28
Busch-Watchdog ® Presence Busch-Watchdog ® Presence EIB Save energy conveniently Designed for the specialised electrical industry

Busch-Watchdog Presence Busch-Watchdog Presence EIB · Basic principles 4 ... Constant lighting control 20 ... 100 Approx. 250 lux Good reflection (”light” surface) See diagrams

  • Upload
    phungtu

  • View
    219

  • Download
    0

Embed Size (px)

Citation preview

Busch-Watchdog® Presence

Busch-Watchdog® Presence EIB

Save energy conveniently

Designed for the specialised

electrical industry

22

Basic principles 4

Prerequisites for detection of people 5

Interference sources for the Busch-Watchdog® Presence 6

Setting options for themeasurement of daylight 7

Setting options forthe OFF delay 8

Extension input operation, master/slave 9

Remote operation 10

Areas of application/flush-mounted inserts 11

Application example:Single office (lighting and heating) 12

Application example:Large office (master/slave) 14

Application example: Large office (separate lighting circuits) 16

Application example:Toilet facilities (lighting and ventilation control) 18

Application example:Constant lighting control 20

Application example:Interface to Powernet 22

Application example: Interface toABB i-bus® EIB 24

33

Contents

Busch-Watchdog®

Presence

Busch-Watchdog®

Presence andBusch-Watchdog®

Presence EIB

Busch-Watchdog®

Presence EIB

4

Basic principles

Infrared radiation, alsoknown as thermalradiation, is associatedwith electromagneticwaves. Each object emitsthermal radiation accordingto its specific temperature.

for detection purposes. TheBusch-Watchdog® Presencehas 4 sensors, an optimisedlens and an additional high-quality system of mirrors sothat even the slightestmovement from peoplewho are seated can bereliably detected.

As a room heats up, itsthermal radiation changesat a very slow rate incomparison. It is therebyguaranteed that anymovement by people (ther-mal movement) can bedetected.

IR sensor technology

Traces of infrared can bedetected with infrared sen-sors and converted intoelectrical signals. As these

sensors only receive and donot emit any infraredradiation themselves, theyare also called “passive” IRsensors.

Optical system

The monitored area is divid-ed into numerous fields orsegments with the aid oflenses, mirrors andsensors. If someone movesfrom one segment to anoth-er, this movement is detect-ed. The higher the numberof segments, the smallerthe movement needs to be

Passive IR sensors

Passive IR sensors aredesigned so that they onlyreact to changes in thermalradiation e.g. due tomovement. If the thermalradiation is at a constantlevel, no signals areproduced.

Gam

ma

X-r

ay

Ult

ravio

let

Vis

ible

Infr

are

d

Rad

io w

aves

1 A 100 A 0.4 �m 0.7 �m 0.1 cm

IR sensor

Lens

5

Prerequisites for detection of people

The movement of people,including the slightestmovements made whilesitting at a PC workstation,is dependent on themounting height and the

“clear view” of the Busch-Watchdog® Presence.

available. The reference lev-el for the detection is thefloor. The diameter of thedetection area produced is8 to 9 m.

reduced. Depending on theapplication, a greaterresolution is not requiredand a higher mountingheight is possible (e.g. instorerooms, corridors,hallways).

Exterior detection area

(with people walking)

When detecting peoplewho are walking around, alarger detection area is

Interior detection area

(with people sitting

down)

People who are seatedmust be positionedcompletely within thedetection area. The smallerthe distance between theperson and the Busch-Watchdog® Presence, thesmaller the movementneeds to be for detection

purposes. The referencelevel for the detection ofseated activities is approx.1 m. At this height, thedetection area is 6 m indiameter (mounting heightof the Busch-Watchdog®

Presence = 2.5 m). At agreater mounting height,the detection area will belarger but the monitoringdensity will be reduced.

Mounting heights

The detection propertieschange dependent on themounting height. As themounting height increases,the sensitivity andmonitoring density are

5

8.0–9.0 m

6.0 m

2.5 m

1.0 m

Mounting height Seated people* Walking people

2.0 m 4 m 8 m2.5 m 6 m 10 m3.0 m 8 m 12 m3.5 m 10 m 14 m4.0 m 12 m ** 16 m5.0 m 16 m** 20 m

*Seated height: 1 m**No longer suitable for pure ‘deskwork’ or OFF delay > 15 min

6

Interference sources

Switching operations arenormally triggered by peoplemoving around. Externalheat sources can also causeunwanted switching

operations which shouldbe taken into account atthe planning stage.

