BSES Bhawan, Nehru Place, New Delhi- 19 agreements, if any number of employees in various categories and last three (3) years turn over 2.0 Bid Validity : 3.0 All the Schedules filled-in : Yes 4.0 All the Deviations brought out in : Yes Schedule – E1and E2 5.0 All the drawings, write-ups, literature, : Yes leaflets, calculations, details, etc as called for in the specification attached 6.0 Is the Bidder agreeable to undertake this : Yes/No contract, if deviations stipulated by him are not acceptable to the Purchaser 382 BSES Bhawan, Nehru Place, New Delhi- 19 Volume – 2 Schedules & Annexure Schedule A Bidders Name : ____________________ Signature : ____________________ Name : ____________________ Designation : ____________________ Seal of Company Date : ____________________ 383 BSES Bhawan, Nehru Place, New Delhi- 19 Volume – 2 Schedules & Annexure Schedule B SCHEDULE – B TRANSFORMER OIL S.No Item Description Specification requirement Data by Vendor 1 Manufacturer Name Name 1.1 Address Address 1.2 Contact person Contact person 1.3 Contact no. Contact telephone no 2 Appearance of oil Clear, transparent and free from suspended matter or sediments Yes / No 3 Density at 29.50C Max. 0.89 g/cm3 4 Kinematics viscosity Max. 16 cSt at 270C 11 cSt at 400C 5 Interfacial tension at 270C 0.04 N/m min 6 Flash point Pensky-Marten (Closed), Min. 1400C 7 Pour Point, Max - 150C 8 Neutralization value 8.1 Total acidity, Max 0.03 mg KOH/g 8.2 Inorganic acidity/ Alkalinity Nil

BSES Bhawan

Embed Size (px)

DESCRIPTION

Bhawan BSES

Citation preview

Page 1: BSES Bhawan

BSES Bhawan, Nehru Place, New Delhi- 19

agreements, if any number ofemployees in various categories and last three(3) years turn over2.0 Bid Validity :3.0 All the Schedules filled-in : Yes4.0 All the Deviations brought out in : YesSchedule – E1and E25.0 All the drawings, write-ups, literature, : Yesleaflets, calculations, details, etc ascalled for in the specification attached6.0 Is the Bidder agreeable to undertake this : Yes/Nocontract, if deviations stipulated by himare not acceptable to the Purchaser382BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule ABidders Name : ____________________Signature : ____________________Name : ____________________Designation : ____________________Seal of Company Date : ____________________383BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule BSCHEDULE – BTRANSFORMER OILS.No Item Description Specification requirement Data by Vendor1 Manufacturer Name Name1.1 Address Address1.2 Contact person Contact person1.3 Contact no. Contact telephone no2 Appearance of oil Clear, transparent and freefrom suspended matter orsedimentsYes / No3 Density at 29.50C Max. 0.89 g/cm34 Kinematics viscosity Max. 16 cSt at 270C11 cSt at 400C5 Interfacial tension at 270C 0.04 N/m min6 Flash point Pensky-Marten(Closed), Min.1400C7 Pour Point, Max - 150C8 Neutralization value8.1 Total acidity, Max 0.03 mg KOH/g8.2 Inorganic acidity/AlkalinityNil9 Corrosive sulfur Non-corrosive10 Electric strengthbreakdown voltageAverage value of sixsamples10.1 New unfiltered oil. Min. 30 kV (rms) min.10.2 After filtration Min. 60 kV (rms)11 Dielectric dissipation factor(tan δ).

Page 2: BSES Bhawan

0.002 at 900C, Max0.0005 at 270C, Max12 Specific resistance (resistivity)12.1 At 900C, Min 150 X 1012 ohm-cm12.2 At 270C, Min 3000 X 1012 ohm-cm13 Oxidation stability13.1 Neutralization value afteroxidation, Max.0.15 mg KOH/g13.2 Total sludge, afteroxidation, Max.0.03 % by weight13.3 Max Tan delta 0.1 at 700C14 Ageing characteristicsafteraccelerated ageing(open breaker method withcopper catalyst)14.1 Specific resistance14.1(a) At 270C Min. 27 X 1012 ohm-cm14.1(b) At 900C Min 2 X 1012 ohm-cm14.2 Dielectric dissipationfactor (tan δ)0.10 at 900C Max14.3 Total acidity, Max 0.05 mg KOH/g14.4 Total sludge, Max 0.05 % by weight15 Presence of oxidation no antioxidant additives384BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule Binhibitor16 Water content, Max 40 ppm17 List of clients To be enclosed18 PCA content 3% max19 PCB content Not detectableBidders Name : ____________________Signature : ____________________Name : ____________________Designation : ____________________Seal of Company Date : ____________________385BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C1SCHEDULE – C111KV INDOOR SWITCHGEARSr. No. Description Incomer Buscoupler Outgoing Capacitor Transformer1 Switchgear assembly1.1 Make1.2 Type1.3 Reference standard1.4 Voltage (normal / Max.KV)1.5 Frequency (HZ)1.6 Short circuit rating1.7 Short time current anddurationA Impulse withstand (KVpeak)

Page 3: BSES Bhawan

B 1min. Power freq.withstand test(KV rms)2 Construction2.1 Metal clad construction(Yes / No)2.2 Degree of Portion2.3 Minimum thickness ofsheet metal used (mm)2.4 Draw out feature providedforABreaker with service, test& isolated position - Yes/NoB Voltage Transformer- Yes/ NoC Protection relays -Yes /No2.5 Breaker cubicleACubical door can beclosed with breaker in testand isolated position -Yes/ NoB Working zone units fromfloor level (mm)2.6All meters, switchgear &relays flush mounted type-Yes /No2.7 Minimum clear spacerequiredA Front for breakerwithdrawal (mm)386BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C1B Rear (mm)2.8 Typical vertical sectionA Overall dimensionsi. Length (mm)ii. Breath (mm)iii. Height (mm)B Weight (Kg)3 Bus Bar3.1 Make3.2 Material & grade3.3 Reference standard3.4 Cross section area (mm2)3.5 Bus connection (joints)A Silver plated -Yes /NoB Conventional made withanti oxide grease -Yes /No3.6 Rated continuous currentamps3.7Maximum temp. rise atrated continuous currentDFG C3.8 Short time current andduration KA … secs

Page 4: BSES Bhawan

3.9 DC resistance at 85 DEGC (Ω/m/Ø)3.10 Minimum clearance of busbar and connectionA Phase to phase (mm)B Phase to earth (mm)3.11 Bus bar provided withA Insulation sleeveB Phase barriersC Cast resin shrouds forjoint3.12 Bus bar supportedspacing (mm)3.13 Bus bar insulatorsA MakeB TypeC Reference standardD Voltage class (KV)E Min. creepage distance(mm)F Cantilever strengthKg/mm2G Net weight (Kg)387BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C14 Circuit Breaker4.1 Make4.2 Type4.3 Reference standard4.4 Related Voltage4.5 Related frequency4.6 Related current and itsreference ambient tempAContinuous current to limitthe max. temp. rise to55DEG C for silver platedconnections and 40DEG Cfor conventionalconnections4.7 Related operating duty4.8Symmetrical breakingcapacity at rated voltage &operating duty KA rms.4.9 Rated making current(Kap)4.10 Short time current andduration KA … secs4.11 Insulation levelA Impulse voltage withstandon 1/50 full waveA 1min. Power freq.withstand test(KV rms)4.12 Maximum overvoltagefactor while switching offA Un loaded transformerB Loaded transformerC Un loaded CABLES

Page 5: BSES Bhawan

D CapacitorE Motors4.13 Opening time max. Noload condition (ms)4.14Number of permissiblebreaker operation undervacuum loss4.15 At 100% breaking capacityA Opening time Max. (ms)B Arcing time max (ms)C Total break time (ms)4.16A Make time (Max) (ms)B Total closing time (ms)388BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C14.17 Total length of contacttravel (mm)4.18No. of breaker operationpermission withoutrequiring inspection,replacement of contactsand other main parts.A At 100% rated currentB At 100% rated breakingcurrent4.19 Types of contents4.20 Maximum clearance in air(mm) from live part4.21 Between phasesA Between live parts andgroundB Type of arc control deviceprovided4.22 Operating mechanismclosing4.23 TypeA No. of breaker operationsstoredB Trip free or fixed tripC Anti pumping featuresprovided4.24 Operating mechanismtrippingA TypeB No. of breaker operationsstoredC Trip free or fixed tripD Anti pumping featuresprovided4.25 Spring charging motorA RatingB MakeC Voltage and permissiblevariation(%)4.26 Closing coilA Voltage (V)

Page 6: BSES Bhawan

B Permissible voltagevariation (%)C Closing current at ratedvoltage (A)D Power at rated voltage (w)4.27 Trapping Coil389BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C1A Voltage (V)B Permissible voltagevariation (%)C Tripping current ratedvoltage (A)D Power at rated voltage (w)4.28Breaker / AccessoriesAccessories such ascontrol switch indicationlamps etc. furnished asspecified.(Please attach separatesheet giving details of allAccessories, inter locksand safety shutters)A Mechanical safetyinterlockB Automatic safety interlockC Operational interlockD Emergency manual tripE Operation counterF Change / dischargeindicatorG Manual spring chargingfacilityH Auxiliary switch with 6 No+ 6 NC for owner's useI Contacts wear indicator4.29 Auxiliary SwitchA Switch contacts typeB Contacts rating at1) Make & Continuous(Amps)2) Break (Inductive)(Amps)4.30 Net weighting of thebreaker (Kg)4.31Impact load foundationdesign ( to include deadload plus impact value onopening at maximuminterrupting rating) (Kg)4.32 On vacuum loss (Amps)A Possible load currentbreaker (Amps)B Possible fault currentbreaker (Amps)4.33 Overall dimensions390

Page 7: BSES Bhawan

BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C1A Length (mm)B Breath (mm)C Height (mm)4.34Type test reportomidentical breakerfurnished5 Control & Indications5.1 Push Button MakeA Type & Catalog No.B Contact rating at110V/220V.D.CC Make & continuous(Amps)5.2 LED lamps: Make:A Type & Catalog No.B Watts /VoltageC Lamps & lens replaceablefrom front with glass cover5.3 Selector switch: Make:A Type & Catalog No.B Contact ratingC Make & continuous(Amps)D Break (Inductive)(Amps)6 Current Transformer6.1 Make6.2 Types & Voltage Level6.3 Reference standard6.4 C.T ratio as specified6.5Short circuit withstandshort time current for 1sec. - KA rms Dynamiccurrent -KA peak6.6 Class of insulation6.7 Temperature rise6.8 Basic insulation level6.9 For metering & protectionA CT ratioB Class of accuracyC Rated burden VAD Knee point voltage VE Excitation current at VK / 4F Rated saturating currentAmp6.10 For differential & restrictedearth fault protection391BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C1A CT ratioB Class of accuracyC Rated burden VAD Knee point voltage VE Excitation current at VK / 4F Rated saturating current

