WITH A MINIMUM
R-VALUE OF 8.0 AND SEAL SEAMS WEATHER TIGHT.
2.2.3. DEDICATED OUTSIDE AIR SUPPLY AND RELIEF DUCTWORK INSIDE THE BUILDING SHALL BE INSULATED WITH 2"
THICK DUCT WRAP WITH A MINIMUM R-VALUE OF 6.0.
2.3. FINAL TESTING AND ADJUSTMENTS:
2.3.1. AIR BALANCE SHALL BE PERFORMED AT THE COMPLETION OF THE PROJECT. BALANCE EACH SUPPLY, RETURN,
OUTSIDE AIR DEVICE WITHIN 5% OF REQUIREMENTS AND FURNISH AN AABC OR NEBB CERTIFIED REPORT TO THE
OWNER, MECHANICAL INSPECTOR AND ENGINEER. THE ENTIRE HVAC SYSTEM MUST BE FULLY OPERABLE,
BALANCED, AND APPROVED BY OWNER'S REPRESENTATIVE ON OR BEFORE THE DAY OF SUBSTANTIAL
COMPLETION.
2.3.2. ADJUST THERMOSTATS AND CONTROL DEVICES TO OPERATE AS INTENDED. ADJUST PUMPS, FANS, ETC. FOR
PROPER AND EFFICIENT OPERATION. CERTIFY TO ARCHITECT THAT ADJUSTMENTS HAVE BEEN MADE AND THAT
SYSTEMS IS OPERATING SATISFACTORILY. CALIBRATE, SET AND ADJUST AUTOMATIC TEMPERATURE CONTROLS.
CHECK PROPER SEQUENCES OF INTERLOCK SYSTEMS, AND OPERATION OF SAFETY CONTROLS.
2.3.3. VERIFY ECONOMIZER OPERATION PER MANUFACTURER PROCEDURE.
2.4. DIFFUSERS AND GRILLES:
2.4.1. ALL SUPPLY AND RETURN AIR DEVICES SHALL BE INSTALLED BY THE CONTRACTOR.
2.4.2. ALL AIR TERMINAL DEVICES SHALL BE INSTALLED AS SHOWN ON THE PLANS IN ORDER TO HANDLE THE DESIGNED
AIR FLOW CAPACITIES WITH A MINIMUM AMOUNT OF NOISE AND STATIC PRESSURE, PROVIDE BALANCING DAMPERS
FOR ALL AIR FLOW DEVICES TO ALLOW ADJUSTMENT WITH A LOCKING SET POINT, ROOM OPERATED SLIDE
ACTUATED DAMPERS ON SUPPLY GRILLES DO NOT MEET THE REQUIREMENTS OF A BALANCING DAMPER.
2.5. CONDENSATE DRAINS:
2.5.1. THE MECHANICAL CONTRACTOR SHALL PROVIDE AND INSTALL AS A MINIMUM A 4" DEEP P-TRAP ON CONDENSATE DRAIN
OUTLETS WHERE THE CONDENSATE WATER WILL EXIT THE P-TRAP AT A POINT 1" LOWER THAN THE DRAIN CONNECTION AT
THE UNIT. THE MECHANICAL CONTRACTOR SHALL PROVIDE AND INSTALL CONDENSATE LINES AS REQUIRED TO MEET LOCAL
CODES AND AS SHOWN ON THE MECHANICAL PLANS. THESE LINES SHALL BE SLOPED AWAY FROM THE UNITS, SUPPORTED AS
REQUIRED TO ASSURE PROPER FLOW, AND AT THE MECHANICAL CONTRACTOR'S OPTION, CONDENSATE DRAIN LINES MAY BE
SCHEDULE 40 PVC OR COPPER. ALL JOINTS SHALL BE SECURELY GLUED OR SOLDERED AS REQUIRED. INSULATE 3/4" THICK
PIPE INSULATION WHERE REQUIRED.
2.6. CONTROLS:
2.6.1. MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR SUPPLYING AND INSTALLING A COMPLETE OPERATIVE SYSTEM
OF CONTROLS, INCLUDING THERMOSTATS, CONTROL DEVICES, TIME CLOCKS, DDC COMPONENTS, AND CONTROL WIRING..
2.6.2. SMOKE DETECTORS AND SAMPLING TUBES PROVIDED AND INSTALLED TO THE UNITS AND IN THE DUCTWORK BY THE
MECHANICAL CONTRACTOR. THE SMOKE DETECTORS SHALL DISABLE HVAC UNIT OPERATION UPON ACTIVATION.
2.7. ELECTRICAL:
2.7.1. LOW VOLTAGE WIRING - ALL PROVISIONS FOR LOW VOLTAGE WIRING SHALL BE PERFORMED BY THE MECHANICAL
CONTRACTOR UNLESS CODES OR LABOR SITUATIONS DO NOT PERMIT. IF THE MECHANICAL CONTRACTOR CAN NOT PERFORM
LOW VOLTAGE WIRING, THE MECHANICAL CONTRACTOR SHALL INFORM THE GENERAL CONTRACTOR, AS A PART OF THE HVAC
BID DOCUMENT, TO HAVE THE ELECTRICAL SUBCONTRACTOR INCLUDE HIS WORK IN THEIR BID.
2.7.2. POWER WIRING - ALL ELECTRICAL POWER WIRING TO INCLUDE FINAL CONNECTIONS SHALL BE PROVIDED BY THE
GENERAL CONTRACTOR'S ELECTRICAL SUBCONTRACTOR.
2.7.3. MOTOR STARTERS SHALL BE PROVIDED BY THE MECHANICAL CONTRACTOR AND TURNED OVER TO THE ELECTRICAL
CONTRACTOR FOR INSTALLATION.
2.8. GAS PIPING:
2.8.1. SCHEDULE 40 BLACK CARBON STEEL WITH MALLEABLE IRON THREADED FITTINGS. PROVIDES SHUT-OFF VALVE, DIRT LEG,
AND UNION AT EACH ROOFTOP UNIT. PAINT ALL GAS PIPING EXPOSED TO WEATHER WITH ONE COAT OF PRIMER, AND TWO
COATS OF RUST-PROOF PAINT. COLOR SHALL MATCH BUILDING COLORS. COORDINATE WITH OWNER'S CONSTRUCTION
MANAGER.
2.8.2. SUPPORT GAS PIPING WITH TREATED WOOD BLOCKING 6X6X12, 8'-0" OC MAX WITH GALVANIZED PIPE STRAP 1 1/4" ZINC
COATED LAG SCREWS, AND RUBBER WALKPAD ADHERED TO THE ROOF.
2.9. REFRIGERATION LINES:
2.9.1. REFRIGERATION LINE SETS FOR HVAC UNITS ARE TO BE PROVIDED WITH THE EQUIPMENT AND SIZED BY THE
MANUFACTURER BASED ON ACTUAL JOB SITE CONDITIONS INCLUDING LENGTH AND ELEVATION CHANGES, AND INSTALLED BY
THE CONTRACTOR.
2.9.2. INSULATE ALL REFRIGERANT LIQUID LINES AND PROVIDE AN ALL WEATHER COATING ON EXTERIOR INSULATION.
2.5. HYDRONIC PIPING:
2.5.1. HARD COPPER TUBING: ASTM B 88, TYPE L (ASTM B 88M, TYPE B) WITH ASME B16.22 WROUGHT-COPPER SOLDER FITTINGS
AND ASTM B 32, 95-5 TIN ANTIMONY SOLDER.
2.5.2. ON PIPING 2 1/2" OR GREATER, MECHANICAL CONTRACTOR MAY USE: STEEL PIPE: ASTM A 53, SCHEDULE 40, PLAIN ENDS
WITH CAST-IRON THREADED FITTINGS.
2.5.3. ALL GAGE COCS AND NIPPLES SHALL BE BRASS OR STAINLESS STEEL.
2.5.4. ALL CONNECTIONS BETWEEN FERROUS AND NON-FERROUS PIPE AND EQUIPMENT SHALL BE MADE WITH DIELECTRIC
FITTINGS.
