104
THIS ISSUE INCLUDES THE NEW QED (QUICK ENROLLLMENT OF DEVICES) PROCEDURE FOR 5800 SERIES TRANSMITTERS VIA-30P SE N7225V2 Rev B 4/99 Installation Instructions • Installation Instructions • Installation Instructions Security System

ADEMCO N7225V2B

Embed Size (px)

DESCRIPTION

ADEMCO N7225V2B

Citation preview

Page 1: ADEMCO N7225V2B

THIS ISSUE INCLUDES THE NEW QED (QUICK ENROLLLMENTOF DEVICES) PROCEDURE FOR 5800 SERIES TRANSMITTERS

VIA-30PSE

N7225V2 Rev B 4/99

Installation Instructions • Installation Instructions • Installation Instructions

Security System

Page 2: ADEMCO N7225V2B

RECOMMENDATIONS FOR PROPER PROTECTIONThe following recommendations for the location of fire and burglary detectiondevices help provide proper coverage for the protected premises.

Recommendations For Smoke And Heat DetectorsWith regard to the number and placement of smoke/heat detectors, we subscribe to therecommendations contained in the National Fire Protection Association's (NFPA) Standard #72 notedbelow.

Early warning fire detection is best achieved by the installation of fire detection equipment in allrooms and areas of the household as follows: For minimum protection a smoke detector shouldbe installed outside of each separate sleeping area, and on each additional floor of a multi-floorfamily living unit, including basements. The installation of smoke detectors in kitchens, attics(finished or unfinished), or in garages is not normally recommended.

For maximum protection the NFPA recommends that you install heat or smoke detectors in theliving room, dining room, bedroom(s), kitchen, hallway(s), attic, furnace room, utility and storagerooms, basements and attached garages.

In addition, we recommend the following:• Install a smoke detector inside every bedroom where a smoker sleeps.• Install a smoke detector inside every bedroom where someone sleeps with the door partly or

completely closed. Smoke could be blocked by the closed door. Also, an alarm in the hallwayoutside may not wake up the sleeper if the door is closed.

• Install a smoke detector inside bedrooms where electrical appliances (such as portableheaters, air conditioners or humidifiers) are used.

• Install a smoke detector at both ends of a hallway if the hallway is more than 40 feet (12meters) long.

• Install smoke detectors in any room where an alarm control is located, or in any room wherealarm control connections to an AC source or phone lines are made. If detectors are not solocated, a fire within the room could prevent the control from reporting a fire or an intrusion.

DININGKITCHEN

BEDROOM

BEDROOM

BEDROOM

BEDROOM

LIVING ROOM

✪ ✪

BEDROOM

BDRM

BDRM

DINING

LIVING ROOM

TV ROOM KITCHEN

■■

✪ ✪

BEDROOM BEDROOMTOBR

LVNG RM

BASEMENT

KTCHN▲

. CLOSEDDOOR

GARAGE▲

Smoke Detectors for Minimum Protection

Smoke Detectors for Additional Protection

Heat-Activated Detectors

THIS CONTROL COMPLIES WITH NFPA REQUIREMENTS FOR TEMPORALPULSE SOUNDING FOR FIRE NOTIFICATION APPLIANCES.

Recommendations For Proper Intrusion ProtectionFor proper intrusion coverage, sensors should be located at every possible point of entry to a home orcommercial premises. This would include any skylights that may be present, and the upper windows ina multi-level building.In addition, we recommend that radio backup be used in a security system so that alarm signals canstill be sent to the alarm monitoring station in the event that the telephone lines are out of order (alarmsignals are normally sent over the phone lines, if connected to an alarm monitoring station).

Page 3: ADEMCO N7225V2B

i

TABLE OF CONTENTS

Section 1. GENERAL DESCRIPTION ................................ ................................ ......................... 1-1

Section 2. INSTALLING THE CONTROL ................................ ................................ .................. 2-1Mounting the Cabinet ................................ ................................ ..................................... 2-1Installing the Lock (if used) ................................ ................................ ............................ 2-1Installing the Control's Circuit Board Alone or (if used)With a 4204, 4219, or 4229 Module................................ ................................ ................ 2-1Installing Control and RF Receiver Circuit Boards Together in the Cabinet................... 2-3Standard Phone Line Connections ................................ ................................ ................. 2-3Wiring the AC Transformer ................................ ................................ ............................. 2-4Installing the Back-Up Battery ................................ ................................ ........................ 2-4Earth Ground Connections ................................ ................................ ............................. 2-4

Section 3. INSTALLING REMOTE KEYPADS ................................ ................................ .......... 3-1Keypads that May Be Used ................................ ................................ ............................ 3-1Wiring to the Keypads ................................ ................................ ................................ .... 3-1

Wiring Run Chart for Devices Drawing AUX Power From the Control ..................... 3-1Mounting the Keypads ................................ ................................ ................................ .... 3-2Using A Supplementary Power Supply To Power Additional Keypads........................... 3-2Preliminary Check-Out Procedure ................................ ................................ .................. 3-3

Section 4. BASIC HARD-WIRED ZONES 5 and 6 ................................ ................................ . 4-1Installing the Hard-Wired Zones ................................ ................................ ..................... 4-1

Common Characteristics For Zones 5 and 6 ................................ ........................... 4-1Wiring Burglary and Panic Devices to Zones 5 and 6 ................................ .................... 4-1Wiring 4-Wire Smoke/Combustion Detectors on Zones 5 ................................ .............. 4-1

Compatible 4-Wire Smoke/Combustion Detectors................................ ................... 4-2Programming Hard-Wired Zones................................ ................................ .................... 4-2

Programming Panic Keys ................................ ................................ ......................... 4-3Check-Out Procedure for Hard-Wired Zones 5 and 6 ................................ .................... 4-4

Section 5. WIRED ZONE EXPANSION (4219, 4229) ............................................. 5-1

Installing Zone Expansion Units ................................ ................................ ..................... 5-1

Connections and Setup ................................ ................................ ................................ .. 5-1

Programming Wired Expansion Zones ................................ ................................ ........... 5-2

Check-Out Procedure for Wired Expansion Zones................................ ......................... 5-3

Section 6. WIRELESS (RF) ZONE EXPANSION (5700 & 5800 RF SYSTEMS) ............. 6-1Wireless Systems Available ................................ ................................ ........................... 6-1Wireless System Operation and Transmitter Supervision ................................ .............. 6-1

Transmitter Battery Life ................................ ................................ ............................ 6-2Receiver Supervision................................ ................................ ................................ ...... 6-2Installation and Setup of the 4281/5881 Series Wireless Receivers .............................. 6-2Installing the 5800TM Module................................ ................................ ......................... 6-35700 Series Transmitter Setup ................................ ................................ ....................... 6-3

Setting the DIP Switches on 5700 Series Wireless Transmitters............................. 6-4Wireless Zone/ID Assignments for 5700 Series Transmitters ................................ . 6-4

DIP Switch Tables for 5700 RF System Wireless Devices ................................ ............. 6-5Compatible 5700 Series Transmitters ................................ ................................ ............ 6-6Programming the Control For a 5700 Wireless System ................................ ................. 6-7

Using the House ID Sniffer Mode (5700 Systems) ................................ .................. 6-7Zone Programming for 5700 Series Transmitters................................ ........................... 6-7

Go/NoGo Test ................................ ................................ ................................ .......... 6-9

Page 4: ADEMCO N7225V2B

ii

Section 6. WIRELESS (RF) ZONE EXPANSION (5700 & 5800 RF SYSTEMS), CONT'D5800 Series Transmitter Setup ................................ ................................ ..................... 6-10

5800 Series Transmitter Input Loops ................................ ................................ ..... 6-105800 Series Transmitter Input Types ................................ ................................ ..... 6-10

Compatible 5800 Series Transmitters ................................ ................................ .......... 6-11Programming the RF Transmitters (5800 RF Systems) ................................ ................ 6-12Enrolling 5800 Transmitters Into the System ................................ ................................ 6-13

Enrolling Through Zone Programming (✱56) ................................ .......................... 6-13To Either Temporarily or Permanently Remove a Zone From the System      (5800 System) ................................ ................................ ................................ ......... 6-16Deleting a Transmitter Serial Number From a Zone in ✱56 Mode (5800 System) ........ 6-16Check-out Procedure for Wireless Zones ................................ ................................ ..... 6-16

