CITY OF EL CERRITO PUBLIC WORKS DEPARTMENT
EL CERRITO SWIM CENTER
LOCKER ROOMS / POOL EQUIPMENT ROOM UPGRADES AND RENOVATIONS CITY PROJECT NO. C3050.4
ADDENDUM NO. 1
November 1, 2017
TO: All Prospective Bidders The additions and/or deletions contained in this Addendum shall be made part of the plans and specifications, Special Provisions, and Contract Documents for the above described project, and shall be subject to all applicable requirements thereunder, as if originally shown and/or specified. Acknowledgement of this addendum is required on page P-2 of your proposal. The Contract Documents are revised as described in the Attachments.
Yvetteh Ortiz, P.E. Public Works Director / City Engineer
Attachments:
Addendum No. 1 Written Narrative Addendum No. 1 Plans Addendum No. 1 Specification Sections
ADDENDUM
Addendum No. 1
Addendum No. (1)
November 1, 2017
To all bidders for furnishing all labor and materials necessary and requires for constructing: City of El Cerrito
El Cerrito Swim Center Locker Rooms / Pool Equipment Room - Upgrades and Renovations
7007 Moeser Lane El Cerrito, CA 94530
City Project Number C3050.4
This addendum forms a part of the Contract Documents and modifies the original Bidding Documents dated October 9, 2017 and Addendum No.1, dated November 1, 2017, as noted below. Acknowledge all addenda in the space provided on the Bid Form. Failure to do so may subject Bidder to disqualification.
REVISIONS TO PRIOR ADDENDA:
1. Not Applicable – no previous addenda issued.
REVISIONS TO BIDDING REQUIREMENTS:
1. Notice to Bidders, Sheet I -2, paragraph 9; add a second sentence, “Lump Sum allowances described insection 012100 shall be included in the contractor’s schedule of values”.
2. Proposal Bid Sheet, Sheet P-1, Bid Additive Alternate Number One; Delete period at end of first sentenceand add, ”,details 9 & 17 on sheet A-500, and details 1 & 2 on sheet S-113. Also reference SpecificationsSection 075216 “.
REVISIONS TO CONDITIONS OF THE CONTRACT:
1. None.
REVISIONS TO SPECIFICATIONS:
1. Section 000110 – Table of Contents;a. Page 1; Insert “Section 012100 – Allowances'''''''.1 – 2”, after “Section 012000”.b. Page 2; Section 083323, delete this line item in its entirety.c. Page 2; Division 23; insert “Reference Section 15772'''..1 – 4”, above “Refer to Drawings”.
2. Add New Specification “Section 012100 – Allowances”.
3. Section 013000 – Administrative Requirements, Article 1.5 PROGRESS MEETINGS, – Paragraph A;Replace “bi-monthly” with “weekly”.
4. Section 083323 – Overhead Coiling Doors; Delete section in its entirety.
5. Section 081500 – Plastic Doors;
a. Article 2.1 MANUFACTURERS AND PRODUCTS – Paragraph A.1,i. At item a; Replace “SL-17” with “AF-100 smooth protruded all fiberglass door”.ii. At item b; Replace “SL-260” with “AF-150”.
El Cerrito Swim Center Addendum No.1 November 1st, 2017 Page 2 of 4
Addendum No. 1
b. Article 2.2 FIBERGLASS REINFORCED PLASTIC (FRP) FLUSH DOORS, NON-RATED –Paragraph A,
i. Item 1; shall be replaced by requirements of attached supplementary basis-of-designinformation, as required to achieve an all FRP finish, with no exposed aluminum parts.
ii. Item 2; rails and stiles materials as required by attached basis-of-design supplementaryinformation.
iii. Item 3; Edge Capping; change aluminum to “FRP”.iv. Item 6; Vision Lites and Louvers; change aluminum to “FRP”.
c. Article 2.3 TUBULAR ALUMINUM DOORS FRAMES; Revise to read “FIBERGLASS FRAMING”:i. Paragraph A; Delete “Tubular”, and replace with, “Fiberglass”.
1. Size; Insert the word “nominal” before dimensions given.2. Material; Replace Aluminum with ”Fiberglass” (see basis-of-design attachment for
more information).3. Perimeter Frame Members; Replace this paragraph with requirements of the basis-
of-design product information attached to this addendum.
d. Article 2.4 MATERIALS AND ACCESSORIES; Requirements of items A, B, C, F, and G shall besuperseded by requirements of basis-of-design product information attached to this addendum.
6. Section 087100 – Door Hardware;
a. Article 2.9 KEY SYSTEMS (CYLINDERS, CORES, AND KEYS) – Paragraph C:i. Item 1a; Delete “TBD”, and replace with, “Existing building site standard, no substitutions,
Schlage Primus Level 3”.ii. Item 2a; Delete “TBD”, and replace with, “Primus Level 3 Patented Series”.
b. Article 3.6 HARDWARE SCHEDULE – Paragraph D.3;i. Hardware Group/Set #101:
1. Replace Deadboldt line item as follows:
2. At Permanent Core; replace “TBD” with “See Section 087100 Keying”.ii. Hardware Group/set #102:
1. At Permanent Core; replace “TBD” with “See Section 087100 Keying”.iii. Insert attached Hardware Group/set #103 before End of Section.
7. Section 096723 – Resinous Flooring;
a. Article 1.4 SUBMITTALS – Paragraph D, item 1, delete “12 inches x 12 inches” and replace with,“48 inches x 48 inches”.
b. Article 1.8 WARRANTY – Paragraph A, delete “one year from date of installation”, and replace with,“ten years from date of substantial completion”.
8. Cover Page, Division 23 – Heating Venting, and Air-Conditioning; add, “and following Reference Section15772”.
9. Insert “Reference Section 15772 – Radiant Heat Flooring” behind Division 23 cover sheet.
El Cerrito Swim Center Addendum No.1 November 1st, 2017 Page 3 of 4
Addendum No. 1
REVISIONS TO DRAWINGS:
1. Sheet G-001, Cover Sheet, Project Data, Project Data; Total Occupant Load has been revised to reflect onlythe total occupant load of the project, which only include the Men’s and Women’s locker rooms.
2. Sheet AS101, Existing Site Plan:
a. General Notes; add general Note “1. Any dumpster in the public right of way shall be from East BaySanitary Curbside Garbage Collection.”
b. Floor Plan Legend; Accessible Path of Travel is defined as, “48” clear width, maximum 5% runningslope and max 2% cross slope per CBC 11B-403”.
c. Existing Site Plan 1;i. The scope of work is clarified and revised where indicated to provide compliant parking in
accordance with CBC 11B-502.ii. Sheet Keynotes #9 added to show location of Occupant Load Sign.
d. Add Site Plan 2; new plan clarifies parking requirements as in accordance with CBC 11B.
3. Sheet A-111, Enlarged Floor Plans; refer to several clouded and referenced as “delta 1” for areas identifyingmiscellaneous changes to notes and plans on this sheet.
4. Sheet A - 211, Exterior Elevation & Schedule; add in right hand margin below Sheet Keynotes, “GeneralNotes, 1. Power wash all existing exterior walls before substantial completion of project is issued”.
5. Sheet A-500, Details;
a. Delete details 14, 15, 16, 18, 19, and 20 in their entirety.b. Details 10 and 11 revised to include “door on exterior side where occurs”, and Door Jambs are,
“FRP 2 Casing”.
6. Sheet A-582, Details – Accessibility; Detail 11 – Detectable Warnings has been revised.
7. Sheet A-521, Schedules / Diagram – Doors;a. Door Schedule, at Frames, Material columns; change all to “FRP”.b. Door Schedule, at Doors and Frames Finish columns; change all to “PU”, which is identified now in
legend as, “two-part polyurethane coating”.c. Door Schedule, door no. 134;
i. Revise width from 5’-4” to, “pair 3’-4” x 1’-8”.”ii. Revise material from aluminum to, “FRP”.iii. Revise head detail to “10/A-500 similar”.iv. Revise jamb detail to “11/A-500 similar”.v. Revise door type from “D01” to “DD2”.
d. Door Schedule, door no. 135;i. Revise width from 6’-0” to, “pair 4’-0” x 1’-8”.”ii. Revise material from aluminum to, “FRP”.iii. Revise head detail to “10/A-500 similar”.iv. Revise jamb detail to “11/A-500 similar”.v. Revise door type from “D01” to “DD2”.
e. Door Types; Door Type D01 is revised to “DD2”, to show a pair of swing hinge doors with louvers.
8. Sheet S-011, Structural Testing and Inspection; Delete this section in its entirety.
9. Sheet P-112, Enlarged Plumbing Demolition Floor Plan – Chemical Rooms, Detail 1, Demolition SheetNotes; Delete sheet note #1 in its entirety and replace with:
El Cerrito Swim Center Addendum No.1 November 1st, 2017 Page 4 of 4
Addendum No. 1
“Room 134: Empty Chlorine Tank and coordinate Chlorine Liquid removal with Knorr Systems (925) 273-0722. Remove Chlorine Tank, Tank Straps, and all connected piping, components and tubing. Securely store Chlorine Tank, Tank Straps, Piping, and all components for re-use.
Room 135: Empty Acid Tank and coordinate Acid Liquid Removal with Knorr Systems (925) 273-0722. Remove Acid Tank, and discard Tank and straps per local Environmental Health Department requirements. Remove and securely store all connected piping, components, and tubing for re-use in
new 350-gallon tank.”
10. Sheet P-112, Enlarged Plumbing Demolition Floor Plan – Chemical Rooms, Detail 2, Demolition Sheet Notes; Delete sheet note #1 in its entirety and replace with:
“Room 134: Clean and re-install Chlorine Tanks, Tank Straps, Piping, and tubing. Seal all tubing and piping connections air tight.
Room 135: Install new 350 gallon Acid Tank (provided by Owner), new straps, and all existing piping, components, and tubing. Seal all tubing and piping connections airtight.”
11. Sheet P0.1, Plumbing Legend, Notes, and Schedules, a. Swimming Pool Equipment Schedule, Tank T-1; Revise gallons to read, “350 gallons”, (all other
accessories remain the same). b. Plumbing Fixture Specification Schedule & Connection Schedule, Symbol SH-1, at column for
fixture manufacturer and model no.; revise to read, “Acorn Model 700HC-7-4-2-B11-F-K-ZZ-BS Column Shower 4 heads”, (see cut sheet attached to this addendum for more information).
