Click here to load reader
Upload
radhouane-damergi
View
215
Download
0
Embed Size (px)
Citation preview
7/23/2019 Advanced_Protection_APAP_WG_B5_07_Korea_2009.pdf
http://slidepdf.com/reader/full/advancedprotectionapapwgb507korea2009pdf 1/6
1
Abstract-- CIGRÉ WG B5-07 was formed to produce adocument entitled "Modern techniques for protecting andmonitoring transmission lines". The WG members decided tooffer a summary of their work for the benefit of the conferenceand to the industry. Transmission line intelligent electronicdevices (IEDs) include a large number of additional protectionelements and control functions, which provide the user with anunlimited amount of flexibility to design secure and dependableprotection and control schemes. Traditional pilot relayingschemes require separate protection and monitoring devices withcostly external communication equipments. Modern transmission
line IEDs integrate many flexible protection, control andmonitoring features including communications functionalitywithin the same hardware and provide relay-to-relay digitalcommunications for high-speed line protection, monitoring, andcontrol. Novel, more secure and dependable protection, controland monitoring applications are now possible with transmissionline IEDs including the relay-to-relay communications capability.In this paper, we discuss new protection, control and monitoringapplications with a special focus on telecommunication assistedfeatures used in this modern technology.
Index Terms— Transmission line protection, Functionalintegration, Communication, Control, IEDs, Metering,Synchrophasors.
I. INTRODUCTION
ODERN transmission line IEDs offer significant
number of functional improvements over previous
generations and technologies. The new state of the art of
modern transmission line protection with its multifunctional
integrated capability provides an unprecedented flexibility in
transmission protection principles, control and monitoring
schemes. This paper discusses some improved techniques
related to filtering techniques for fast fault elimination time;
new transmission line protection techniques backed with many
application examples using different levels of integration with
faster and more reliable communications to share synchronizeddata between IEDs within the same substation or between
IEDs in different substations.
WG Contributors: S.R. Chano (CA)-Convenor; J. Afonso (PT)-Secretary; A.
Menon (CH); S. Sofroniou (GR); D. Tziouvaras (USA); Alexander Apostolov
(US); Florin Balasiu (RO); Gareth Baber (UK); Juan Maria García (ES);
Kenneth Opskar (NO); Denys Lellys (BR); François L’Homme (FR); Graeme
Topham (ZA); Leif Koppari (SE); Kai Kühl (CH)
II. PROTECTION, CONTROL & MONITORING
(1) Modern Transmission Line
Protection
A transmission line protection IED must provide a highly
selective protection system that is immune to changes in the
surrounding power system. Applications to two and three
terminal lines, cables and transformer feeders should also be
supported. The device must provide adequate protection with
or without a communications channel to the remote end of the
transmission line. The integration of many functions allowsapplication to a wide range of electrical power systems,
providing both local and remote backup protection.
Protection IEDs often perform as universal metering, control
and recording devices. They provide multiple communications
interfaces which allow them to become the servers in an
integrated substation automation system over a substation
LAN.
One of the main goals in today's extremely competitive utility
environment is to switch from scheduled to event driven
maintenance. A universal protection IED can significantly help
in achieving this goal, by providing tools which monitor the
substation primary equipment and indicate, as necessary, therequirement for specific maintenance actions.
All of the above listed requirements are taken into
consideration in the concept of a Universal Transmission Line
Protection IED.
(2) Universal Transmission Line
Protection IED
A universal transmission line protection IED should be
designed for the protection of a wide range of overhead lines
and underground cables and for both sub-transmission and
transmission voltage levels. It should also include a
comprehensive range of non-protection features to meet the
requirements for substation and power system integration andaid the user with power system diagnosis and fault analysis
facilities. All these features should be accessible locally,
through the substation LAN or remotely through one of the
IED’s serial communications ports.