Page 8: BSES Bhawan

Amp6.11 For restricted earth faultprotectionA CT ratioB Class of accuracyC Rated burden VAD Knee point voltage VE Excitation current at VK / 4F Rated saturating currentAmpG Secondary resistance (Ω)6.12 For stand by earth faultprotectionA CT ratioB Class of accuracyC Rated burden VAD Knee point voltage VE Excitation current at VK / 4F Rated saturating currentAmpGOver current ratingcontinuous % over load(%)6.13 For sensitive by earth faultprotection (CBCT)A CT ratioB Class of accuracyC Rated burden VAD Knee point voltage VE Excitation current at VK / 4F Rated saturating currentAmpGOver current ratingcontinuous % over load(%)7 Potential Transformer7.1 Make7.2 Types & Voltage Level7.3 Reference standard392BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C17.4 Voltage ratio7.5 AccuracyA Corer-1B Corer-27.6 Rated burdenA Corer-1B Corer-27.7 Over voltage factorA ContinuousB 30 Seconds7.8 Class of insulation7.9 Temperature rise overambient ( 0 C)7.10 Basic impulse level (KVpeak)7.11 Winding connection

Page 9: BSES Bhawan

A PrimaryB Secondary7.12 FusesA Continuous rating HV / LV(Amp)B Symmetrical fault ratingHV /LV KA rmsC Make7.13 Maximum ratio error atA90% to 100% of ratedvoltage and 25% to 100%of rated secondary burdenat unity power factorB90% to 106% of ratedvoltage and 10% to 50%of rated secondary burdenat 0.2 p.f.7.14 Maximum Phasedifference atA90% to 106% of ratedvoltage and 10% to 50%of rated secondary burdenat 0.2 p.f.B90% to 106% of ratedvoltage and 10% to 50%of rated secondary burdenat 0.2 p.f.7.15 E=Weight (Kg)8 Relay8.1 Manufacture8.2 Model Type393BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C18.3 Draw out type with built intest facilities. Yes/ No8.4 Built in test facility Yes /No8.5 Type of mounting8.6 Reference standard8.7 All relays furnished as perdrawing and specification8.8 All relevant relay leafletsand catalogue furnished8.9 Communication port type8.10 Auxiliary Supply8.11 Measurement and dataacquisition feature8.12 Control and supervisionA IEC protocolB Open protocol featureC Programming facilityD Separate output forindividual elementE Event recording facilitynumber of eventsF Required software offered

Page 10: BSES Bhawan

8.13 C.T.secondary current8.14 Self diagnostic feature8.15 Modular design8.16 Relay details8.16.1 Over currentA MakeB TypeC Characteristic availableDRange of settingi. Currentii. TimeERange of settingi. Currentii. TimeF Rated burden8.16.2 Synchronizing check relayA MakeB TypeC Setting range8.16.3 Earth faultA MakeB TypeC Characteristic available394BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C1DRange of settingi. Currentii. TimeE Rated burden8.16.4 Over current (Directional)A MakeB TypeC Characteristic availableDRange of settingi. Currentii. TimeE Rated burden8.16.5 Earth fault (Directional) ifapplicableA MakeB TypeC Characteristic availableDRange of settingi. Currentii. TimeE Rated burden8.16.6 Neutral unbalance relayA MakeB TypeC Characteristic availableDRange of settingi. Currentii. Time

Page 11: BSES Bhawan

E Rated burden8.16.7 Under voltage relayA MakeB TypeCRange of settingi. Currentii. TimeD Rated burden8.16.8 Over voltage relayA MakeB TypeCRange of settingi. Currentii. TimeD Rated burden8.16.9 Busbar differential relayA Make395BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C1B TypeC High impedance / lowimpedanceDFacility of CT radioadjustment possiblethrough software. Yes / NoE CT supervision facilityavailable. Yes /No8.16.10 Transformer differentialrelayA MakeB TypeC High impedance / lowimpedanceDFacility of CT radioadjustment possiblethrough software. Yes / NoEFacility of transformervector group adjustmentpossible through software.Yes/ NoF Setting rangeG Rated burden8.16.11 Restricted earth fault relayA MakeB TypeC Combined with differentialrelay. Yes / NoD Setting rangeE Rated burden8.16.12 Stand by earth fault relayA MakeB TypeC CharacteristicsD Setting range

Page 12: BSES Bhawan

E Rated burden9 Meters9.1 ammeterA MakeB TypeC Reference standardD SizeE ScaleF Accuracy class9.2 VoltmeterA Make396BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C1B TypeC Reference standardD SizeE ScaleF Accuracy class9.3 Energy MeterA MakeB TypeC Reference standardD SizeE ScaleF Accuracy classG MeasurementH kWhI kVARhJ kVAHK Any OtherL Data stored capabilityM Pulse output facilityN Data down loading facility10 Secondary Wiring10.1 Type of insulation10.2 Voltage grade10.3 Conductor material10.4 Conductor Size (minimum)and insulation wiringA Potential circuitB Control & current circuit11 Terminal Block11.1 Make11.2 Type11.3 Catalog No.11.4 20% spare terminalfurnished12 Cable Termination12.1 Clearance for power cabletermination12.2 Removable gland plateA Material for multicorecableB Material for single corecableC Thickness of plate13 Name Plate13.1 Material397

Page 13: BSES Bhawan

BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C113.2 Thickness13.3 Size forA Breaker cubicleB Instrument / devices14 Space heater / plugsocket14.1 Cubicle heaterA Thermostat controlledB WattageC VoltageD Resistance (ohms)E Thermostat range14.2 Plug SocketA TypeB Rating14.3Cubical heater & plugsocket circuit providedwith MCB's15 A.C. /D.C. Supply15.1 Isolated switches forincoming supplyA A.C. Type & ratingB D.C. Type & rating15.2 Isolated switches at eachcubicleA A.C. Supply type & ratingB D.C. Supply type & rating16 Tropical Protection16.1 Any Special treatment fortropical protection17 Painting17.1 Finish of switchgearA InsideB Outside18 No. of AccessoriesfurnishedA Breaker lifting & handlingtrolleyB Any other19 Tests19.1 Reference standard19.2 Routine test to beperformed on switchgear19.3 Type test certificatessubmitted20 Drawing / Data398BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C120.1 General arrangement forpanel board20.2 Foundation Panel20.3 Bill of material20.4Cross sectional drawingfor every type ofswitchgear (Add sheets if

Page 14: BSES Bhawan

necessary)Bidders Name : ____________________Signature : ____________________Name : ____________________Designation : ____________________Seal of Company Date : ____________________399BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C10SCHEDULE – C10AC DISTRIBUTION BOARDSS.No Description Buyers Requirement Sellers Data1 Panel Construction1.1 Enclosure Type Free standing, indoor, Fullycompartmentalized, Metal clad,Vermin Proof1.2 Enclosure degree of protection IP 5X1.3 Enclosure Material CRCA steel1.4 Load bearing members Minimum 2.5 mm thick1.5 Doors and covers Minimum 2.0 mm thick1.6 Gland Plate (detachable type) 3.0mm MS detachable type orAluminum 5.0mm for singlecore cables1.7 Separate compartment for Bus bar, circuit breaker,incoming cable, outgoing cablePT, LV instruments.1.8 Breaker compartment door Separate with lockable handle1.9 Fixing arrangementi. Doorsii. Coversiii. GasketConcealed hingedBolted with SS boltsNeoprene1.10 Panel Base Frame Steel base frame as permanufacturer’s standard.1.11 Handle Removable bolted covers forcable chamber and busbarchamber shall be provided with“C” type handles1.12 Space Heater Required1.13 Panel extension possibility Required2 MCCB2.1 Mounting Flush Mounted2.2 Rated Operational Voltage(V) 415 volt2.3 Ultimate breaking Capacity2.3.1 630A MCCB As per requirement2.3.2 100A MCCB As per requirement2.4 Rated Service breakingcapacity at rated voltage IcsIcs =100% Icu2.5 Rotary handle Required2.6 Interlocking arrangement Between Incomer MCCBs2.7 Trip time As per requirement2.8 Test Certificates Should have test certificates forbreaking capacities fromindependent test authorities400BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C10

Page 15: BSES Bhawan

CPRI / ERDA or equivalent3 MCB3.1 Rated Operational Voltage(V) 415 VAC 50 Hz3.2 Protection relay/Release Magnetic thermal release forover current and short circuitprotection3.3 Breaking capacity Shall not be less than 10 KA at415 VAC3.4 Mounting Din mounted3.5 MCB classification As required3.6 ISI Marked The complete range shall beISI markedBidders Name : ____________________Signature : ____________________Name : ____________________Designation : ____________________Seal of Company Date : ____________________401BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C2SCHEDULE – C266 kV CONTROL & RELAY PANELParameter Technical Particulars1.00.00 CONTROL PANEL BOARD1.01.00 Make1.02.00 Type1.03.00 Reference Standard1.04.00 Construction1.04.01 Degree of protection1.04.02 Sheet metal thickness mm1.04.03 Floor channel sills, vibration damping padsand kick plate furnished?1.05.00 Equipment Mounting1.05.01 All relays, meters and switches are flushmounted?1.05.02 Relays furnished in draw out cases withbuilt in test facilitate?1.06.00 Name plate1.06.01 Material1.06.02 Thickness1.06.03 Size for:-EquipmentPanels1.07.00 Mimic1.07.01 Material1.07.02 Width1.08.00 Internal Illumination1.08.01 Volt1.08.02 Watt1.08.03 Door switched controlled1.09.00 Space Heater1.09.01 Volt1.09.02 Watt1.09.03 Thermostat Controlled?1.10.00 Plug Socket1.10.01 Type1.10.02 Rating1.11.00Panel Illumination, space heater & plugsocket circuits provided with individual