2.5.5. BELOW GRADE PIPING SHALL BE THERM-ACOR FERRO-THERMO OR APPROVED EQUAL. CARRIER PIPE SHALL BE
SCHEDULE 40 STEEL WITH CLOSED CELL POLYURETHANE INSULATION HAVING A MINIMUM DENSITY OF 2.0 POUNDS PER FOOT
AND A K-FACTOR OF .016 OR LOWER @75°F PER ASTM C-C158. JACKET SHALL BE HIGH DENSITY POLYETHYLENE WITH A
MINIMUM WALL THICKNESS OF 100 PROVIDE WITH MANUFACTURERS RECOMMENDED FITTINGS FOR LAYOUT AND INSTALL PER
MANUFACTURERS RECOMMENDED INSTALLATION PROCEDURES.
2.5.6. INSULATION: 1 1/2" WALL ONE-PIECE FIBERGLASS COVERING HAVING A CONDUCTIVITY NOT EXCEEDING 0.27 WITH FIRE
RESISTANT JACKET WITH SELF-SEALING LAP TO PROVIDE A CONTINUOUS VAPOR BARRIER BY CERTAINTEED, OWENS-CORNING
OR ARMSTRONG.
2.5.6.1. ARMAFLEX INSULATION SHALL NOT BE USED.
2.5.6.2. ALL PIPE INSULATION WITHIN THE MECHANICAL ROOM SHALL HAVE A PVC JACKET INCLUDING FITTINGS, AND SHALL
BE MARKED WITH APPLICATION AND DIRECTION OF FLOW EVERY 10-0 OR BETWEEN CHANGES IN DIRECTION. LETTERING
SHALL BE A MINIMUM 1 1/2" HIGH. MARKINGS SHALL BE PERMANENT WATER PROOF STICKERS. EXTERIOR ABOVE GROUND
PIPING SHALL BE PROVIDED WITH HEAT TRACE AT 5 WATTS PER FOOT ON PIPE SIDE OF INSULATION. EXTERIOR PIPING SHALL
HAVE A CONTINUOUS
2.5.6.3. VAPOR BARRIER AND BE COVERED WITH RIGID ALUMINUM PIPE JACKET, SMOOTH JACKETING IS NOT ACCEPTABLE.
2.6. MECHANICAL CONTRACTOR RESPONSIBILITIES:
2.6.1. AFTER COMPLETION OF THE WORK DESCRIBED IN THIS SPECIFICATION AND SHOWN ON THE DRAWINGS, THE MECHANICAL
CONTRACTOR SHALL THOROUGHLY CLEAN ALL EXPOSED EQUIPMENT, REMOVING ALL LABELS AND STICKERS NOT
CONTAINING OPERATION INSTRUCTION. MECHANICAL CONTRACTOR SHALL REMOVE CRATING DEBRIS. LEAVING THE
INSTALLATION FINISHED AND READY FOR OPERATION, TO INCLUDING CLEAN FILTERS IN AIR HANDLING UNITS.
2.6.2. TEST AND DEMONSTRATE TO THE OWNER THE ENTIRE SYSTEM IN ALL MODES OF OPERATION TO INSURE PROPER
OPERATION.
20
CIT
Y O
F H
AM
PT
ON
OLD
H
AM
PT
ON
C
IR
CU
IT
C
OU
RT
RE
PL
AC
E H
VA
C
19-0
15
11/
12/
2019
2406 Princess Anne Road,
Virginia Beach, VA 23456Phone (757) 563-9027
Facsimile(757) 563-9028
Suite 200
COASTALE N G I N E E R I N G
RM
K
CO
MM
ONWEALTH OF VIRGIN
IA
PROFESSIONAL ENGIN
EER
RICHARD M. KLEIN
No. 027864
TH
E C
OP
YR
IG
HT
S T
O A
LL
D
ES
IG
NS
A
ND
D
RA
WIN
GS
A
RE
T
HE
P
RO
PE
RT
Y O
F C
OA
ST
AL
E
NG
IN
EE
RIN
G, P
LL
C. R
EP
RO
DU
CT
IO
N O
R U
SE
F
OR
A
NY
P
UR
PO
SE
O
TH
ER
T
HA
N T
HA
T A
UT
HO
RIZ
ED
B
Y C
OA
ST
AL
E
NG
IN
EE
RIN
G, P
LL
C IS
F
OR
BID
DE
N.
15
E-001
EL
EC
TR
ICA
L L
EG
EN
D, N
OT
ES A
ND
AB
BR
EV
IAT
ION
SB
PM
BP
M
ABBREVIATIONSLEGEND GENERAL NOTES
1. THE INSTALLATION OF ALL ELECTRICAL EQUIPMENT, DEVICES AND FIXTURES SHALL
CONFORM TO ALL CURRENT LOCAL CODES, ORDINANCES, NATIONAL ELECTRIC CODE, AND
UTILITY COMPANY REQUIREMENTS.
2. ALL RECEPTACLES AND SWITCHES SHALL BE FLUSH MOUNTED FOR ALL AREAS, UNLESS
OTHERWISE NOTED.
3. THE ELECTRICAL DRAWINGS ARE GENERALLY DIAGRAMMATIC. THE ELECTRICAL
INSTALLATION SHALL BE COORDINATED WITH ALL OTHER TRADES SO THAT INTERFERENCES
BETWEEN THE ELECTRICAL INSTALLATION AND ARCHITECTURAL, STRUCTURAL, MECHANICAL,
PLUMBING, FIRE PROTECTION AND EQUIPMENT INSTALLATION WILL BE AVOIDED. REFER TO
ARCHITECTURAL DRAWINGS. CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND ALL
RELATED ELECTRICAL NOTES AND SHALL BE RESPONSIBLE FOR INCLUDING FIELD
VERIFICATIONS IN HIS BID. NO CHANGE ORDERS SHALL BE CONSIDERED FOR LACK OF FIELD
VERIFICATION OF ALL PLAN NOTES AND DIMENSIONS.
4. SEE ARCHITECTURAL DRAWINGS FOR DIMENSIONS, ROOM, AND AREA FINISHES, CEILING
PLANS, DOOR SWINGS, FIRE RELATED PARTITIONS, CABINET AND CASE AND BUILT-IN
DETAILS.
5. CONTRACTOR SHALL PROVIDE ALL DISCONNECTS TO MEET LOCAL CODES.
6. CONTRACTOR SHALL VERIFY ALL DOOR SWINGS BEFORE INSTALLING LIGHT SWITCHES. ALL
LIGHT SWITCHES TO BE INSTALLED ON STRIKE SIDE OF DOOR UNLESS SPECIFICALLY NOTED
OTHERWISE. WHERE SWITCHES ARE LOCATED ON HINGE SIDE OF DOOR, SWITCH SHALL BE
INSTALLED A MINIMUM OF 36" FROM HINGE.
7. ALL FINAL CONNECTIONS SHOWN ON THE DRAWINGS ARE ACTUAL REQUIREMENTS OF THE
EQUIPMENT AND ARE SHOWN IN THEIR APPROXIMATE LOCATION.
8. ALL MOTOR STARTERS SHALL BE PROVIDED BY THE MECHANICAL CONTRACTOR FURNISHING
THE EQUIPMENT AND INSTALLED, WIRED AND CONNECTED BY ELECTRICAL CONTRACTOR
9. ALL EXTERIOR EQUIPMENT AND DEVICES SHALL BE WEATHERPROOF AND RAIN TIGHT.
10. COORDINATE ALL LIGHTING WITH MECHANICAL AND PLUMBING EQUIPMENT.
11. ALL BATHROOM RECEPTACLES SHALL BE GROUND FAULT PROTECTED. (TYPICAL)
12. FINAL DETERMINATION OF FIRE STOPPING REQUIREMENTS SHALL BE BASED ON LOCAL CODE
REQUIREMENT.
13. SPECIFICATIONS SHALL TAKE PRECEDENCE OVER PLAN SPECIFICATIONS.
14. CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD VERIFYING ALL DIMENSIONS AND
MEASUREMENTS. NOTIFY ENGINEER OF ANY DISCREPANCIES PRIOR TO BID.