(3)Integrated Protection and Control Features
A transmission line protection IED must support multiple
integrated protection and control elements to meet the
requirements for primary and backup applications. Phase
Modern Techniques for Protecting and
Monitoring Transmission linesS.R. Chano, Hydro-Québec(CA); J. Afonso, REN(PT); A. Menon, ABB(CH);
S. Sofroniou, HTSO (GR); D. Tziouvaras, SEL(USA)
M
7/23/2019 Advanced_Protection_APAP_WG_B5_07_Korea_2009.pdf
http://slidepdf.com/reader/full/advancedprotectionapapwgb507korea2009pdf 2/6
2
current differential protection – Phase segregated restrained
differential protection- Distance protection – Overcurrent
protection – Stub bus protection- CB failure protection –
Two-stage CB fail protection. Direct/permissive inter-trip –
Independent inter-tripping facility using the device’s
protection communications channels – Dual redundant
communications – Option for dual communications channels
to provide a high degree of security. Protection
communications supervision – Voltage transformersupervision – To prevent maloperation of voltage dependent
protection elements upon loss of a VT input signal – Current
transformer supervision– Programmable scheme logic –
Allowing user-defined protection and control logic to suit
particular customer applications – Autoreclosing schemes
Integrated for three phase or single/three phase multi-shot
autoreclose applications – Check synchronism capability –
Local/remote measurements – Various measurement values
from the local and remote line ends available for display on the
device or accessed from the serial communications –
Fault/event/disturbance records – Fault locator features –
Synchro-phasor measurements – Real time clock/time
synchronization through IRIG-B input – CB state monitoring –CB control - CB condition monitoring – Remote serial
communications – Continuous self-monitoring – Power on
diagnostics and self checking routines to provide maximum
device reliability and availability.
(4)Protection & Control Applications
R
T
S
1
2
3
L1 L2
4
G1
T1 T2
S
Relay 1
S
5
Relay 5Relay 2
6
Relay 6
Relay-to-RelayCommunications
Figure 1.0 - Blocking High-speed Reclosing for CB Failure
Conditions or to Avoid an Out-of-Synch Reclosing
Attempts
In figure 1.0 , a fault occurs inside Transformer T1, and CB 2
fails to trip at Station T. For this fault, CB 1 at Station R must
open due to the CB failure condition of CB 2 at Station T andnot be allowed to reclose. In a traditional protection scheme, a
separate direct transfer trip is applied between Stations R and
T to perform the above function. Relay-to-relay
communications capability between relays of L1 and L2 in
conjunction with relay programmable logic can be used to
send a direct transfer trip from Station T to Stations R and S
during CB failure conditions at Station T and block reclosing
at the remote stations.
Let us now consider a fault on L1 for which CB 1 at Station R
and CB 2 at Station T open to clear the line fault, and at the
same time a mal-operation occurs at Station S, which opens
CB 6. If high-speed reclosing is applied on both CBs of L1
without any other considerations, there is a possibility to
reclose out of synchronism with generator G1 and cause
considerable damage to the generator. For this scenario, using
relay-to-relay communications and programmable logic, we
can design a protection scheme at Station T to detect L2
tripping at the remote Terminal S, block high-speed reclosing
of CB 2 at Station T, and transmit a reclose blocking bit toblock high-speed reclosing of CB 1 at Station R in order to
prevent possible damage to Generator G1. Slow-speed
reclosing from Station R, followed by CB 2 closing at Station
T with synch-check and slip frequency supervision, allows the
two systems to parallel and improves system reliability.
(5) Auto-reclosing with Secondary Arc Extinction Recognition
A secondary arc extinction detector, in single-pole tripping
applications, could supervise the closing signal to the CB to
prevent auto-reclosing when the secondary arc is still present
and minimize the possibility of unsuccessful reclosings.
Complete reclosing relay supervision requires three secondaryarc extinction detectors, one per phase. These detectors
measure the angle, φ, between the phase-to-ground voltage of
the faulted phase (Vγ) and the sum of the sound-phases phase-
to-ground voltages (VΣ). For -β ≤ φ ≤ β, and | Vγ | > Vthre, the
detector determines the secondary arc extinction and asserts
the SAED bit. Vthre and β determine the region that detects the
secondary arc extinction. Table 1 shows the Vγ and VΣ
voltages for A-, B-, and C-phase SAEDs.
Table 1.0 - Vγ and VΣ Voltages for A-Phase, B-Phase,and C-Phase SAEDS
Detector Vγ γγ γ VΣΣΣΣ
A-phase VA VB + VC
B-phase VB VC + VA
C-phase VC VA + VB
Figure 2. and Figure 3. show that Vγ is inside the SAED region
and the angle φ = 0° during an A-phase single-pole open
condition, after the secondary arc extinguishes. The A-phase
detector asserts the SAED bit for this condition, allowing the
reclosing sequence to continue.