• strips of luminaires whichhave been inserted deeper than the Busch-Watchdog® Presence

• large plants• partition walls• panes of glass

• additional fans• switching on/off of lamps

which are in the direct vicinity (< 1.5 m) of the Busch-Watchdog®

Presence, especially incandescent and halogen lamps

• moving machinery, flapping posters

• radiators (distance> 0.5 m)

• surfaces warmed bythe sun

• EDP systems (computers, printers, monitors)

• ventilation systems as the warm air is flowing directly into the detectionarea of the Busch-Watchdog® Presence

Limited view of the

Busch-Watchdog®

Presence

The detection area of theBusch-Watchdog® Presencecan be concealed bydifferent objects e.g.

External heat sources

Rapid temperature changesin the environment of theBusch-Watchdog® Presencecan likewise triggerunwanted switchingoperations e.g.

Heat sources without a

disruptive influence

If the temperature onlychanges slowly, it has noinfluence on the switchingbehaviour of the Busch-Watchdog® Presence e.g.

7

Setting options

1. Measuring daylight

A main advantage of theBusch-Watchdog®

Presence lies in the evalua-tion and disconnection ofthe lighting without

dependence on movementin order to achieve thegreatest potential forsaving energy. In contrastto conventional motiondetectors which are only

activated below a dusk val-ue, the Busch-Watchdog®

Presence must constantlymeasure and assess thebrightness and then switchthe light on or off

accordingly.

7

value measured at theworkstation is thus storedas the new higherbrightness limit.

2 Brightness limit is set

too high

This means that the lightingis still switched on althoughthe daylight coming into theroom would be sufficient.The lighting is switched offvia remote control and thebrightness value is stored.A lower current brightnesslimit is therefore stored andthe lighting is switched onearlier.

* The function is not availablefor the Busch-Watchdog®

Presence EIB as modificationscan be carried out in this casevia the laptop

Adaptation of the

brightness limit via IR

remote control*

The Busch-Watchdog®

Presence enables a simpleadaptation of the set bright-ness value using IR remotecontrol without disruptingthe operating sequence andinstallation work.

1 Brightness limit is set

too low

This means that the lightingis switched off too early.The lighting is switched onvia remote control and thebrightness value is stored.The current brightness

6 12 18

400

Current brightness

BrightnessLux

Time

500

Lux

100

5

6 12 18

400

BrightnessLux

Time

1

2Adapted limit

Adapted limit

Set brightness limit

ing). The ambientbrightness is not only takeninto account but also thereflected light of surfaceslying below it (e.g. desk).This brightness isdependent on theconditions (reflectiveproperties) of thecorresponding surface (seetable). In case of doubt, areference measurement isrequired at a workstation todefine the actual conditions.

Selection of the brightness

limit

The brightness limit can beselected with the help ofthe “Lux” setting. Whenthis limit is exceeded, thelighting is switched offwhile the light is switchedon again when the valuedrops below this limit. Itshould be noted that theBusch-Watchdog®

Presence measures thebrightness at theinstallation site (on the ceil-

Setting on Brightness on Commentsthe “Lux” the work surface potentiometer

100 Approx. 500 lux Poor reflection(“dark” surface)

100 Approx. 400 lux Medium reflection 100 Approx. 250 lux Good reflection

(”light” surface)

See diagramson page 10 forsetting of theremote control

8

TimeMovementTime0.5

TimeMovementTimeMovement

1

3 4

2

HVAC

Light

Setting options

2. OFF delay

The OFF delay is set whenbridging idle times andirregularities in thesequences within thedetection area (e.g. leaving

the room temporarily). Thesettings “Time/Light” and“Time/HVAC” are used forthis. An intelligent ONdelay for heating,ventilation and air

conditioning applications isalso integrated in thesetting “Time/HVAC”.

with low movementpotential (e.g. at PCworkstations etc.), aninterval > 10 minutes is rec-ommended. A shorterperiod can be set in roomswith more movement(storerooms, corridors etc.)

inertia of the systems inuse. In heating systems, atime range between 20 and30 minutes is recommend-ed. Shorter periods (approx.5 minutes) should beconsidered in connectionwith fans..

are defined in connectionwith the desired OFF delay.It is thus guaranteed thatthe HVAC output is onlyswitched on if continuousmovement has been detect-ed.