12. Sheet M-112, Enlarged Mechanical Floor Plan - Detail 2; At column Line 16, existing boiler flues, revise
detail reference from “2/M0.2” to: “2/M0.1”.
13. Sheet M0.1, Legend, Notes, and Details; Revise detail 2/ M0.2 per the attached Detail 2/M0.2 and add Detail 3/M0.1.
END OF ADDENDUM
Lionakis No. 016336 01 21 00 November 1, 2017 Allowances Page 1
SECTION 01 21 00
ALLOWANCES COORDINATE WITH BID PROPOSAL FORM
PART 1 GENERAL
1.1 SECTION INCLUDES
A. Cash Allowances.
B. Submission procedures.
1.2 RELATED SECTIONS
A. Section 09 30 00 – Tiling.
B. Section 09 65 00 – Resilient Flooring.
C. Reference Section 15772 – Radiant Heat Flooring.
1.3 REQUIREMENTS
A. The purpose of cash allowances is intended to provide adequate budget and bonding to cover cost of items not precisely determined by Owner prior to bidding. Allow with the Contract Sum the amounts described in this Section.
B. Costs Included in Cash Allowances: Cost of product to Contractor or subcontractor, less applicable trade discounts; delivery to site and applicable taxes.
C. Costs Not Included in Cash Allowances but included in the Contract Sum: Product handling at the site, including unloading, uncrating, and storage; protection of products from elements and from damage; labor for installation, and finishing; and all accessories necessary to complete the job not listed in the description of the allowance.
D. Architect Responsibilities:
1. Consult with Contractor for consideration and selection of products.
2. Select products and estimate cost of repairs in consultation with Owner and transmit decision to Contractor.
3. Prepare Change Order, Construction Change Directive, or Architect’s Supplementary Instruction, if necessary.
E. Contractor Responsibilities:
1. Assist Architect in selection of products, suppliers and installers.
2. Present cost proposals from three suppliers and installers and offer recommendations.
3. On notification of selection by Architect, Owner will execute purchase agreement with designated supplier.
4. Promptly inspect products upon delivery for completeness, damage and defects. Submit requests for transportation damage.
5. Determine the quantity of product or material required to complete the job.
01 21 00 Lionakis No. 016336 Allowances November 1, 2017 Page 2
F. Product descriptions given in the specific specification Sections and listed below are given for reference to describe the type of product that may be selected.
1.4 ALLOWANCE SCHEDULE
A. Section 09 30 00, Ceramic Wall Tile; Grout joint repair – Include cost per square foot for re-grout of all existing wall tile area in need of repair (that are otherwise not called out to be removed) when submitting repair proposal. Allowance total for project is $7,500.
B. Reference Section 15772, Radiant Heat Flooring; include a per reconnection cost when submitting repair proposal. Cost should be for labor to make reconnection, tubing material, and testing. Allowance total for project is $10,000.
1.5 VERIFICATION OF QUANTITIES
A. Contractor will submit a list of quantities estimated for each unit price towards allowances listed above at the time of submittal, for the schedule of values. This does not relieve Contractor of responsibility for all quantities and takeoffs.
PART 2 PRODUCTS
Not Used
PART 3 EXECUTION
Not Used
END OF SECTION
El Cerrito Swim Center - Addendum No. 1Use clouded information for bidding purposes in lieuof Spec section 08 15 00, Articles 2.2, 2.3, and 2.4.
Hardware is specified under section 08 71 00.
Basis of Design for FRP Framesand Doors - Specification Section081500 - El Cerrito Swim Center
08 71 00 Lionakis No. 016336 Door Hardware May 26, 2017 Page 20
required (type/quantity as required by locking device)1 Ea. Permanent Core 20-740 626 SC NOTE 1: For doors/openings assigned this hardware group/set, the cylinder is for unit-type pricing. At each opening assigned this hardware group/set, provide final keying as required per locking and/or key control devices (examples include but are not limited to Coiling Door locking devices and/or control switches that activate or control the on/off switches). NOTE 2: Furnish all devices & components for hardware groups/set above in accordance with Contract Documents (including but not limited to notes below, additional hardware devices requirements in the above specification language, architectural plans & full specification documents).
Hardware Group/Set #104 2 Ea. Continuous Hinge FM300 630 MA 2 Ea. Manual Flush Bolts 3917 626/
630 TR
1 Ea. Dust Proof Strike #3911 626 TR 1 Ea. Storeroom-Type Lock L9080T X 17A 630 SC 1 Ea. Permanent Core 20-740 (see Section 08 71 00 keying) 626 SC 2 Ea. Overhead Stops 9ADJ (-326 or size as required per door width x
90 degree hold-open/stop position) 630 TR
1 Ea. Weatherstripping Provide seals at head & jambs: - If frame is hollow metal, furnish S88D seals (head &
jambs) by Pemko or approved seal manufacturer. - If frame is aluminum, then seals are to be furnished by
aluminum frame manufacturer 2 Ea. Sweep 315CN (installed on pull side of doors) by Pemko or
approved manufacturer. 1 Ea. Astragal 355CS by Pemko or approved manufacturer. NOTE 1: Egress door application (free egress at all times). NOTE 2: Furnish and install all devices and components for hardware groups/set above in accordance with Contract Documents (including but not limited to additional hardware devices required in specifications language above, architectural plans and full specification documents).
END OF SECTION
El Cerrito Swim Center RADIANT HEATING PIPING NTD# 2001-0155 15772 - 1
SECTION 15772 - RADIANT HEATING PIPING
PART 1 - GENERAL
1.1 SUMMARY
A. This Section includes radiant heating piping, including pipes, manifolds, fittings, and piping specialties.
B. See Division 15 Section "Hydronic Piping" for pipes and connections to hydronic systems.
1.2 SUBMITTALS
A. Product Data: Radiant heating piping specialties, including rated capacities and water flow and pressure drops of selected models.
B. Shop Drawings: Show piping layout and details drawn to scale, including valves, manifolds, controls, and support assemblies and their attachments to the building structure.
C. Operation and maintenance data.
1.3 COORDINATION
A. Coordinate layout and installation of radiant heating piping and suspension system with building and structural components.
B. Coordinate size and location of access panels to allow access to manifolds concealed in ceilings, walls, and floors.
C. Coordinate thickening of slabs where required for adequate encasement of radiant heating piping components.
D. Revise locations and elevations from those indicated as required to suit field conditions and ensure integrity of piping and as approved by Architect.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
B. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. Distribution Manifolds:
a. Watts Radiant
b. Heatlink USA Inc.
c. Heatway, Inc.
d. Hume Snow Melting Systems, Inc.
Reference for Allowance Item B
El Cerrito Swim Center RADIANT HEATING PIPING NTD# 2001-0155 15772 - 2
e. Infloor Heating Systems.
f. Rehau Inc.
g. Tekmar Control Systems, Ltd.
h. Vanguard Plastics, Inc.
i. Wirsbo Co.
2. Mixing Valves:
a. Watts Radiant
b. Heatlink USA Inc.
c. Infloor Heating Systems.
d. Rehau Inc.
e. Wirsbo Co.
3. Controls:
a. Watts Radiant
b. Heatlink USA Inc.
c. Hume Snow Melting Systems, Inc.
d. Infloor Heating Systems.
e. Tekmar Control Systems, Ltd.
f. Wirsbo Co.
4. Thermostats:
a. Watts Radiant
b. Heatlink USA Inc.
c. Infloor Heating Systems.
d. Rehau Inc.
e. Tekmar Control Systems, Ltd.
f. Wirsbo Co.
El Cerrito Swim Center RADIANT HEATING PIPING NTD# 2001-0155 15772 - 3
2.2 HEAT-TRANSFER PIPES AND FITTINGS
A. PE Plastic: ASTM D 2239, SIDR-11.5 for service at 30 psig (210 kPa) and 140 deg F (60 deg C).
1. Fittings: ASTM F 1807, copper with stainless-steel clamps.
B. PEX Plastic: ASTM F 876.
1. Fittings: ASTM F 1807, [copper or brass compression] [copper crimping] type.
C. Single-Tube Rubber Hose: Braided-fiber-reinforced, EPDM elastomeric with extra carbon steel with high-temperature, oxygen-barrier cover; for service at 100 psig (690 kPa) and 210 deg F (99 deg C).
1. Fittings: ASTM F 1807, copper with stainless-steel crimps or clamps.
2.3 PIPING SPECIALTIES
A. Radiant-Pipe Mounting Tracks: Aluminum, with pipe supports permitting pipe spacing at [2-inch (50-mm)] <Insert spacing> intervals.
2.4 RADIANT HEATING SPECIALTIES
A. Distribution Manifolds: Brass modular design with three mixing valve, main shutoff and balancing valves with thermometers, zone shutoff and balancing valves with flow meter, and identification plate.
1. Mixing Valves: 125 psig (862 kPa), 230 deg F (110 deg C) maximum operating pressure and temperature, brass or cast-bronze body, EPDM seals, and threaded connections.
2. Identification Plate: Valve plate shall identify room served and loop number.
3. If more than one loop serves a room, provide identification plates on manifolds to identify rooms served.
2.5 CONTROLS
A. Thermostats: 32 to 160 deg F (0 to 71 deg C), 3 position, 24 V for day and night setback and clock program.
B. Radiant Heating Control Sequence: Flow-through radiant heating piping is modulated to satisfy space thermostat.
PART 3 - EXECUTION
3.1 HEAT-TRANSFER PIPING INSTALLATION
A. Install piping downstream from manifolds without joints.
B. Secure piping in concrete floors by attaching pipes to concrete reinforcement using plastic tie straps.
El Cerrito Swim Center RADIANT HEATING PIPING NTD# 2001-0155 15772 - 4
1. Install a sleeve of foam-type insulation around tubing and extending for a minimum of 6 inches (75 mm) on each side of the slab penetration to protect the tubing passing through expansion joints.
C. Install manifolds in accessible locations.
D. Fill system with 30 percent of ethylene glycol-to-water solution.
3.2 FIELD QUALITY CONTROL
A. Test Preparation:
1. Temporarily restrain expansion joints so they are not damaged due to test pressure. If temporary restraints are impractical, isolate expansion joints from testing.