Vγ = V
A
VB
VC
VΣ = V
B + V
C
7/23/2019 Advanced_Protection_APAP_WG_B5_07_Korea_2009.pdf
http://slidepdf.com/reader/full/advancedprotectionapapwgb507korea2009pdf 3/6
3
Figure 2.0 – Vγ is inside the SAED region after the arc extinguishes
0.5
1
1.5
30
210
60
240
90
270
120
300
150
330
180 0
Prefault
Fault
Secondary ArcPresent
Secondary ArcExtinguishes
Figure 3.0– A-phase voltage phasor enters the SAED region after the
secondary arc extinguishes
Figure 7. shows the close supervision logic using secondary
arc extinction detection (SAED) for close supervision. The
SAED can minimize the dead time by initiating the reclose
after the secondary arc extinguishes. The SAEDD time delay
provides time for the air formerly occupied by the arc to regain
dielectric capabilities.
SAEDClose
Enable
SAEDD
DO
ReclosingRelaySupervision
Secondary ArcExtinction Detection(SAED)
Figure 4.0 – Reclosing relay close supervision using secondary arc extinction
detection
(6) CB and Station Bypass-CB Bypassing (Substitution)
Different bus arrangements are used in a power network
depending on service reliability requirements, economical
considerations, switching flexibility, and equipment
maintainability. The main and transfer bus arrangement
provides a low-cost solution for switching lines to a transfer or
auxiliary bus, usually to perform maintenance on the line CB.
The transfer bus is rated to feed only one serviced line at a
time. It has been implemented mostly in North America and it
is preferred on sub-transmission applications for its practicality
and low cost.
The double-bus single-CB configuration has two main buses
that are equally rated. This arrangement allows any circuit to
be connected via isolator switches to either bus. A bus parallel
(coupler) CB connects the two buses together and
sectionalizing CBs divide the bus in sections. Each feeder CB
is equipped with a bypass switch and isolator switches to
facilitate CB maintenance. The bus parallel (coupler) CB isused temporarily to protect any of the feeder or transformer
bank circuits when the actual feeder or bank CB is taken out
for maintenance. During the CB substitution, one bus becomes
part of the feeder circuit with all other circuits connected to the
remaining bus, increasing power availability in case of bus
faults. This bus configuration delivers a good compromise
between reliability and flexibility on one hand and economical
considerations on the other.
CB substitution is a switching operation which is used to
isolate a CB for maintenance while maintaining its circuit
energized. The system in figure 5.0 shows a simple double-bus
single-CB arrangement with a bus-tie (coupler) CB. Feeder 2and Feeder 3 could be served by either Bus 1 or Bus 2
depending on which isolator switches are closed.
Figure 5.0 – Double-bus single-CB configuration
In a double-bus single-CB or a main and transfer bus
arrangements, the relay systems installed on the bus-tie CB are
used to protect a transmission line when the line CB is out-of-
service for maintenance. In such an arrangement, the
performance of the protection is degraded unless the
communications channel used for high-speed line protection is
rerouted to the bus-tie CB protection system. This was almost
impossible with earlier electromechanical and static relay
systems. Modern numerical relays having multiple settings
together with intelligent communications channel fibre-optic
transfer switches can be used to maintain high-speed pilot line
protection and system stability and integrity during CB
maintenance.
Let us assume that we desire to maintain CB3 while Feeder 3
is connected to Bus 1. System operators will switch all feeders
7/23/2019 Advanced_Protection_APAP_WG_B5_07_Korea_2009.pdf
http://slidepdf.com/reader/full/advancedprotectionapapwgb507korea2009pdf 4/6
4
to Bus 2 except Feeder 3 which will be connected to Bus 1.
The bus-tie CB and its isolators are closed connecting the two
buses together. Just before the bypass switch of CB3 is closed,
the operator enables the distance and directional ground
overcurrent relays on the bus-tie CB, and takes out-of-service
the distance protection (21), line differential protection (87L),
and the pilot protection channels of Feeder 3. Distance (21)
and directional ground overcurrent (67N) relays on the bus-tie
CB are now protecting Feeder 3 and Bus 1 which is now partof Feeder 3. The protection of Feeder 3 has now been
compromised because high-speed pilot protection is out-of-
service on Feeder 3 during the duration of CB3 maintenance
that could last several days.