Setting the OFF delay for

the lighting

An OFF delay for thelighting can be selected viathe potentiometer“Time/Light”. The timeshould be selecteddependent on theapplication. In applications

Setting the OFF delay for

HVAC

The setting “Time/HVAC” isavailable for applications inheating, ventilation and airconditioning technology.The OFF delay should beselected dependent on the

Intelligent ON delay

Depending on its use in theheating/ventilation/airconditioning (HVAC) sector,the Busch-Watchdog®

Presence takes into accountspecific requirements which

5 Time10 15 20 25 30 35 40 45 50 55 60 65

Movement

30

20

1510 5

1

10sec

min

Time/Light

Movement

Time20 3010 40 50 60 70 80 90 100 110 120 130

60

4030

15

1

5

T

Time/HVAC

Setting for ON delay Application HVAC outputOFF delay

< 10 min. 30 sec. Ventilation/ AlwaysWC switches

> 10 min. Motion- Heating/ Only switches dependent office after continuous up to 15 min. movement

9

Extension input operation

If required, the Busch-Watchdog® Presenceoffers the possibility at anytime for manualintervention into automatic

processes. The lighting canfor example be switched offin this way for presen-tations. In exceptionalcases, it is possible to

switch on the lighting direct-ly at any time regardless ofthe selected setting. Thereturn to the automaticmode is carried out

“automatically” accordingto fixed rules.

9

references values fordisconnection. Theextension units are onlyused for detection of move-ment.

Active extension units

with push button

operation

Additional plateswitchescan also be installed whenactive extension units areused. Their function isdescribed above.

*Does not apply to the Busch-Watchdog® Presence EIB

Active extension unit*

In large rooms in which oneBusch-Watchdog® Presenceis not sufficient, thedetection area can beextended using additional,economical extension units.The switching function iscarried out by the masterunit. It is advisable to installthis master in the darkestplace in the room and todefine the brightnessvalues measured as

• after continuous movement and underflow of the brightness limit over 4 hours.

2. Lighting is switched off

The lighting can beswitched off (if already on)by pressing the rocker on aconnected plateswitch.When the lighting isswitched on again for aminimum of 2 hours, theBusch-Presence reverts toautomatic operation, wherethe light setting isdependent on movementand brightness.

Push button operation*

In this case, conventionalplateswitches areconnected to the extensioninputs of the respectiveflush-mounted inserts.

1. Lighting is switched on

The lighting can beswitched on (if already off)by pressing the rocker on aconnected plateswitch.The automatic mode isreactivated:• if no movement has

been detected for 30 minutes and the brightness value has fallen below the limit

10

Control with Busch-Ferncontrol® IR*

Apart from enabling theflexible adaptation of thebrightness value, theremote control functioncan also be used toimplement switching func-

tions e.g. in places where itis not possible to connectpush button extension unitsduring a retrofit.

*Does not apply to the Busch-Watchdog® Presence EIB

and off with the “ON/OFF”buttons. This function is iden-tical to switching on/off usinga conventional plateswitch.Wall-mounted transmittersare also available as analternative to the hand-heldtransmitter for integrationinto the flush-mounted instal-lation environment.

adopts the currentbrightness value as thenew brightness limit.

3 Adapting the brightness

limit for constant lighting

control

In connection with a flush-mounted dimmer insert,the lighting can beswitched on or off ordimmed with remotecontrol. The lighting isswitched on and off after ashort push button actionbut the brightness limit isnot changed. The lightingcan be dimmed with a longpush button action. If theset brightness is to bestored as the limit value,the “Memo” button mustbe pressed twice. If thebrightness is changed by adimming process duringnormal operation (withoutpressing the “Memo”button twice), the automat-ic function is interrupted for2 hours. The Busch-Watchdog® Presence thenreverts to the originalstored value.

Switching on/off with IR

remote control

Channel 10 (blue) ➀ is locat-ed on the Busch-Ferncontrol® IR hand-heldtransmitter. The pair of pushbuttons 5 ➁ + ➂ arereserved for the Busch-Watchdog® Presence. Thelighting can be switched on

Storing the brightness

limit via remote control

The brightness limit can beset via the “Lux”potentiometer. It ishowever more convenientto adapt the limit value viaremote control without anyadditional assemblyrequired.