Page 16: BSES Bhawan

switch fuse units?1.12.00 AC/DC Supply - Type & rating of isolatingswitch fuse units for1.12.01 Incoming AC Supply1.12.02 Incoming DC Supply1.13.00 Internal Wiring1.13.01 Wire Type1.13.02 Voltage Grade402BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C21.13.03 Conductor Material1.13.04 Conductor Size fori) Current / control circuitii) Voltage Circuit1.13.05 Wires identified at both ends with ferrules?1.14.00 Terminal block1.14.01 Make1.14.02 Type / Catalogue No1.14.03 20% spare terminals furnished?1.15.00 Ground Bus1.15.01 Materials1.15.02 Size (mm)1.16.00 Painting1.16.01 Type of finish1.16.02 Colour Shade - Inside/Outside1.16.03 Details of Painting procedure finished?2.00.00 BREAKER CONTROL SWITCH2.01.00 Make2.02.00 Type2.03.00 Reference Standard2.04.00 Contact Rating 220V DC 240V AC2.04.01 Make & Continuous (A)2.04.02 Break (inductive) (A)3.00.00 ISOLATING CONTROL SWITCH3.01.00 Make3.02.00 Type3.03.00 Reference Standard3.04.00 Contact Rating 220V DC 240V AC3.04.01 Make & Continuous (A)3.04.02 Break (inductive) (A)4.00.00 METER SELECTOR SWITCH4.01.00 Make4.02.00 Type4.03.00 Reference Standard4.04.00 Contact Rating 220V DC 240V AC4.04.01 Make & Continuous (A)4.04.02 Break (inductive) (A)5.00.00 PUSH BUTTON5.01.00 Make5.02.00 Type5.03.00 Reference Standard5.04.00 Contact Rating5.04.01 Make & Continuous (A)5.04.02 Break (inductive) (A)5.05.00 NO & type of Contacts provided per button6.00.00 LAMPS6.01.00 Make6.02.00 Type6.03.00 Reference Standard

Page 17: BSES Bhawan

6.04.00 Rating:403BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C26.04.01 Volt6.04.02 Watt6.04.03 Series Resistance6.05.00 10 % Extra lamps furnished?6.06.00 Size of lens7.00.00 SEMAPHORE INDICATORS7.01.00 Make7.02.00 Type7.03.00 Diameter of the Disc7.04.00 Operating voltage7.05.00 Burden (Watt DC)7.06.00 Whether latch in type or supply Failuretype8.00.00 INDICATING INSTRUMENT Ammeter Voltmeter8.01.00 Make8.02.00 Type8.03.00 Reference Standard8.04.00 Type of Movement8.05.00 Accuracy Class8.06.00 Scale in Degrees8.07.00 VA Burden9.00.00 MULTIFUNCTION METER9.01.00 Make9.02.00 Type9.03.00 Reference Standard9.04.00 Furnished in Draw out Case or not9.05.00 Type of Register9.06.00 Accuracy Class9.07.00 VA Burden9.07.01 Current Coil9.07.02 Voltage Coil10.00.00 ANNUNCIATOR10.01.00 Make10.02.00 Type10..03.00 Reference Standard10.04.00 No. of Annunciator groups furnished?10.05.00 No. of Windows per group10.06.00 Overall Dimension of a group (mm)10.07.00 Detailed Write-up on Scheme furnished?11.00.00 TRANCDUCERS11.01.00 Whether provided as per specification11.02.00 Make11.03.00 Type11.04.00 Output11.05.00 Accuracy11.06.00 Response Time11.07.00 Power Supply11.08.00 Isolation11.09.00 Catalogue furnished404BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C212.00.00 RELAYS Make Type12.01.00 Relays furnished in draw out cases withbuilt in test facilitates?12.02.00 Line Protection Panel

Page 18: BSES Bhawan

12.03.00 Transformer Panel12.04.00 Bus coupler Panel12.05.00 Miscellaneous Auxiliary Relays12.06.00 Auxiliary Relay, Voltage Operated with4 pair of contacts8 pair of contacts12.07.00 Auxiliary Relay, Current Operated with4 pair of contacts12.08.00 Catalogue of all relays submitted with bidBidders Name : ____________________Signature : ____________________Name : ____________________Designation : ____________________Seal of Company Date : ____________________405BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C3SCHEDULE – C3BATTERY CHARGERSr.No. Description Data to be filled by manufacturer1 Manufacturer equipment type2 Conformance to design standards as perspecification Yes / No3 Conformance to design features as perspecification Yes / No4 Submitted to deviation sheet for eachspecification clause no - Yes / No5 Panel dimension in mm ( length x depth x height)6 Panel weight in kg7 Panel enclosure protection offered8 Voltage regulation as per specification ( value tobe specified)9 Boost charging DC current adjustment range(Value to be specified)10Amount of Ripple in DC in %- output with battery- without battery11 Charger efficiency offered12 Max temperature rise above ambient13 Power factor at rated load14 Rectifier bridge as per specification15 Heat generated by the panel in Kw16 AC MCCB - Make , rating17 DC MCCB - Make , rating18 Rectifier transformer - Make , rating19 Semiconductor rectifier - Make , rating20 DC conductor - Make , rating21.1 DCDB integral part of charger or separate?21.2 MCB for DC distribution boards - Make, rating22 Conformance to metering & indication as perspecification23 Conformance to make of component as perspecification24 Conformance to mimic diagram, labels & finishas per specification25 Submission of component catalogue - Yes / No26 DC charger nominal output current - ( battery

Page 19: BSES Bhawan

trickle charge + DC load)27 DC charger boost charge current406BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C328 DC battery29 DC battery duty cycle30 DC distribution board output DP MCB feedersrequired30.1 63 amp DP MCB30.2 40 amp DP MCB30.3 25 amp DP MCB30.4 16 amp DP MCB30.5 10 amp DP MCBBidders Name : ____________________Signature : ____________________Name : ____________________Designation : ____________________Seal of Company Date : ____________________407BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C4SCHEDULE – C4Ni – Cd BATTERYS.NO. Description Data to be filledby Manufacturer1 Battery ( as per scope of supply annexure A) - Yes / No2 Manufacturing battery type3 Conformance to design standards as per specificationclause no. 2.0 - Yes / No4 Conformance to design feature as per specificationclause no. 3.0 & 4.0 - Yes / No5 Submitted of deviation sheet for each specificationclause no - Yes / No6 Battery GA drawing submitted - Yes / No6.1 Battery selection / sizing calculation submitted - Yes /No7 Battery rating (C5) offered in Ahr7.1 Rating at temperature 27 deg C as per IS7.2 Rating at temperature 20 deg C as per IEC8 Battery race type offered -steel or FRP8.1 Number of steps in a tire8.2 Number of tires in a rack9 Battery bank dimensions in mm ( length x depth xheight)10 Battery cell weight in kg11 Battery cell anode --- no. of plates & thickness in mm12 Battery cell cathode --- no. of plates & thickness in mm13 Battery cell nominal voltage13.1 Battery cell float charge voltage14 Battery cell maximum boost charge voltage15 Battery cell end cell voltage16 Total battery bank float charging voltage required involts17 Total battery bank boost charging voltage required volts17.1 Total time required for boost charging from and cellvoltage to rated voltage /capacity.18 Battery internal resistance ( in Ohms ) at fully chargedcondition19 Heat generated by battery at rated full load (in Kw)

Page 20: BSES Bhawan

20 Electrolyte chemical name21 Electrolyte specific gravity at 27 deg C22 Recommended topping up frequency (in weeks ormonths)23 Amount of gas evolution in one full charge dischargecycle (in liter / Ahr)24 Type of separators used in battery cell408BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C425 Shelf life period ( to retain 90% of energy from fullcharge condition at 27 deg C)26 Total battery bank short circuit fault level ( in KA)27 Battery bank terminal bus bar with insulating shrouds -Yes /NoBidders Name : ____________________Signature : ____________________Name : ____________________Designation : ____________________Seal of Company Date : ____________________409BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C5SCHEDULE – C5STATION AUXILIARY TRANSFORMERSr. Particulars Specified / Required Offered1.0 General1.1 Make1.2 Type Oil immersed, core type, step downlocated generally outdoor but maybe located indoor also with poorventilation. Bidder shall confirm fullrating available in indoor locationalso2.0 Nominal Continuous Rating, KVA2.1 HV winding 400kVA2.2 LV winding 400kVA3.0 Rated voltage ( kV )3.1 HV Winding 11 kv3.2 LV Winding 433 volt4.0 Rated current ( Amps )4.1 HV Winding4.2 LV Winding5.0 Connections5.1 HV Winding Delta5.2 LV Winding Star with neutral5.3 Vector Group reference Dyn116.0 Impedance at principal tap ratedcurrent and frequency, ohm @75 degC6.1 Impedance 5.0 % with IS tolerance410BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C56.2 Reactance6.3 Resistance6.4 Impedance at lowest tap at ratedcurrent and frequency6.5 Impedance at highest tap at ratedcurrent and frequency

Page 21: BSES Bhawan

7.0 Resistance of the winding at 750 C inohm7.1 a) HV7.2 b) LV8.0 Zero sequence impedance in ohm8.1 a) HV8.2 b) LV9.0 Guaranteed maximum losses atprincipal tap full load and 75°Cwithout any positive tolerance,kW9.1 No load losses (max.) 0.79.2 Load losses (max.) 5.19.4 Total I2R losses of windings @ 75deg C, KW9.5 Total stray loses @ 75 deg C, KW9.6 Total losses (max.), KW 5.89.7 No load loss at maximum permissiblevoltage and frequency (approx.),kW10.0 Temperature rise over referenceambient of 50 0C10.1 Top oil by thermometer 0 C 40 0C10.2 Winding by resistance 0 C 45 0C411BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C511.0 Efficiency11.1 Efficiency at 750C and unity powerfactor %11.1.1 at 110% load11.1.2 at 100% load11.1.3 at 80% load11.1.4 at 60% load11.1.5 at 40% load11.1.6 at 20% load11.2 Efficiency at 750C and 0.8 powerfactor lag %11.2.1 at 110% load11.2.2 at 100% load11.2.3 at 80% load11.2.4 at 60% load11.2.5 at 40% load11.2.6 at 20% load11.3 Maximum efficiency at 750C %11.4 Load and power factor at which itoccurs12.0 Regulation , (%)12.1 Regulation at full load at 750 C12.1.1 at unity power factor12.1.2 at 0.8 power factor lagging12.2 Regulation at 110% load at 750 C12.2.1 at unity power factor12.2.2 at 0.8 power factor lagging13.0 Tappings412BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C513.1 Type Off Circuit taps on HV winding13.2 Capacity Full capacity13.3 Range-steps x % variation +5% to -5% @ 2.5%