2. Flush with clean water, and clean strainers.
3. Install relief valve set at a pressure no more than one-third higher than test pressure.
B. Tests:
1. Subject piping to hydrostatic test pressure that is not less than 1.5 times the design pressure but not more than 100 psig (690 kPa).
2. After hydrostatic test pressure has been applied, examine piping, joints, and connections for leakage. Eliminate leaks by tightening, repairing, or replacing components, and repeat hydrostatic test until there are no leaks.
3. Prepare a written report of testing.
END OF SECTION 15772
Acorn Engineering Co. • 15125 Proctor Ave. • P.O. Box 3527 • City of Industry, CA 91744-0527 U.S.A.
Tel: (800)488-8999 • (626) 336-4561 • (626) 961-2200 • www.acorneng.com • E-mail: [email protected]
Page 1
Fixture May Show Some Available Options
Handicap Capital Column Showers Two to Six Station Models - Non ADA Compliant
Handicap Capital Column Showers Two to Six Station Models - Non ADA CompliantColumn Shower is heavy gage, type 304 stainless steel with satin finish. Column showers are completely pre-piped to the valve, showerhead, and optional soap system. All Column Showers are hydrostatically tested to 150 PSI.
Handicap Station is located at Station #1 and includes a lever handle diverter valve for hand shower and fixed upper head. Hand shower includes 60" long stainless steel hose and mounting bracket. Diverter valve is located at 48" above the floor (6'-0" discharge). Handicap station includes welded vertical 24" grab bar. Shower does not conform with ADA Accessibility Guidelines.
Showerheads are solid brass, triple chrome-plated and include a 2.2 GPM flow restrictor (not available in California, see Showerhead Options for alternate choices). The Acorn Logan Wizard Showerhead design provides self-cleaning with every use, and has an adjustable spray pattern from a coarse stream to a fine mist.
Bronze Manifolds and valve bodies are used for long life and maximum corrosion protection in all Column Showers. Fittings for connecting to 3/4" NCT inlets are furnished by others.
Control Valve type is indicated by selected Capital model number. All valves have replaceable cartridges, which contain all wearing parts and are serviced from the face of the shower for easy maintenance. Valve is tamper-resistant with an easy to close mechanism and low leverage handle to protect the operating parts from excessive torque. Control valve at handicap station includes lever handle when applicable. Note: Air-Control and Electronic Valves (-MVC, -EVS) must be located remotely or positioned above unit within -SC Supply Cover. Refer to appropriate factory installation detail for additional information.
Circular Soap Tray is furnished standard, except when Diana compartments are used. Built-in Liquid Soap is optional.
Drain Base is cast iron with a rust preventative coating, and provides a secure mounting for the column. If a separate or area drain is to be utilized, an Acorn drain base may be installed to provide column anchoring only or column may be mounted directly to floor. Option -LD Less Drain Slots is recommended on these types of installations.
Fasteners. Acorn furnishes all exposed tamper-resistant fasteners necessary to complete the on-site shower assembly installation; however, supply cover ceiling fasteners are not furnished.
GUIDE SPECIFICATION
Provide and install Acorn Handicap Capital Column Showers (specify model number and options). Column shall be 16 gage, type 304 stainless steel with satin finish. Column shall be factory pre-piped and hydrostatically tested to 150 PSI. Drain base shall be heavy cast iron with a rust preventative coating. Provide handicap station complete with diverter valve, fixed upper head, handshower and vertical grab bar. Showerhead discharge height shall be (specify). Shower shall be provided with the following optional equipment: (example -GG Unit Shutoff Valve). Installation shall be made in accordance with manufacturer's recommendations and details.
S.700HC
® Shower-Ware 700HC Series
745-HC-B21-LD
Please visit www.acorneng.com for most current specifications.
Revised: 08/09/17
Acorn Engineering Co. • 15125 Proctor Ave. • P.O. Box 3527 • City of Industry, CA 91744-0527 U.S.A.
Tel: (800)488-8999 • (626) 336-4561 • (626) 961-2200 • www.acorneng.com • E-mail: [email protected]
Page 2
Selection Summary
Model No. & Option___________________________
Quantity____________________________________
Approved for Manufacturing
Company__________________Title______________
Signature_________________ Date______________
Important: Installation instructions and current rough-in are furnished with each fixture. Do not rough in without certified dimensions.Dimensions are subject to manufacturer’s tolerance of plus or minus 1/4" and change without notice. Acorn assumes no responsibility for use of void or superseded data. © Copyright 2006 Acorn Engineering Company
S.700HC Revised: 08/09/17
®Shower-Ware : 700HC Handicap Capital Column Showers - Non ADA Compliant
MODEL# 745HC-B11
Handicap Station with Optional
Handicap Station Diverter Valve
Handicap Station Hand Shower
Fixed Conventional Showerhead
NOTES:
Canopy Control Handle shown
Optional B-11 Drain Base w/
Stainless Steel Grab Bar
Optional -SC Supply Cover
MODEL# 745HC-T21-SC
4-
3-
2-
1-
6-
9-
10-
5-
Dome Grate Shown
Flo-Cloz Valve & Lever Handle
with Lever Handle
Shown
Access Cover7-
Circular Soap Tray (Not Available8-
with Diana Privacy Compartments)
with 60" Flex Hose
1
2
3
5
4
8
7 6
9
10
9
8
7
312"
(89)
718"
(181)
24"(610)
48"(1219)
OR LESS
Acorn Engineering Co. • 15125 Proctor Ave. • P.O. Box 3527 • City of Industry, CA 91744-0527 U.S.A.
Tel: (800)488-8999 • (626) 336-4561 • (626) 961-2200 • www.acorneng.com • E-mail: [email protected]
Page 3
Selection Summary
Model No. & Option___________________________
Quantity____________________________________
Approved for Manufacturing
Company__________________Title______________
Signature_________________ Date______________
Important: Installation instructions and current rough-in are furnished with each fixture. Do not rough in without certified dimensions.Dimensions are subject to manufacturer’s tolerance of plus or minus 1/4" and change without notice. Acorn assumes no responsibility for use of void or superseded data. © Copyright 2006 Acorn Engineering Company
S.700HC
®Shower-Ware : 700HC Handicap Capital Column Showers - Non ADA Compliant
Showerhead Discharge Height (Not Part of Model Number)o 6'-0" o 5'-6" o 5'-0" o Other (Specify) __________
MODEL NUMBER AND OPTIONS SELECTION
SERIES (Must Specify)-7 Handicap Capital
NUMBER OF STATIONS (Must Specify)o 2 o 3 o 4 o 5 o 6
VALVE (Must Specify)-0 Electronic Valves, Single Temp. Metering
(Requires -SC Supply Cover or -VC Valve Cover)-5 Flo-Cloz, Single Temperature-6 Air-Control, Single Temperature Metering
(Requires -SC Supply Cover or -VC Valve Cover)
ELECTRONIC VALVE SELECTION Master-Trol (Electronic)
-EVS1 Single Temp o -EVSP1 Single Temp, Piezo Button
Master-Trol PLUS (Electronic)
-MTP1 Single Temp o -MTPP1 Single Temp, Piezo Button
Time-Trol (Electronic)
-MVC1 Single Temp
Programmable (Electronic) w/9VDC Plug-In Transformer -PPZ1 Single Temp Programmable Piezo Button
SUPPLY BUILD (Must Specify) Supply
Top Supply
OPTIONAL DRAIN TYPE For Bottom Supply:
B11 B15 B21 B25
For Top Supply:T11 T15 T21 T25
o
o
o o
o
o
o
o
o Bottomo
o o o o
o o o o
o -2 Safti-Trol, H & C Pressure Balancing
®
®
®
3
Please visit for most current specifications.www.acorneng.com
Revised: 08/09/17
VALVE OPTIONS o -CI Cycle Interrupt for Time-Trol Valves
-GG Unit Shutoff Valve -LVR Lever Handle (-5 Valve)
o -TF Transformer, 120VAC to 24VAC (-MVC option only)
SHOWERHEAD OPTIONS o -F Flow Control
o 1.4 GPM o 1.6 GPM o 2.0 GPM (Not Available in California)
o -H Hand Volume Control o -K Allen Key Volume Control o -MSH Multi-Stream Showerhead o -P Penal Showerhead
-QD Quick Disconnect for Hand Showero -PSO Positive Shut-Off
o -Y Universal Ball Jointo -YY Lockable Universal Ball Jointo -Z Up-Down Ball Jointo -ZZ Lockable Up-Down Ball Joint
DRAIN OPTIONS-BDA Bradley Drain Adapter -FO 4" No-Hub Waste Outlet (B11, T11 drains) -IC 3" Inside Caulk Waste -LD Less Drain Slots (with B21 & T21 only) -TC Thermostatic Controller
(Available With Vent Off Drain Style Only)
PRODUCT OPTIONS-BS Built-in Liquid Soap System-CA Ceiling Anchor Plate for Supply Cover-CF Adjustable Column Flange -DS Diana Circular Privacy (See Diana Privacy Tab)-EG Enviro-Glaze Color, Specify ______________ -FS Foot Shower at One Station, Specify
Station # o 1 o 2 o 3 o 4 o 5 o 6 -LGB Less Grab Bar
o -MS Modular Privacy Compartments (See Diana Privacy Tab)
o -RD Recessed Soap Dish -SC Supply Cover, Ceiling Height __________
(Air-Control/Electronic Valves - Bottom Supply)-VC Valve Cover to Conceal Optional Air Control /
Electronic Valve &/or Thermostatic Controllerwith Bottom Supply (108” Min Ceiling Height)
o o
o
o o o o o
o o o o o o
o
o
o
Get Started www.mgispecbuilder.comConfigure products and create specs with ease.