Transmitter ID Sniffer Mode (5700 RF Systems Only) ................................ ........... 6-16Go/No Go Test Mode (5700 and 5800 RF Systems)................................ .............. 6-17

Section 7. RELAY OUTPUT DEVICES ................................ ................................ ....................... 7-1Relay Device Basics ................................ ................................ ................................ ....... 7-14204 Relay Modules ................................ ................................ ................................ ....... 7-1

4204 Setup ................................ ................................ ................................ ............... 7-1Supervision................................ ................................ ................................ ............... 7-1

Programming Options Defined................................ ................................ ........................ 7-1Programming Output Relays................................ ................................ ........................... 7-3

Example of Output Relay Programming ................................ ................................ ... 7-5

Section 8. 4285 PHONE MODULE ................................ ................................ ............................ 8-1Installing the Phone module................................ ................................ ............................ 8-1

General Information ................................ ................................ ................................ .. 8-1Mounting The Phone module................................ ................................ .................... 8-1Phone module Wiring ................................ ................................ ............................... 8-1Caller ID Units................................ ................................ ................................ ........... 8-2

Programming The Control For Phone Access ................................ ................................ 8-4Checking the Operation of the 4285 Phone module ................................ ....................... 8-5

Section 9. EXTERNAL SOUNDERS ................................ ................................ ............................ 9-1Compatible Sounders ................................ ................................ ................................ ..... 9-1Sounder Connections ................................ ................................ ................................ ..... 9-2Programming For External Sounders ................................ ................................ ............. 9-2Testing the Sounder................................ ................................ ................................ ........ 9-2

Section 10. LONG RANGE RADIO ................................ ................................ .............................. 10-1General Information ................................ ................................ ................................ ...... 10-1Connection ................................ ................................ ................................ .................... 10-1Programming for Long Range Radio ................................ ................................ ............ 10-1

Section 11. AUDIO ALARM VERIFICATION (AAV) UNIT ................................ ..................... 11-1General Information ................................ ................................ ................................ ...... 11-1Wiring Connections ................................ ................................ ................................ ....... 11-1Programming ................................ ................................ ................................ ............... 11-1

Section 12. FINAL POWER UP ................................ ................................ ................................ .... 12-1Earth Ground Connections................................ ................................ ............................ 12-1AC Power-Up ................................ ................................ ................................ ................ 12-1Connecting the Back-Up Battery ................................ ................................ ................... 12-1

Calculating the Battery Size Needed ................................ ................................ ...... 12-1Making the Battery Connections ................................ ................................ ............ 12-2

Auxiliary Device Current Draw Worksheet ................................ ................................ .... 12-2

Page 5: ADEMCO N7225V2B

iii

Section 13. ALPHA DESCRIPTOR PROGRAMMING ................................ ............................. 13-1Assigning Zone Descriptors................................ ................................ .......................... 13-1

Entering Zone Descriptors (in program Menu Mode ✱82) ................................ ...... 13-1Programming the Descriptors ................................ ................................ ................ 13-1

Alternate Method for Programming Zone Descriptors ................................ .................. 13-3Adding Custom Words................................ ................................ ................................ .. 13-4Alpha Vocabulary List (For Entering Zone Descriptors) ................................ ............... 13-5Character (ASCII) Chart ................................ ................................ ............................... 13-5

Section 14. SEQUENTIAL MODE(For 5800 Series Wireless Transmitters) ................................ ......................... 14-1

Section 15. SYSTEM COMMUNICATION ................................ ................................ ................. 15-1Report Code Formats ................................ ................................ ................................ ... 15-1

Table of Contact ID Event Codes................................ ................................ ........... 15-3Communication Programming ................................ ................................ ...................... 15-3

Section 16. TESTING THE SYSTEM ................................ ................................ .......................... 16-1Test Procedure ................................ ................................ ................................ ............. 16-1To the Installer ................................ ................................ ................................ .............. 16-2

Section 17. SYSTEM OPERATION ................................ ................................ ............................. 17-1Security Codes ................................ ................................ ................................ ............. 17-1

Installer Code ................................ ................................ ................................ ......... 17-1Assigning the Master Code ................................ ................................ .................... 17-1Changing the Master Code ................................ ................................ .................... 17-1User Codes ................................ ................................ ................................ ............ 17-1Duress Code ................................ ................................ ................................ .......... 17-1

Keypad Functions ................................ ................................ ................................ ......... 17-2General Information................................ ................................ ................................ 17-2Arming Functions ................................ ................................ ................................ ... 17-2Panic Keys ................................ ................................ ................................ ............. 17-34285 Phone module (if used) ................................ ................................ ................. 17-3Relays Outputs (if used)................................ ................................ ......................... 17-3Exit Alarm Displays (if programmed) ................................ ................................ ...... 17-3

Trouble Conditions ................................ ................................ ................................ ....... 17-4General Information................................ ................................ ................................ 17-4"Check" and "Battery" Displays ................................ ................................ .............. 17-4Power Failure ................................ ................................ ................................ ......... 17-4Other Displays ................................ ................................ ................................ ....... 17-4

Section 18. TROUBLESHOOTING GUIDE ................................ ................................ ................ 18-1Contacting Technical Support ................................ ................................ ....................... 18-3

Section 19. SPECIFICATIONS & ACCESSORIES ................................ ................................ .. 19-1Specifications ................................ ................................ ................................ ............... 19-1 Accessories (Compatible Devices) ................................ ................................ .............. 19-3

Appendix A: REGULATORY AGENCY STATEMENTS................................................ A-1

Appendix B: LIMITATIONS OF THIS ALARM SYSTEM ............................................. B-1

LIMITED WARRANTY ........................................................................ B-2

SUMMARY OF CONNECTIONS DIAGRAM ...................... Inside Back Cover

NOTE: A separate Programming Guide is supplied with this manual.

Page 6: ADEMCO N7225V2B

iv

LIST OF FIGURES

Figure 1. Installing the Cabinet Lock ................................ ................................ ........... 2-1

Figure 2. Installing The PC Board Alone, or (if used),

With a 4204, 4219, or 4229 Module ................................ .............................. 2-2

Figure 3. Installing the PC Board & RF Receiver Together in the Cabinet ................ 2-2

Figure 4. Standard Telephone Line Connections................................ ........................ 2-3

Figure 5. Keypad Connections to the Control Board................................ .................. 3-2

Figure 6. Using a Supplementary Power Supply for Keypads ................................ ... 3-3

Figure 7. 4-Wire Smoke Detector Connections to Zone 5 ................................ .......... 4-1

Figure 8. Wiring Connections, 4219 and 4229 Expanders ................................ .......... 5-1

Figure 9. 4281, 5881, and 5882 Wireless Receivers (cover removed) ........................ 6-3

Figure 10 . 4204 Connections To Control ................................ ................................ ....... 7-1

Figure 11: 4229 Connections to Control................................ ................................ ........ 7-2

Figure 12. 4285 Phone module Wiring Connections................................ ..................... 8-3

Figure 13. Typical Sounder Wiring................................ ................................ ................. 9-2

Figure 14. Long Range Radio Connections ................................ ................................ 10-1

Figure 15. Connection of AAV Unit When Not Using a 4285 Phone module ............. 11-2

Figure 16. Connection of AAV Unit When Also Using a 4285 Phone module............ 12-2

Figure 17. VIA-30PSE Summary of Connections Diagram .................. Inside Back Cover

Page 7: ADEMCO N7225V2B

v

HOW TO USE THIS MANUALThis manual is written to accommodate both the new and the experienced installer ofAdemco products. A general description of the entire system is located in the firstsection of this manual. This includes the various features available and the optionalperipheral devices that the system can support.

This manual is divided into separate sections. A section covering the hardwired zonesprovides complete information on the capabilities of each basic hardwired zone,including its usage, programming, and a checkout procedure. Separate sections arealso provided for each peripheral device that can be used in the system and includeswiring setup, programming requirements, and a checkout procedure for that device.The checkout procedures ensure that the specific device is operational in the systembefore proceeding to the next section. This “sectional” arrangement is also particularlyuseful if you are making an addition to the system at a later time (e.g., adding Wirelesszones, adding a 4285 Phone module, etc.).