Ø, PH PHASE
JB JUNCTION BOX
A, AMP AMPERE
KVA KILOVOLT AMPERES
AFF ABOVE FINISHED FLOOR
KW KILOWATT
AFG ABOVE FINISHED GRADE
MLO MAIN LUGS ONLY
AIC AMPERE INTERRUPTING
CAPACITY
MT MOUNT (RMS SYMMETRICAL)
MTD MOUNTED ALTERNATE ALT
MTG MOUNTING
MCB MAIN CIRCUIT BREAKER
APPROX APPROXIMATELY
NF NONFUSIBLE
C CONDUIT
NTS NOT TO SCALE
℄ CENTERLINE
P POLE
EF EXHAUST FAN
RTU ROOF TOP UNIT
EQUIP EQUIPMENT TYP TYPICAL
EXIST EXISTING
UON UNLESS OTHERWISE NOTED
F FUSE
V VOLT, VOLTAGE
FLEX FLEXIBLE
W WIRE
GFI GROUND FAULT INTERRUPTER
WP WEATHERPROOF
GND GROUND
HP HORSE POWER
E EXISTING
N NEW
CIRCUIT BREAKER
PANELBOARD 208Y/120V OR 120/240V
PANELBOARD 480Y/277V
ELECTRICAL CONNECTION AS NOTED.
WATER HEATER CONNECTION.
ROOM NUMBER
NEW WORK NOTE SYMBOL
DEMO WORK NOTE SYMBOL
BRANCH CIRCUIT OR FEEDER WIRING IN CONDUIT. NO
TICK MARKS INDICATE 2 CONDUCTORS & 1 GROUND IN
CONDUIT UON. TICK MARKS, WHEN SHOWN, INDICATE
QUANTITY OF CONDUCTORS IF OTHER THAN THREE; ( )
INDICATES GROUND, ( ) INDICATES INSULATED
ISOLATED GROUND. FOR CONDUIT AND WIRE SIZES
REFER TO PANELBOARD SCHEDULES.
POINT OF WORK, DEMO AND NEW WORK.
NOTE: ALL SYMBOLS BELOW MAY NOT BE USED ON PLANS, SYMBOLS NOT SHOWN BELOW
ARE IDENTIFIED WHERE THEY OCCUR.
F
CONDUIT HOMERUN WITH PANELBOARD & CIRCUIT
DESIGNATIONS BRANCH CIRCUIT OF FEEDER WIRING
IN CONDUIT. PROVIDE SIZE AND QUANTITY OF
CONDUCTORS AS REQUIRED TO FACILITATE CIRCUIT
CONFIGURATION AND/OR SWITCHING INDICATED.
MINIMUM CONDUCTOR SIZE SHALL BE #12 AWG (OR AS
INDICATED), MINIMUM CONDUIT SIZE SHALL BE 1/2".
HOMERUNS TO PANEL. PANEL & CIRCUIT DESIGNATIONS
AS INDICATED.
FIRE ALARM SYSTEM SMOKE SENSOR, CEILING MOUNT,
U.O.N.
FIRE ALARM SYSTEM HEAT SENSOR, CEILING MOUNT,
U.O.N.
FIRE ALARM SYSTEM CONNECTION TO FLOW SWITCH
FIRE ALARM SYSTEM CONNECTION TO TAMPER SWITCH
FIRE ALARM SYSTEM CONNECTION TO ALARM CHECK
VALVE
FIRE ALARM SYSTEM MANUAL PULL STATION, MOUNT
+42" AFF, U.O.N.
FIRE ALARM SYSTEM AUDIO ALARM, MOUNT 6" BELOW
CEILING OR 90" AFF MAXIMUM
FIRE ALARM SYSTEM VISUAL ALARM, MOUNT 6" BELOW
CEILING OR 90" AFF MAXIMUM
FIRE ALARM SYSTEM AUDIO/VISUAL ALARM, MOUNT
6"BELOW CEILING OR 90" AFF MAXIMUM
FIRE ALARM SYSTEM CONTROL PANEL
JUNCTION BOX (J.B.) FLUSH MOUNTED 4"SQ x DEPTH
REQ'D UON. S=SURFACE MOUNTED
MOTOR CONNECTION, HP, AND CHARACTERISTICS AS
NOTED
MOTOR STARTER, CONTROLLER, OR RELAY FOR
MECHANICAL EQUIPMENT. DEVICE SUPPLIED BY
MECHANICAL CONTRACTOR; INSTALLED AND
CONNECTED BY ELECTRICAL CONTRACTOR. VERIFY
EXACT LOCATION.
DISCONNECT SAFETY SWITCH & CONNECTION
3P = NO. OF POLES
60 = SWITCH RATING
40 = FUSE RATING (NF INDICATES NON-FUSIBLE).
TELECOMMUNICATIONS OUTLET BOX AND JACK.
MOUNT 18" AFF. TO BOTTOM OF BOX U.O.N. PROVIDE
3/4" CONDUIT STUBBED ABOVE ACCESSIBLE CEILING
SPACE WITH CAT-6 CABLING BACK TO TELEPHONE
MAIN EQUIPMENT U.O.N. (VOICE AND DATA).
MOUNT +18" AFF. U.O.N.
48" = MOUNTING HEIGHT AFF. IN INCHES
WM = WIREMOLD BOX AND RACEWAY
JUNCTION BOX (J.B.) SURFACE MOUNTED ABOVE
CEILING. SIZE AS NOTED ON DRAWINGS.
TWO DUPLEX CONVENIENCE TYPE
RECEPTACLES(QUADRIPLEX), EACH NEMA 5-20R,
MOUNT IN TWO GANG RECEPTACLE BOX WITH SINGLE
COVER PLATE, MOUNT 18" AFF TO BOTTOM OF BOX
U.O.N.
DUPLEX CONVENIENCE RECEPTACLE. 20A, 125VAC,
NEMA 5-20R, MOUNT 18" AFF TO BOTTOM OF BOX
U.O.N.
C = CEILING MOUNT
WP = WEATHERPROOF
GFI = GROUND FAULT INTERRUPTER
48 = MOUNTING HEIGHT AFF IN INCHES
10
WM
WM WM
9
10
10
10
10
9
9
9
910
9
10
10 9 10 10
10
9
9
11
11
11
(E) DOMESTIC HOT
WATER HEATER TO
REMAIN
(E) AIR COMPRESSOR TO
REMAIN
(E) AIR DRYER TO REMAIN
(E) JOHNSON CONTROLS
PANEL TO REMAIN
(E) AHU STARTER
ROOM 101
ROOM 102
ROOM 103
ROOM 104
ROOM 105
(E) FACP TO REMAIN
(E) DIALBOX TO REMAIN
(E) DIALBOX TO REMAIN
(E) TBB TO REMAIN
(E) PANEL MDP
(E) PANEL A
(E) FAN STARTER
(E) PUMP STARTER
(E) CHILLER PUMP
STARTER
(E) PUMP
STARTER
(E) HOT WATER UNIT
HEATER TO REMAIN
(E) FACP
(E) DIALBOX
(E) DIALBOX
(E) TBB
(E) BOILER
AND FLUE
ROOM 104
1
2
4
6
6
7
8
8
8
4
5
33
(E) COOLING TOWER
CHEMICAL TREATMENT
SYSTEM TO BE
REMOVED BY OWNER.