5
A
6 7 8 9 10 11
D
4
4
66
7
7
7
10 10
ø 60" C
LEAR
ø 60"
CLEAR
1616
1
A-211
ø 60"
CLEAR
5
5 5
1919
20.1
20
48" MIN 30" MIN
7'-3"
ø 60" C
LEAR21
21
16
18
4'-2"
2222
17
17
17
17
17
17
17
1717
17
22
ø 60" C
LEAR
20.1
19
4'-0" MIN 30" MIN
7'-0"
23
18
WOMEN'S LOCKER
ROOM
MEN'S LOCKER
ROOM
MECHANICALROOM
15 15
127119
125
119
HALLWAY 127
HALLWAY
125
FAMILY
2'-8" CLR
9'-6"4'-0"
25
25
25
21
3'-0
" M
IN
EQEQ
21.121.121.121.121.1
22
21
21.121.1
21
21
21.121.1
21.121.121.121.121.1
21.1
25
25
27 27
RIDGE
RID
GE
RIDGE
RID
GE
RID
GE
RID
GE
RID
GE
RID
GE
RIDGE
RID
GE
RID
GE
RIDGE
RIDGE
RID
GE
RID
GE
RID
GE
RIDGE
RID
GE R
IDG
E
RID
GE
RID
GE
RIDGE
(E) TWO TIER LOCKERS(E) TWO TIER LOCKERS
25
15
(E) LAV
(E) LAV
28 TYP OF 10
28 TYP OF 10
28
19
1'-0"26
16
ø 60" C
LEAR
ø 6
0" C
LE
AR ø 6
0" CLEAR
ø 60" C
LEAR
S9
4'-0"
2'-6
"
4 7
4 7
16
5'-1"
5'-0
"
1'-9" 2'-6"
30 30
11
ACCESSIBLE LOCKERS
5% MIN LOCKERS REQUIRED TO BE ACCESSIBLE PER CBC 11B-225.2.1
WOMEN'S LOCKER ROOMTOTAL NUMBER OF LOCKERS 50
TOTAL NUMBER IF ACCESSIBLE WOMEN'S LOCKERS 3 (6%)
MEN'S LOCKER ROOM TOTAL NUMBER OF LOCKERS 54
TOTAL NUMBER OF ACCESSIBLE MEN'S LOCKERS 3 (5%)
1
CLE
AR
1'-6
" M
IN
CLE
AR
1'- 6
" M
IN
CLE
AR
1'-6
" M
IN
CLE
AR
1'-6
" M
IN
60"X60" LANDING EITHERSIDE OF DOOR MAY SLOPE2.08% MAX EA DIRECTION.TYPICAL ALL THREE DOORS
1
1'-0 1/2"
6" TYP2'-0"
6"
TY
P
TY
P
2'-3"
MA
X2
'-6
"
11
A
D
12 13 14 15 16
MECHANICAL DUCTTHIS AREA
134
CHEM
135
CHEM
135134134
1515
1
FLOOR PLAN LEGEND
-BEAD BLAST EXISTING CONRETE AREA
- HOOK @ 5' AFF
- HOOK @ 3' AFF
- NEW ELECTRICAL OUTLET (DUPLEX)
- AREAS NOT IN CONTRACT
GENERAL SHEET NOTES
1. GENERAL CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS AND NOTIFYTHE AOR OF CONFLICTS OR EXISTING CONDITIONS THAT WILL INTERFERE WITH INSTALLATION OFWORK AS SHOWN ON THESE DOCUMENTS.
1. DO NOT CLOSE OR OBSTRUCT EGRESS WIDTH TO EXITS.2. DO NOT DISTURB OR DISRUPT BUILDING FIRE OR LIFE SAFETY SYSTEMS WITHOUT 3 DAY PRIOR
WRITTEN NOTICE TO OWNER.3. ERECT AND MAINTAIN BARRIERS OR PARTITIONS TO PREVENT SPREAD OF DUST, ODORS, & NOISE TO
ADJOINING OCCUPIED SPACES. BARRIERS OR PARTITIONS SHALL BE INSTALLED PRIOR TODEMOLITION OF EXISTING WORK OR INSTALLATION OF ANY NEW WORK.
4. PROTECT EXISTING MATERIALS AND FINISHES THAT ARE NOT REQUIRED TO BE DEMOLISHED.REPAIR,PATCH AND REPLACE ANY DAMAGED MATERIALS TO MATCH NEW & EXISTING CONDITIONS.
5. DEMOLISH IN AN ORDERLY MANNER, PROTECT EXISTING SUPPORTING STRUCTURAL MEMBERS.6. REPAIR ANY AND ALL DAMAGED TILES IN THE FAMILY ROOM AND LOCKER ROOMS TO MATCH
EXISTING.7. REFER TO STRUCTURAL, MECHANICAL & ELECTRICAL FOR NEW AND DEMOLITION SCOPE OF WORK.
NORTHPLAN
A B
1 2 3 4 5
D
C
B
A
SHEET
TITLE
AGENCY
MANAGEMENT
ISSUED
PROJECT
SEAL
CONSULTANT
CLIENT PROJECT NO:
COPYRIGHT:
LIONAKIS PROJECT NO:
LIONAKIS 2015
IF T
HIS
SH
EE
T IS
NO
T 3
0"x
42",
IT
IS
A
RE
DU
CE
D P
RIN
T -
SC
ALE
AC
CO
RD
ING
LY
01/4
"1/2
"1"
2"
KEY PLAN
CLIENT
11/1
/2017 4
:58:2
7 P
MC
:\U
sers
\georg
e.w
illia
ms\D
ocum
ents
\016336_B
IM_A
-MA
ST
ER
_R
16_C
EN
TR
AL_georg
e.w
illia
ms.r
vt
A-111
ENLARGEDFLOOR PLANS
016336
C3050.4
CITY OF EL CERRITO
EL CERRITO SWIM CENTERLOCKER ROOMS / POOL
EQUIPMENT ROOMUPGRADES & RENOVATION
7007 MOESER LANEEL CERRITO, CA 94530
10890 SAN PABLO AVE, EL CERRITO CA
SCALE 1/4" = 1'-0"2ENLARGED LOCKER ROOM
SCALE 1/4" = 1'-0"1ENLARGED POOL ROOM
SHEET KEYNOTES
4 GRIND SURFACE OF EXISTING FLOOR TILE TO REMOVE GLAZE. REGRADE THE ENTIRE FLOOR WITHMORTAR BED IN THE MEN'S AND WOWEN'S LOCKER ROOMS WITH 2% MAXIMUM SLOPE IN ANYDIRECTION TO DIRECT WATER TOWARDS DRAINS PER DETAIL 10/A-572. MAINTAIN THE LOCATIONAND ELEVATION OF THE (E) RIDGES. INSTALL EPOXY FLOORING PER MANUFACTURER'SRECOMMENDATION.
5 ACCESSIBLE SHOWER SEAT PER DETAIL 12/A-581, 15/A-581, 16/A-581, BOBRICK B-918116 SERIES.
6 INSTALL SHOWER TOWERS; CONTROLS SHALL BE ACCESSIBLE IN ACCORDANCE WITH CBC11B-608.5.2.
7 REPAIR SUBSTRATE, WATER BARRIER,GROUT AND WALL TILE TO MATCH EXISTING AT ALLLOCATIONS WITH DAMAGED TILES.
10 WALL TILE ASSEMBLY PER SPECIFICATIONS.
15 FRP DOOR FRAME. PROVIDE DOOR HARDWARE PER SPECIFICATIONS.
16 INSTALL LAVATORY. PROVIDE 2X6 BACKING FOR ANCHORAGE. SEE NOTE 8 ON SHEET P-111.
17 TRENCH DRAINS AND COVER: INSTALL TRENCH DRAIN AND COVER FLUSH WITH RESINOUSFLOORING. SEE DETAIL 12/A-500.
18 REPLACE DAMAGED WOOD STUDS AS NECESSARY. PROVIDE BLOCKING BETWEEN STUDS FORSUPPORT OF ACCESSIBLE SHOWER SEAT (DETAIL 16/A-581) AND GRAB BARS. INSTALL 5/8"MOISTURE RESISTANT GYP BD. INSTALL WALL TILE (MATCH EXISTING). REINSTALL GRAB BARS.
19 TOILET PARTITIONS, ANCHOR TO WALL PER MANUFACTURER'S RECOMMENDATION.
20 WALL MOUNTED BENCH PER DETAIL 4/A-500.
20.1 WALL MOUNTED ACCESSIBLE BENCH PER DETAIL 4/A-500.
21 TWO TIER 15"W X 18"D LOCKERS, OVER EXISTING HOUSEKEEPING PAD PER DETAIL 20/A-572.BOTTOM LOCKER ACCESSIBLE.
21.1 TWO TIER 15"W X 18"D LOCKERS OVER EXISTING HOUSEKEEPING PAD PER DETAIL 20/A-572.
22 FLOOR MOUNTED ACCESSIBLE BENCH PER DETAIL 3/A-500.
23 EXISTING ACCESSIBLE DRINKING FOUNTAIN.
25 INSTALL EPOXY FLOORING PER MANUFACTURER'S RECOMMENDATION ON EXPOSED SURFACES OFCONCRETE HOUSEKEEPING PAD .
26 ADD 36"W x 12"D COUNTER 34" AFF PER DETAIL 18/A-572.
27 INSTALL 48" LONG GRAB BAR VERTICALLY 24" AFF. PRVIDE BLOCKING BETWEEN STUDS.
28 INSTALL TOWEL HOOKS-SEE HEIGHTS UNDER FLOOR PLAN LEGEND.
30 OCCUPANT LOAD SIGN. SEE DETAIL 10/A-582. OCCUPANT LOAD FOR BOTH THE WOMEN'S LOCKERROOM AND MEN'S LOCKER ROOM IS 23.
S9 MINIMUM 5% OF THE LOCKERS TO BE ACCESSIBLE PER CBC 11B-225.2.1; SEE DETAIL 4/A-581.
101 Montgomery Street, Suite 500San Francisco CA 94104P 415.777.4811 F 415.777.4523www.lionakis.com
C27466
LIC
ENSED A
T
RCHITEC
R 9E N. 0 - 31 - 1
S
ATA
TE
O F C A L I F O
RN
I
7
NITRAM.DLUAP
MARK DATE DESCRIPTION
08/08/2017 SUBMIT FOR PERMIT
10/09/2017 BID SET
1 11/01/2017 ADDENDUM #1
1
1
1
6".1".
REMOVE EXISTING METALFLASHING AND INSTALL NEWMETAL FLASHING & DRIP.PRIME AND PAINT TO MATCHEXISTING.
REINSTALL 3 PLY BUILT-UP ROOFMEMBRANE TO MATCH EXISTING
(E) GUTTER
REMOVE PORTION OF EXISTINGPLASTER AND CLAY BRICKVENEER ACCENT BAND TOACCOMMODATE NEW WORK.REPLACE TO MATCH EXISTING
PLASTER ASSEMBLYTO MATCH EXISTING.