Page 22: BSES Bhawan

13.4 Taps provided on HV winding (Yes /No)Yes.13.5 Rated current of rotary switch 60 A14.0 Cooling system -14.1 Type of cooling ONAN14.2 No. of cooling unit Groups14.3 Capacity of cooling units14.4 Mounting of radiators14.5 Number of Radiators14.8 Total radiating surface , sqmm14.9 Thickness of radiator tubes, mm Minimum 1.2 mm15.0 Details of Tank15.1 Material Robust mild steel plate withoutpitting and low carbon content15.2 Thickness of sides mm15.3 Thickness of bottom mm15.4 Thickness of cover mm15.5 Confirmation of Tank designed andtested for Vacuum, Pressure ( Ref:CBIP Manual ) , (Yes/ No)15.5.1 Vacuum mm of Hg. / (kN/m2) As per CBIP15.5.2 Pressure mm of Hg. Twice the normal head of oil /normal pressure + 35kN/m2

whichever is lower, As per CBIP15.6 Is the tank lid sloped? Yes15.7 Inspection cover provided (Yes / No) as per clause 4.2.1.515.8 Location of inspection cover (Yes /No)15.9 Min. dimensions of inspection cover (413BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C5provide list of all inspection cover withdimension), mm x mm16.0 Core16.1 Type: Core16.2 Core material grade Premium grade minimum M416.3 Core lamination thickness in mm 0.27 Max16.4 Insulation of lamination With insulation coating on bothsides16.5 Design flux density at rated conditionat principal tap, Tesla16.6 Maximum flux density at 10 %overexcitation /overfluxing, Tesla1.9 Tesla16.7 Equivalent cross section area mm²16.8 Guaranteed No Load current at 100%rated voltage , Amps16.8.1 HV16.8.2 LV16.9 Guaranteed No Load current At 110%rated voltage, Amps16.9.1 HV16.9.2 LV17.0 Type of Winding17.1 HV17.2 LV17.3 Conductor material Electrolytic Copper17.4 Current density (HV/LV) Maximum allowed 3.0 A per sqmm.

Page 23: BSES Bhawan

At any tap17.5 Gauge/area of cross section ofconductor17.5.1 a) HV17.5.1 b) LV414BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C517.6 Insulating material17.6.1 HV Turn17.6.2 LV Turn17.6.3 LV Core -17.6.4 HV - LV -17.7 Insulating material thickness, mm17.7.1 HV Turn17.7.2 LV Turn -17.7.3 LV to Core17.7.4 HV to LV-18.0 Minimum design clearance, mm18.1 HV to earth in Air18.2 HV to earth in oil18.3 LV to earth in Air18.4 LV to earth in oil18.5 Between HV & LV in Air18.6 Between HV & LV in oil18.7 Top winding and yoke18.8 Bottom winding and yoke19.0 Insulating oil19.1 Quantity of oil Ltrs19.1.1 In the Transformer tank19.1.2 In each radiator19.1.4 Total quantity19.2 10% excess oil furnished? Yes19.3 Type of Oil As per BSES Spec Annex -C20.0 Bushing / Support Insulator20.1 Make -20.2 Type415BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C520.2.1 HV side As per Cl. 3.2.7.1 of the spec20.2.2 LV side As per Cl. 3.2.7.2 of the spec20.3 Reference Standard20.4 Voltage class, kV20.4.1 HV side Bushing/ Support Insulator 12 kV20.4.2 LV side line and neutral bushing/Support Insulator1.1 kV20.5 Creepage factor for all bushing /Support Insulator mm/KV31 mm / kV20.6 Rated thermal short time current20.6.1 HV bushing 25 times rated current for 2 secs.20.6.2 LV line and neutral bushing 25 times rated current for 2 secs.20.7 Weight, Kg20.7.1 HV bushing20.7.2 LV line and neutral bushing20.8 Free space required for bushingremoval, mm

Page 24: BSES Bhawan

20.8.1 HV bushing20.8.2 LV line and neutral bushing21.0 Terminal connections21.1 HV Cable size as per annexure A 22.021.2 LV Cable size as per annexure A 23.021.3 LV Neutral Cable size as per annexure A 23.022.0 H.V. Cable box Required22.1 Suitable for cable type , size As per annexure A cl. 22.022.2 Termination height, mm 750 mm, minimum22.3 Gland Plate dimension, mm x mm22.4 Gland Plate material Aluminium22.5 Gland Plate Thickness, mm 5 mm minimum22.5 Phase to phase clearance inside box,mm180 mm22.6 Phase to earth inside box, mm 120 mm416BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C522.7 HV Cable Box Protection Class IP 5523.0 L.V Cable termination arrangement With cable box23.1 Suitable for cable type , size Cable size as per annexure A cl.23.023.2 Termination height, mm 1000 mm, minimum23.3 Gland Plate dimension, mm x mm23.4 Gland Plate material Aluminium23.5 Gland Plate Thickness, mm 5 mm minimum23.5 Phase to clearance inside box, mm 25 mm minimum23.6 Phase to earth inside box, mm 25 mm minimum23.7 LV Cable Box Protection Class IP 5524.0 L.V neutral Cable terminationarrangementSeparate cable box not required25.0 Current Transformer on LV phases25.1 Type25.2 Make25.3 Reference Standard25.4 CT Ratio As per annexure C cl 21.025.5 Burden, VA As per Cl. 3.2.9.5 of the spec.25.6 Class of Accuracy As per Cl. 3.2.9.4 of the spec.25.7 CT terminal box size As per Cl. 3.2.9.8.1 of the spec.26.0 Pressure release device26.1 Minimum pressure the device is set torupture26.1.1 For Main Tank27.0 Fittings Accessories EachTransformer furnished as per ClauseNo 5. (Bidder shall attach separatesheet giving details, make and bill ofmaterials)417BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C528.0 Painting: as per clause for thetransformer, cable boxes, radiator,Marshalling box (Yes/No)29.0 Over all transformer dimensions29.1 Length, mm 170029.2 Breadth, mm 150029.3 Height, mm 1700

Page 25: BSES Bhawan

30.0 Transformer Tank Dimensions30.1 Length, mm30.2 Breadth, mm30.3 Height, mm31.0 Weight data31.1 Core, kG31.2 Frame parts, kG31.3 Core and frame, kG31.4 Total Winding, kG31.5 Core , Frame, Winding, kG31.6 Tank, kG31.7 Tank lid, kG31.8 Empty conservator tank, kG31.9 Each radiator empty, kG31.10 Total weight of all radiators empty, kG31.11 Weight of oil in Tank, kG31.12 Weight of oil in Conservator, kG41.13 Weight of oil in each Radiators, kG31.14 Total weight of oil in Radiators, kG31.16 Total Transport weight of thetransformer, kG32.0 Volume Data418BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C532.1 Volume of oil in main tank, litres32.2 Volume of oil between highest andlowest levels of main conservator,litres32.4 Volume of oil in each radiator, litres32.5 Total volume of oil in radiators, litres32.7 Transformer total oil volume, litres33.0 Shipping Data33.1 Weight of heaviest package, kG33.2 Dimensions of the largest package (Lx B x H) mm34.3 Tests34.1 All in process tests confirmed as perCl. (Yes/ No)34.2 All Type Tests confirmed as per Cl.(Yes / No)34.3 All Routine Tests confirmed as per Cl.(Yes/ No)34.4 All Special Tests confirmed as per Cl.(Yes/ No)Bidders Name : ____________________Signature : ____________________Name : ____________________Designation : ____________________Seal of Company Date : ____________________419BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C6SCHEDULE – C611kV CAPACITOR BANKSr. No. Description Data to be filled by Manufacturer2.0 Manufacturer equipment type/make3.0 Conformance to design standards as perspecification clause no. 2.0- Yes/No- Capacitor Unit

Page 26: BSES Bhawan

- Series Reactor- LA- Isolator4.0Conformance to capacitor designrequirements as per specification clause no.4.0 to 7.0 - Yes/No5.0 Submission of deviation sheet for eachspecification clause no. -Yes/No6.0 Capacitor single phase unit6.1 Enclosure sheet metal thickness in mm6.2Hermetic sealing method (pressurewelding/gas welding/sealant/ if any other pl.specify)6.3 No. of series group/unit6.4 No. of parallel elements/ series group6.5 No. of APP layers -double/triple6.6 Thickness of APP film6.7 Thickness of Al foil6.8 Maximum voltage stress per APP layer6.9 Rated capacitance in micro farad6.10 Output at rated system voltage (in kVAR)6.11 Rated current in Amp.7.0 Overall capacitor bank rating7.1At rated system voltage(in kVAR)(requirement is 5.4 MVAR at 11kV with subbank rating of 3.6 & 408 MVAR7.2 Rated current in Ampere7.3 Connection in double star?- Yes/No7.4 Space provided for future capacity addition asper Annexure B clause 9.0? -Yes/No7.5 Accessories provided for future capacityaddition as per Annexure B cl:9.0? -Yes/No7.6 Spare capacitor unit offered? Yes/No420BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C67.7 Series Reactor rating details(bank rating ≥22kV)8.0 Capacitor bank insulation level8.1 Impulse withstand voltage (kV peak)8.2 One minute power frequency withstandvoltage (kV rms)9.1 Bus bar cross-section in sq. mm9.2 Bus bar short time withstand capacity in kAfor 3sec10.1 Bus bar support insulator make & type10.2 Bus bar support insulator voltage class11 Capacitor unit maximum temperature riseabove ambient in Deg. Celsius12 Capacitor unit power loss in kilowatt13 Capacitor bank total power loss in kilowatt14.1 Discharge device type & material14.2Minimum time gap required betweencapacitor switching OFF & ON operation (insec.)15.0 Dimension in mm

Page 27: BSES Bhawan

15.1 Capacitor unit -width x breadth x height15.2 Capacitor bank -width x breadth x height15.3 Enclosure -width x breadth x height16.0 Weight in kg16.1 Capacitor single phase unit16.2 Steel enclosure & rack/structure16.3 Total assembly17.0 Neutral Current Transformer as per clause no.4.20 -Yes/No18.0 Conformance to label & finish as perspecification clause no. 7 -Yes/No19.0 Copy of type test certificate submitted? -Yes/No20.0 Submission of GA drawing/documentation asper Annexure A clause 2.0 -yes/NoBidders Name : ____________________Signature : ____________________Name : ____________________Designation : ____________________Seal of Company Date : ____________________421BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C7SCHEDULE – C7LT POWER CABLESFor each size / rating separate GTP need to be furnished.S.No. Description Buyer's requirement Seller's Data1 Make ………………2 Type (AS PER IS) A2XFY (Multicore)3 Voltage Grade (KV) 1.14 Maximum conductor temperatureA Continuous ( 0 C) 90 0CB Short time ( 0 C) 250 0C5 ConductorA Size (mm2) 4CX300,4CX50, 4CX25,4CX10 & 2CX10 SqmmB No. of wire in each conductors Nos. As per ManufacturerstandardC Dia of wires in each conductorsbefore compaction (mm)As per ManufacturerstandardD Shape of conductor As per specificationE Diameter over conductor (mm) ……………F Maximum conductor resistance at 200