1 1
1
(N) AHU-1
20
CIT
Y O
F H
AM
PT
ON
OLD
H
AM
PT
ON
C
IR
CU
IT
C
OU
RT
RE
PL
AC
E H
VA
C
19-0
15
11/
12/
2019
2406 Princess Anne Road,
Virginia Beach, VA 23456Phone (757) 563-9027
Facsimile(757) 563-9028
Suite 200
COASTALE N G I N E E R I N G
RM
K
CO
MM
ONWEALTH OF VIRGIN
IA
PROFESSIONAL ENGIN
EER
RICHARD M. KLEIN
No. 027864
TH
E C
OP
YR
IG
HT
S T
O A
LL
D
ES
IG
NS
A
ND
D
RA
WIN
GS
A
RE
T
HE
P
RO
PE
RT
Y O
F C
OA
ST
AL
E
NG
IN
EE
RIN
G, P
LL
C. R
EP
RO
DU
CT
IO
N O
R U
SE
F
OR
A
NY
P
UR
PO
SE
O
TH
ER
T
HA
N T
HA
T A
UT
HO
RIZ
ED
B
Y C
OA
ST
AL
E
NG
IN
EE
RIN
G, P
LL
C IS
F
OR
BID
DE
N.
16
E-101
AN
D S
PE
CIA
L S
YST
EM
SE
LE
CT
RIC
AL
1ST
FL
OO
R P
LA
N -
DE
MO
LIT
ION
PO
WE
R
BP
M
BP
M
ELECTRICAL 1ST FLOOR PLAN - DEMOLITION POWER AND SPECIAL SYSTEMS
1
DEMOLITION WORK NOTES:
(THIS SHEET ONLY)
SCALE: 1/4" = 1'-0"
GRAPHIC SCALE
1/4" = 1'-0"
4' 8'0 2' 12'
DISCONNECT ELECTRICAL CONNECTION TO FAN COIL UNIT. REMOVE
CONDUIT, WIRE, AND ASSOCIATED HARDWARE BACK TO PANEL "A".
DISCONNECT EXISTING COOLING TOWER. REMOVE CONDUIT AND
CONDUCTORS BACK TO PANEL 'MDP'.
DISCONNECT EXISTING PUMP. EXISTING CIRCUIT TO REMAIN FOR
RE-USE.
DISCONNECT EXISTING PUMP. REMOVE CONDUIT AND CONDUCTORS
BACK TO PANEL 'MDP'.
DISCONNECT WATER COOLED CHILLER. REMOVE CONDUIT AND
CONDUCTORS BACK TO PANEL 'MDP'.
DISCONNECT ELECTRICAL CONNECTION TO AHU. REMOVE ALL CONDUIT,
WIRE, SUPPORTS, STARTER, AND ASSOCIATED HARDWARE BACK TO
PANEL MDP.
REMOVE EXISTING 400AMP 3PH OBSOLETE GE QMR STYLE PANEL. RETAIN
EXISTING CIRCUITS AND SECONDARY FEEDER FOR RE-TIE INTO NEW
PANEL MDP.
REMOVE EXISTING STARTER AND ALL ASSOCIATED CONDUIT, WIRE,
SUPPORTS.
EXISTING RECEPTACLE TO REMAIN UNLESS OTHERWISE NOTED.
EXISTING TELEPHONE/DATA JACK TO REMAIN UNLESS OTHERWISE
NOTED.
EXISTING CEILING MOUNTED SMOKE DETECTOR TO REMAIN.
2
3
4
5
6
7
8
9
10
11
1
2
3
44 4
4
4 4
4
4
4
4 4
4 4
4 4444
4
4
4
4
4
4
4
4
4
44
4444
4
4
4
4
4
5
4
4 4
4
4 4
4
4 4
4
4
6 66
6
6 6
6
6 6
6
4
6
6
6
7 7
7 7
7
7
7
7
7
ROOM 201
JUDGES CHAMBERS 202
ROOM 203
COPY ROOM 204
HEARING ROOM 205
JURY ROOM 206
ATTORNEY CONFERENCE ROOM 207
ROOM 208
ROOM 209
ROOM 210
ROOM 211
JURY ROOM JUDGES
LOUNGE
8
1
8
8
8
8
8
8 8
8
8
8
20
CIT
Y O
F H
AM
PT
ON
OLD
H
AM
PT
ON
C
IR
CU
IT
C
OU
RT
RE
PL
AC
E H
VA
C
19-0
15
11/
12/
2019
2406 Princess Anne Road,
Virginia Beach, VA 23456Phone (757) 563-9027
Facsimile(757) 563-9028
Suite 200
COASTALE N G I N E E R I N G
RM
K
CO
MM
ONWEALTH OF VIRGIN
IA
PROFESSIONAL ENGIN
EER
RICHARD M. KLEIN
No. 027864
TH
E C
OP
YR
IG
HT
S T
O A
LL
D
ES
IG
NS
A
ND
D
RA
WIN
GS
A
RE
T
HE
P
RO
PE
RT
Y O
F C
OA
ST
AL
E
NG
IN
EE
RIN
G, P
LL
C. R
EP
RO
DU
CT
IO
N O
R U
SE
F
OR
A
NY
P
UR
PO
SE
O
TH
ER
T
HA
N T
HA
T A
UT
HO
RIZ
ED
B
Y C
OA
ST
AL
E
NG
IN
EE
RIN
G, P
LL
C IS
F
OR
BID
DE
N.
17
E-102
AN
D S
PE
CIA
L S
YST
EM
SE
LE
CT
RIC
AL
2N
D F
LO
OR
PL
AN
- D
EM
OL
ITIO
N P
OW
ER
BP
M
BP
M
ELECTRICAL 2ND FLOOR PLAN - DEMOLITION POWER AND SPECIAL SYSTEMS
1
DEMOLITION WORK NOTES:
(THIS SHEET ONLY)
EXISTING DUPLEX RECEPTACLE LOCATED IN JUDGES BENCH AREA TO BE
REMOVED INCLUDING CONDUIT, WIRE, AND ASSOCIATED HARDWARE.
FLOOR MOUNTED DUPLEX RECEPTACLE LOCATED IN WITNESS STAND TO
BE REMOVED. REMOVE WIRING FROM CONDUIT AND CUT OFF CONDUIT
FLUSH WITH FLOOR AND PLUG.
EXISTING IT ROOM WITH IT EQUIPMENT. EQUIPMENT RACK TO BE
RELOCATED TO NEW IT ROOM PER NEW WORK DRAWINGS.
EXISTING RECEPTACLE TO REMAIN UNLESS OTHERWISE NOTED.
EXISTING COPY MACHINE RECEPTACLE TO REMAIN.
EXISTING TELEPHONE/DATA JACK TO REMAIN UNLESS OTHERWISE
NOTED.
EXISTING CEILING MOUNTED SMOKE DETECTOR TO REMAIN.
DISCONNECT ELECTRICAL CONNECTION TO FAN COIL UNIT. REMOVE
CONDUIT, WIRE, AND ASSOCIATED HARDWARE BACK TO PANEL "B".
SCALE: 1/4" = 1'-0"
GRAPHIC SCALE
1/4" = 1'-0"
4' 8'0 2' 12'
2
3
4
5
6
7
8
ACC-1
2
4 4
5
6
7
8
WM
WM WM
(E) AIR COMPRESSOR TO
REMAIN
(E) JOHNSON CONTROLS
PANEL TO REMAIN
ROOM 101
ROOM 102
ROOM 103
ROOM 104
ROOM 105
(E) HOT WATER UNIT
HEATER TO REMAIN
(E) FACP
(E) DIALBOX
(E) DIALBOX
(E) TBB
(E) BOILER
AND FLUE
ROOM 104
9
(E) AIR COMPRESSOR TO
(N) AHU-1
BC
-6
BC-7
BC-5
BC-2
1
1
1
1
BC-1
10
CU-1
11
12
4 4
20
CIT
Y O
F H
AM
PT
ON
OLD
H
AM
PT
ON
C
IR
CU
IT
C
OU
RT
RE
PL
AC
E H
VA
C
19-0
15
11/
12/
2019
2406 Princess Anne Road,
Virginia Beach, VA 23456Phone (757) 563-9027
Facsimile(757) 563-9028
Suite 200
COASTALE N G I N E E R I N G
RM
K
CO
MM
ONWEALTH OF VIRGIN
IA
PROFESSIONAL ENGIN
EER
RICHARD M. KLEIN
No. 027864
TH
E C
OP
YR
IG
HT
S T
O A
LL
D
ES
IG
NS
A
ND
D
RA
WIN
GS
A
RE
T
HE
P
RO
PE
RT
Y O
F C
OA
ST
AL
E
NG
IN
EE
RIN
G, P
LL
C. R
EP
RO
DU
CT
IO
N O
R U
SE
F
OR
A
NY
P
UR
PO
SE
O
TH
ER
T
HA
N T
HA
T A
UT
HO
RIZ
ED
B
Y C
OA
ST
AL
E
NG
IN
EE
RIN
G, P
LL
C IS
F
OR
BID
DE
N.