Without an understanding of the programming method for this system, you will not beable to successfully perform the required programming. Before any programming isattempted, we therefore urge you to read the “Mechanics of Programming” and the“Data Field Descriptions” in the separate PROGRAMMING GUIDE that has beensupplied.

If you are an experienced user of Ademco products, you may choose to wire and thenprogram the entire system at one time. If so, refer to “Mechanics of Programming”and “Data Field Descriptions” in the separate PROGRAMMING GUIDE after thehardware setup is complete. The separate PROGRAMMING GUIDE contains all of theinformation you will need to program the system (including a blank ProgrammingForm), except for detailed programming for hardwired zones 5 and 6, hardwiredexpansion zones, and wireless zones, which are contained in the following sections inthis manual: BASIC HARDWIRED ZONES 5 and 6, HARDWIRED ZONEEXPANSION (4219, 4229), and WIRELESS (RF) ZONE EXPANSION (5700 & 5800RF SYSTEMS).

This manual uses various icons to denote critical notes and technical tips to assist youwith the installation of this system (see next page).

Page 8: ADEMCO N7225V2B

vi

CONVENTIONS USED IN THIS MANUAL

MAIN SECTION TITLES ARE SHOWN IN REVERSE TYPE

UL These notes include specific information which must be followed if you are

installing this system for a UL Listed application.

These notes include information that you should be aware of before continuingwith the installation, and which, if not observed, could result in operationaldifficulties.

This symbol indicates the presence of critical information that, if not observed,could seriously affect the operation of the system, or could cause damage to thesystem. Please read each warning carefully. This symbol also denotes warningsabout physical harm to the installer.

Enter Zn Num.

(00 = Quit) 01

Many system options are programmed in an interactive menumode by responding to Alpha keypad display prompts. Theseprompts are shown in a double-line box.

✱00 When programming the system, data fields are indicated by a“star” [✱] followed by the data field number.

PRODUCT MODEL NUMBERS: Unless noted otherwise, references to specific modelnumbers represent Ademco products.

Page 9: ADEMCO N7225V2B

1 –1

Section 1. GENERAL DESCRIPTIONThe VIA-30PSE is a control that supports up to 32 zones, using basic hardwired, wiredexpansion, and/or wireless, plus remote keypads.

Basic Hardwired Zones (5 and 6)Provides 2 basic hardwired zones having the following characteristics:• 300–500 millisecond response time.• EOLR supervision supporting N.O. or N.C. sensors.• Zone 5 supports as many 4-wire smoke or heat detectors as can be

powered from the control.• Zone 7, 95 and 96 are keypad Panics.• Zone 8 is Duress.• Zone 9 is Tamper.

Optional Expansion Zones (30 total, wired and wireless)Wired

Expansion:Supports up to 8 additional wired zones using a 4219 expansion module, or a4229 expansion/relay module. Expansion zones have the followingcharacteristics:• EOLR supervision supporting N.O. or N.C. sensors.• 300-500 msec normal response with an option for fast (10–15msec)

response on loop A (first expansion zone).

WirelessExpansion:

Supports up to 30 wireless zones (less if using wired expansion zones).• Requires the use of a 4281 type RF receiver (with 5700 series wireless

transmitters) or 5881 (5882 in Canada) type RF Receiver (with 5800 serieswireless transmitters), as shown below.

Receiver Model No. of Zones Transmitter Type4281L Up to 4 57004281M Up to 8 57004281H Up to 8 57005881L/5882L* Up to 8 58005881M Up to 16 58005881H/5882H* Up to 30 5800* 5882L or 5882H used in Canada.

Remote KeypadsSupports up to 4 of any of the following keypads:Fixed-Word Keypads: 4127*, 4137AD, 6127*, 6128, and 6137.

* These keypads cannot be used if the 4285 Phone module is being used.

Alpha Keypads: 5137AD , 6139 (2-line alphanumeric displays)6138 (1-line alphanumeric display).

For programming from a keypad, a 5137AD or 6139 2-line Alpha keypad mustbe connected (but need not necessarily stay in the system).

Security Codes• One Master code for entire system (user 2). Installer code is user 1.• 4 secondary user codes (users 3–6).• One duress code (User 8).

Duress Code: An emergency code which, when used to disarm or arm thesystem, will send a silent duress message to the central station .

Keypad Panic Keys• Up to 3 programmable panic key functions are provided.• Designated as Zones 95, 96, 7.• Activated by wired & wireless keypads.• Reported separately, distinguished by subscriber ID number.

Page 10: ADEMCO N7225V2B

1 –2

Paging FeatureIf the paging feature has been programmed for your system, your pager willrespond to certain conditions as they occur in your system, and display codenumbers indicating the type of condition that has occurred.

Quick Arm Feature“Quick Arm” may be programmed , allowing use of the [#] key in place of thesecurity code for arming (Quick Arm will not work unless the Master code hasbeen programmed into the system).

Optional Output RelaysSupports up to 4 relays using one 4204 Relay Module, or 2 relays using one4229 Zone Expansion/Relay Module.• Actions programmable to respond to zone activity or manual keypad

entries.

Optional Phone moduleSupports the Ademco 4285 VIP Phone Module.• Provides access to the system via on premises or off-premises phones for

arming, disarming, etc., plus control of relay outputs.

Optional Long Range Radio• Allows all messages that have been programmed to go to the primary

telephone number to be reported additionally to a 7720 PLUS or 7820radio.

Alarm OutputProvides a 12VDC, 2 AMP output that can drive the compatible sounders listedin the EXTERNAL SOUNDERS section (assumes a fully charged battery isconnected).• Steady output for Burglary/Panic, or temporal pulse sounding output for

Fire notification, as required by UL.• Uses current limiting circuitry for protection.

Auxiliary Power OutputProvides 12VDC, 500mA maximum. Uses current limiting circuitry forprotection.• Output interrupts for smoke detector reset if 4-wire smoke detectors are

used.

Programming• Programmed options are stored in electrically erasable, non-volatile

EEROM memory (information can be reprogrammed at any time and willnot be lost in the event of a power loss).

• The system can be uploaded, downloaded, or controlled via an IBMcompatible computer, using either Ademco's V-Link downloading software(Rev. 4 or higher) or Ademco's Compass Windows downloading software,and a modem specified by Ademco.

Keypad programming consists of:• Data field programming.• Interactive (menu) mode programming.

For programming from a keypad, a 5137AD or 6139 2-line Alpha keypad mustbe connected (but need not necessarily stay in the system).

Communication Formats Supported• Ademco Low Speed (Standard or Expanded).• Sescoa/Radionics (Standard or Expanded).• Ademco Express.• Ademco Contact ID.

Zone DescriptorsYou can assign Alpha descriptors to all zones (useful only when using Alphakeypads and/or the 4285 Phone module).

Page 11: ADEMCO N7225V2B

2 –1

Section 2. INSTALLING THE CONTROLThis section provides instructions for mounting the control cabinet, andinstalling the cabinet lock (if used). Also included in this section are instructionsfor the following:• Installing the main PC board (and 4204 Relay Unit, if used).• Mounting the RF Receiver board (if used) in the cabinet.• Standard phone line connections.• Installing the back-up battery in the cabinet.• Connecting the AC transformer.• Making earth ground connections.

Mounting the CabinetMount the control cabinet to a sturdy wall using fasteners or anchors (notsupplied), in a clean, dry area which is not readily accessible to the generalpublic. Four mounting holes are provided at the back of the cabinet.If an RF Receiver is being used and you intend to mount its PC board withinthe cabinet, note the following:• Do not mount the cabinet on or near metal objects. This will decrease RF

range and/or block RF transmissions from wireless transmitters.• Do not locate the cabinet in an area of high RF interference (revealed by

frequent or prolonged lighting of the LED in the receiver after it isoperational). Random flicker is OK.

Installing the Lock (if used)Use an Ademco No. N6277 Cam Lock and No. N6277–1 Push-On Clip(Retainer Clip).Note: The cabinet can be closed and secured without a lock by using 2

screws in the cover's edge.

CABINET DOOR BOTTOM

RETAINERCLIP

RETAINER CLIP(NOTE POSITION)

RETAINERSLOTS

LOCKED

UNLOCKED

   Figure 1. Installing the Lock

1. Remove the cabinet door. Itis easily removable forservicing and is easily re-installed.

2. Remove the lock knockoutfrom the control cabinetdoor. Insert the key into thelock. Position the lock in thehole making certain that thelatch will make contact withthe latch bracket when thedoor is closed.