1 Brightness limit is too

low

The lighting is switched offtoo early. The lighting isswitched on ➀ withremote control (pushbutton 10, “ON” button)and the “Memo” button ➁is then pressed twice. TheBusch-Watchdog®

Presence adopts thecurrent brightness value asthe new brightness limit.

2 Brightness limit is too

high

The lighting is switched offtoo late. The lighting isswitched off ➀ withremote control (pushbutton 10, “OFF” button).The “Memo” button ➁ isthen likewise pressedtwice. The Busch-Watchdog® Presence

1

2

3

2

1

2

3

1

2

1

11

Areas of application

The Busch-Watchdog®

Presence can be combinedwith various flush-mountedinserts depending on theapplication.

The following table containssuggestions for equipmentrelated to applications.Further combinations arepossible.

* in preparation

Area of Flush-mounted HVAC Active Passive Comment

application insert, extension extension

order no. unit unit

Office 6402 U* • • Constant lighting control 6401 U-102 • is recommended for6812 U-101 more convenience

Large office 6402 U* • • •6401 U-102 • •

Meeting room 6402 U* • • •6401 U-102

Conference room 6402 U* • • • Constant lighting6401 U-102 • • control ensures6590 U-103* • • more convenience6550 U-101* • •

Recreation room 6402 U* •6401 U-102

Production area 6401 U-102 • •6812 U-101

Laboratory 6401 U-102 • • Constant lighting6590 U-103* • • control ensures6550 U-101* • • more convenience

Classroom 6402 U* • • •6401 U-102 • •

Corridor 6401 U-102 • •6812 U-101

Staircase 6401 U-102 • •

Entrance hall 6401 U-102 • •6812 U-101

WC 6402 U* • • • Additional fan 6401 U-102 • • control6812 U-101

Cloakroom 6401 U-102 • •6812 U-101

Storeroom 6401 U-102 • •

12

Time/Light

30

20

1510 5

1

10sec

min

Lux

1000

500 100

5

Time/HVAC

60

4030

15

1

5

T

Example

Time/Light

Example

30

20

1510 5

1

10sec

min

Lux

1000

500 100

5

12

Application example: Single office

Task

The lighting in an officeshould be controlledefficiently via a Busch-Watchdog® Presence. Itshould also be possible to

switch the lighting on andoff manually with a pushbutton. The heatingshould then be integratedas the next phase.

Installation and settings

The installation site of theBusch-Watchdog® Presenceshould be selected abovethe workstation to providethe best level of detection.The installation can beflush-mounted or surface-mounted if an adapter isused. The brightnesssetting is carried out via the“Lux” potentiometer. A set-ting between 50 and 100lux measured at the ceiling

can correspond to abrightness level of 300-400lux at the workstation,depending on the reflectiveproperties of the room. TheOFF delay is defined inthese applications atapprox. 10 minutes. Anadapter is provided for thesimplemounting/dismantling ofthe sensor during theadjustment and installationstage.

Additional integration of

heating control

The greatest energy-savingpotential lies in heating con-trol. It is a good idea toreduce the temperature inthe room via night reductionif no movement is detected.It is however generally notadvisable to disconnect theheating completely. Eachdegree of temperaturereduction leads to a savingin heating energy of approx.6%. In the case of roomtemperature controllerswith night reduction, thetemperature is lowered byapprox. 5°C. Depending onthe thermostat used, the230 V input for the night

reduction must be interrupt-ed on detection ofmovement so that thethermostat regulates thetemperature to the normallevel. This circuit can beconverted with the help ofan external, NC relaycontact. A motion-dependent ON delay is alsolinked to the OFF delay. Ifthe OFF delay is set at > 10minutes, the HVAC output isonly activated if continuousmovement is detected. It isnot advisable for example toswitch the heating on (orincrease to comfort temper-ature) if someone brieflyenters the room.

L1

NL1

6804 UPush button/NO contact

N L1

NL1

6401 U-102Push button/NO contact

NL

NL1

6812 U-101

1077 U

N

1 2N

2L

1

L1

NL1

T>

RF

TA

N

L

Load

6402 U

Heating

1313

Automatic lighting control

Alternative 1Application without extension unit:Universal standard insert 6812 U-101Load types: max. 700 W/VABusch-Watchdog® Presence 6813Surface-mounted adapter 6885(if required)

Alternative 2Application with extension unit:Mos-Fet insert 6804 ULoad types: min. 40 W, max. 420 WBusch-Watchdog® Presence 6813Surface-mounted adapter 6885(if required)

Alternative 3Application with extension unit:Busch universal relay insert 6401 U-102Load types: max. 2300 W/VA Busch-Watchdog® Presence 6813Surface-mounted adapter 6885(if required)

Automatic lighting and heating control

Application with extensionunit and HVAC:Busch universal series insert 6402 U*Load types: max. 2300 W/VA Busch-Watchdog® Presence 6813Surface-mounted adapter 6885(if required)Room temperature controller insert 1077 U

* in preparation

141414

Application example: Large office (master/slave)

should be motion-dependent and implement-ed as the next stage.