18
E-201
AN
D
SP
EC
IAL
SY
ST
EM
SE
LE
CT
RIC
AL
1ST
FL
OO
R P
LA
N -
NE
W W
OR
K P
OW
ER
BP
M
BP
M
ELECTRICAL 1ST FLOOR PLAN - NEW WORK POWER AND SPECIAL SYSTEMS
1
NEW WORK NOTES:
(THIS SHEET ONLY)
NEW 20AMP 208V 1PH CIRCUIT (3)#12 CU IN 1/2" CONDUIT TO BLOWER
COIL. PROVIDE LOCAL FUSED DISCONNECT AT EACH BLOWER COIL. FUSE
AT 15AMPS.
NEW CIRCUIT FOR ACC-1. FURNISH AND INSTALL (3) 2/0 THHN CU, (1) #6 CU
GND IN 2" CONDUIT FROM NEW DISCONNECT TO MDP.
NOT USED
PROVIDE ELECTRICAL CONNECTION TO NEW HOT WATER PUMPS P-3 AND
P-4 FROM EXISTING CIRCUIT RETAINED FROM DEMOLITION. EXTEND
CIRCUIT(S) TO NEW DISCONNECT SWITCHES AND STARTERS ON WALL.
PROVIDE NEW FLEXIBLE LIQUIDTITE CONNECTION TO MOTORS.
FURNISH AND INSTALL (4) #12 THHN CU IN 1/2" CONDUIT FROM NEW
CHILLED WATER PUMPS P-1 AND P-2 TO PANEL MDP. PROVIDE FLEXIBLE
LIQUIDTITE CONNECTION TO MOTORS.
NEW DISTRIBUTION PANEL "MDP" SEE RISER DIAGRAM AND PANEL
SCHEDULES ON SHEET E-601.
CUT AND PATCH ASPHALT AS REQUIRED FOR NEW CONDUIT AND WIRE.
PROVIDE PENETRATION THROUGH EXTERIOR WALL WITH "LB" CONDUIT
FITTING AS LOW ON WALL AS POSSIBLE AND CONTINUE CONDUIT
ROUTING INSIDE MECHANICAL ROOM TO PANEL MDP.
STARTERS FOR CWP'S P-3 AND P-4, FURNISHED BY MECHANICAL
CONTRACTOR AND INSTALLED BY ELECTRICAL CONTRACTOR.
NEW 20AMP 125V QUAD RECEPTACLE FOR NEW TELEPHONE/DATA
EQUIPMENT.
NEW 20AMP 208V 3PH CIRCUIT (4)#12 CU IN 1/2" CONDUIT TO BLOWER
COIL. PROVIDE LOCAL FUSED DISCONNECT AT BLOWER COIL"BC-1". FUSE
AT 15AMPS.
LINE VOLTAGE THERMOSTAT FOR EUH-1. FURNISHED BY MECHANICAL
CONTRACTOR, INSTALLED AND WIRED BY ELECTRICAL CONTRACTOR.
NEW CONTROL PANEL.
SCALE: 1/4" = 1'-0"
GRAPHIC SCALE
1/4" = 1'-0"
4' 8'0 2' 12'
2
3
4
5
6
7
8
9
10
11
GENERAL WORK NOTES:
(THIS SHEET ONLY)
1. ALL DEVICES, DATA, AND FIRE ALARM DEVICE
SHOWN ARE EXISTING UNLESS INDICATED OTHERWISE.
2. STARTERS FOR P-1 THRU P-4 FURNISHED BY MECHANICAL
CONTRACTOR AND INSTALLED AND WIRED BY ELECTRICAL
CONTRACTOR.
12
1
ROOM 201
JUDGES CHAMBERS 202
ROOM 203
COPY ROOM 204
HEARING ROOM 205
JURY ROOM 206
ATTORNEY CONFERENCE ROOM 207
ROOM 208
ROOM 209
ROOM 210
ROOM 211
JURY ROOM JUDGES
LOUNGE
BC
U-8
BC-4
BC-9
BC-3
BC-10
BC-11
DS
S-1
2
2
2
2 2
2
3
20
CIT
Y O
F H
AM
PT
ON
OLD
H
AM
PT
ON
C
IR
CU
IT
C
OU
RT
RE
PL
AC
E H
VA
C
19-0
15
11/
12/
2019
2406 Princess Anne Road,
Virginia Beach, VA 23456Phone (757) 563-9027
Facsimile(757) 563-9028
Suite 200
COASTALE N G I N E E R I N G
RM
K
CO
MM
ONWEALTH OF VIRGIN
IA
PROFESSIONAL ENGIN
EER
RICHARD M. KLEIN
No. 027864
TH
E C
OP
YR
IG
HT
S T
O A
LL
D
ES
IG
NS
A
ND
D
RA
WIN
GS
A
RE
T
HE
P
RO
PE
RT
Y O
F C
OA
ST
AL
E
NG
IN
EE
RIN
G, P
LL
C. R
EP
RO
DU
CT
IO
N O
R U
SE
F
OR
A
NY
P
UR
PO
SE
O
TH
ER
T
HA
N T
HA
T A
UT
HO
RIZ
ED
B
Y C
OA
ST
AL
E
NG
IN
EE
RIN
G, P
LL
C IS
F
OR
BID
DE
N.
19
E-202
AN
D
SP
EC
IAL
SY
ST
EM
SE
LE
CT
RIC
AL
2N
D
FL
OO
R P
LA
N -
NE
W W
OR
K P
OW
ER
BP
M
BP
M
ELECTRICAL 2ND FLOOR PLAN - NEW WORK POWER AND SPECIAL SYSTEMS
1
NEW WORK NOTES:
(THIS SHEET ONLY)
NEW 20AMP 125V QUAD RECEPTACLE FOR NEW TELEPHONE/DATA
EQUIPMENT.
NEW 20AMP 208V 1PH CIRCUIT (3)#12 CU IN 1/2" CONDUIT TO BLOWER
COIL. PROVIDE LOCAL FUSED DISCONNECT AT EACH BLOWER COIL. FUSE
AT 15AMPS. SEE PANEL SCHEDULES SHEET E-601 FOR CIRCUITS.
DSS-1 FED FROM CU-1 ON EXTERIOR OF BUILDING WITH (3)#12 CU IN 1/2"
CONDUIT.
SCALE: 1/4" = 1'-0"
GRAPHIC SCALE
1/4" = 1'-0"
4' 8'0 2' 12'
2
3
GENERAL WORK NOTES:
(THIS SHEET ONLY)
1. ALL DEVICES, DATA, AND FIRE ALARM DEVICE
SHOWN ARE EXISTING UNLESS INDICATED OTHERWISE.
20
CIT
Y O
F H
AM
PT
ON
OLD
H
AM
PT
ON
C
IR
CU
IT
C
OU
RT
RE
PL
AC
E H
VA
C
19-0
15
11/
12/
2019
2406 Princess Anne Road,
Virginia Beach, VA 23456Phone (757) 563-9027
Facsimile(757) 563-9028
Suite 200
COASTALE N G I N E E R I N G
RM
K
CO
MM
ONWEALTH OF VIRGIN
IA
PROFESSIONAL ENGIN
EER
RICHARD M. KLEIN
No. 027864
TH
E C
OP
YR
IG
HT
S T
O A
LL
D
ES
IG
NS
A
ND
D
RA
WIN
GS
A
RE
T
HE
P
RO
PE
RT
Y O
F C
OA
ST
AL
E
NG
IN
EE
RIN
G, P
LL
C. R
EP
RO
DU
CT
IO
N O
R U
SE
F
OR
A
NY
P
UR
PO
SE
O
TH
ER
T
HA
N T
HA
T A
UT
HO
RIZ
ED
B
Y C
OA
ST
AL
E
NG
IN
EE
RIN
G, P
LL
C IS
F
OR
BID
DE
N.