C (ohm / km)As per table 2 of IS -7098Part -16 InsulationA Nominal thickness (mm) As per table 3 of IS -7098Part -1B Minimum thickness (mm) ……………C Diameter over insulation (mm)Approx ……………7 Inner SheathA Minimum thickness As per table 5 of IS -7098Part -1B Approx dia over sheath (mm) Approx ……………8 Galvanized steel Armour As per table 6 of IS -7098Part -1

Page 28: BSES Bhawan

A Number of strips As per manufacturer Std.B Size (Thickness X width ) in mm 0.8 x 4C Dia of wire for 2CX10sqmm 1.4mm MinD Dia over Armour -Approx ……………9 Outer Sheath As per table 8 of IS -7098Part -1A Thickness (Minimum)B Colour YellowC Weather proof paint (applicable for 2cx 10 sqmm and 4c x 10 sqmm only) ……………10 Approx. overall dia (mm) ……………11 End Cap Required12 Continuous current rating forstandard I.S. condition laid Direct422BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C7a. In ground 30 0C Amps ……………a. In duct 30 0C Amps ……………a. In air 40 0C Amps ……………13 Short circuit current for 1 sec ofconductor (KAmp) ………………14 Electrical Parameters at Maximumoperating temperatureA Resistance (Ohm / Km) (ACResistance) ……………B Resistance AT 50 C/s (Ohm / Km) ……………C Impedance (Ohm / Km) ………….D Capacitance (Micro farad /Km) …………15 Recommended minimum bendingradius …………….. X O/D16 De-rating factor for following AmbientTemperature in Ground /Aira. At 30 OCa. At 35 OCa. At 40 OCa. At 45 OCa. At 50 OC17 Group factor for following Nos. ofcables laid Touching TrefoilA 3 Nos.B 4 Nos.C 5 Nos.D 6 Nos.18 Process of cross linking ofpolyethylene Dry cureBidders Name : ____________________Signature : ____________________Name : ____________________Designation : ____________________Seal of Company Date : ____________________423BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C8SCHEDULE – C8CONTROL CABLESSr. Description Buyers's requirement Seller's Data1.0 Make2.0 Type (As per IS-1554 part-1) YWY3.0 Voltage Grade (kV) 1.1

Page 29: BSES Bhawan

4.0 Maximum conductor temperatureA Continuous (°C) 70°CB Short time (°C) 160°C5.0 ConductorA Size (mm2) 10CX2.5, 6CX2.5SqmmB No. of wire in each conductor Nos. As per Manufacturer standardC Dia. of wires in each conductorsbefore compaction (mm) As per Manufacturer standardD Shape of conductor As per the specificationE Maximum conductor resistance at20°C (Ω/Km.) As per Table 2 of IS 8130F Number of conductor core6.0 InsulationA Nominal thickness (mm) As per CI & table 2 of IS-1554Part-1B Minimum thickness (mm)C Diameter over insulation (mm)approx.7.0 Inner SheathA Minimum thickness As per Table 4 of IS-1554Part-1B Approx. dia Over sheath (mm)approx.8.0 Galvanized steel armoura) As per Cl 13.2 of IS 1554Part-1: Galvanized steelround wire armour.b) Minimum area of coverageof armouring shall be 90%.A Number of wire/strip As per Manufacturer standardB Size (Dia/thickness x width) in mmC Dia over Armour -Approx9.0 Outer SheathA Thickness (Minimum) As per Table 7 of IS-1554Part-1B Colour Black10.0 Approx overall dia (mm)11.0 End Cap Required12.0 Drums provide with MS Spindleplate & nut bolts arrangement Required424BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C813.0 Continuous current rating forstandard I.S. condition laid Directa) In ground 30°C Ampsb) In duct 30°C Ampsc) In air 40°C Amps14.0 Recommended minimum bendingradius 12 x O/D15 Minimum Armour Coverage 90% minimum16 Lay Ratios16.1 Main Conductor16.2 ArmourBidders Name : ____________________Signature : ____________________Name : ____________________Designation : ____________________Seal of Company Date : ____________________425

Page 30: BSES Bhawan

BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C9SCHEDULE – C9ILLUMINATION SYSTEM1 General+1.01 Make*1.02 Applicable Standards*1.03 Degree of protection2Lighting Panel /Feeder Pillarm Box(LP/ELP/DLP/FPB/EPB/LDB/ELDB/Construction Features)2.01 Make2.02 Rated Value (V)*2.03 Busbar continuous current rating (A)*2.04 Busbar material and cross section 1 2 33 Minimum current breakers :+3.01 Service3.02 Make+3.03 Type*3.04 No. of poles*3.05 Rated continuous current (A)*3.06 Short time current rating (Ka)*3.07 Related Voltage (V)*3.08 Breaking Current (Ka)4 Load Breaking Switches4.01 Service+4.02 Make+4.03 Type*4.04 No. of poles*4.05 Related Voltage (V)*4.06 Rated continuous current (A)*4.07 Rated making current (Ka peak)*4.08 Rated breaking current (Ka)*4.09 Rated short time one (1) second current(Ka)*4.10 Rated dynamic current (kApeak)5 Fuses5.01 Service+5.02 Make*5.03 Type*5.04 Standard applicable*5.05 Related Voltage (V)*5.06 Rated current (A)*5.07 Fusing factor426BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C9*5.08 Category of duty*5.09 Rupturing capacity (prospective current)(Ka)6 Earth Leakage current Breaker+6.01 Make+6.02 Type*6.03 No. of poles*6.04 Rated continuous current (A)6.05 Short time current rating (Ka)6.06 Rated Tripping current7 Lighting Fixtures Type A B C+7.01 Manufacturer

Page 31: BSES Bhawan

+7.02 Type7.03 Description of different types*7.04 Type and wattage of lamp*7.05 Rated life of the lamp*7.06 Applicable standardsNote:- In case luminaries other than the ones specified in specification are offered, allthe deviations shall be listed out otherwise these shall be considered as being fully inline with luminaries specified.8 Receptacles with Switches 1 2 3+8.01 Make+8.02 Type+8.03 Related Voltage (V)*8.04 Rated current (A)8.05 Technical brochures (Attach brochuresand state brochure Nos.)9 Cables / Wire 1 2 39.01 Service+9.02 Make+9.03 Type*9.04 Voltage Grade (V)*9.05 Conductor Material*9.06 Size of conductors (mm2)*9.07 Current rating of conductors (A)9.08 Applicable Standards10 Conduits and Accessories10.01 Make10.02 Type10.03 Material10.04 Applicable Standards11 Lamp and Luminaries IncandescentLampsFluorescentTubesHPSVLamps11.01 Make427BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C911.02 Type*11.03 Lumen output throughout life (Lumen)*11.04 Derating factor due to temperature*11.05 Derating factor due to aging12 Lighting Poles / Towers12.01 Manufacturer12.02 Applicable Standards12.03 Material and Painting12.04 HeightNotes :1. Single asterisk (*) marked particulars are guaranteed.2. Other particulars are bonafide and may vary slightly upon completion of detailed design.3. Particulars against items marked * and + shall be furnished with the Bid.Bidders Name : ____________________Signature : ____________________Name : ____________________Designation : ____________________Seal of Company Date : ____________________428BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C11

Page 32: BSES Bhawan

SCHEDULE – C11CABLE TRAYS, ACCESSORIES AND TRAY SUPPORT, CONDUITS, PIPESAND DUCTS1 Generala Name of the Contractorb Name of sub contractors, if anyc Applicable standards2 Cable Trays and Fittingsa Cable Trays and Fittingsi. Makeii. Typeiii. Material1. Thickness (mm)2. Thickness of galvanization (microns)3. Zinc coating per sq meter (gms)3 Conduits , Fitting and Accessoriesa Pipes with fittingi. Makeii. Typeiii. Material1. Thickness (mm)2. Thickness of galvanization (microns)b Flexible conduits with fittings and accessoriesi. Makeii. Typeiii. Material1. Thickness (mm)2. Thickness of galvanization (microns)Bidders Name : ____________________Signature : ____________________Name : ____________________Designation : ____________________Seal of Company Date : ____________________429BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C12SCHEDULE – C12GROUNDING & LIGHTNING PROTECTION SYSTEMS.No. Description Unit Data by vendor1 Earth mata Materialb Size of conductorc Fault withstand current & duration2 Equipment Earthinga Materialb Size of conductor3 Earth Electrodea Materialb Sizec Length4 Lightning Protection SystemaMaterial and size of horizontal airterminationb Material and size of vertical air terminationc Material and size of down conductord Size of test linke Material of enclosure for test linkf Material and size of earth electrode

Page 33: BSES Bhawan

Bidders Name : ____________________Signature : ____________________Name : ____________________Designation : ____________________Seal of Company Date : ____________________430BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C13SCHEDULE – C13CABLE ACCESSORIES1 Cable Accessories1.01 Makes1.02 Termination kits1.03 Straight through joint kits1.04 Cable glands1.05 Cable lugs1.06 Termination blocks1.07 Types1.08 Termination kits1.09 Straight through joints1.1 Cable glands1.11 Cable lugs1.12 Terminal blocksBidders Name : ____________________Signature : ____________________Name : ____________________Designation : ____________________Seal of Company Date : ____________________431BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C14SCHEDULE – C1466 KV OUT DOOR LIGHTNING ARRESTER432BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C14Corporate office: BSES Bhawan, Nehru Place, New Delhi- 19433BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C14Corporate office: BSES Bhawan, Nehru Place, New Delhi- 19Bidders Name : ____________________Signature : ____________________Name : ____________________Designation : ____________________Seal of Company Date : ____________________434BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C15SCHEDULE – C16GAS INSULATED SWITCHGEARProposed Technical data 66 / 11k V Gas insulated switchgearSr.No. Description Proposed Data1.0 Manufacturer2.0 Country of origin3.0 Type designation4.0 Indoor or outdoor

Page 34: BSES Bhawan

5.0Applied standard,publication number andyear6.0 Segregated phase type or‐common enclosure type7.0 Rate voltage kV rms8.0 Number of phase9.0 Rated lightning impulsewithstand voltage kV peak9.1 phase to earth9.2 phase to phase9.3 across open contact10.0 Rated 1 min powerfrequencywithstand voltage kV rms11.0 Auxiliary circuit 50HZ, 1 minwithstand voltage12.0 Rated frequency Hz13.0 Rated short time withstandcurrent kA14.0 Rated peak withstandcurrent kA15.0 Degree of protection forauxiliary and control circuit16.0 Rated supply voltage ofclosing and opening device Vdc17.0 Permissible ambienttemperature 0C435BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C1518.0 Maximum temperature riseat..................A19.0 Material of enclosure Al/alloy/steeI20.0 Average Thickness mm21.0 Guarantee SF6 gas lossesper compartment per year %22.0 Design Maintenance period23.0 Rated SF6 gas pressure at 200C24.0Minimum safe gas pressureat 200C required for safeoperation25.0 Setting of pressure reliefdevice ( 20 0C)26.0 Emergency operation atrated voltage and yes/no