CERAMIC TILES
MITRED END ALUM "F" MOLD
WATERPROOFING MEMBRANEO/ EXISTING CMU
EXTERIOR
INTERIOR
4'-0" ALONG GRID C (VIF)
5'-3" ALONG GRID D (VIF)
6".
6". 3 PLY BUILT-UP ROOF MEMBRANETO MATCH EXISTING
METAL FLASHINGAND DRIP. PRIMEAND PAINT TOMATCH EXISTING
METAL FLASHING ANDDRIP. PRIME AND PAINTTO MATCH EXISTING
1".
(E) GUTTER
1/2" MINIMUM THICKNESSTAPERED COMPOSITIONINSULATION BOARD
2x4 REDWOOD TRIMRIPPED TO SIZE
NOTES:
1. REPLACE ANY DETERIORATED MEMBERS TO MATCH EXISTING.2. SEE 1 & 5/S-113 FOR ADDITIONAL INFORMATION
2x6 T&G DECKING TOMATCH EXISTING
6".
8".
AT 4' SLOPE IS APPROX. 1.9 DEG
DOOR HEAD FRP2" CASING
(E) CMU LINTELCOURSE
CONTINUOUS BEADSEALANT ANDBACKER ROD
SHIM AS REQUIRED
METAL FLASHING,PRIME AND PAINT
"J" MOLD
PLASTER, MATCHEXISTING
3/8" DIA x 2-5/8"EMBED STAINLESSSTEEL EXPANSIONANCHORS @ 16" OCCENTERED ATWALL
FRP DOOR
EXTERIOR INTERIOR
1
DOOR JAMB FRP2" CASING
(E) CMU LINTELCOURSE
CONTINUOUS BEADSEALANT ANDBACKER ROD
SHIM AS REQUIRED
"J" MOLD
PLASTER, MATCHEXISTING
3/8" DIA x 2-5/8" EMBED STAINLESSSTEEL EXPANSION ANCHORS @ 16"OC CENTERED AT WALL
FRP DOOR
INTERIOR
EXTERIOR
1
FRP DOOR WHEREINTERIOR DOOR OCCURS
(E) CMU WALLASSEMBLY
(E) 2x10 SILL
(E) 6x10 OUTRIGGERBEYOND
(E) 2x6 T&GDECKING
(E) INSECTSCREEN
CONTINUOUS BEAD SEALANTAND BACKER ROD
MITRED END ALUM "F" MOLD
CERAMIC TILE ASSEMBLY
WATERPROOFINGMEMBRANE O/ EXISTING CMU
EXTERIOR INTERIOR
3/8"
FF
MITRED ENDALUM "F" MOLD
CERAMIC TILEASSEMBLY
WATERPROOFINGMEMBRANE O/EXISTING CMU
3/16" WEEPHOLES @ 6"OC
EXTERIOR INTERIOR
(E)
(E)
(E)
(E)
(E)
(E)
ALUMINUM FRAMEBEYOND
THRESHOLD
FLOOR FINISH
1/4" DIA ANCHOR W/DTEEL EXPANSIONSHIELD
EXTERIORINTERIOR
SLOPE 0.0%MAX
SLOPE 2.08%MAX
EXTERIOR INTERIOR
1/4" SOLID CORIANSURFACE O/ 3/4" MARINEPLYWOOD PRIMED. PAINTEXPOSED SURFACES;SLIP RESISTANT
17"
- 19"
EPOXY FLOORINGO/ CONC SLAB
(E) CERAMIC TILEFINISH
(E) CMU WALL
(E) CEMENT PLASTER
BRACKET BY WBMANUFACTURING WALLMOUNT BRACKET @ 16" OC.
#8 GALVANIZED FH SCREWS
SEE NOTE
NOTE:1. 20" FOR ACCESSIBLE BENCH (BKT0812)2. 15" AT NON-ACCESSIBLE BENCH (BKT1218-B)
(2) 3/8" DIA x 2-5/8" EMBEDSTAINLESS STEELEXPANSION ANCHORS @ EABRACKET
RESINOUS FLOORING,SEE SPECIFICATIONS
EXISTING
EXISTING
EXISTING
SEE PLUMBINGDRAWINGS
2% MAX 2% MAX
1/4" SOLID CORIANSURFACE O/ 3/4"MARINE PLYWOODPRIMED. PAINTEXPOSED SURFACES;SLIP RESISTANT
EPOXYFLOORING
COUNTERSUNKSTAINLESS STEELFH SCREWS @ 6"OC
95°
1"
1".
1'-8"
2x2x1/8 STAINLESS STEELTUBE FRAME @ 24" OCMAX AND 5" FROMCENTERLINE OF FRAMETO EDGE OF SEAT,PRIME AND PAINT
3/16
(2) 3/8 DIA "HILTI" HIS-NSTAINLESS STEELINSERT W/ "HILTI" HIT-RE500 V3 W/ BUTTON HEADBOLTS CENTERED ATTUBE AT EACH TUBEFRAME (ICC ESR-3814)
18".
TYPICAL ALL EDGES
NON SHRINKGROUT
(E) 6" MINCONC SLAB
18".
1'-0" 1 1/2"1 1/2"
1/8TYP
(1/8)TYP
(1/8)
END PL TOHSS. ROUND &GRINDSMOOTH ALLCORNERS, TYP
(1/8)PJP, (3) SIDES
MITER CORNER
1/2" MIN
NOTES:1. GRIND SMOOTH ALL ARCHITECTURALLY EXPOSED WELDED CONNECTIONS
1/8" END PL, TYP
5"
RESINOUS FLOORINGSUBSTRATE
REMOVE (E) 2X6SLEEPER AND FILL VOIDWITH NON-SHRINKGROUT
RESINOUS FLOORING
(E) MORTAR BED
(E) CONCRETE
(E) CERAMIC TILE
(E) WALL
1 2 3 4 5
D
C
B
A
SHEET
TITLE
AGENCY
MANAGEMENT
ISSUED
PROJECT
SEAL
CONSULTANT
CLIENT PROJECT NO:
COPYRIGHT:
LIONAKIS PROJECT NO:
LIONAKIS 2015
IF T
HIS
SH
EE
T IS
NO
T 3
0"x
42",
IT
IS
A
RE
DU
CE
D P
RIN
T -
SC
ALE
AC
CO
RD
ING
LY
01/4
"1/2
"1"
2"
CLIENT
11/1
/2017 5
:16:1
8 P
MC
:\U
sers
\Jim
my.v
o\D
ocum
ents
\016336_B
IM_A
-MA
ST
ER
_R
16_C
EN
TR
AL_Jim
my.v
o.r
vt
A-500
DETAILS
016336
C3050.4
CITY OF EL CERRITO
EL CERRITO SWIM CENTERLOCKER ROOMS / POOL
EQUIPMENT ROOMUPGRADES & RENOVATION
7007 MOESER LANEEL CERRITO, CA 94530
10890 SAN PABLO AVE, EL CERRITO CA
NTS17
(E) COVERED TRELLIS FLASHINGMODIFICATION
101 Montgomery Street, Suite 500San Francisco CA 94104P 415.777.4811 F 415.777.4523www.lionakis.com
SCALE 3" = 1'-0"6PLASTER - TILE REVEAL
SCALE 3" = 1'-0"9
(E) UNCOVERED TRELLIS MODIFICATION -BID ADD ALTERNATE NO.1
SCALE 3" = 1'-0"10ALUMINUM DOOR FRAME - HEAD
SCALE 3" = 1'-0"11ALUMINUM DOOR FRAME - JAMB
SCALE 3" = 1'-0"5HEAD @ CERAMIC TILE ASSEMBLY
SCALE 3" = 1'-0"7SILL @ CERAMIC TILE ASSEMBLY
NTS8THRESHOLD DETAIL
SCALE 3" = 1'-0"4BENCH
NTS12TRENCH DETAIL
SCALE 3" = 1'-0"3BENCH - FLOOR MOUNTED
SCALE 1 1/2" = 1'-0"1
MODIFICATIONS @ EXPOSEDHOUSEKEEPING PADS
C27466
LIC
ENSED A
T
RCHITEC
R 9E N. 0 - 31 - 1
S
ATA
TE
O F C A L I F O
RN
I
7
NITRAM.DLUAP
MARK DATE DESCRIPTION
08/08/2017 SUBMIT FOR PERMIT
10/09/2017 BID SET
1 11/01/2017 ADDENDUM #1
- BID ADD ALTERNATE NO.1
1
- BID ADD ALTERNATE NO.1
11
Q2
TOILET ROOM DOOR SIGNAGEAE_G_0570_001
150901.
3/8
"-1/2
"
1/32" RAISED TEXTAT WALL SIGN
1/8" BACKPLATEAT WALL SIGN
CONTRACTED GRADE 2BRAILLE AT WALL SIGN
1/4" BACKING AT DOORSIGN FOR EACH CIRCLEAND TRIANGLE
60" AFF MAXBOT OF
HIGHEST LINEOF RAISED
CHARACTERS
48" AFF MINBOT OF LOWESTLINE OF BRAILLE
A-582
15
CL
EQ EQ
A-582
13CHARACTERS AND BRAILLE PER TYP
Q2
RESTROOM SIGNAGEAE_G_0570_002
150901.
A-582
13CHARACTERS AND BRAILLE PER
FINISH FLOORA
6" 12
"
12"
6"
B
60"
AF
F
60"
AF
F
C
12"
6"
60"
AF
F
C OF DOORL
PROVIDE SIGNAGE PER: CBC 11B-703
SIGNAGE IS TO BE OF CONTRASTING COLOR FROM THE DOOR
TO MEET THE 2013 CALIFORNIA TITLE 24 CODE AND AMERICANS WITH DISABILITIES ACT, ACOMBINATION OF THE TWO FOLLOWING SIGNS ARE REQ'D FOR RESTROOM IDENTIFICATION:
FIRST SIGN REQUIREDTHE 12" CIRCLE DESIGNATES THE WOMEN'S RESTROOM, THE 12" EQUILATERAL TRIANGLEDESIGNATES THE MEN'S RESTROOM. A UNISEX RESTROOM IS DESIGNATED BY A 12" CIRCLE WITHA 1/4" THICK SOLID TRIANGLE SUPERIMPOSED ON IT. IF THE RESTROOM MEETS ACCESSIBILITYSTANDARDS. CENTERED SIGN 60" ABOVE THE FLOOR.