20
E-601
EL
EC
TR
ICA
L R
ISE
R D
IAG
RA
M A
ND
PA
NE
LB
OA
RD
SC
HE
DU
LE
SB
PM
BP
M
NO SCALE
ELECTRICAL RISER DIAGRAM
(E)(4)#3 THHN CU,
(1)#8 CU GND IN 1-1/4"C
(E)(2)SETS (4)-250MCM THWN CU,
(1)#4 CU GND IN 3" C.
(E)(4)#3 THHN CU,
(1)#8 CU GND IN 1-1/4"C.
REMOVE AND REPLACE WITH (4)#3/0,(1)#6 CU GND IN 2"C.
2ND FLOOR
.
.
.
REMOVE EXISTING 100AMP PANEL
AND REPLACE WITH NEW 225AMP MLO 120-208V
3PH 4W 42 CIRCUIT SURFACE MOUNT 10KAIC PANEL
20
CIT
Y O
F H
AM
PT
ON
OLD
H
AM
PT
ON
C
IR
CU
IT
C
OU
RT
RE
PL
AC
E H
VA
C
19-0
15
11/
12/
2019
2406 Princess Anne Road,
Virginia Beach, VA 23456Phone (757) 563-9027
Facsimile(757) 563-9028
Suite 200
COASTALE N G I N E E R I N G
RM
K
CO
MM
ONWEALTH OF VIRGIN
IA
PROFESSIONAL ENGIN
EER
RICHARD M. KLEIN
No. 027864
TH
E C
OP
YR
IG
HT
S T
O A
LL
D
ES
IG
NS
A
ND
D
RA
WIN
GS
A
RE
T
HE
P
RO
PE
RT
Y O
F C
OA
ST
AL
E
NG
IN
EE
RIN
G, P
LL
C. R
EP
RO
DU
CT
IO
N O
R U
SE
F
OR
A
NY
P
UR
PO
SE
O
TH
ER
T
HA
N T
HA
T A
UT
HO
RIZ
ED
B
Y C
OA
ST
AL
E
NG
IN
EE
RIN
G, P
LL
C IS
F
OR
BID
DE
N.
21
E-701
EL
EC
TR
ICA
L S
PE
CIF
ICA
TIO
NB
PM
BP
M
ELECTRICAL SPECIFICATIONS
1. GENERAL CONDITIONS
1.a. WORK UNDER THIS DIVISION SHALL BE SUBJECT TO THE AIA GENERAL AND SPECIAL
CONDITIONS.
2. SCOPE
2.a. THE WORK REQUIRED FOR THIS SECTION INCLUDES LABOR, MATERIALS, EQUIPMENT,
APPURTENANCES, SERVICE AND SUPERVISION TO PROVIDE COMPLETE ELECTRICAL
SYSTEMS AS SHOWN ON THE DRAWINGS.
3. SPECIFICATIONS, CODES AND STANDARDS
3.a. THE LATEST EFFECTIVE PUBLICATIONS OF THE FOLLOWING STANDARDS, CODES, ETC.
FORM A PART OF THESE SPECIFICATIONS:
3.a.a. 2011 NATIONAL ELECTRICAL CODE (NEC)
3.a.b. STANDARD RULES OF THE INSTITUTE OF ELECTRICAL AND ELECTRONIC
ENGINEERS.
3.a.c. NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION
3.a.d. INTERNATIONAL BUILDING CODE
3.a.e. NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
3.b. THIS CONTRACTOR SHALL GIVE REQUIRED NOTICES, OBTAIN NECESSARY PERMITS,
AND PAY PERMIT FEES.
4. DRAWINGS
4.a. THE DRAWINGS INDICATE DIAGRAMMATICALLY THE EXTENT OF THE WORK. MINOR
VARIATIONS IN LOCATION OF EQUIPMENT SHALL BE MADE UPON WRITTEN APPROVAL
OF THE ENGINEER AT NO ADDITIONAL CHARGE.
5. EQUIPMENT
5.a. STARTERS, CONTROLLERS, CONTROL TRANSFORMERS, RELAYS, CONTACTORS, ETC;
SHALL BE PROVIDED UNDER THE DIVISION PROVIDING EQUIPMENT OTHERWISE NOTED.
5.b. POWER WIRING AND POWER CONNECTIONS TO EQUIPMENT SHALL BE PROVIDED
UNDER "ELECTRICAL" UNLESS OTHERWISE INDICATED ON THE ELECTRICAL DRAWINGS.
5.c. WHEN SUBSTITUTED MOTORS AND/OR EQUIPMENT REQUIRES ELECTRICAL
MODIFICATIONS, THE COST OF THE ELECTRICAL MODIFICATIONS AND COORDINATION
SHALL BE INCLUDED UNDER THE DIVISION PROVIDING THE MOTOR AND/OR EQUIPMENT.
6. COORDINATION
6.a. COOPERATE AND COORDINATE THE WORK OF THIS DIVISION WITH OTHER TRADES.
6.b. CONTRACTOR TO SUBMIT 6 SETS (OWNER WILL RETURN 3 SETS NOTED WITH ACTION
TAKEN)SPECIFICATIONS AND DETAIL FOR EQUIPMENT AND FABRICATED MATERIALS
FOR OWNER'S APPROVAL PRIOR TO ISSUING PURCHASE ORDER. OWNER'S APPROVAL
DOES NOT RELIEVE CONTRACTOR OF ANY RESPONSIBILITY FOR PERFORMANCE AND
OPERATION.
2. MATERIAL AND EQUIPMENT
2.a. ELECTRICAL MATERIALS AND EQUIPMENT SHALL BE NEW, LISTED, AND LABELED BY AN
APPROVED TESTING AGENCY.
2.a.a. INSTALL MATERIALS AND EQUIPMENT IN A FIRST CLASS AND WORKMANLIKE
MANNER AND RUN CONCEALED THROUGHOUT THE BUILDING, EXCEPT AS
INDICATED.
2.b. MATERIAL AND EQUIPMENT SHALL BE PROPERLY STORED AND PROTECTED AT THE
PROJECT SITE.
2.c. SIX COMPLETE SCHEDULES OF MATERIALS AND EQUIPMENT PROPOSED FOR
INSTALLATION SHALL BE SUBMITTED TO THE ENGINEER WITHIN 30 DAYS AFTER AWARD
OF THE CONTRACT. THE SCHEDULES SHALL INCLUDE CATALOG CUTS, DIAGRAMS AND
SUCH OTHER DESCRIPTIVE DATA AND/OR SAMPLES AS MAY BE REQUIRED BY THE
ENGINEER. LIGHTING FIXTURE SUBMITTALS SHALL INCLUDE PHOTOMETRIC REPORTS
BY INDEPENDENT TESTING LABORATORIES FOR EACH FIXTURE INDICATED BASED ON
ITS PUBLISHED PROCEDURES.
2.d. SUBMITTALS THAT DO NOT BEAR THE GENERAL CONTRACTORS STAMP OF APPROVAL
THEREON WILL BE REJECTED WITHOUT REVIEW.
2.e. CONTRACTOR SHALL FURNISH AND INSTALL ALL EQUIPMENT AND MATERIALS FOR A
COMPLETE INSTALLATION IN ALL RESPECTS READY OF INTENDED USE AND THE STRICT
ACCORDANCE WITH STATE AND LOCAL CODES AND MANUFACTURER'S
RECOMMENDATIONS. PAY NECESSARY FEES AND OBTAIN PERMITS. INITIATE, MAINTAIN
AND SUPERVISE ALL SAFETY PRECAUTIONS AND PROCEDURES.