Task

The lighting in a large officeshould be controlled by theBusch-Watchdog®

Presence. 3 detectorsmust be installed in parallel

in order to cover the areacompletely. It should alsostill be possible to switchthe lighting on and off viapush buttons. The controlof the heating system

Installation and settings

The installation sites of thepresence detectors mustbe selected directly abovethe workstations to providethe best level of detection.The sensors have an almostcircular detection area. Theareas must overlap slightlyto guarantee that there areno gaps in the detection.The master which the loadis connected to is responsi-ble for monitoring thebrightness level and the

OFF delay. Refer to the sin-gle office application forinformation about settingthe potentiometer. Theslaves have the task ofrouting detected movementto the master. To do so, the“Lux” potentiometer mustbe set to day mode(symbol: sun). The“Time/Light” potentiometermust be set to short-timepulse and the “Time/HVAC”potentiometer may not beset to test mode.

Gru

pp

e 2

30

20

1510 5

1

10sec

min

Time/Light

60

4030

15

1

5

T

Time/HVAC

Slave

1000

500

Lux

100

5

100030

20

1510 5

1

10sec

min

Time/Light

60

4030

15

1

5

T

Time/HVAC

Master

500

Lux

100

5

Additional integration of

heating control

The master alone takes onthe task of heating control.The slaves only ensure thatthe heating is increased ifmovement is detected intheir area. The settings ofthe master are identical to

those in the single officeapplication. The slaves alsoonly have the task of routingmovement in their areas tothe master. The potentiome-ter setting of the slaves isidentical to the onedescribed previously.

The“Time/HVAC”potentiometermay not be setto test mode.

15

6805 U 6804 U

N L1

NL1

6401 U-102Push button/NO contact

N L

6805 U

N L

6805 U

L1

NL1

Push button/NO contact

N L

1515

Automatic lighting control

Alternative 1Mos-Fet insert 6804 ULoad types: min. 40 W, max. 420 WBusch extension unit insert 6805 UBusch-Watchdog® Presence 6813Surface-mounted adapter 6885(if required)

Alternative 2Busch universal relay insert 6401 U-102Load types: max. 2300 W/VA Busch extension unit insert 6805 U

Automatic lighting and heating control

Busch universalrelay insert 6402 U*Load types: max. 2300 W/VABusch extension unit insert 6805 UBusch-Watchdog® Presence 6813Surface-mounted adapter 6885(if required)Room temperature controllerinsert 1077 U

* in preparation

1077 U

N

1 2N

2L

1

L1

NL1

T>

RF

TA

N

L

Load

N L

6805 U 6402 U

Heating

16

Application example: Large office (separate lighting circuits)

Task

The lighting in a large officeshould be controlled viapresence detectors. Thereare 4 workstations whoselighting should be controlled

separately via the Busch-Watchdog® Presence. Thecontrol of the heatingsystem should be motion-dependent and imple-mented at the next stage.

Installation and settings

The installation site of theBusch-Watchdog®

Presence should be select-ed directly above the work-stations to provide the bestlevel of detection. Thedetection area of each indi-vidual device must beadapted to the environmentby covering the long-distance plane or part ofthe medium-range plane(special film is suppliedwith the device) so thatonly the corresponding sec-tion is detected. In thisapplication, it is necessaryto ensure that the individuallighting circuits influenceeach other as little as possi-ble. The greater theinfluence exerted, the moredifficult the setting of the

brightness limit of each indi-vidual Busch-Watchdog®

Presence becomes.Increasing the brightnessby switching on an adjacentgroup of luminaires is thesame as an increase in theexternal brightness for theBusch-Watchdog® Presenceand can lead to thedisconnection of its groupof luminaires. If IR remotecontrol is to be used itshould be ensured that themaximum range of theremote control is 7 m. Torule out faulty operation/programming of otherdetectors it must be aimedas vertically as possible atthe Busch-Watchdog®

Presence which is to beoperated.