SECOND SIGN REQUIREDTHE SECOND SIGN REQUIRED IS A PERMANENT ROOM IDENTIFICATION SIGN.
MEN
D E F G H I
EDGE OF DOOR
9"
MIN
MENMENMEN
RESTROOMRESTROOM
WOMENWOMEN
WOMENWOMEN
RESTROOMRESTROOM
6"
9" MIN
A-582
18MOUNTING PER
REFER TO 9/A-582 FOR TEXT DESCRIPTOR LOCATION OF PICTOGRAMS.
60" A.F. F.48" A.F.F.
1 1/2" HIGH CHARACTERS
TAMPERPROOF SCREWS
MAXIMUM OCCUPANTLOADXXXX
BY ORDER OF THESTATE FIRE MARSHAL
2'-0" MIN
Q2
OCCUPANCY LOAD SIGNAE_G_0570_004
150901.
16"
MIN
NOTES:1. SIGN TO BE POSTED NEAR MAIN EXIT (CBC
1004.3), SEE SIGNAGE PLAN FOR LOCATIONSAND SIGN INFORMATION
2. VERIFY INFORMATION FROM ARCHITECT PRIORTO SIGN FABRICATION
3. OCCUPANT LOAD DETERMINED FROM THE LIFESAFETY EXITING PLAN SHEET
Q2
TACTILE EXIT SIGNAGEAE_G_0570_006
150901.
EXIT
ILLUMINATED EXIT SIGN, IF REQD,SEE RCP & ELEC DWGS
A-582
13CHARACTERS AND BRAILLE PER
A-582
2
TYP
4'-0" TYP
Q2
BUILDING ENTRY SIGNAGEAE_G_0570_005
150901.
6"
6"
SIGN, EXTERIOR
ALTERNATELOCATION
INTERNATIONALSIGN OFACCESSIBILITY
4'-0" TYP
LOCATE AT MAIN ENTRY DOOR(S)
SIDELITE, WHENAPPLICABLE
NOTES:1. THE INTERNATIONAL SYMBOL OF ACCESSIBILITY IS TO BE PROVIDED AT ALL ACCESSIBLE
ENTRANCE DOORS.2. ENTRANCES THAT ARE NOT ACCESSIBLE SHALL HAVE SIGNAGE INDICATING DIRECTION TO
THE NEAREST ACCESSIBLE ENTRANCE.3. THESE LOCATIONS SHALL BE VERIFIED WITH THE ARCHITECT.4. NON GLARE CONTRASTING BACKGROUND DARK ON LIGHT OR LIGHT ON DARK.
ENTRANCE
Q2
ROOM ID SIGNAGEAE_G_0570_007
150901.
NOTES:1. VERIFY ROOM NAMES W/
ARCHITECT BEFOREFABRICATION
2. MOUNTED TO WALL PERSPECIFICATIONS
3. LEFT JUSTIFY CHARACTERSAND BRAILLE
AS REQUIRED
3"
MIN
A1ROOM IDENTITY
60" AFF MAXBOT OF HIGHEST
BASELINE OF RAISEDCHARACTERS
48" AFF MINBOT OF LOWEST
BASELINE OFBRAILLE
A-582
13CHARACTERS AND BRAILLE PER TYP
234
Q2
SIGNAGE FOR FUNCTIONALROOMS AND SPACES
AE_G_0570_008
150901.
CORRESPONDING BRAILLE
RAISED CHARACTERS(ROOM NAME AND NUMBER)
NOTES:
1. PERMANENT SIGNAGE TO BE INSTALLED ON THE WALL ADJACENT TO THE LATCHSIDE OF THE DOOR.
2. MOUNTING LOCATION MUST ALLOW A PERSON TO APPROACH WITHIN 3" OF SIGNAGEWITHOUT ENCOUNTERING PROTRUDING OBJECTS OR STANDING WITHIN THE SWINGPATH OF THE DOOR.
3. SIGNS AND IDENTIFICATION SHALL BE FIELD INSPECTED AFTER INSTALLATION ANDAPPROVED BY THE ENFORCING AGENCY, IN ACCORDANCE WITH SECTION 11B-703.1.1.2 "INSPECTION"
234
REQD
AS
9
A-582
3" MIN60" AFF MAXBOT OF HIGHESTLINE OF RAISEDCHARACTERS
48" AFF MINBOT OF LOWESTLINE OF BRAILLE
A-582
13CHARACTERS AND BRAILLE PER TYP
Q2
SIGNAGE LOCATIONAE_G_0570_022
150901.
45°
CL
18" MIN 18" X 18" MIN CLEAR FLOORSPACE TO BE PROVIDEDCENTERED ON SIGNAGE
NOTES:
1. WHERE A TACTILE SIGN IS PROVIDED AT DOOR, THE SIGN SHALL BE LOCATEDALONGSIDE THE DOOR AT EACH LATCH
2. WHERE A TACTILE SIGN IS PROVIDED AT DOUBLE DOORS WITH WITH ONE ACTIVELEAF, THE SIGN SHALL BE LOCATED ON THE INACTIVE LEAF
3. WHERE A TACTILE SIGN IS PROVIDED AT DOUBLE DOORS WITH TWO ACTIVE LEAFS,THEN THE SIGN SHALL BE LOCATED TO THE RIGHT OF THE RIGHT HAND DOOR
4. WHERE THERE IS NO WALL SPACE AT THE LATCH SIDE OF A SINGLE DOOR OR AT THERIGHT SIDE OF A DOUBLE DOOR, SIGNS SHALL BE LOCATED ON THE NEARESTADJACENT WALL
5. WHERE PERMANANT IDENTIFICATION SIGNAGE IS PROVIDED FOR ROOMS AND SPACESTHEY SHALL BE LOCATED ON THE APPROACH SIDE OF THE DOOR AS ONE ENTERSTHE ROOM OR SPACE
6. SIGNS THAT IDENTIFY EXITS SHALL BE LOCATED ON THE APPROACH SIDE OF THEDOOR AS ONE EXITS THE ROOM OR SPACE
7. TACTILE SIGNS TO BE MOUNTED AT 60" ABOVE THE FLOOR TO THE CENTER OF THESIGN PROVIDED THAT BASED ON THE SIGN CONTENT THE RAISED CHARACTERS ARE60" MAXIMUM TO THE BASELINE OF THE HIGHEST RAISED CHARACTER AND 48"MINIMUM TO THE BASELINEOF THE LOWEST RAISED CHARACTER OR BRAILLE
18"
MIN
NO WALL MOUNTEDPROTRUDING OBJECTSMORE THAN 3" BEYONDFACE OF WALL AT SIGNLOCATION
EXIT ROUTE
3/8
"
AE
C
D
F
BC
LOCATION VARIES BY TYPE
SIGNAGE SIZE AND CHARACTER
RAISED CHARACTERS SHALL BEUPPERCASE, SANS-SERIF, HORIZONTALFORMAT, WITH FONTS PER CBC 11B-703.2.4
RAISED CHARACTER REQUIREMENTS AND LEGEND:
A. CHARACTERS SHALL BE RAISED 1/32" MINIMUM ABOVE THEIR BACKGROUND.B. CHARACTER HEIGHT SHALL BE A MINIMUM OF 5/8" AND A MAXIMUM OF 2" HIGH BASED ON
THE UPPERCASE "I".C. CHARACTERS SHALL BE SEPERATED FROM ANY RAISED BORDER OR DECORATIVE
ELEMENT BY 3/8"D. CHARACTER FONT PROPORTION WITH THE UPPERCASE 'O' WIDTH BEING 60 PERCENT
MINIMUM TO 110 PERCENT MAXIMUM THE HEIGHT OF THE UPPERCASE 'I'.E. CHARACTER STROKE THICKNESS OF THE UPPERCASE 'I' SHALL BE 15 PERCENT MAXIMUM
THE HEIGHT OF CHARACTER.F. CHARACTER THAT ARE RECTANGULAR IN CROSS SECTION SHALL BE A 1/8" MINIMUM AND 4
TIMES THE RAISED CHARACTER STROKE WIDTH MAXIMUM.G. RAISED CHARACTERS SHALL HAVE EASED EDGES.
BRAILLE REQUIREMENTS AND LEGEND:
BRAILLE SHALL BE PER CBC 11B-703.3 INCLUDING, BUT NOT LIMITED TO THEFOLLOWING: DISTANCES IN INCHES, MIN TO MAX
A. DISTANCE BETWEEN CORRESPONDING DOTS FROM ONE CELL DIRECTLYBELOW: 0.395 TO 0.400
B. DISTANCE BETWEEN TWO DOTS IN THE SAME CELL : 0.100C. DISTANCE BETWEEN CORRESPONDING DOTS IN ADJACENT CELLS: 0.300D. SINGLE BRAILLE CELLE. BLANK CELL SPACE BETWEEN WORDSF. BASE DIAMETER: 0.059 TO 0.063G. NO RAISED DOT
RAISED CHARACTERS AND SIGN FIELD TOHAVE NON-GLARE FINISH.
Q2
ACCESSIBILE TACTILE SIGN REQUIREMENTSAE_G_0570_026_
150901.
SIG
NA
GE
SIZ
E A
ND
CH
AR
AC
TE
RLO
CA
TIO
N V
AR
IES
BY
TY
PE
C B
BB
A
F
D
E
G
SIGN FIELD TO BE CONTRASTING COLORS,EITHER LIGHT ON DARK OR DARK ON LIGHT.COORDINATE WITH ARCHITECT FORSPECIFIC COLORS.
G
NOTES:PROVIDE EXIT SIGNAGE PER: CBC 1011, 11B-216, 11B-703
TYPE 1LOCATE AT GRADE LEVEL EXIT DOORS.
TYPE 2LOCATE AT EACH ACCESS DOOR FROM ANINTERIOR ROOM OR AREA TO A CORRIDOR ORHALLWAY, AND EACH DOOR THAT LEADS TO AGRADE LEVEL EXIT BY MEANS OF EXITENCLOSURE OR EXIT PASSAGEWAY.
TO EXIT
EXITROUTE
EXITSTAIRDOWN
EXITSTAIRUP
EXITRAMPDOWN
EXITRAMPUP
EXIT
TYPE 4LOCATE AT EXIT DOORS LEADING TO GRADELEVEL EXTERIOR EXIT THROUGH STAIR.