2.f. EQUIPMENT AND MATERIALS SHALL BE OF THE TYPE, SIZE AND MANUFACTURERS
INDICATED ON THE DRAWINGS OR AN APPROVED EQUIVALENT.
2.g. THE CONTRACTOR SHALL SUPPLY AND INSTALL THE MATERIALS AND EQUIPMENT
COVERED BY THE PLANS AND SPECIFICATIONS TO THE OWNER COMPLETE AND IN
FIRST CLASS CONDITION IN EVERY RESPECT. HE SHALL GUARANTEE THAT THE
MATERIAL, EQUIPMENT, AND WORKMANSHIP SUPPLIED AND INSTALLED BY HIM SHALL
BE ENTIRELY FREE FROM DEFECTS AND THAT HE WILL REPAIR OR REPLACE AT HIS
OWN EXPENSE, ANY MATERIALS, EQUIPMENT, AND WORKMANSHIP IN WHICH DEFECTS
ARE FOUND.
3. SUBSTITUTION OF MATERIAL AND EQUIPMENT
3.a. THE NAME OF A CERTAIN BRAND, MAKE, MANUFACTURER OF DEFINITE SPECIFICATION
IS TO DENOTE THE QUALITY STANDARD OF ARTICLE DESIRED AS A BASIS OF DESIGN.
SUBSTITUTION OF ANY OTHER BRAND, MAKE, OR MANUFACTURER, WHICH IN THE
OPINION OF THE ENGINEER IS RECOGNIZED THE EQUAL OF THAT SPECIFIED, MAY BE
ACCEPTED.
3.b. WHERE THREE OR MORE MANUFACTURERS ARE SPECIFIED, THERE WILL BE NO
SUBSTITUTIONS
4. RECORD DRAWINGS
4.a. UPON COMPLETION OF THE WORK, THE CONTRACTOR SHALL SUBMIT (1) ELECTRONIC,
(1) CD COPY, AND (3) HARD COPIES OF AS-BUILT/MARKED UP DRAWINGS AND
SKETCHES TO THE ENGINEER.
5. CONDUIT
5.a. CONDUIT AND FITTINGS SHALL CONFORM TO THE FOLLOWING:
5.a.a. RIGID STEEL - ANSI C80.1
5.a.b. INTERMEDIATE METAL CONDUIT - UL 1242
5.a.c. ELECTRICAL METALLIC TUBING (EMT) - ANSI C80.3
5.a.d. FLEXIBLE METAL CONDUIT - UL-1
5.a.e. PLASTIC CONDUIT (PVC) - NEMA TC-2 AND TC-3
5.b. CONDUIT SHALL BE RUN CONCEALED, EXCEPT CONDUIT MAY BE EXPOSED ABOVE
JOIST IN MECHANICAL ROOMS AND SPACES WITH EXPOSED CONSTRUCTION AS
APPROVED BY THE ARCHITECT. CONDUIT INDICATED CONCEALED IN WALLS AND
ABOVE CEILINGS SHALL BE THIN-WALL TYPE ELECTRICAL METALLIC TUBING FOR SIZES
UP TO TWO INCHES.
5.c. INTERMEDIATE METAL CONDUIT SHALL BE PERMITTED IN LIEU OF RIGID WHERE
ALLOWED IN ARTICLE 345 OF THE NEC.
5.d. MINIMUM SIZE CONDUIT SHALL BE ONE-HALF INCH WITH LARGER SIZES AS REQUIRED
BY THE NATIONAL ELECTRICAL CODE FOR NUMBER OF WIRES CONTAINED THEREIN.
5.e. RIGID CONDUIT FITTINGS SHALL BE THREADED, EXCEPT WHERE RIGID CHANGES TO
EMT ABOVE SLAB, FITTING MAY BE THREADLESS TYPE. ELECTRICAL METALLIC TUBE
FITTINGS SHALL BE GALVANIZED SET SCREW STEEL; CAST METAL NOT ACCEPTABLE.
5.f. FLEXIBLE CONDUIT SHALL BE GALVANIZED, SINGLE STRIP TYPE. IN AREAS SUBJECT TO
MOISTURE, OR WHERE CALLED FOR ON THE DRAWINGS, FLEXIBLE CONDUIT SHALL
HAVE PLASTIC COVERING IN ACCORDANCE WITH NEC, ARTICLE 351-A. FITTINGS SHALL
BE STANDARD UL APPROVED WITH GROUND CONNECTOR. WATERTIGHT
CONNECTORS SHALL BE USED WITH PLASTIC COVERED CONDUIT, FLEXIBLE CONDUIT,
MINIMUM 18 INCHES IN LENGTH, SHALL BE USED FOR CONNECTIONS TO MOTORS AND
OTHER EQUIPMENT SUBJECT TO VIBRATION, AND FOR CONNECTIONS TO RECESSED
OR SEMI-RECESSED FIXTURES.
5.g. EXPOSED CONDUITS SHALL BE RUN PARALLEL AND PERPENDICULAR TO BUILDING
CONSTRUCTION AND SHALL BE SUPPORTED AS HEREINAFTER SPECIFIED AND IN
ACCORDANCE WITH NEC. THE METHODS OF INSTALLATION SHALL BE REVIEWED BY
THE ARCHITECT PRIOR TO INSTALLATION.
5.h. CONDUIT SUPPORTS SHALL BE APPROVED WALL BRACKETS, TRAPEZE, STRAP HANGER
OR PIPE STRAPS SECURED TO HOLLOW MASONRY WITH TOGGLE BOLTS; TO METAL
SURFACES WITH MACHINE SCREWS; AND TO WOOD WITH WOOD SCREWS. ANY FORM
OF TIE WIRE IS UNACCEPTABLE.
5.i. CONDUIT TERMINATIONS ONE AND ONE-QUARTER INCH AND LARGER AND CONDUIT
STUBS SHALL HAVE O.Z. TYPE "B" INSULATING BUSHINGS. RIGID CONDUIT
TERMINATIONS ONE INCH AND SMALLER SHALL HAVE O.Z. TYPE "A" INSULATING
BUSHINGS.
5.j. CONDUITS AND CABLES PASSING THROUGH FIRE RATED ASSEMBLIES SHALL BE
SEALED BY APPROVED METHODS OR BY INSTALLING O.Z. FIRE-SEALS TO MAINTAIN "UL"
CLASSIFIED FIRE RATING.
6. RECEPTACLE(WIRING DEVICE) BOXES
6.a. RECEPTACLE BOXES SHALL BE HOT DIPPED GALVANIZED STEEL TYPE WITH STANDARD
KNOCKOUTS AS REQUIRED FOR CONDUIT TERMINATION. MINIMUM SIZE OF
RECEPTACLE BOX SHALL BE FOUR INCHES SQUARE, ONE AND ONE-QUARTER INCHES
DEEP. RECEPTACLE BOXES FOR EXPOSED TILE AND BLOCK SHALL BE PROVIDED WITH
SQUARE CORNERED TILE RING, SIZE AS REQUIRED.
6.b. RECEPTACLE BOXES OCCURRING IN FINISHED OUTSIDE WALLS AND WET AREAS SHALL
BE CAST AND PROVIDED WITH GASKETS BETWEEN BOX AND WATERPROOF IN-USE
COVER.
6.c. WHERE SEVERAL FEEDERS PASS THROUGH A COMMON PULL BOX OR JUNCTION BOX,
THE FEEDERS SHALL BE TAGGED TO INDICATE CLEARLY THEIR ELECTRICAL
CHARACTERISTICS, CIRCUIT NUMBER, AND PANEL DESIGNATION. PAINT SAME
INFORMATION ON COVER OF THE BOX.
7. WIRING DEVICES
7.a. WIRING DEVICES SHALL BE AS MANUFACTURED BY LEVITON, PASS AND SEYMOUR, OR
HUBBELL OR APPROVED EQUAL.
7.b. DEVICE PLATES SHALL BE SMOOTH THERMOPLASTIC ON FINISHED WALLS AND METAL
ON UNFINISHED WALLS AS REQUIRED. COLOR SHALL MATCH DEVICE COLOR.