Page 35: BSES Bhawan

27.0 No. of Gas Compartment27.1 Bus Bar27.2 Feeder28.0 Heat losses per feeder atrated power KW29.0 Bay width mm30.0 Volume of gas contained ineach compartment M331.0Burn through time ofenclosure for internal faultof 31.5KASec32.0 Weight per bay ( ready foroperation ) Sec33.0 Heaviest part Kg34.0 Net total weight Kg35.0 Packing detailed drawingnumber ( to be attached ) KgCIRCUIT BREAKER1.0 Manufacturer436BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C152.0 Country of manufacture3.0 Type designation, numberof pole4.0 Indoor or outdoor5.0Applied standard,publication number andyear6.0 Catalog number (to beattached)7.0 Outline drawing number (tobe attached)8.0 Rated voltage kV9.0 Rated lightning impulsewithstand voltage kV peak10.0 Rated 1 min powerfrequencywithstand voltage kV rms11.0 Rated frequency Hz12.0 Rated normal current A13.0 Rated short circuit breaking‐current kA14.0 Rated short circuit making‐current kA15.0 Rated duration of shortcircuit

Page 36: BSES Bhawan

s16.0 Rated operating sequence17.0 Short time withstand‐current, 3 sec kA18.0 Total break time ms19.0 Rated capacitive breakingcurrent A20.0 Rated small inductivebreaking current A21.0 Rated out of phase breaking‐ ‐current A22.0 Switching over currentfactor pu23.0 Rated characteristics of437BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C15short line faults23.1 TRV of supply circuit23.2 TRV peak value uc23.3time delay td24.0 Opening time24.1 Maximum25.0 Maximum closing time26.0 Maximum make time27.0 Minimum dead time28.0 Gas operating pressure28.1 Rated pressureat................... 0C Kg/cm28.2 Alarm pressureat................... 0C Kg/cm28.3 Lock out pressureat................... 0C Kg/cm29.0 Contacts29.1 Type of contact29.2 Material29.3 Surface treatment29.4 Maximum temperature riseat.......A 0C30.0Guaranteed contact life interms of number ofoperation31.0 Operating mechanism31.1 Type31.2Method of operation

Page 37: BSES Bhawan

(hydraulic, pneumatic ormotor operated springcharging)438BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C1531.3 Mechanical life in terms ofnumber of operation31.4 Method of interlocking31.5 Number of auxiliarycontacts, NO/NC31.6 Rated voltage of tripping,closing and31.7 interlocking coil vdc31.8 Method of interlocking32.0 Motor32.1 Rated voltage32.2 Voltage range in % of rated32.3 Number of phase32.4 Frequency32.5 Power33.0Number of operationswithin one maintenanceperiod33.1At rated normal currentRecommended33.2 Maximum33.3 At Rated Breaking capacityRecommended33.4 Maximum33.5 Accumulated current perone set KA33.6 Static weight complete set Kg33.7 Dynamic weight completeset Kg33.8 Detailed complete set ofdrawing to be attachedCONDUCTOR439BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C15S.No. Description Proposed DataLine & Buscoupler BaysTransformer

Page 38: BSES Bhawan

Bays1.0 Manufacturer2.0 Country of manufacture k V3.0 Type designation, numberof poleK V peak4.0 Indoor or outdoor kV rms5.0Applied standard,publication number andyearHz6.0 Catalog number (to beattached)A7.0 Outline drawing number (tobe attached)8.0 Material9.0 Rated voltage10.0 Rated lightning impulsewithstand voltage11.0 Rated 1 min powerfrequencywithstand voltage12.0 Voltage13.0 Rated normal current14.0 Rated short time withstandcurrent, 1sec. kA15.0 Rated Peak withstandcurrent Amp16.0 Rated capacitive current Amp17.0 Gas operating pressure18.0 Rated pressureat................... 0Ckg/cm19.0 First stage alarm pressureat................... 0C20.0 Second stage alarmpressure at................... 0C21.0 Material ( Copper oraluminum)440BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C1522.0 Packing detailed drawingnumber( to be attached)DISCONNECTORS.NO. Description Proposed DataBus Other

Page 39: BSES Bhawan

DisconnectorDisconnector1.0 Manufacturer2.0 Country of manufacturer3.0 Type designation, numberof poles, indoor or outdoor4.0Applied standard,publication number andyear5.0 Catalog number (to beattached)6.0 Outline drawing number (tobe attached)7.0 Rated voltage kV8.0 Rated lightning impulsewithstand voltage8.1 To earth and betweenpole kV peak8.2 Across isolating distance kV peak9.0 Rated power frequencywithstand voltage, 1 min9.1 To earth and between pole kV rms9.2 Across isolating distance kV rms10.0 Rated frequency11.0 Rated normal current12.0 Rated short time withstandcurrent , 3 sec. kA13.0 Rated duration of shortcircuit s441BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C1514.0 Rated peak withstandcurrent kA peak15.0Rated capacitive breakingcurrent and recoveryvoltage A, kV16.0Rated inductive breakingcurrent and recoveryvoltage A, kV17.0 Closed loop currentswitching A, V18.0 Gas operating pressure kA18.1 Rated pressureat................. 0C kg/cm

Page 40: BSES Bhawan

18.2 First stage alarm pressureat................. 0C kg/cm18.3 Second stage alarmpressure at............... 0C kg/cm19.0 Contact19.1 Type19.2 Material19.3 Surface treatment19.4 Temperature riseat............................... 0C20.0 Operating mechanism20.1 Type20.2 Method of operation20.3 Method of interlocking20.4 Operating time, close/open s20.5 Number of auxiliary contact,NO/NC20.6 Power requirement W20.7 Rated supply voltage Vac/phaseRated supply frequency HzRecommendedmaintenance period YearPacking detailed drawingnumber( to be attached )442BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C15Earthing SwitchS.No. Description Proposed DataHigh Speed Slow Acting1.0 Operating speed2.0 Manufacturer3.0 Country of manufacturer4.0 Type designation, numberof poles, indoor or outdoor5.0Applied standard,publication number andyear6.0 Catalog number( to beattached)7.0 Outline drawing number( tobe attached)8.0 Rated voltage k V9.0 Rated lightning impulsewithstand voltage k Vpeak10.0 Rated power frequencywithstand voltage, 1 min. k Vrms

Page 41: BSES Bhawan

11.0 Rated frequency Hz12.0 Rated short circuit making‐current A13.0 Guranteed number of shortcircuitmaking operation14.0 Rated short time withstand‐current15.0 Rated duration of shortcircuit16.0 Rated peak withstandcurrent17.0 Gas operating pressure17.1 Rated pressure at.................0C17.2 First stage alarm pressureat.................. 0C17.3 Second stage alarmpressure at............. 0C443BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C1518.0 Contact18.1 Type18.2 Material18.3 Surface treatment18.4 Temperature riseat................................A19.0 Operating mechanism19.1 Type19.2 Method of operation19.3 Method of interlocking19.4 Operating time, close/open19.5 Number of auxiliary contact,NO/NC19.6 Power requirement W20.0Rated supply voltageVac /Phase20.1 Vdc20.2 Rated supply frequency Hz21.0 Interrupting capability21.1 Inductive current21.2 Interrupting current21.3 Recovery voltage22.0 Capacitive current22.1 Interrupting current22.2 Recovery voltage22.3 Recommended

Page 42: BSES Bhawan

maintenance period23.0 Packing detailed drawingnumber ( to be attached )24.0 Interrupting capabilityVOLTAGE TRANSFORMERS.NO. DescriptionProposed Data1.0 Manufacturer444BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C152.0Country3.0 Type designation, numberof phases4.0Applied standard,publication number andyear5.0 Catalog number (to beattached)6.0 Outline drawing number (tobe attached)7.0 Rated voltage k V8.0 Rated Lightning impulsewithstand voltage k V peak9.0 Rated power frequencywithstand voltage, 1 min kV rms10.0 Rated frequency Hz11.0 Rated burden VA12.0 Rated second voltage V13.0 Metering core13.1 Rated output and accuracyclass13.2 Rated transformation ratio13.3 Rated voltage factor14.0 Protective core14.1 Rated output and accuracyclass14.2 Rated transformation ratio14.3 Rated voltage factor15.0 Class of insulation andmaterial 0C16.0 Maximum temperature riseat...........................A kg17.0 Net weight18.0 Packing detailed drawing (to be attached )

Page 43: BSES Bhawan

445BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C15Current TransformerS.No. Description Proposed DataLine BusCouplerTransformerBay Bay Bay1.0 Manufacturer2.0Country of manufacturer3.0 Type designation, numberof phases4.0Applied standard,publication number andyear5.0 Catalog number (to beattached)6.0 Outline drawing number (tobe attached)7.0Mounted inside GISenclosure or on powercables8.0 Ring type or bushing type9.0 Rated voltage kV10.0 Rated lightning impulsewithstand voltagekV peak11.0 Rated power frequencywithstand voltage, 1 minkV rms12.0Rated frequency Hz13.0 Rated primary current A14.0 Rated short time thermalcurrent(3s) kA15.0 Rated dynamic current kA peak16.0Rated continuous thermalcurrent in percentage ofrated primary current %17.0 Class of insulation &446BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C15

Page 44: BSES Bhawan

material18.0Maximum temperature riseat......................A19.0 Metering core19.1 Rated transformation ratio19.2 Rated output and accuracyclass19.3 Instrument security factor20.0 Protection core20.1Rated transformation ratio20.2 Rated output and accuracyclass20.3 Accuracy limit factor21.0 Net weight22.0 Packing detailed drawingnumber ( to be attached )Sealing EndS.No. Description Proposed Data1.0 Manufacturer2.0 Standards3.0 Material4.0 Rated power frequencyvoltageYes / no4.1 ( 1 min/20 _C ) k V5.0 Breakdown dielectric stress k V /mm6.0 Maximum working dielectricstress k V /mm7.0 Impulse withstand voltage k V8.0 Creepage distance (minimum )mm9.0 Expansion devices Yes / no10.0 Splicing method ofconductor447BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C1511.0 Compound for internalinsulation12.0 Nominal weight Kg /pcBay BoardS.No Description Proposed Data1.0 Manufacturer2.0 Type3.0