TYPE 6LOCATE AT EXIT DOORS LEADING TO GRADELEVEL EXTERIOR EXIT THROUGH STAIR.
TYPE 5LOCATE AT EXIT DOORS LEADING TO GRADELEVEL EXTERIOR EXIT THROUGH RAMP.
TYPE 7LOCATE AT EXIT DOORS LEADING TO GRADELEVEL EXTERIOR EXIT THROUGH RAMP.
TYPE 3LOCATE AT EXIT DOOR OF A HORIZONTAL EXIT
EXIT
EXIT ROUTE
EXIT STAIR DOWN
EXIT STAIR UP
EXIT RAMP DOWN
EXIT RAMP UP
TO EXIT
.
48" AFF, MIN TOLOWEST BASELINE
OF BRAILLE
.
60" AFF MAX TOHIGHEST BASELINE
OF RAISED CHARACTER
.
48" AFF, MIN TOLOWEST BASELINE
OF BRAILLE
.
60" AFF MAX TOHIGHEST BASELINE
OF RAISED CHARACTER
.
48" AFF, MIN TOLOWEST BASELINE
OF BRAILLE
.
60" AFF MAX TOHIGHEST BASELINE
OF RAISED CHARACTER
.
48" AFF, MIN TOLOWEST BASELINE
OF BRAILLE
.
60" AFF MAX TOHIGHEST BASELINE
OF RAISED CHARACTER
.
48" AFF, MIN TOLOWEST BASELINE
OF BRAILLE
.
60" AFF MAX TOHIGHEST BASELINE
OF RAISED CHARACTER
.
48" AFF, MIN TOLOWEST BASELINE
OF BRAILLE
.
60" AFF MAX TOHIGHEST BASELINE
OF RAISED CHARACTER
.
48" AFF, MIN TOLOWEST BASELINE
OF BRAILLE
.
60" AFF MAX TOHIGHEST BASELINE
OF RAISED CHARACTER
Q1
EXIT SIGNAGEAE_G_0570_027?YYMMDD?.
A-582
13CHARACTERS AND BRAILLE PER TYP
60" AFF MAX TOHIGHEST BASELINE
OF RAISED CHARACTER
12'-0" MIN 5'-0" MIN 9'-0" MIN
18'-0" MIN
MAX
3'-0"2'-0" MIN
UN
OB
ST
RU
CT
ED
AR
EA
NOPARKING
12"
MIN
VAN ACCESSIBLEPARKING STALL
REGULARACCESSIBLE
PARKING STALL
4" WHITELINE
ACCESSIBLE PARKINGSIGN, FOR VAN SIGN, SEEDETAIL
ACCESSIBLE PARKINGSIGN, FOR STANDARDSTALL SIGN, SEE DETAIL
4" BLUE LINEBORDER
NOTE: TO COMPLY WITH CBC 11B-5022% MAX SLOPE IN ANY DIRECTION FOR ACCESSIBLE STALLS AND ACCESS AISLES
36" x 36" INTERNATIONALSYMBOL OFACCESSIBILITY. CL OFISA 6" MAX FROM CL OFSTALL, SIDES OF ISAPARALLEL TO STALL ANDLOWER SIDE ALIGNEDWITH END OF PARKINGSPACE LENGTH. TYPFOR ALL PARKING
4'-0" CONCRETEWHEELSTOP, TYP SEEDETAIL
EXTENT OF STALL, SEE SITEPLAN FOR ADDITIONALINFORMATION
WHITETEXT
6"6"
SIGN
SEE PLAN FOR SPECIFIC SIGN TYPE,FOR SPECIFIC SIGNAGEINFORMATION, SEE DETAIL
1 1/2" DIA GALV STD PIPE
1" CROWN AT PAVING
EXP JOINT, TYP AT PERIMETER
CONCRETE OR PAVING
12" DIA CONCRETE FOOTING
3"
2'-9" MIN
80" MIN AT ACCESSIBLE ROUTE60" MIN AT PLANTERS
NO PARKINGPASSENGER
LOADING ZONE
(7" MIN)
1'-0"
(10" MIN)1'-6"
FOR INSTALLATION,SEE DETAIL 12/A-582
NOTES:1. PROVIDE GALV/ THEFT PROOF BRACKETS, STL BOLTS, NUTS & WASHERS THROUGH SIGN AND POST2. SIGN PANEL TO BE 0.08" MIN ALUM SHEET, ENAMEL PAINTED AFTER SMOOTHING WITH WHITE
LETTERS, NUMBERS AND BORDER STRIPE3. CHARACTERS TO BE WHITE ON A BLUE BACKGROUND4. ALL SIGNS TO HAVE 1/2" RADIUS AT THE CORNERS
LE
TT
ER
1"
MIN
3'-0"
3'-0"
PAINT WITH TRAFFIC PAINT:SYMBOL: WHITEBACKGROUND: BLUE EQUAL TOPED SPEC 595A COLOR # 15090
3" R CORNERS
CL
SIDES OF ISA PARALLEL TOSTALL
LOWER EDGE OF ISAALIGNED WITH END OFPARKING STALL.
CENTERLINE OF ISA &STALL, 6" MAX.OFFSETALLOWED
NOTE: SIGN SHALL INCLUDE ISA AND COMPLY WITH CBC 11B-703.7.2.1
10" MIN1'-6"PARKING
ONLY
MINIMUMFINE $250
7" MIN
1'-0"
60"
MIN
AT
PLA
NT
ER
S
80"
MIN
CLR
PARKINGONLY
VANACCESSIBLE
UNAUTHORIZED VEHICLESPARKED IN DESIGNATED
ACCESSIBLE SPACES NOTDISPLAYING DISTINGUISHING
PLACARDS OR SPECIALLICENSE PLATES ISSUED FORPERSONS WITH DISABILITIES
WILL BE TOWED AWAY ATOWNER'S EXPENSE. TOWED
VEHICLES MAY BE RECLAIMEDAT (ADDRESS) OR BY
TELEPHONING (TELEPHONENUMBER) C.V.C. 22507.8
60"
MIN
MINIMUMFINE $250
VANACCESSIBLE
MINIMUMFINE $250
MINIMUMFINE $250
1'-5" MIN
1'-10" MIN2'-6"
NOTES:1. SIGNS SHALL HAVE A MINIMUM AREA OF 70 SQ
INCHES2. SIGNAGE TO BE INSTALLED CENTERED AT
INTERIOR END OF EACH PARKING SPACE3. GALV/ THEFT PROOF BRACKETS, STL BOLTS, NUTS
& WASHERS THROUGH SIGN AND POST4. SIGN PANEL OF 0.08" MIN ALUM SHEET, ENAMEL
PAINTED AFTER SMOOTHING WITH WHITELETTERS, NUMBERS AND BORDER STRIPE
5. CHARACTERS TO BE WHITE ON A BLUEBACKGROUND
6. ALL SIGNS TO HAVE 1/2" RADIUS AT THE CORNERS7. LETTERS SHALL BE 1" MINIMUM IN HEIGHT
TO BE DISPLAYED:
UNAUTHORIZED VEHICLES PARKED INDESIGNATED ACCESSIBLE SPACESNOT DISPLAYING DISTINGUISHINGPLACARDS OR SPECIAL LICENSEPLATES ISSUED FOR PERSONS WITHDISABILITIES WILL BE TOWED AWAY ATOWNER'S EXPENSE. TOWED VEHICLESMAY BE RECLAIMED AT (ADDRESS) ORBY TELEPHONING (TELEPHONENUMBER) C.V.C. 22507.8
ACCESSIBLEFREE STANDING
A B C D EVAN ACCESSIBLEFREE STANDING
AT SITE ENTRYFREE STANDING
ACCESSIBLEWALL MOUNTED
VAN ACCESSIBLEWALL MOUNTED
APPROPRIATE INFORMATION
MUST BE INCLUDED ON SIGN AS
PERMANENT PART OF SIGN,
VERIFY WITH ARCHITECT
PARKINGONLY
PARKINGONLY
SURFACE SLOPES OF ACCESSIBLE PARKING SPACES SHALL NOT EXCEED 1/4 INCH PERFOOT (2% GRADIENT) IN ANY DIRECTION.ACCESSIBLE PARKING SPACES SHALL BE LOCATED SO AS NOT TO REQUIRE USERS TOWHEEL OR WALK BEHIND ANY OTHER NON-ACCESSIBLE OR ACCESSIBLE PARKING SPACE.IN EACH PARKING AREA, A BUMPER OR CURB SHALL BE PROVIDED AND LOCATED TOPREVENT ENCROACHMENT OF CARS OVER THE REQUIRED WIDTH OF WALKWAYS.PARKING SPACES RESERVED FOR PERSONS WITH PHYSICAL DISABILITIES SHALL BEIDENTIFIED BY A REFLECTORIZED SIGN PERMANENTLY POSTED IMMEDIATELY ADJACENT TOAND VISIBLE FROM EACH STALL OR SPACE CONSISTING OF A PROFILE VIEW OF AWHEELCHAIR WITH OCCUPANT, IN WHITE ON DARK BLUE BACKGROUND. THE SIGN SHALLNOT BE SMALLER THAN 70 INCHES IN AREA AND, WHEN IN THE PATH OF TRAVEL, SHALL BEPOSTED AT A MINIMUM HEIGHT OF 80 INCHES FROM THE BOTTOM OF THE SIGN TO THEPARKING SPACE FINISHED GRADE. SIGNS MAY ALSO BE CENTERED ON THE WALL AT THEINTERIOR END OF THE PARKING SPACE AT A MINIMUM HEIGHT OF 60 INCHES FROM THEPARKING SPACE FINISHED GRADE, GROUND, OR SIDEWALK.
PARKING1.
2.
3.
4.
Q2
DETECTABLE WARNINGS0500_0280_DETECTABLE WARNING
PAD_01170614.