IEDs together with intelligent fibre-optic transfer switches can
be applied to prevent the above mentioned protection
compromise while maintain high-speed protection of Feeder 3
when CB CB3 is maintained. This is illustrated with Figure 6.
and Figure 7. where we show a normal system where the
communications channels of Feeder 2 and Feeder 3 are routed
to the multiplexer via a fibre-optic transfer switch.
Figure 6.0 – Feeder communications channels routed via a fiber-optic switch
IEDs and intelligent fibre-optic transfer switches can be
applied to:
• Maintain high-speed transmission line protection by
communications assisted tripping schemes (POTT,
DCB, DCUB, 87L) during CB maintenance.
• Maintain Main 1 and Main 2 high-speed protection
communications during CB maintenance operations
on main-bus transfer-bus or double-bus single-CBconfigurations.
• Automatically change group protection settings on the
bus coupler relays to accurately match the bypassed
CB relay protection settings.
• Quickly and cleanly reroute any communications
protocol carried on the IEEE C37.94 fibre-optic
interface standard without changing communications
equipment programming.
• Reroute current differential communications or any
synchronous communications converted to the IEEE
C37.94 interface standard.
Figure 7. shows the switching of pilot communications
channels to the bus coupler CB during maintenance of Feeder
3 CB CB3.
Figure 7.0 – CB3 bypassed while Feeder 2 is protected by the bus coupler CB
(CB1)
(7.0) Substation topology and auto-reclosing
applications
The substation layout has a large impact on the integrated AR
function in transmission line protection and its associated
synchro-check functions. Some application examples arepresented below.
(7.1)Double Busbar arrangement
In such kind of layout, Main 1 and Main 2 multi-function
protection relays, the BBP including the BFP and the
teleprotection equipment normally providing two independent
physical channels A and B. Main 1 protection is related to trip
coil 1, while Main 2 is related to trip coil 2. For reclosing
purposes several philosophies could be used as for example:
external separate AR relay started by both Main 1 and Main 2,
internal AR function used by both Main 1 and Main 2 or each
Main 1 and Main 2 use their corresponding internal AR
function. In case of the latter one “master-follower” logic
could be used or the logic based on time delay discrimination.
(7.2)Common External AR
This is a standard arrangement where the AR function could be
located in a Bay Controller. Figure illustrates the various
functions starting AR. Both Main 1 and Main 2 work with the
AR function. The Synchrocheck function is also along with the
AR function in the same numerical terminal. This arrangement
7/23/2019 Advanced_Protection_APAP_WG_B5_07_Korea_2009.pdf
http://slidepdf.com/reader/full/advancedprotectionapapwgb507korea2009pdf 5/6
5
results in optimum CB related signal requirements besides the
choice of Main 1 and Main 2 from different manufacturers.
Figure 8.0 – AR Function in Main 1 / Main 2
When there is no common numerical terminal housing the AR
function, the function has to be duplicated in the Main
protection terminals itself. Otherwise, loss of a numerical
terminal would take away the reclosing facility possible with
the second Main terminal. It has to be ensured that at any point
of time, only one AR function should have the authority to
issue the reclose command lest different dead times from the
two functions attempt improper reclose upon permanent faults
etc.
There are two different approaches, one approach wherein
only one AR function is active while the other AR is inblocked state whereas the second approach where in both AR
functions are active but only one is allowed to issue reclose.
The first approach is termed Main – Hot standby and the
second approach termed Redundant. This approach eliminates
need for AR functionality in separate hardware besides the
choice of Main 1 and Main 2 from different manufacturers.
However, primary requirements are twice since there are two
AR functions besides additional binary inputs/outputs in the
protection terminals.
The sketches below illustrate the two approaches.