Additional integration of

heating control

The process is dependenton the respective heatingsystem. There are heatingsystems which permit eachheater to be controlled sep-arately. These heaters canbe regulated as describedin the single officeapplication. If it is not possi-

ble to control the heatingseparately for each area,the HVAC outputs of therespective universal seriesinserts 6402 U must beconnected in parallel. It istherefore ensured that theroom is heated even if onlyone workstation isoccupied.

Time/Light

30

20

1510 5

1

10sec

min

Lux

1000

500 100

5

Time/HVAC

60

4030

15

1

5

T

Example

Time/Light

Example

30

20

1510 5

1

10sec

min

Lux

1000

500 100

5

17

L1

NL1

6804 UPush button/NO contact

N L1

NL1

6401 U-102Push button/NO contact

NL

NL1

6812 U-101

1077 U

N

1 2N

2L

1

L1

NL1

T>

RF

TA

N

L

Load

6402 U

Heating

Automatic lighting control

Alternative 1Application without extension unit: Universal standard insert 6812 U-101Load types: max. 700 W/VABusch-Watchdog® Presence 6813Surface-mounted adapter 6885(if required)Alternative 2Application with extension unit:Mos-Fet insert 6804 ULoad types: min. 40 W, max. 420 WBusch-Watchdog® Presence 6813Surface-mounted adapter 6885(if required)Alternative 3Application with extension unit:Busch universalrelay insert 6401 U-102Load types: max. 2300 W/VA Busch-Watchdog® Presence 6813Surface-mounted adapter 6885(if required)

Automatic lighting and heating control

Application with extensionunit and HVAC:Busch universal series insert 6402 U*Load types: max. 2300 W/VA Busch-Watchdog® Presence 6813Surface-mounted adapter 6885(if required)Room temperature controller insert 1077 U

* in preparation

18

Application example: Toilet facilities

Task

Toilet facilities should becontrolled intelligently via aBusch-Watchdog®

Presence. The lighting isswitched dependent on

movement and brightness.The fan should only beswitched with motiondependence and with alonger OFF delay.

Lighting control

The lighting is switcheddirectly dependent onmovement and brightness.Depending on the roomdivisions, it is necessary to

install several detectorsusing the active extensionunit in order to be able todetect the individual areas(hand basins, urinals,cubicles).

60

4030

15

1

5

T

Time/HVAC

Master

30

20

1510 5

1

10sec

min

Time/Light

1000

500

Lux

100

5

Integration of the ventila-

tion system

The fan should not bedependent on brightnessbut should be switcheddependent on movement.The HVAC output can beused for this. Theadjustable OFF delay isdependent on theapplication.

Application 1

The fan should start with anON delay of 30 sec. andcontinue for a maximum of10 min. The setting on the“Time/HVAC”potentiometer must be setbetween 1 and 10 min.

Application 2

The fan starts with an ONdelay but only if amovement is detected overa longer period (e.g. 5 min.). This should preventthe fan from starting whensomeone has only enteredthe toilets for a short time.If a movement is detectedover a longer period, the fanshould continue for sometime. The “Time/HVAC”potentiometer must be setat > 10 min. The ON delayis based on the frequencyof movement in the firstfew minutes. If only onemovement is detected, theHVAC output is notswitched.

19

L1

NL1

6804 U

N L1

NL1

6401 U-102

NL

NL1

6812 U-101

Automatic lighting control

Alternative 1Application without extension unit:Universal standard insert 6812 U-101Load types: max. 700 W/VABusch-Watchdog® Presence 6813Surface-mounted adapter 6885(if required)Alternative 2Application with extension unit:Mos-Fet insert 6804 ULoad types: min. 40 W, max. 420 WBusch-Watchdog® Presence 6813Surface-mounted adapter 6885(if required)Alternative 3Application with extension unit:Busch universalrelay insert 6401 U-102Load types: max. 2300 W/VA Busch-Watchdog® Presence 6813Surface-mounted adapter 6885(if required)

Automatic lighting and heating control

Application with extension unit and HVAC:Busch universal series insert 6402 U*Load types: max. 2300 W/VA in totalBusch extension unit insert 6805 UBusch-Watchdog® Presence 6813Surface-mounted adapter 6885(if required)

* in preparation

N

1 2N

2L

1

L1

N L

6805 U6402 U

Fan

20

Application example: Constant lighting control

Task

Constant lighting controlensures increased comfortin offices and conferencerooms. The lighting isgenerally a mixture of

daylight and artificial light.In this type of lighting con-trol, the brightness is main-tained at a constant levelby dimming the artificiallight. If daylight alone is

sufficient, the artificial lightis switched off.