3. Hold the lock steady, and in-sert the retainer clip into theretainer slots. Position theclip as illustrated in order topermit easy removal.

Before installing the cabinet's contents, remove the metal cabinet knock-outsrequired for wiring entry. Do not attempt to remove the knockouts after thecircuit board has been installed.

Installing the Control's Circuit Board Alone, or (if used), with a 4204, 4219, or 4229 RelayUnit

Control's Circuit Board 1. Hang two long Red mounting clips (provided) on the raised cabinet tabs(see Detail B in Fig. 2).

2. Insert the top of the circuit board into the slots at the top of the cabinet.Make sure that the board rests on the correct row (see Detail A in Fig. 2).

3. Swing the base of the board into the mounting clips and secure the boardto the cabinet with the accompanying screws (see Detail B in Fig. 2).

Page 12: ADEMCO N7225V2B

2 –2

4204, 4219, or 4229/Expansion Unit

(if installed in cabinet)

1. Insert self-tapping screws (provided) in two adjacent raised cabinet tabs.Leave the heads projecting 1/8".

2. Hang the unit on the screw heads via two of the slotted holes at the rear ofits housing, as shown in Figure 2.

3. The expansion unit's cover can be left off if the unit's DIP switch is set withits position 1 "ON" (to the right) as shown in its instructions. The tamperedcover is necessary for installations outside of the control's cabinet.

TAMPERE

NOT TAMPERED

DETAIL C4219/4229

COVER TAMPERJUMPER

DETAIL ASIDE VIEW OF

BOARD SUPPORTING SLOTS

CIRCUITBOARD

CABINET

DETAIL BSIDE VIEW OF

LONG MOUNTING CLIPSCONTROLCIRCUITBOARD

Figure 2. Installing The PC Board in the Cabinet Alone, or (if used), witha 4204, 4219, or 4229 Module.

Figure 3. Installing The PC Board And RF Receiver Together In The Cabinet

Page 13: ADEMCO N7225V2B

2 –3

Installing the Control and RF Receiver Circuit Boards Together in the Cabinet

1. Hang two short (black) mount ing clips (provided with receiver) on theraised cabinet tabs, as shown in Detail B in Figure 3.

2. Insert the top of the receiver board (removed from its own case as de-scribed in its instructions) into the slots at the top of the cabinet, as shownin Detail A in Figure 3. Make sure that the board rests on the correct row oftabs, as shown.

3. Swing the base of the board into the mounting clips and secure it to thecabinet with the accompanying screws (see Detail B in Fig. 3).

4. Insert the top of the control's board into the slot in the clips and positiontwo long (red) clips at the lower edge of the board (see Detail C).

5. Swing this board into place and secure it with two additional screws.

6. Insert grounding lugs (supplied with the receiver) through the top of thecabinet into the left-hand terminals of the antenna blocks (at the upperedge of the receiver board) and secure them to the cabinet top with thescrews provided, as shown in Detail D.

7. Insert the receiver's antennas through the top of the cabinet, into theblocks' right-hand terminals, and tighten the screws.

8. Setup and wiring of the receiver. is contained in the WIRELESS (RF)ZONE EXPANSION (5700 & 5800 RF SYSTEMS) section.

Standard Phone Line Connections

The wiring connections shown here are not applicable if the 4285 Phonemodule is used. Refer to the 4285 Phone module section for informationregarding phone line connections, which are different than those shown here.

Incoming phone line and handset wiring is connected to the main terminalblock (via a RJ31X jack) as indicated below and shown in Figure 4.

Term. 17: Local Handset (TIP – Brown*).Term. 18: Local Handset (RING – Gray*).Term. 19: Incoming Phone Line (TIP – Green*).Term. 20: Incoming Phone Line (RING – Red*).* Colors of wires in Direct Connect Cord.

TERMINALS ON CONTROL EARTH GROUND➡

PREMISESPHONES

HandsetIncomingTelco Line

TIP

RIN

G

BR

OW

N (

TIP

)

GR

AY

(RIN

G)

GR

EE

N (

TIP

)

RE

D (

RIN

G)

RJ31XJACK

PLUG

DIRECTCONNECT

CORD

➧TIPRING

GR

OU

ND

▲▲

INCOMING TELCO LINE

{ {

17 18 19 20 21

Figure 4.  Standard Telephone Line Connections

Page 14: ADEMCO N7225V2B

2 –4

Wiring The AC Transformer      No. 1321 Wire the No. 1321 transformer to terminals 1 and 2 on the control board. See

wiring table below for wire gauge to use.

WIRING TABLE

Distance of Transformer Wire GaugeFrom the Control Panel To Use

Up to 50 feet # 20

50–100 feet # 18

100–250 feet # 16

Wiring to the AC Transformer must not exceed 250 feet using 16 gauge wire.Do not plug the transformer into the AC outlet until you are instructed to do solater in the manual.

Installing The Back-Up Battery

Do not attach the connector cable to the battery terminals until you areinstructed to do so later in the manual.

1. Place the 12-volt back-up battery in the control cabinet.

2. Attach Red and Black wires on the battery connector cable to the controlboard as follows: †

a. Red to the positive (+) battery tab on the control board (see Summaryof Connections Diagram for location, if necessary).

b. Black to the negative (–) battery tab on the control board. † These wires may have already been connected to the battery tabs on the control

board. If so, disregard steps a. and b.

DO NOT CONNECT THE WIRES TO THE BATTERY YET!

UL Use a 4AH battery or larger for UL installations.

Earth Ground ConnectionsThe designated earth ground terminal (21), must be terminated in a good earthground for the lightning transient protective devices in this product to beeffective. The following are examples of good earth grounds available at mostinstallations:

Metal Cold Water Pipe:Use a non-corrosive metal strap (copper is recommended) firmly secured tothe pipe to which the ground lead is electrically connected and secured.

AC Power Outlet Ground:Available from 3-prong, 120VAC, power outlets only. To test the integrity of theground terminal, use a three-wire circuit tester with neon lamp indicators, suchas the UL-Listed Ideal Model 61–035, or equivalent, available at most electricalsupply stores.

Page 15: ADEMCO N7225V2B

3 –1

Section 3. INSTALLING REMOTE KEYPADSThis section lists the wired keypads that may be used and providesinstructions for wiring and mounting the keypads.A preliminary check-out procedure is also provided to ensure that theconnected keypads are functioning properly in the system.

Keypads That May Be Used• Fixed-Word Display: 4127, 4137AD, 6127, 6128, 6137

• Alpha Display: 5137AD, 6138, 6139

• Up to 4 keypads, independent of auxiliary power considerations (you mayneed to use an auxiliary power supply if the 500mA aux. output isexceeded)

If you are going to use a 4285 Phone module, you MUST use addressablekeypads (4137AD, 5137AD, 6128, 6137, 6138, 6139) in the system, but set tothe non-addressable mode (address 31).

Wiring To The Keypads1. Determine wire gauge by referring to the wiring length/gauge chart below.

For devices (Keypads, RF Receivers, etc.) connected to a single 4-wirerun, determine the current drawn by all units connected to the single wirerun, then refer to the Wiring Run chart to determine the maximum wirelength that can be safely used for each wire size. Current draw for alldevices can be found in the SPECIFICATIONS AND ACCESSORIESsection.

Note: Refer to “Auxiliary Device Current Draw Worksheet” in the FINALPOWER UP section for current draw for all keypads.

Maximum wire lengths for any device that is homerun to the control can alsobe determined from the chart, based on the current draw of that device alone.

Wiring Run Chart For Devices* Drawing Aux Power From The Control (12V+ & 12V–)

TOTAL CURRENT DRAWN BY ALL DEVICES CONNECTED TO A SINGLE WIRE RUN

  Wire Size 50mA or less 100mA 300mA 500mA

#22   500 ft (152m) 250 ft (76m)  80 ft (24m)    50 ft (15m)

#20   750 ft (228.6m) 380 ft (116m) 130 ft (39.6m)    80 ft (24m)

#18 1300 ft (396m) 650 ft (198m) 220 ft (67m)  130 ft (39.6m)

#16 1500 ft (457m) 1000 ft (305m) 330 ft (100.5m)  200 ft (70m)

* Includes Keypads, RF Receivers, Relay Units, or 4285 Phone module.