(7.3)Main – Hot Standby
If the AR in Main 1 terminal is Main, then both Main 1 and
Main 2 protections work with this AR function. The AR in
Main 2 terminal as hot standby is kept blocked and is
automatically released by a logic formed out of Main 1
terminal out of service / Test mode or if the Synchrocheck
function is blocked due to a VT MCB failure. In such a
situation, the AR in Main 2 works with its own protection. The
AR in Main 2 working with Main 1 protection is an option.
Instead of a fallback approach, it is also possible to maintain
flexibility in choice of AR between Main 1 and Main 2 by
keeping connections between Main 1 protection and AR in
Main 2. This approach eliminates need for AR functionality in
separate hardware besides the choice of Main 1 and Main 2
from different manufacturers.
Figure 9.0 – Main AR with hot standby
(7.4)Redundant, Master-Follower
Both Main 1 and Main 2 protections work with their own AR
functions. In order to ensure that both AR functions choose the
same type of dead time even upon contradictory protection
operation, the Main 2 signal “Trip three pole” is also
connected to Main 1 AR function. One AR is termed Master
and the other Follower. If Main 1 AR is Master, upon
occurrence of a fault, even if Main 2 operates faster, its AR
function is on hold by the Master AR. However, there has to
be a co-ordination of reclose commands and only one ARfunction shall issue the close command to CB.
The Follower AR is released only after a certain fixed time
after Master AR issues reclose command. If fault persists,
Master AR issues “AR Unsuccessful”. If fault is transient,
Follower AR is released but then shall not issue any reclose
signal. Hence an additional signal comprising of above two
conditions called “Inhibit Output” is sent from Master to
Follower AR and vice versa.
This approach is more suited for Protection/ AR function
terminals from same manufacturer because of the special
signal above
7/23/2019 Advanced_Protection_APAP_WG_B5_07_Korea_2009.pdf
http://slidepdf.com/reader/full/advancedprotectionapapwgb507korea2009pdf 6/6
6
Figure 10.0 – Redundant AR, Master/Follower
(7.5)Two IEDs with two AR functions
A potential block diagram for such an arrangement is shown infigure 10.0. For proper operation some data exchange is
needed between the two AR functions in case of applying the
logic based on time delay discrimination. This logic applies for
both AR functions to be started by their own allowed
protection functions and the first reclosing command blocks
the other AR function, discrimination being time based. Thus
one AR dead time is a little bit longer and is pre-assigned
usually to Main-2. If the first AR function fails to operate for
one reason, the second one from Main-2 will still operate and
reclose the CB.
Each multi-function relay has to be able to trip single-pole the
CB and to reclose it. For multi-pole faults the trip should be
three-pole.
III. CONCLUSIONS
The integration in modern transmission line protection of
programmable logic, digital relay-to-relay communications,
math capability, and their proper application improves the
security, dependability, and speed of protection systems. As a
result, it improves the reliability of the overall power system.
The addition of synchrophasor measurement in a distance relay
results in increased power system reliability and provides
easier disturbance analysis, protection, and control capabilities.The integration of control functions in the IEDs like
autoreclosing or synchrocheck functions simplifies the
physical wiring in the installation and, in some cases, it
improves their performance.
As for the cases of many other fields, in protection as well a
re-orientation and re-engineering must always be in mind.
Frontiers between studies and site, between protection and
control, protection and operation now do not exist. Engineers
must collaborate, designing intelligent systems and with
synergy, achieving better results, saving money, time and
respecting the environment as well! They must think integrated
solutions, where protection systems, SCADA systems,
recordings or data logger systems, telecommunication systems,
RTU systems, metering systems, control systems, PLC systems,
maintenance systems and algorithms are combined, and finally
can be executed by common devices. In order to fight the
dependability to one device, two systems, based in different
algorithms and principles may be installed assuring
redundancy, flexibility, extensibility, security, high speed, fastreactions hence less possibilities for energy shortages or black
outs, stability, economy, optimization, friendship to
environment, saving room, capitals and manpower. Moreover,
the analyzed auxiliary functions of the IEDs offer usually tools
for executing power system appraisal and system operation
benchmarking, in the new de-or re-regulated competitive
environment, approaching finally the system (total) quality.
Therefore the new term for the protection relays as IEDs or
smart system units is more successful, as we have realized
from the preceded analysis that the so-called non-protective or
auxiliary functions of the IEDs are as much as the
conventional ones and at least of the same importance and
usefulness.