Page 45: BSES Bhawan

Applied standard,publication number andyear4.0 Confirm to be suppliedaccording to specification Yes /no5.0Material5.1Steel thickness ( minimum )5.2 door Mm‐5.3 side/top/near panels Mm‐6.0 Surface finish k V /mm6.1 Total Paintthickness(Minimum)7.0 Dimension7.1 Length7.2 Width7.3 Height8.0 Total net weight9.0 Packing detailed drawingnumber( to be attached)Type test certificationType test made on identical design of equipment tothose offeredProposed Data448BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C15a Circuit breakersTerminal faults: ( Test duties1,2,3,4 and 5to IEC 56 ) ( with a firstphase to clear factor of 1.5 )Making currentShort time current‐DielectricTemperature riseMechanical enduranceShort line faults ( 60%, 75%,‐90% )Out of Phase tests‐ ‐Capacitance switchingLow inductive switchingSpecial tests : ParallelswitchingPartial dischargesb) DisconnectorsShort time current One second‐

Page 46: BSES Bhawan

ThreesecondPeak currentDielectric withstandTemperature enduranceCapacitance switchingPeak currentc) Busbars and ConnectionsShort time current One second‐Threesecondd) Earthing switchesShort time current One second‐Threesecond449BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C15Peak currentMaking current capabilityDielectric withstandDielectric withstandMechanical enduranceType Tests Made onIdentical Designs ofEquipment to ThoseOfferedInterrupting capability forline coupling currents : capacitive currents‐ inductive currents‐

Peak currentMaking current capabilityDielectric withstandBidders Name : ____________________Signature : ____________________Name : ____________________Designation : ____________________Seal of Company Date : ____________________450BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C16SCHEDULE – C16POWER TRANSFORMERSr.No. Particular Specified / Required Offered1.0 General1.1 Make1.2 Type As per Annexure C ofspecification2.0 Nominal continuous rating, KVA2.1 HV winding As per Annexure C ofspecification

Page 47: BSES Bhawan

2.2 LV winding As per Annexure C ofspecification2.3 Type of Cooling ONAN/ONAF2.4 Rating available at different cooling ONAN - 80%ONAF-100%3.0 Rated voltage (KV)3.1 HV winding As per Annexure C ofspecification3.2 LV winding As per Annexure C ofspecification4.0 Rated current (Amps)4.1 HV winding4.2 LV winding5.0 Connections5.1 HV winding As per Annexure C ofspecification5.2 LV winding As per Annexure C ofspecification5.3 Vector group reference As per Annexure C ofspecification6.0 Impedance at principal tap ratedcurrent and frequency at 75 °C with 100% Rating (% )6.1 Impedance (% ) As per Annexure C ofspecification6.2 Reactance (% )6.3 Resistance (% )6.4 Impedance at lowest tap rated currentand frequency at 75 °C with 100 %Rating (% )6.5 Impedance at highest tap rated currentand frequency at 75 °C with 100 %Rating (% )7.0 Resistance of the winding at 750Catprincipal tap (ohm)7.1 a) HV451BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C167.2 b)LV8.0 Zero sequence impedance ( ohm )8.1 a) HV8.2 b) LV9.0 Guaranteed maximum losses atprincipal tap at full load and 750 Cwithout any positive tolerance kW9.1 No load losses (max.) As per Annexure C ofspecification9.2 Load losses (max.) As per Annexure C ofspecification9.3 Cooler fan losses (max.)9.4 Total I2R losses of winding @ 75 deg C9.5 Total stray losses @ 75 deg C9.6 Total Load losses (max.)9.7 No load loss at maximum permissiblevoltage and frequency (approx.) kW10.0 Temperature rise over reference designambient of 40 0C10.1 Top oil by thermometer 0C 400 C10.2 Winding by thermometer 0C 450 C

Page 48: BSES Bhawan

10.3 Winding gradient at rated current 0C10.3.1 HV10.3.2 LV11.0 Efficiency11.1 Efficiency at 750 C and unity powerfactor %11.1.1 At 110% load11.1.2 At 100% load11.1.3 At 80% load11.1.4 At 60% load11.1.5 At 40% load11.1.6 At 20% load11.2 Efficiency at 750 C and 0.8 power factorlag %11.2.1 At 110% load11.2.2 At 100% load11.2.3 At 80% load11.2.4 At 60% load11.2.5 At 40% load11.2.6 At 20% load11.3 Maximum efficiency %11.4 Load and power factor at which Maxefficiency occurs12.0 Regulation (%)12.1 Regulation at full load at 750 C12.1.1 At unity power factor12.1.2 At 0.8 power factor lagging12.2 Regulation at 110% load at 750 C12.2.1 At unity power factor12.2.2 At 0.8 power factor lagging452BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C1613.0 Tapping13.1 Type13.2 Capacity13.3 Range-steps x % variation As per Annexure C ofspecification13.4 Taps provided on HV winding (Yes/No)14.0 OLTC gear14.1 Make14.2 Type14.3 Reference std14.4 No of compartment14.5 Mounting arrangement Side mounted14.6 Rated current Amp14.7 Rated step capacity, kVA14.8 Short circuit withstand for 2 secs, kA14.9 Time required for one step change sec.14.10 Rated voltage for motor, V AC14.11 Rating of motor14.12 Rated voltage for auxiliaries V14.13 Consumption of auxiliaries14.14 OLTC features as per specification,Yes/No14.15 Does the overload rating of OLTCmatch with that of the transformer underall conditions Yes/No15.0 Transformer Monitoring relay – REGDA15.1 Make

Page 49: BSES Bhawan

15.2 Reference standard15.3 Overall dimensions, mm16.0 Cooling system16.1 Type of cooling As per Annexure C ofspecification16.2 No. of cooling unit groups16.3 Capacity of cooling units16.4 Mounting of radiators16.5 Number of radiators and Size16.6 Type & size of radiator header mainvalve16.7 Type & size of individual radiator valve16.8 Total radiating surface, sq mm16.9 Thickness of radiator tubes, mm Minimum 1.2 mm16.10 Schematic flow diagram of the coolingsystem furnished (Yes/No)16.11 Type and make of Fan motor16.12 No. of fan motor per bank (Working +Standby )16.13 Rated Power Input ( kW)16.14 Rated Voltage, Speed of Motor16.15 Efficiency of motor at Full load(%)16.16 Locked Rotor current(Amps)17.0 Details of tank453BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C1617.1 Material Robust mild steel platewithout pitting and lowcarbon content17.2 Thickness of sides mm17.3 Thickness of bottom mm17.4 Thickness of cover mm17.5 Confirmation of tank designed andtested for vacuum pressure (Ref: CBIPmanual ) (Yes/No)17.5.1 Vacuum mm of Hg. / (kN/m2) As per CBIP17.5.2 Pressure mm of Hg Twice the normal head ofoil / normal pressure + 35kN/m2 whichever is lower ,As per CBIP17.6 Is the tank lid slopped? Yes17.7 Inspection cover provided (Yes/No) As per clause No 3.2.1.517.8 Location of inspection cover (Yes/No) As per clause No 3.2.1.517.9 Min. dimensions of inspection cover(provide list of all inspection cover withdimension), mm x mm18.0 Core18.1 Type: Core18.2 Core material grade Premium grade minimumM4 or better18.3 Thickness of lamination mm Max. 0.27 mm withinsulating coating on bothsides18.4 Insulation between core lamination18.5 Design flux density of the core at ratedcondition at principal tap, Tesla18.6 Maximum flux density allowed in thecore at extreme over excitation / overfluxing , Tesla

Page 50: BSES Bhawan

18.7 Equivalent cross section area of core,mm2

18.8 Guaranteed No load current at 90% /100% / 110% rated voltage & frequency( Amp )18.8.1 HV18.8.2 LV19.0 Type of winding19.1 HV19.2 LV19.3 Conductor material Electrolytic copper as perrelevant standard19.4 Maximum current density allowed, Ampper mm2

3.0 A/ mm2

19.5 Gauge/area of cross section ofconductor, mm2

19.5.1 HV19.5.2 LV454BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C1619.6 Maximum current density achieved inwinding (LV/HV/HVT) – Amps/mm2

19.7 Insulating material19.7.1 HV turn19.7.2 LV turn19.7.3 LV- core19.7.4 HV-LV19.8 Insulating material thickness, mm19.8.1 HV turn19.8.2 LV turn -19.8.3 LV to core19.8.4 HV to LV20.0 Minimum design clearance , mm20.1 HV to earth in air20.2 HV to earth in oil20.3 LV to earth in air20.4 LV to earth in oil -20.5 Between HV & LV in Air20.6 Between HV & LV in oil20.7 Top winding and yoke -20.8 Bottom winding and yoke21.0 Insulating oil21.1 Quantity of oil Ltrs -21.1.1 In the transformer tank21.1.2 In each radiator21.1.3 In OLTC chamber21.1.4 Total quantity21.2 10% excess oil furnished? Yes21.3 Type of oil New insulating oil as per IS:335, and CI. 4.2.7 of thespecification21.4 Oil preservation system provided(Yes/No)As per Annexure C ofspecification22.0 Bushing22.1 Make

Page 51: BSES Bhawan

22.2 Type22.3 Reference standard22.4 Voltage class, kV22.4.1 HV side bushing22.4.2 LV side line and neutral bushing22.5 Creepage factor for all bushing mm / kV As per Annexure C ofspecification22.6 Rated current , Amp22.6.1 HV bushing22.6.2 LV line and neutral bushing22.7 Rated thermal shortcurrent22.7.1 HV bushing As per Annexure C ofspecification22.7.2 LV line and neutral bushing As per Annexure C of455BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C16specification22.8 Weight Kg22.8.1 HV bushing22.8.2 LV line and neutral bushing22.9 Free space required for bushingremoval, mm22.9.1 HV bushing22.9.2 LV line and neutral bushing23.0 Terminal connections23.1 HV As per Annexure C ofspecification23.2 LV As per Annexure C ofspecification23.3 LV Neutral As per Annexure C ofspecification24.0 H.V. Cable box/Terminals24.1 Suitable for cable/conductor type size As per Annexure C ofspecification24.2 Termination height , mm 1000 mm , minimum24.3 Gland plate dimension mm x mm24.4 Gland plate material Aluminum24.5 Gland plate thickness , mm 5 mm minimum24.5 Phase to clearance inside box /terminals , mm24.6 Phase to earth inside box / terminals ,mm25.0 L.V line side cable box25.1 Suitable for cable type , size As per Annexure C ofspecification25.2 Termination height , mm 1000 mm , minimum25.3 Gland plate dimension mm x mm25.4 Gland plate material Aluminum25.5 Gland plate thickness , mm 5 mm minimum25.6 Phase to clearance inside box /terminals , mm25.7 Phase to earth inside box , mm26.0 LV Neutral cable box26.1 Suitable for cable type , size As per Annexure C ofspecification26.2 Termination height , mm26.3 Gland plate dimension mm x mm26.4 Gland plate material Aluminum