The length of all wire runs must not exceed 1500 feet (457m) whenunshielded quad conductor cable is used (750 feet if shielded cable is used).This restriction is due to the capacitive effect on the data lines when quadcable is used.

2. Run field wiring from the control to the keypads (using standard 4-conductor twisted wire cable using the wire gauge determined in step 1).

3. Connect remote Keypads to terminals 4, 5, 6, and 7 on the control board,as shown in Figure 5.

Page 16: ADEMCO N7225V2B

3 –2

KEYPADS

BLACK

RED

GREEN

YELLOW

4

5

6

CONTROLTERMINALS

KEYPAD CONNECTOR CABLE ↓

7

Figure 5. Keypad Connections To The Control Board

Mounting the Keypads1. Make sure addressable type keypads (4137AD, 5137AD, 6128, 6137,

6138, and 6139) are set to non-addressable mode (address 31), which isthe factory default setting. Refer to the instructions provided with thekeypad for address setting procedure.

2. Mount the keypads at a height that is convenient for the user. Refer tothe instructions provided with the keypad for mounting procedure.You can either surface mount or flush mount keypads (using anappropriate Trim Ring Kit: 5137TRK or 6139TRK). Refer to the mountinginstructions and template included with the keypad and/or trim ring kit forspecific information.

Using a Supplementary Power Supply to Power Additional KeypadsThe control provides 500mA for powering keypads (up to a maximum of 4 )and other devices from the auxiliary power output. The backup battery willsupply power to these keypads in the event that AC power is lost.

When the control’s auxiliary power load for all devices exceeds 500mA, youcan power additional keypads from a regulated, 12VDC power supply (e.g.,487-12 supplies 12V, 250mA; 488-12 supplies 12V, 500mA). Use a UL Listed,battery-backed supply for UL installations.

The 487-12/488-12 power supplies have a backup battery which can powerthese keypads in the event of AC power loss.

Keypads powered from supplies which do not have a backup battery will notfunction when AC power is lost. Therefore, be sure to power at least onekeypad from the Control's auxiliary power output.

Connect the additional keypads as shown in Figure 6, using the keypad wirecolors shown. Be sure to observe the current ratings for the power supplyused.

Make connections directly to the screw terminals as shown in Figure 6. Makeno connection to the keypad blue wire (if present).Be sure to connect the negative (–) terminal on the Power Supply unit toterminal 4 (AUX – ) on the control.

Page 17: ADEMCO N7225V2B

3 –3

SUPPLEMENTARYPOWER SUPPLY

+ –

CONTROLTERMINAL STRIP

AUX AUX. DATA DATA– + IN OUT4 5 6 7

IMPORTANT:MAKE THESE CONNECTIONSDIRECTLY TOSCREW TERMINALSAS SHOWN.

TO

KE

YP

AD

RE

D W

IRE

TO

KE

YP

AD

BLK

WIR

E

TO

KE

YP

AD

YE

LW

IRE

TO

KE

YP

AD

GR

N W

IRE

TO

KE

YP

AD

BLK

WIR

E

TO

KE

YP

AD

RE

D W

IRE

TO

KE

YP

AD

GR

N W

IRE

TO

KE

YP

AD

YE

LW

IRE

Figure 6. Using A Supplementary Power Supply For Keypads

Preliminary Check-out ProcedureIf you want to check that the system is working before connecting field wiringfrom zones and devices, do the following:

1. Temporarily connect a 1000 ohm end-of-line resistor across each of thebasic hard-wire zones 5 and 6, as shown in the Summary of Connectionsdiagram.Without actual zone wiring or EOL resistors connected, the keypads in thesystem will not display the “Ready” message.

2. Power up the system temporarily by plugging the AC transformer(previously wired to the control) into a 120VAC outlet.

3. Bus y – S ta ndby (Alpha keypads) or dI (Fixed-word keypads) will bedisplayed.After approximately 1 minute*, the green “READY” LED (or “POWER”LED on some types of keypads) should light, and the word READY (Fixed-word keypads), or DISARMED...READY TO ARM (Alpha keypads) shouldbe displayed.* To bypass the 1-minute delay, press # plus 0.

If the “Ready” message is not displayed on any of the keypads in thesystem, or a “Not Ready” message is displayed, check the keypad wiringconnections, and make sure each of the 6 basic hard-wired zones has a1000 ohm resistor connected across its terminals.

4. When you get the proper “Ready” displays on the keypad(s), the system isfunctioning properly at this point.

Do not remove the EOL resistors until you are ready to make connections tothe hard-wired zones, to allow for testing later in the manual.

If an OC or OPEN CIRCUIT display is present on the keypad, data from thecontrol is not reaching the keypad. Check the wiring.

Page 18: ADEMCO N7225V2B

3 –4

Page 19: ADEMCO N7225V2B

4 –1

Section 4. BASIC HARD-WIRED ZONES 5 AND 6This section provides general information for the hard-wired zones in thesystem, plus specific instructions for installing 4-wire smoke/combustiondetectors. Also included is a procedure for programming the hard-wired zones.

Installing the Hard-Wired ZonesCommon Characteristics for Zones 5 and 6

• Response time from 300 –500 milliseconds (400 milliseconds nominal).• EOLR supervised zones support both open-circuit & closed-circuit devices.• As many 4-wire smoke detectors as can be powered from Aux Power on

the control (on zone 5).

Wiring Burglary and Panic Devices To Zones 5 and 61. Connect sensors/contacts to the hard-wired zone terminals (8 through 16).

See the Summary of Connections diagram .2. Connect closed circuit devices in series in the high (+) side the loop. The

EOL resistor must be connected in series with the devices, following thelast device. See the Summary of Connections diagram.

3. Connect open circuit devices in parallel across the loop. The 1,000 ohmEOLR must be connected across the loop wires at the last device.

If the EOLR is not at the end of the loop, the zone will not be properlysupervised, and the system may not respond to an open circuit on the zone.

Wiring 4-Wire Smoke/Combustion Detectors on Zone 5The system will support as many 4-wire detectors as can be powered fromAuxiliary Power on the control on zone 5. Refer to the detector’s instructionsfor complete details regarding its proper installation and operation.1. Connect 12 volt power for the detectors from Auxiliary Power terminals 4

and 5, (which will interrupt power for fire alarm reset). Observe properpolarity when connecting detectors. See Figure 7.

2. Connect detectors (including heat detectors, if used) across terminals ofzone 5. All detectors must be wired in parallel.

Remove 1000 ohm EOL resistor if connected across the zone terminals. Youmust connect the EOL resistor across the loop wires at the last detector.

3. To meet NFPA 72 requirements, you must use a supervisory module tosupervise power (e.g., System Sensor No. A77-716B Relay module).

AUX PWROUTPUT

TERMINALS

+

-

TO HI SIDEOF ZONE 5(TERM 14)

TO LO SIDEOF ZONE 5(TERM 15)

-+

-+

••

•EOLPOWERSUPERVISIONRELAYMODULEA77-716B

1000OHMSEOLR

-+

4-WIRE SMOKEDETECTORS

+-

HEAT DETECTOR

HEAT DETECTOR

➔➔VIOLET

BLK

Figure 7. 4-wire Smoke Detector Connections (Zone 5).

Page 20: ADEMCO N7225V2B

4 –2

Compatible System Sensor 4-Wire Smoke/Combustion Detectors

1412 4-wire ionization products of combustion detector.

2412 4-wire photoelectric smoke detector.

2412TH 4-wire photoelectric smoke detector w/135°F (57°C) heatdetector.

A77–716B EOL relay module (supervisory module for wired 4-wire firezone).

2112/24T Low-profile 4-wire photoelectric smoke detector w/135°F(57°C) heat detector.

Programming Hard-Wired Zones1. With at least one 2-line Alpha keypad (5137AD or 6139) connected to the

keypad terminals on the control, power up the system temporarily. If youhad previously connected the AC transformer to the control panel, youneed only plug in the transformer (to 120VAC outlet) to power up thesystem.

2. Enter the programming mode by keying the following on the Alpha keypad:    INSTALLER code (4 1 1 1) + 8 + 0.

Data fields ✱22 RF SYSTEM, and ✱25 OUTPUT RELAY MODULE must beprogrammed as required before continuing.