7.c. DEVICES SHALL BE IVORY U.O.N.
8. DISCONNECT SWITCHES
8.a. SWITCHES SHALL NEMA TYPE "GD" OR "HD" AS REQUIRED. FUSED SWITCHES SHALL BE
NEMA TYPE "HD" UNLESS OTHERWISE INDICATED, WITH CLASS "R" FUSE CLIPS. MAIN
DISCONNECT SWITCHES AND SWITCHES RATED 600 VOLTS SHALL BE TYPE "HD" AND
HAVE FULL COVER INTERLOCKS AND QUICK-MAKE, QUICK-BREAK MECHANISM.
8.b. FUSED SWITCHES SHALL BE PROVIDED COMPLETE WITH FUSES.
8.c. SWITCHES SHALL BE SQUARE D, GENERAL ELECTRIC, SIEMENS/I.T.E., OR CUTLER
HAMMER.
8.d. SWITCHES SHALL BE SECURELY MOUNTED TO WALL, STRUCTURE, OR EQUIPMENT.
PROVIDE MISCELLANEOUS ACCESSORIES FOR MOUNTING SWITCHES, INCLUDING
STEEL ANGLES WHERE REQUIRED.
9. FUSES
9.a. FUSES FOR PROTECTION OF MECHANICAL AND PLUMBING EQUIPMENT SHALL BE
"FUSETRON" UL CLASS "RK5" SIZED PER MANUFACTURERS RECOMMENDATION,
UNLESS OTHERWISE INDICATED.
10. WIRE AND CABLE
10.a. WIRE AND CABLE SHALL BE INSTALLED IN CONDUIT. MC CABLE ACCEPTABLE WHERE
INSTALLED WITHIN WALLS OR ABOVE CEILINGS. NO EXPOSED MC CABLE ALLOWED.
10.b. WIRE AND CABLE SHALL BE GENERAL ELECTRIC, ANACONDA, ROME, GENERAL CABLE,
OR PHELPS DODGE OR APPROVED EQUAL..
10.c. WIRE AND CABLE SHALL BE COPPER 600 VOLT INSULATION, MINIMUM SIZE NO. 12, TYPE
"THW", "THWN" OR "THHN" AS APPLICABLE, UNLESS OTHERWISE INDICATED ON
DRAWINGS.
10.d. BRANCH CIRCUIT WIRING AND WIRING IN FLUORESCENT FIXTURES SHALL BE TYPE
"THHN".
10.e. WIRES NO. 10 AND 12 AWG SHALL BE CONNECTED WITH COIL SPRING INSERT "WIRE-
NUT" OR "WING-NUT" CONNECTORS MANUFACTURED BY IDEAL INDUSTRIES OR
APPROVED EQUAL. CONNECTORS SHALL BE RATED 600 VOLTS. COPPER WIRES NO. 8
AND LARGER SHALL BE JOINED OR TERMINATED WITH PRESSURE TYPE COPPER
CONNECTORS.
10.f. WIRE SHALL BE COLOR CODED AS FOLLOWS:
10.f.a. 120/208 VOLT SYSTEM
10.f.a. PHASE A - BLACK
10.f.b. PHASE B - RED
10.f.c. PHASE C - BLUE
10.f.d. NEUTRAL - WHITE
10.f.e. GROUND - GREEN
10.g. ELECTRICAL DESIGNS ARE BASED ON COPPER WIRE AND CABLE. (ALUMINUM WIRE
AND CABLE SHALL NOT BE PERMITTED.)
11. LIGHTING FIXTURES
11.a. LIGHTING FIXTURES SHALL BE PROVIDED COMPLETE WITH LAMPS, DRIVERS, MOUNTING
HARDWARE AND ACCESSORIES.
11.b. LED COLOR SHALL BE 3500K U.O.N.
11.c. WHERE RECESSED LIGHTING FIXTURES ARE INDICATED, THIS CONTRACTOR SHALL BE
RESPONSIBLE FOR COORDINATING THE TYPE FIXTURES WITH THE ACTUAL CEILING
BEING INSTALLED. THIS SHALL INCLUDE CHANGES RESULTING FROM ALTERNATE BID
ITEMS, CHANGE ORDERS, ETC.
11.d. SURFACE MOUNTED LIGHTING FIXTURES SHALL BE MOUNTED INDEPENDENT OF
CEILING CONSTRUCTION. LIGHTING FIXTURES MOUNTED IN OR ON PLASTER CEILING
SHALL ALSO BE MOUNTED INDEPENDENT OF CEILING CONSTRUCTION. WHERE
RECESSED FLUORESCENT LIGHTING FIXTURES OCCUR IN LAY-IN TILE OR CONCEALED
SPLINE CEILINGS, THE ELECTRICAL CONTRACTOR SHALL INSTALL FIXTURES IN
ACCORDANCE WITH ARTICLE 410-16(C) OF NEC AND HAVE THE CEILING CONTRACTOR
INSTALL ADDITIONAL SUPPORTING HANGERS WHERE FIXTURES OCCUR, OR SUPPORT
FIXTURES INDEPENDENTLY OF CEILING.
11.e. FIXTURES SUPPORTED INDEPENDENTLY OF CEILING SHALL BE HUNG BY STEEL
CHANNEL, THREADED RODS AND NUTS, OR AS APPROVED.
11.f. INSULATION SHALL NOT BE PLACED ON TOP OF RECESSED LIGHTING FIXTURES.
11.h. LED FIXTURES, DRIVERS, AND COMPONENTS SHALL MEET IP 67 , UL1310, UL CLASS 2, BE
DIMMABLE 1-10VDC, POWER FACTOR OF MINIMUM .90 PF.
12. CUTTING AND PATCHING
12.a. CUTTING, DRILLING, AND CHANNELING REQUIRED FOR THIS WORK SHALL BE DONE
UNDER THIS SECTION BY SKILLED MECHANICS OF TRADE INVOLVED.
13. EQUIPMENT MARKING AND PAINTING
13.a. SAFETY SWITCHES, CABINETS, ETC., SHALL BE PROVIDED WITH PERMANENTLY
ATTACHED (ADHESIVES NOT ACCEPTABLE) ENGRAVED BAKELITE DESIGNATION PLATES
TO INDICATE EQUIPMENT OR CIRCUIT CONTROLLED.
14. ACCESS DOORS
14.a. THIS CONTRACTOR SHALL FURNISH, AND THE GENERAL CONTRACTOR SHALL INSTALL
STEEL ACCESS DOORS WHERE REQUIRED, STYLE NECESSARY FOR SURFACE IN WHICH
PLACED. SUBMIT SHOP DRAWINGS OF PROPOSED MATERIAL, INSTALLATION AND
EXACT LOCATIONS TO THE ARCHITECT FOR APPROVAL.
15. SUBSTANTIAL COMPLETION
15.a. UPON COMPLETION OF THE ENTIRE WORK, THE CONTRACTOR SHALL PERFORM SUCH
TESTS AS REQUIRED BY THE ENGINEER. THE ENGINEER SHALL BE GIVEN 48 HOURS
NOTICE BEFORE TESTS ARE MADE. THE CONTRACTOR SHALL FURNISH THE
ARCHITECT A CERTIFICATE OF APPROVAL FROM THE LOCAL INSPECTION AUTHORITY
HAVING JURISDICTION.
16. WARRANTY
16.a. CONTRACTOR SHALL FURNISH WRITTEN WARRANTY, COUNTERSIGNED, AND
GUARANTEED BY THE GENERAL CONTRACTOR, STATING THAT THE WORK EXECUTED
UNDER THIS DIVISION OF THE SPECIFICATIONS SHALL BE FREE FROM DEFECTS OF
MATERIAL AND WORKMANSHIP FOR A PERIOD OF 12 MONTHS FROM DATE OF FINAL
ACCEPTANCE. DEFECTS DEVELOPING DURING THAT PERIOD SHALL BE CORRECTED
WITHOUT COST TO THE OWNER. LED FIXTURES, DRIVERS, LAMPS SHALL CARRY A (5)
YEAR WARRANTY.