Page 52: BSES Bhawan

26.5 Gland plate thickness , mm 5 mm minimum26.6 Phase to clearance inside box , mm26.7 Phase to earth inside box , mm27.0 Marshalling box cubical provided as perclause no. of spec. (Yes / no)27.1 Mounting of marshalling box Project specific to be filledup (Separate / tankmounted )456BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C1628.0 Neutral Current Transformer (NCT)28.1 Type28.2 Make28.3 Reference standard28.4 CT Ratios28.5 Burden ,VA28.6 Class of Accuracy PS 5P2028.7 KPV , volts , minimum28.8 Resistance, ohm @ 75 deg C,maximum28.9 Magnetizing current @ Vk/4 , mA ,maximum28.10 Short time withstand current 26.3 kA for 3 sec.29.0 Winding current transformer (WCT)29.1 Type29.2 Make29.3 Reference standard29.4 CT ratio29.5 Burden ,VA Manufacturer Std.29.6 Class of accuracy Manufacturer Std.30.0 Pressure release device30.1 Minimum pressure the device is set torupture30.1.1 For main tank30.1.2 For OLTC31.0 Alarm and trip contact ratings ofprotective devices31.1 Rated/making/ breaking currents , Amp@ voltage for31.1.1 PRV for main tank31.1.2 PRV for OLTC31.1.3 Buchholz relay31.1.4 Oil surge relay for OLTC31.1.5 Sudden pressure relay31.1.6 OTI31.1.7 WTI31.1.8 Magnetic oil gauge32.0 Fittings accessories each transformerfurnished as per clause No. (Biddershall attach separate sheet givingdetails, make and bill of materials)33.0 Painting: as per clause for thetransformer , cable boxes, radiator,marshalling box, RTCC etc (Yes/No)34.0 Over all transformer dimensions34.1 Length , mm 6.5 meters maximumallowed34.2 Breadth , mm 5.0 meters maximumallowed

Page 53: BSES Bhawan

34.3 Height , mm 5.0 meters maximum457BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C16allowed35.0 Transformer tank dimensions35.1 Length , mm35.2 Breadth , mm35.3 Height , mm36.0 Marshalling box dimensions36.1 Length , mm36.2 Breadth , mm36.3 Height , mm37.0 Weight data37.1 Core, kG37.2 Frame parts, kG37.3 Core and frame, kG37.4 Total winding, kG37.5 Core and frame winding, kG37.6 Tank, kG37.7 Tank lid, kG37.8 Empty conservator tank , kG37.9 Each radiator empty , kG37.10 Total weight of all radiator empty , kG37.11 Weight of oil in tank , kG37.12 Weight of oil in each conservator , kG37.13 Weight of oil in each radiators , kG37.14 Total weight of oil in radiator , kG37.15 OLTC gear including oil , kG37.16 Total transport weight of the transformer, kG37.17 Total transport weight of the transformerwith OLTC and all accessories38.0 Volume data38.1 Volume of oil in main tank , liters38.2 Volume of oil between highest andlowest levels of main conservator ,liters38.3 Volume of oil between highest andlowest levels of OLTC conservator,liters38.4 Volume of oil in each radiator , liters38.5 Total volume of oil in radiators , liters38.6 Volume of oil in OLTC , liters38.7 Transformer total oil volume , liters39.0 Shipping data39.1 Weight of heaviest package, kG39.2 Dimensions of the largest package (L xB x H) mm40.0 Tests40.1 All in process tests confirmed as per Cl.(Yes /No)40.2 All types tests confirmed as per Cl.(Yes /No)40.3 All in routine tests confirmed as per Cl.458BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C16(Yes /No)40.4 All in special tests confirmed as per Cl.(Yes /No)

Page 54: BSES Bhawan

Bidders Name : ____________________Signature : ____________________Name : ____________________Designation : ____________________Seal of Company Date : ____________________459BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule E1SCHEDULE – E1TECHNICAL DEVIATIONS FROM THE SPECIFICATION(This shall form part of Technical Bid)All the technical deviation from the tender specification shall be listed out by the Bidder, para bypara in this schedule. Deviation taken in covering letter, standard terms and/or body of the Bid butnot listed herein will make the Bid liable for rejection as ‘Irresponsive’S.No. Section/Sub-Section Part Para Deviation Justification1 2 3 4 5 6Certified that above are the only technical deviations from the tender SpecificationName of Firm : ____________________Signature of Bidder : ____________________Designation : ____________________Date : ____________________Seal of Company460BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule E2SCHEDULE – E2COMMERCIAL DEVIATIONS FROM THE SPECIFICATION(This shall form part of Technical Bid)All the commercial deviation from the tender specification shall be listed out by the Bidder, para bypara in this schedule. Deviation taken in covering letter, standard terms and/or body of the Bid butnot listed herein will make the Bid liable for rejection as ‘Irresponsive’.S.No. Section/Sub-Section Part Para Deviation Justification1 2 3 4 5 6Certified that above are the only technical deviations from the tender SpecificationName of Firm : ____________________Signature of Bidder : ____________________Designation : ____________________Date : ____________________Seal of Company461BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule FSCHEDULE – FLIST OF DRAWINGS ENCLOSED WITH BID(This shall form part of Technical Bid)S.No. Drawing No Title1 2 3Name of Firm : ____________________Signature of Bidder : ____________________Designation : ____________________Date : ____________________Seal of Company462BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & AnnexureSCHEDULE – GSCHEDULE OF TEST(This shall form part of Technical Bid)

Page 55: BSES Bhawan

Tests as per the relevant Indian Standard except as modified and/or as additionally called for in thetender specification shall be performed. Detailed list of the type test certificates enclosed for thevarious equipments offered shall be listed in the schedule.S.No. Type of test Equipment Description1 2 3 41.0 TYPE TESTS2.0 TESTS– DURING MANUFACTURE3.0 ROUTINE TESTS– ON COMPLETION OF MANUFACTUREName of Firm : ____________________Signature of Bidder : ____________________Designation : ____________________Date : ____________________Seal of Company463BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & AnnexureSCHEDULE – HLIST OF INSTRUMENTS, TESTING EQUIPMENTS, TOOLS AND TACKLESFOR ERECTION AND MAINTANANCE(This shall form part of Technical Bid)S.No. Description Capacity Quantity Delivery(1) (2) (3) (4) (5)1.0 INSTRUMENTS, TESTING EQUIPMENT, TOLLS & TACKLES FOR ERECTION(To be taken back by the Bidder after completion of job)2.0 INSTRUMENTS, TESTING EQUIPMENT, TOOLS & TACKLES FOR MAINTENANCE(To be taken back by the Bidder after completion of job)3.0 SPECIAL INSTRUMENTS, TSTING EQUIPMENT, TOOLS & TACKLES FOR ERECTION(To be taken back by the Bidder after completion of job)4.0 SPECIAL INSTRUMENTS, TSTING EQUIPMENT, TOOLS & TACKLES FOR MAINTENANCE(To be taken back by the Bidder after completion of job)Name of Firm : ____________________Signature of Bidder : ____________________Designation : ____________________Date : ____________________Seal of Company464BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule ISCHEDULE – ILIST OF INSTALLATIONSS.No. Purchaser Project PFRef.BriefDescription Value TargetCommissioning Commissioned PerformancePerson to whomreference maybe madeRemarks1 2 3 4 5 6 7 8 9 10 11Bidders Name : ____________________Signature : ____________________Name : ____________________Seal of Company Designation : ____________________Date : ____________________465

Page 56: BSES Bhawan

BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule JSCHEDULE – JDELIVERY TERMS AND CONDITIONS1 Quoted for all the items & in the manner as calledfor in Specification *Yes/No1.1 If not, furnish details of deviations2 Price FOR site delivery basis2.1 Freight:1 Applicable rate * Not included/included2.2 Transit Insurance including forty five(45) daysstorage1 Applicable rate * Not included/included2.3 Excise duty1 Applicable rate * Not included/included2.4 Sales tax1 Applicable rate * Not included/included2.5 Are quoted price firm *Yes/No3 Delivery from LOI3.1 Supply3.2 Erection3.3 Testing & commissioning3.4 Whether penalty clause acceptable *Yes/No4 Validity5 Terms of payment5.1 As per tender specification *Yes/No5.2 If not, give details6 Guarantee period6.1 Is it as per the tender specification *Yes/No6.2 If not, state alternative guarantee period acceptable7 Earnest money furnished *Yes/No8 Agreeable to furnish security deposit as per thetender specification *Yes/No8.1 *Yes/No9 Agreeable to furnish performance Bank as per thetender specification *Yes/No10Correspondence, drawings, test certificates,instruction manuals, BAR/PERT charts progressreports etc. shall be furnished in number of copiesas per distribution schedule attachedto the tender specification*Yes11Agreeable to approval of above documents in our(4) weeks from date of receipt as per tenderspecificationYes12Agreeable to commercial as well as technical terms& conditions of the tender specification, unless listeddeviations are acceptedYes13 Commencing & completion of submission ofdrawings from LOI466BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule JBidders Name : ____________________Signature : ____________________

Page 57: BSES Bhawan

Name : ____________________Designation : ____________________Seal of Company Date : ____________________467BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule KSCHEDULE – KSCHEDULE OF RECOMMENDED SPARESBidder shall offer the prices for spares for destination, rate of taxes & duties to beconsidered shall be indicated.S.No. Description Quantity Unit Price Total Price1 2 3 4 5Bidders Name : ____________________Signature : ____________________Name : ____________________Designation : ____________________Seal of Company Date : ____________________468BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule LSCHEDULE – LDECLARATION(This shall form part of Technical Bid)I, ________________________ certify that all the typed data & information pertaining to thesubject tender specification are correct & are true representation of the equipment covered by ourformal Bid No_________________dated________________.I hereby, certify that I am duly authorized representative of the Bidder whose name appears abovemy signature.Bidders Name : ____________________Authorized RepresentativeSignature : ____________________Authorized RepresentativeName (Typed) : ____________________Authorized RepresentativeDesignation : ____________________Seal of Company Date : ____________________Bidder’s Intent : The bidder hereby agrees to fully comply with the requirements& intents of the subject tender specification for the price(s)indicatedAuthorized RepresentativeSignature : ____________________