3. Press ✱56. Note that this is an interactive programming mode. You willuse it to program zone numbers, zone types, and alarm report codes forhard-wired zones (and RF zones).Note: If you enabled the 5800 wireless system in field ✱22 (a “2” entry),

the first screen prompt will be “Program Tool?... 0 = No 1 = Yes”.Enter “0” (No). The next prompt will ask you to enter zone number.

Enter Zn Num.

(00 = Quit) 05

  Zone Number ↑

Enter the first zone number that you wish toprogram (or [0][0] to exit zone programming). Ifyou are starting with zone 5, enter and press[✱] to continue.If programming another zone, enter the desiredzone number, 06, etc. (zone 02 is shown in thenext display). Press [✱] to continue.

Typical summary display

Zn ZT – RC In L

05 03 – 00 HW: –

A summary display will appear, showing thepresent status of that zone's programming.Zn = zone number;ZT = zone type;RC = report code for that zone;In = input type of zone.Values displayed are currently programmedvalues.If it is programmed satisfactorily, press [#] toback up one step and enter the next zonenumber, if desired.

↓ Zone Number

05 Zone Type

Perimeter 03

Zone Type ↑

If you want to change a zone’s programming,press [✱ ]. A prompt for Zone Type will appear.Each zone must be assigned a zone type,which defines the way in which the systemresponds to faults in that zone. A detailedexplanation of each zone type is provided in“Response Type Definitions” in the ZONERESPONSE TYPE DEFINITIONS section inthe Programming Guide.Enter the desired zone type code, as listednext. The example on the left shows zone type“03”, Perimeter, entered.

Page 21: ADEMCO N7225V2B

4 –3

Zone Types00 = Zone Not Used01 = Entry/Exit #102 = Not used03 = Perimeter04 = Interior Follower05 = Trouble Day/Alarm Night06 = 24 Hr Silent07 = 24 Hr Audible

08 = 24 Hr Aux09 = Fire10 = Interior w/Delay20 = Arm Stay o 580021 = Arm-Away o  RF22 = Disarm o Systems23 = No Alarm Only

   Response

When the display shows the zone type youwant, press [✱] to continue.

You must enter “00” as the zone type for any hard-wired zone that is notused.

05  Report Code

1st 03  2nd 12 3C

The report code consists of 2 hexadecimaldigits, each in turn consisting of 2 numericaldigits. For example, for a report code of "3C",enter [0][3] for "3" and [1][2] for "C". Refer to theSYSTEM COMMUNICATION section f o rcomplete information on report codes, ifnecessary.Enter the desired report code and then press [✱]to continue.

 Typical summary display

Zn ZT – RC In L

05 03 – 3C HW: –

A summary display will appear, showing thedata for the zone that was just programmed.If it is programmed satisfactorily, press [✱ ] tocontinue.

Program Alpha?

0 = No 1 = Yes 0

The next request is to enter Alpha descriptorsfor the zones. The entry may be done now(enter 1), or may be done at a later time using✱82 interactive mode (enter 0). See the ALPHADESCRIPTOR PROGRAMMING section forspecific procedure.

Enter Zn Num.

(00 = Quit) 03

Enter next zone number ↑

If “0” (no) was entered above, the system willreturn to the Enter Zone Number prompt.Proceed with the programming for the nextzone, i.e., [✱] and zone number.

ProgrammingPanic Keys

When programming zones, note the following:The defaults for individual panic keys or panic key pairs are:Zone 07. ✱ & #, or B: zone type 06 (24-hr silent).Zone 95. 1 & ✱ , or A: zone type 00 (not used).Zone 96. 3 & #, or C: zone type 00 (not used).

Panic keys are programmed (or re-programmed) by keying the zone number,e.g., ✱07, ✱95, and ✱96, and entering the desired zone type that will providethe desired panic function for each of these keys, using the list of zone typesbelow.

06 = 24 Hr Silent07 = 24 Hr Audible08 = 24 Hr Aux09 = Fire

Page 22: ADEMCO N7225V2B

4 –4

When you have programmed all the hard-wired zones and Panic keyssatisfactorily, exit ✱ 56 interactive mode at the Enter Zn Num. prompt byentering [0] [0] as the next zone number.

Then exit the programming mode by keying ✱99.

See the special notes below, then proceed to the check-out procedure thatfollows.

Special Notes onZone

Programming

• In field *56, at the summary line for each zone, the entered values can bechecked. If you wish to change anything, press [#] to move to the previousentry. Press [#] a number of times to move to earlier entries. Press [✱ ] tomove to later entries again.

• Zone entries can be reviewed by pressing [#][5][6]. Changes cannot bemade here, so this is safer for review. Enter the first zone number to beviewed and press [#]. To view each zone, press [#] and the zone numberwill advance to the next programmed zone. When the end of the list isreached, press [0][0] to exit. This method of exiting may also be done at anytime during the review.

• To either temporarily or permanently remove a zone from the system, gointo programming mode and press [✱][5][6]. Enter the zone number andpress [✱]. At the Zone Type prompt, enter [0][0] and [✱]. This sets the typeof the zone to Not Used. The next prompt will be "Delete Zone?". "Yes" willpermanently remove the zone from the system while "No" will disable it butretain all data except the original zone type. You can then go back to thiszone later and put back an active Zone Type to re-enable it.

Check-Out Procedure For Hard-Wired ZonesAfter installation of all hard-wired devices is completed, the security systemshould be checked, as follows.1. Make certain that all devices and sensors connected to the hard-wired

zones are not in a faulted state. Doors and windows with contacts shouldbe closed, PIRs should be covered (use a cloth to mask them temporarily ifnecessary).

2. Plug in the AC Transformer if you have not already done so..

3. With all hard-wired zones intact, the Alpha keypad connected to the systemshould display:

✮ ✮ ✮ DISARMED ✮ ✮ ✮

READY TO ARM

If the following is displayed,

DISARMED P r e ss ✱to show fa u lts

press the [✱] key to display the faulted zone(s). Restore any faulted zone(s)as necessary (also make sure that you have connected a 1000 ohm EOLresistor across the terminals of unused zones).When the DISARMED ...READY TO ARM message is displayed, you canproceed to the next step.

4. Fault and then restore every contact or sensor on each zone individually toensure that it is being monitored by the system. Each time a zone is faulted,the keypad should display the number of the faulted zone. When each zoneis restored, the READY TO ARM message should appear again.

5. When you get the proper displays on the keypad(s), the hard-wired zones inthe system are functioning properly.

Page 23: ADEMCO N7225V2B

5 –1

Section 5. WIRED ZONE EXPANSIONThis section provides information regarding the use of expansion modules (4219 or 4229) forexpanding the number of wired zones in the system, describes the modules that can be usedand their wiring connections, plus a procedure for programming the wired expansion zones.

Installing Zone Expansion UnitsYou can add an additional 8 wired expansion EOLR zones to the basiccontrol's 8 hardwired zones, for a total of 14 wired zones, by using a No. 4219Wired Expansion Unit, or 4229 Wired Expansion/Relay Unit.

Location • You can mount an expansion unit within the controlcabinet if space permits. Otherwise, mount the unitoutside the cabinet.

Supervision • Units are supervised against removal. Keypads willdisplay CHECK and zone 09 if a zone expander isdisconnected.

• Units have tamper protection for security whenmounted outside of the cabinet.

Zone Information • Assign zone numbers 10–17 for the eight wiredexpansion loops (designated A to H). You canprogram these zones individually (in ✱56 interactivemode, as indicated in “Programming WiredExpansion Zones” later in this section.

Connectionsand Set-Up

1. Connect the 4219 or 4229 module to the control's keypad terminals (seediagram below).

2. Set the 4219 or 4229's DIP switch for device address "1" (switch 2"OFF" and switches 3, 4, 5 "ON"). Switch 1 determines expansion zone A'sresponse time ("ON" = normal response, "OFF" = fast response). Forlocation of the DIP switch in the unit, see the diagram below (location of DIPswitch for both units is in the same location).

For additional information, see instructions supplied with the 4219 and4229.