Lighting control

The lighting must bedimmable. The flush-mounted dimmer insert isselected dependent on theload (fluorescent lamps,incandescent lamps etc.).Manual intervention viaplateswitch or IR remotecontrol is also possiblewith constant lightingcontrol.

The lighting can beswitched on and off withthe plateswitch. It ispossible to distinguishbetween short and longoperations with IR remotecontrol. A short push buttonaction is identical to thefunction of the plateswitch.The lighting is dimmed aftera long push button action.

30

20

1510 5

1

10sec

min

Time/Light

1000

500

Lux

100

5

Adaptation of the

brightness limit with

remote control

Using infrared remotecontrol, it is possible toadapt the brightness limitwhich is kept at a constantlevel.

The lighting is dimmed dark-er or brighter after a longpush button action. If thedimming process hasfinished, the “Memo”button is pressed twice tostore the values.

21

NL1

1

6590 U-103

NL1

6550 U-101

N 1

N

L

Electronic lamp ballast

N

L

Electronic lamp ballast

Automatic lighting control

Alternative 1Busch-Universal-Dimmer® 6590 U-103*Load types: min. 50 W, max. 420 WBusch-Watchdog® Presence 6813

Alternative 2Memory control device 6550 U-101*Load types: min. 50 W, max. 700 WBusch-Watchdog® Presence 6813Surface-mounted adapter 6885(if required)

Automatic lighting control

Alternative 1Busch-Universal-Dimmer® 6590 U-103*Load types: min. 50 W, max. 420 WBusch-Watchdog® Presence 6813Busch extension unit insert 6805 U

Alternative 2Memory control device 6550 U-101*Load types: min. 50 W, max. 700 WBusch extension unit insert 6805 UBusch-Watchdog® Presence 6813Surface-mounted adapter 6885(if required)

* in preparation

Note: A relay (K1) must be used for constant

lighting control above 4 A.

NL1

N L

6805 U

1

6590 U-103

NL1

N L

6805 U6550 U-101

N 1

N

L

Electronic lamp ballast

K1

22

Application example: Interface to Busch-Powernet® EIB

Task

To extend a Busch-Powernet® EIB installationwith a presence detector,the outputs of the flush-mounted insert are

connected to the Busch-Powernet® EIB installationvia a binary input.

Installation and settings

The choice of location andthe detection area of theinstallation area is identicalto that of the single officeapplication. The outputs ofthe Busch-Watchdog®

Presence must be connect-ed to a binary input. Thiscan for example be mount-ed directly in suspendedceilings or installed in the

distribution board. The set-tings are identical to thoseof the single office applica-tion.The connection of theplate-switch and themaster/slave concept aswell as the use of IRremote control is possibleas described in theprevious applications.

Addition of heating

control

The universal series inserthas 2 outputs. Both outputsmust be linked to theBusch-Powernet® EIB via abinary input. Further heatingcontrol is then achieved byusing EIB. It is also a goodidea to lower the

temperature in the room viathe adjustable nightreduction of the appropriatethermostats if no movementis detected. All furthersettings regarding the OFF-delay in combination withthe intelligent ON-delay areidentical to those of thesingle office application.

23

Push button/NO contact L N

NL1

N L1

6401 U-102

E2

E1

6963 U

Automatic lighting control

Busch universal relay insert 6401 U-102Flush-mounted binary input 6963 UBusch-Watchdog® Presence 6813Surface-mounted adapter 6885(if required)Load is controlled via the Busch-Powernet® EIB switch actuator

Automatic lighting control

Busch universal series insert 6402 U*Flush-mountedbinary input 6963 UBusch-Watchdog® Presence 6813Surface-mounted adapter 6885(if required)Load is controlled via the Busch-Powernet® EIB switch actuator

* in preparation

Push button/NO contact L N

NL1

E2

E1

1 2N

2L

1

6402 U6963 U

23

2424

Busch-Watchdog® Presence EIBApplication example: Interface to ABB i-bus® EIB

Task

Controlling the lighting andtemperature in a room withstandby, comfort and night-time modes. The processneeds to be fully automatic

and involve both energysavings and costreductions. When linked tothe ABB i-bus® EIB, it ispossible for the respectivefunctions to communicate

and react with each other.The detection of variousbrightness values within aroom and the direct reactionto these values is alsorequired.