0.90"
0.45-0.47"
0.6
5"
MIN
2.3" -2.4"
0.1
8"
TO
0.2
2"
HT
SECTION VIEW3'-0" MIN
SEE PLAN
NOTES:1. THE MATERIAL USED TO PROVIDE VISUAL CONTRAST SHALL BE AN INTEGRAL PART
OF THE SURFACE.2. DETECTABLE WARNING SURFACES SHALL BE YELLOW AND APPROXIMATE FS 33538
OF FEDERAL STANDARD 595C.3. DETECTABLE WARNING SURFACES SHALL PROVIDE A 70% MIN VISUAL CONTRAST
WITH ADJACENT WALKING SURFACES. IF VISUAL CONTRAST IS NOT AVAILABLE SEE11B-705.1.1.3.2
4. WHERE INSTALLED IN A RADIAL PATTERN, DOMES SHALL HAVE A CENTER TO CENTERSPACING OF 1.6-2.4 INCHES.
5. DETECTABLE WARNING SURFACES MUST DIFFER FROM ADJOINING SURFACES INRESILIENCY OR SOUND-ON-CANE CONTACT.
NORTHPLAN
A B
1 2 3 4 5
D
C
B
A
SHEET
TITLE
AGENCY
MANAGEMENT
ISSUED
PROJECT
SEAL
CONSULTANT
CLIENT PROJECT NO:
COPYRIGHT:
LIONAKIS PROJECT NO:
LIONAKIS 2015
IF T
HIS
SH
EE
T IS
NO
T 3
0"x
42",
IT
IS
A
RE
DU
CE
D P
RIN
T -
SC
ALE
AC
CO
RD
ING
LY
01/4
"1/2
"1"
2"
KEY PLAN
CLIENT
11/1
/2017 5
:00:5
4 P
MC
:\U
sers
\georg
e.w
illia
ms\
Docum
ents
\016336_B
IM_A
-MA
ST
ER
_R
16_C
EN
TR
AL_georg
e.w
illia
ms.
rvt
A-582
DETAILS -ACCESSIBILITY
016336
C3050.4
CITY OF EL CERRITO
EL CERRITO SWIM CENTERLOCKER ROOMS / POOL
EQUIPMENT ROOMUPGRADES & RENOVATION
7007 MOESER LANEEL CERRITO, CA 94530
10890 SAN PABLO AVE, EL CERRITO CA
1/4" = 1'-0"14
3/16" = 1'-0"15
1 1/2" = 1'-0"10
1/2" = 1'-0"7
1/4" = 1'-0"6
3" = 1'-0"9 1/4" = 1'-0"5
1/2" = 1'-0"18
6" = 1'-0"13
1/2" = 1'-0"2
101 Montgomery Street, Suite 500San Francisco CA 94104P 415.777.4811 F 415.777.4523www.lionakis.com
C27466
LIC
ENSED A
T
RCHITEC
R 9E N. 0 - 31 - 1
S
ATA
TE
O F C A L I F O
RN
I
7
NITRAM.DLUAP
SCALE 1/8" = 1'-0"16
ACCESSIBLE PARKINGPERPINDICULAR
SCALE 1/2" = 1'-0"12
TYP SIGN POLE & BASE FOR EXTMOUNTED SIGN
SCALE 1 1/2" = 1'-0"8
PASSENGER LOADINGZONE SIGNAGE
SCALE 1" = 1'-0"4 ACCESSIBLE PARKING SYMBOL
SCALE 1/2" = 1'-0"3 ACCESSIBLE PARKING SIGNAGESCALE 1/2" = 1'-0"19 ACCESSIBILITY REQUIREMENTS
MARK DATE DESCRIPTION
08/08/2017 SUBMIT FOR PERMIT
10/09/2017 BID SET
1 11/01/2017 ADDENDUM #1
3" = 1'-0"11
1
PO
RT
OLA
DR
IVE
MO
ES
ER
LA
NE
ASHBURY
NORVELL
STREET
STREET
PG&EENTRY
PO
RT
OLA
DR
IVE
MO
ES
ER
LA
NE
ASHBURY
NORVELL
STREET
STREET
PG&EENTRY
GENERAL LIMITSOF WORK
S1 S1
S3 S4S2
(E) OFFICE
2
A-111
1
A-111AD-111
2
AD-111
1
(E) FIREHYDRANT
(E) FIREHYDRANT
(E) SWIMMINGPOOL
(E) SWIMMINGPOOL
S6
(E) CIVICCENTER
LOCKER ROOMS POOL EQUIPMENT RM
ISA
OLSISA
OLS
S7 S8D15 D15
FLOOR PLAN LEGEND
ACCESSIBLE ENTRY
ACCESSIBLE PATH OF TRAVEL
(E) BUILDING - NOT IN SCOPE
(E) BUILDINGS - AREA OF WORK
(E) SWIMMING POOLS
ISA INTERNATIONAL SYMBOL OF ACCESSIBILITY; SEE 6/A-582
OLS OCCUPANCY LOAD SIGN; SEE 10/A-582
GENERAL NOTES
GENERAL LIMITSOF WORKS5S5
S1 S1
S3 S4S2
(E) OFFICE
2
A-111
1
A-111AD-111
2
AD-111
1
(E) FIREHYDRANT
(E) FIREHYDRANT
(E) SWIMMINGPOOL
(E) SWIMMINGPOOL
S6
(E) CIVICCENTER
ACCESSIBLE PARKING STALLS
• TOTAL PARKING SPACES 76 STALLS• REQUIRED ACCESSIBLE SPACES ( PER CBC TABLE 11B-208.2) 4 STALLS• REQD VAN PARKING (PER CBC 11B-208.2.4) 1 MINIMUM
LOCKER ROOMS POOL EQUIPMENT RM
ISA
OLSISA
OLS
S7S5S5 S8 S9
S8S81
12'-0" MIN9'-0" MIN
9'-0" MIN 9'-0" MIN
18
'-0
" M
IN
18
'-0
" M
IN
S10S10
NORTHPLAN
A B
1 2 3 4 5
D
C
B
A
SHEET
TITLE
AGENCY
MANAGEMENT
ISSUED
PROJECT
SEAL
CONSULTANT
CLIENT PROJECT NO:
COPYRIGHT:
LIONAKIS PROJECT NO:
LIONAKIS 2015
IF T
HIS
SH
EE
T IS
NO
T 3
0"x
42",
IT
IS
A
RE
DU
CE
D P
RIN
T -
SC
ALE
AC
CO
RD
ING
LY
01/4
"1/2
"1"
2"
KEY PLAN
CLIENT
11/1
/2017 4
:22:1
0 P
MC
:\U
sers
\georg
e.w
illia
ms\D
ocum
ents
\016336_B
IM_A
-MA
ST
ER
_R
16_C
EN
TR
AL_georg
e.w
illia
ms.r
vt
AS101
SITE PLAN
016336
C3050.4
CITY OF EL CERRITO
EL CERRITO SWIM CENTERLOCKER ROOMS / POOL
EQUIPMENT ROOMUPGRADES & RENOVATION
7007 MOESER LANEEL CERRITO, CA 94530
10890 SAN PABLO AVE, EL CERRITO CA
SCALE 1" = 30'-0"1EXISTING SITE PLAN
101 Montgomery Street, Suite 500San Francisco CA 94104P 415.777.4811 F 415.777.4523www.lionakis.com
SHEET KEYNOTES
D15 RESTRIPE PARKING SPACES PER PLAN 2/AS-101.
S1 EXISTING ACCESSIBLE DRINKING FOUNTAINS.
S2 EXISTING UNISEX TOILET.
S3 EXISTING WOMEN'S LOCKER ROOM.
S4 EXISTING MEN'S LOCKER ROOM.
S5 ACCESSIBLE PARKING SPACE. SEE DETAIL 16/A-582.
S6 EXISTING CHEMICAL ROOMS.
S7 ACCESSIBLE ROUTE THAT IS A MINIMUM 48" CLEAR WIDTH, MAXIMUM 5% RUNNING SLOPE AND MAX3% CROSS SLOPE PER CBC 11B-403.
S8 EXIT AND EXIT ACCESS DOORS SHALL BE MARKED BY APPROVED EXIT SIGNS; SEE DETAILS 2/A-582,7/A-582; MAIN EXTERIOR ARE PERMITTED TO BE EQUIPPED WITH KEY-OPERATED LOCKING DEVICESFROM EGRESS SIDE PROVIDED, A READILY VISIBLE, DURABLE, SIGN POSTED ON THE EGRESS SIDEOR ON ADJACENT TO THE DOOR STATING: THIS DOOR TO REMAIN UNLOCKED WHEN THIS SPACE ISOCCUPIED PER CBC 1008.1.9.3. THE SIGN SHALL BE IN LETTERS 1-INCH HIGH ON A CONTRASTINGBACKGROUND.
S9 MINIMUM 5% OF THE LOCKERS TO BE ACCESSIBLE PER CBC 11B-225.2.1; SEE DETAIL 4/A-581.
S10 NEW TRUNCATED DOMES. SEE DETAIL 11/A-582.
C27466
LIC
ENSED A
T
RCHITEC
R 9E N. 0 - 31 - 1
S
ATA
TE
O F C A L I F O
RN
I
7
NITRAM.DLUAP
MARK DATE DESCRIPTION
08/08/2017 SUBMIT FOR PERMIT
10/09/2017 BID SET
1 11/01/2017 ADDENDUM #1
SCALE 1" = 30'-0"2SITE PLAN
1
1
1
1
101 Montgomery St, Suite 500
San Francisco, CA 94104
P 415.777.4811 F 415.xxx.xxxx
www.lionakis.com
1 2 3 4 5
D
C
B
A
SHEET
TITLE
AGENCY
MANAGEMENT
ISSUED
PROJECT
SEAL
CONSULTANT
CLIENT PROJECT NO:
COPYRIGHT:
LIONAKIS PROJECT NO:
LIONAKIS 2015
IF
T
HIS
S
HE
ET
IS
N
OT
3
0"x4
2", IT
IS
A
R
ED
UC
ED
P
RIN
T - S
CA
LE
A
CC
OR
DIN
GL
Y
01
/4
"1
/2
"1
"2
"
CLIENT
11
/3
0/2
01
5 1
:4
0:1
2 P
M
CITY OF CERRITO
UPGRADES AND
REMEDIATION
7007 MOESER LANE
EL CERRITO, CA 94530
10890 SAN PABLO AVE, EL CERRITO, CA
MARK DATE DESCRIPTION
08/08/2017 SUBMIT FOR PERMIT
08/30/2017 BID SET
016336
C3050.4
10/09/2017 BID
11/01/2017 ADDENDUM #1DELTA #1
M0.1
MECHANICAL
LEGEND, NOTES
AND DETAILS