BR

N

1 2 3 4 5 6 7 8 9 10 11 121

2

3

4GRN DATA OUT

TO CONTROLBLK

(–) GROUND

RED (+) 12V

YEL DATA INFROMCONTROL

432

1

TERMINATE EACHPROGRAMMED ZONEWITH 1000 OHM (1K)END-OF-LINE RESISTOR(EACH ZONE'S MAX.LOOP RESISTANCE:300 OHMS + E.O.L.)

ZONES: A B C D E F G H

1K

DIP SWITCHFOR SETTING ADDRESSAND ZONE “A” RESPONSE

REED(TAMPER)SWITCH

TAMPER JUMPER POSITION4229 IN CABINET (NOT TAMPERED)4229 REMOTE(TAMPER PROTECTED) TB1

4229

TB24-PIN CONSOLE PLUG

EITHER OR BOTH CAN BE USED

➞ ➞

WH

TG

RY

VIO

BLK

YE

LO

RG

NO

NC

CG

ND

NO

NC

C

RLY2

RLY1

RELAYS"OFF"

RELAYCONNECTOR

NO C NC

{ {{

RELAY2

}

}

RELAY1

TERMINALS ONCONTROL PANEL

(TERM 6)

(TERM 4)

(TERM 5)

(TERM 7)

4229

Figure 8. Wiring Connections, 4219 & 4229 (4229 shown)

Page 24: ADEMCO N7225V2B

5 –2

Programming Wired Expansion Zones1. With at least one 2-line Alpha keypad (6139) connected to the keypad

terminals on the control, power up the system temporarily. If you hadpreviously connected the AC transformer to the control panel, you needonly plug in the transformer (to 120VAC outlet) to power up the system.

2. Enter the programming mode by keying the following on the Alpha keypad:    Installer code (4 1 1 1) + 8 + 0.

If RF zones, or wired expansion is used, data fields ✱22 RF SYSTEM TYPE ,and ✱ 25 WIRED EXPANSION/RELAY USED must be programmed asrequired before continuing (see Programming Form in the separateProgramming Guide.

3. Press ✱56. Note that this is an interactive programming mode. It is usedto program zone numbers, zone types, and alarm report codes for allzones that are going to be used.Note: If you enabled the 5800 wireless system in field ✱22 (entry of “2”),

the first screen prompt will be “Program Tool?... 0 = No 1 = Yes”.Enter “0” (No). The next prompt will ask you to enter zone number.

Enter Zn Num.

(00 = Quit) 10

Zone Number ↑

Enter the first zone number that you wish toprogram (or [0][0] to exit zone programming).Normally, you will be starting with zone 10 (thisis the default).Press [✱] to continue.

Zn ZT RC In L

10 00    –    00 RF: 1

A summary display will appear, showing thepresent status of that zone's programming.Zn = zone number.ZT = zone type.RC = report code for that zone.In = input type of zone (AW for Aux Wired).L = Loop (not used for wired expansion zones)Values in the summary display are the currentlyprogrammed values.To start programming zone 10, press [✱ ]. Aprompt for Zone Type will appear.

 ↓  Zone Number

10 Zone Type

Perimeter 03

Zone Type 03 entry shown ↑

Each zone must be assigned a zone type, whichdefines the way in which the system responds tofaults in that zone. A detailed explanation ofeach zone type is provided in “Response TypeDefinitions” in the in the separate ProgrammingGuide.

Enter the desired zone type from the list below.00 = Zone Not Used01 = Entry/Exit #103 = Perimeter04 = Interior Follower05 = Trouble Day/Alarm Night

06 = 24 Hr Silent07 = 24 Hr Audible08 = 24 Hr Aux09 = Fire10 = Interior w/Delay23 = No Alarm Response

When the display shows the zone type youwant, press [✱] to continue.

10 Report Code

1st 03 2nd 12 3C

The report code consists of 2 hexadecimaldigits, each in turn consisting of 2 numericaldigits. For example, for a report code of "3C",enter [0][3] for "3" and [1][2] for "C". Refer to theSYSTEM COMMUNICATION section for com-plete information on report codes, if necessary.Enter the report code and then press [✱ ] tocontinue.

Page 25: ADEMCO N7225V2B

5 –3

10 Input Dev:        LP#AUX WIRED   AW: 01

At the “INPUT DEVICE” prompt, enter “2” (AUXWired) as the input device. The display on theleft will appear.Press [✱] to continue.

     Typical summary display

Zn  ZT   RC In    L

10  03  – 03 AW: –

A summary display will appear, showing thedata for the zone that was just programmed.Note that AW indicates an auxiliary wired (zoneexpansion module) zone.If it is programmed satisfactorily, press [✱ ] todisplay the next prompt.

Program Alpha?

0 = No 1 = Yes 0

For all zone types, the next request is to enterAlpha descriptors for the zones. The entry maybe done now (enter 1) or may be done at a latertime using ✱82 interactive menu mode (enter 0).We recommend that the entry of Alphadescriptors be done later using ✱82 menumode.See ALPHA DESCRIPTION PROGRAMMINGsection for specific procedure.

Enter Zn Num.

(00 = Quit) 11

  Enter next zone number ↑

If “0” (No) was entered above, the system willdisplay a prompt for entry of the next wiredexpansion zone number. Proceed with theprogramming for the next zone, as indicatedpreviously.

When all wired expansion zones areprogrammed satisfactorily, exit ✱56 mode at theEnter Zn Num . prompt by pressing: [0 ] [0] ✱.

Exit the programming mode by keying ✱99.

Proceed to the check-out procedure that follows.

Check-Out Procedure For Wired Expansion Zones

After you have completed installation of all devices, all wired expansion zonesshould be checked as follows:1. Make certain that all devices and sensors connected to the wired expansion

zones are not in a faulted state. Doors and windows with contacts should beclosed, PIRs should be covered (use a cloth to mask them temporarily ifnecessary).

2. With all zones intact (including hard-wired zones), the Alpha keypadconnected to the system should display:

✶ ✶ ✶ DISARMED ✶ ✶ ✶

READY TO ARM

If the following is displayed,

DISARMED Pre s s ✱

to s how fa ul ts

press the [✱ ] key to display the faulted zone(s). Restore any faulted zone(s)as necessary (also make sure that you have connected a 1000 ohm EOLresistor across the terminals of unused expansion zones on the 4219 or4229 module).

When the READY TO ARM message is displayed, you can proceed to thenext step.

(Continued)

Page 26: ADEMCO N7225V2B

5 –4

3. Fault and restore every contact or sensor in each expansion zoneindividually to ensure that it is being monitored by the system. Each time azone is faulted, the keypad should display the number of the faulted zone(as programmed by you just previously in ✱56 mode). When each zone isrestored, the READY TO ARM message should appear again.

4. When you get the proper displays on the keypad(s), the wired expansionzones in the system are functioning properly.

5. Unplug the AC transformer.

If a "CHECK 09" message appears on the display, data from the control is notbeing received by the zone expander module. Check your wiring and DIPswitch settings.

Page 27: ADEMCO N7225V2B

6 –1

Section 6. WIRELESS (RF) ZONE EXPANSION(5700 AND 5800 RF SYSTEMS)

This section provides the following information:• Wireless systems available.• Installing the wireless receiver.• Installing the 5800TM Module.• Programming for the wireless receiver.• Setup and installation of the wireless transmitters (5700 or 5800 series).• Programming the wireless transmitters (5700 or 5800 series).• Checkout procedure for wireless zones (test modes).

UL Wireless may not be used in UL Commercial Burglary installations.

Wireless Systems AvailableThe VIA-30PSE supports wireless zones which may be used exclusively, or inaddition to hardwire zones 5 and 6. The system supports two different wirelesssystems which have many similarities, but notable differences in theprogramming of the transmitters for each system.The following receivers may be used with this system and each supports thenumber of zones shown:

TABLE 15700 Series

         Receiver Wireless Zones

4281L/4281CN-L† up to 4

4281M/4281CN-M† up to 8

4281H/4281CN-H† up to 30

5800 Series         Receiver Wireless Zones

5881L/5882L† up to 8

5881M up to 16

5881H/5882H† up to 30

† 4281 and 5882 type receivers are for use in Canada. See special note below.