Example 1:

Presence/HVAC/Signal

Switching from standby

to comfort mode for light

and temperature

As soon as someone entersthe room, the presencedetector switches the lighton and the room thermostatswitches from standby tocomfort mode. If nobody isin the room, the heating is

set to standby mode oncethe respective overshootperiod has expired and thelight is switched off. In theevening, the roomthermostat is automaticallyset to night operation via atimer. The signallingfunction of the presencedetector is enabled at thesame time so that roommonitoring can take place.

1000

500

Lux

100

51000

500

Lux

100

5

Example 2: Presence

1/Presence 2/Signal

Detection and adjustment

of various brightness

values

The presence detector canprocess 2 brightness limitsand thus adjust to variablelighting conditions in theroom. This makes itpossible, for example to

switch-off the row ofluminaires at the window(setting = 200 lux) earlierthan the row inside theroom (setting = 300 lux).Once the signalling functionhas been successfullyactivated via the bus, it canbe used to monitor theroom.

2525

6121 U+ 6326-xx-101

+-

6164 U

-+

NL1

24V AC - 230V AC

6120 U+ 6131-74

+ -

EIB 24V

Up to 5 thermoelectronicvalve drives

Automatic control of the lighting and

heating with room monitoring

Busch-Watchdog®

Presence EIB 6131-74Bus coupler/1-fold switch actuator 6120 U/6110 U Busch-triton® room temperaturecontroller 6326-xx-101Bus coupler 6121 UHeating actuator 6164 U

Automatic control of the lighting on 2

levels with room monitoring

Switch actuator e.g. 6152 EB-101 Busch-triton® 3-fold 6322-xx Busch-Watchdog®

Presence EIB 6131-742 bus couplers 6120 U

+ -

6120 U+ 6322U

6120 U+ 6131-74

-+

6152 EB-101

+ -

+ -

L N

EB 24

NL1

26

1000

500

Lux

100

51000

500

Lux

100

5

Busch-Watchdog® Presence EIBApplication example: Interface to ABB i-bus® EIB

Example 3: Presence

1/Presence 2/HVAC

Individual reaction and

connection of the

heating or air

conditioning system

The lighting controlfunction corresponds toprevious application exam-

ples but also includes theHVAC mode. This meansthat if someone is in theroom, the heating or airconditioning system switch-es to comfort mode. Ifnobody is present, it revertsto the cost-effectivestandby function.

Example 4: Presence

detector combined with

constant light controller

Reaction to ambient

brightness by constant

lighting control

When dimmable electronicballasts are used (0-10 V),constant lighting controlcan be produced in additionto the presence detectorfunction. This combinationoffers the highest potentialfor saving energy in theroom. To do so, a constant

light controller such asOsram HF DIM MICO isconnected in parallel to the0-10 V control terminal ofthe electronic ballasts.

This controller maintains thelighting at a constant levele.g. at 500 lux. If theambiant light levelincreases, the artificial light-ing is dimmed down, sothat additional energy issaved even when the roomis occupied.

27

6164 U

+ -

6120 U+ 6131-74

6121 U+ 6326-xx-101

-+

NL1

+ -

EIB 24V

6152 EB-101+ -

L N

Automatic control of the lighting on 2

levels with heating control

Busch-Watchdog®

Presence EIB 6131-74Bus coupler 6120 UBusch-triton® room temperaturecontroller 6326-xx-101Bus coupler 6121 UHeating actuator 6164 USeries actuator 6152 EB-101

Automatic constant lighting control with

presence detection

Busch-Watchdog®

Presence EIB 6131-74Bus coupler 6120 UConstant light controller e.g. Osram HFDIM MICO

-+

6110+ 6131-74

L N

NL

+ -

EVG

Constant lightcontroller0-10V

EIB 24V

BJE

0001-0

-0068 /

7.01

/ 05

02-T

, dpi

010

509

Member ofthe ABB Group

P.O.Box D-58505 Lüdenscheid/Germany

Telephone: +49 (0) 23 51 95 60Telefax: +49 (0) 23 51 95 66 94www.busch-jaeger.com

Busch-JaegerElektro GmbH