In Canada , 5700 systems must use 4281CN series receivers (4281CN-L,4281CN-M, or 4281CN-H) (with Canadian versions of 5700 typetransmitters). 5800 systems must use 5882 series receivers (5882L or5882H). Information in this manual relative to the 4281 series of receiversapplies as well to the 4281CN series. Information relative to the 5881 seriesof receivers applies as well to the 5882 series. 5881 and 5882 seriesreceivers can use the same transmitters (5800 type).

Any zone number from 10–63 can be used as a 5700 or 5800 series wirelesszone (do not confuse this with the number of zones that can be used, which isshown in Table 1 above).

Wireless System Operation and Transmitter SupervisionThe receiver responds to status and alarm signals from wireless transmitters[operating at 345MHz for 5700 series in USA (315MHz in Canada), and 345MHz for 5800 series (in USA and Canada)] within a nominal range of 200 feet;the receiver then relays this information to the control.

Except for transmitters that may be carried off-premises (such as the 5700system's 5701 and 5727, the 5800 system's 5802, 5802CP, 5803, 5804, and5827, and either system's 5827BD), each transmitter is supervised by a check-in signal that is sent to the receiver at 70–90 minute intervals. If at least onecheck-in is not received from each supervised transmitter within a 12-hourperiod, the "missing" transmitter number(s) and "CHECK" will be displayed onthe keypad.

Page 28: ADEMCO N7225V2B

6 –2

The supervision for a particular transmitter in the 5800 system may be turnedoff by entering it as a "UR" (unsupervised RF) type, as described later.5800 series transmitters have built-in tamper protection and will cause a“CHECK” condition to be annunciated if covers are removed.Each transmitter is also supervised for low battery and will transmit a lowbattery signal to its receiver, with the battery having at least 30 days of life re-maining. A low battery message and appropriate zone number will appear ona wired keypad's display.If a 5727, 5827, or 5827BD wireless keypad has a low battery, it will bedisplayed as Zone “00” when it transmits.Note: After a low or dead battery is replaced, activate the transmitter and

then enter the security code + OFF to clear the system's memory ofthe "Low Battery" signal.

TransmitterBattery Life

• Batteries in the wireless transmitters may last from 4-7 years, depending onthe environment, usage, and the specific wireless device being used.External factors such as humidity, high or low temperatures, as well aslarge swings in temperature may all reduce the actual battery life in a giveninstallation. The wireless system can identify a true low battery situation,thus allowing the dealer or user of the system time to arrange a change ofbattery and maintain protection for that given point within the system.

• Some transmitters (e.g., 5802, 5802CP, and 5803) contain long-life but non-replaceable batteries. At the end of their life, the complete unit must bereplaced (and a new serial number entered into the control).

• Button type transmitters (e.g.,. 5802, 5802CP, 5803, 5804) should beperiodically tested by the user for battery life.

Receiver Supervision

The receiver itself is supervised. A tamper report (zone 9) will be generated:a) If communication with the receiver is interrupted

    orb) If valid RF signals are not received within 12 hours from at least one

supervised wireless transmitter (if any are included in the system)

Wireless SystemInstallationAdvisories

Disregard the following advisories if the receiver is mounted in the controlcabinet as described in the INSTALLING THE CONTROL section.1. Place the receiver in a high, centrally located area for best reception. Do

not place receiver on or near metal objects. This will decrease the rangeand/or block transmissions. Do not mount receivers or transmitters in anattic, where extreme temperatures could prevent proper operation.

2. The house IDs must be entered for the receiver (applies only to 5700 RFsystem or if using a 5827/5827BD wireless keypad in a 5700 or 5800 RFsystem).

Installation and Setup of the 4281/5881 Wireless Receivers1. Mount the receiver(s) if not installed previously in the control cabinet, as

indicated in the INSTALLING THE CONTROL section. Receivers candetect signals from transmitters within a nominal range of 200 feet. Takethis into consideration when determining mounting location outside of thecabinet.

2. Make sure that the receiver’s DIP switches are set for device address “0”,as shown in Figure 8 (all switches to the right...OFF).

3. Connect the receiver's wire harness to the control's keypad terminals (4, 5,6, and 7). Plug the connector at the other end of the harness into thereceiver (see Figure 9).

4. Refer to the receiver’s installation instructions for further installationinstructions regarding antenna mounting, etc.

Page 29: ADEMCO N7225V2B

6 –3

4

3

2

1

ON OFF

MOUNTINGHOLES INTERFERENCE

INDICATORLED

CIRCUITBOARD

DIP SWITCH

PLUG&SOCKET

INSERT INRIGHT-HANDTERMINALS

ANTENNAS

YELLOWREDBLACKGREEN } TO CONTROL’S REMOTE

KEYPAD CONNECTIONPOINTS. EACH RECEIVERMUST BE ON INDIVIDUALHOME RUN.

WIRINGOPENING

KNOCKOUTAREA FORSURFACEWIRING

5882LOCATION

@@@@@@@@e?@@@@@@@@e?@@h?@@h?@@h?@@h?@@h?@@h?

@@@@@@@@e?@@@@@@@@e?

@@@@@@@@@@@@@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

?@@?@@?@@?@@?@@?@@

?@@@@@@@@?@@@@@@@@

?@@@@@@@@?@@@@@@@@

@@g@@g@@g@@g@@g@@g@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

{TO RELEASE CIRCUITBOARD, REMOVESCREWS (2) AND BENDBACK TABS (S)

NOTE: WHEN CIRCUIT BOARD ISMOUNTED IN CONTROL’S CABINET,GROUNDING LUGS (2) PROVIDEDMUST BE INSERTED IN LEFT-HANDTER-MINALS OF ANTENNA BLOCKS ANDSECURED TO CABINET (SEE RECEIV-ER’S AND CONTROLS INSTRUCTIONS)

Figure 9. 4281, 5881, & 5882 Series Wireless Receivers (cover removed)

Installing the 5800TM ModuleInstallation of this module is necessary only if you are using one or more5827BD Wireless Bi-directional keypads.

The 5800TM must be located between one and two feet from the 4281 or 5881receiver's antennas. The 5800TM must not be installed within the controlcabinet. Mount the unit using its accompanying mounting bracket.

5800TM WiringConnections

Connect the 5800TM to the control panel’s keypad connection terminals, usingthe supplied connector with flying leads, as follows:

WIRE TERMINAL ON CONTROLRED (+12VDC) Terminal 5BLACK (Ground) Terminal 4GREEN (Data to Control) Terminal 6YELLOW (Data from Control) Terminal 7BLUE: Not Used

Do not cut any of the jumpers on the 5800TM when using it with theVIA-30PSE.

For additional information, refer to the 5800TM’s instructions.

5700 Series Transmitter SetupEach 5700 series transmitter has DIP switches to set both the transmitter'szone number (Transmitter zone/ID) and the system House ID. The House IDwill be the same for all transmitters and must match the House ID programmedinto the system (in data field ✱24) for the wireless receiver. This can belikened to a family in which everyone has the same last name (House ID), buteach person has a different first name (Transmitter zone/ID). The zone/IDnumber must then be programmed into the system using ✱ 56 interactivemode.

A variety of wireless transmitters can be used to make up the wireless zones.These include window/door units, smoke detectors, PIRs, and panic buttons.Zone/ID number assignments can be from 10–63 . Remember, the 5700system supports up to 8 wireless zones, depending on the RF receiver used(see Table 1 previously).

Page 30: ADEMCO N7225V2B

6 –4

Setting the DIP Switcheson 5700 Series

Transmitters

Set the DIP switches on each 5700 series transmitter to the appropriatezone/ID number and House ID. Refer to the Compatible 5700 SeriesTransmitters table on a following page in this section for zone numbers andprogramming information for each particular transmitter. Refer also to DIPSWITCH TABLES FOR 5700 RF WIRELESS DEVICES later in this section.

The House ID allows the 5700 RF system to identify 5700 transmitters with amatching House ID. If using a 5700 RF wireless system, the DIP switches onthe transmitters must match the system House ID programmed into thecontrol (in data field ✱24). If using a 5827BD wireless keypad, the House IDalso applies. Other than the 5827 and 5827BD, 5800 series devices do notcommunicate by House ID, but by transmitting a unique serial number to thecontrol. In this case, programming a House ID is not necessary.

Wireless Zone/IDAssignments for 5700

Series Transmitters

Each wireless zone can be assigned any zone response type, such asEntry/Exit, Interior Follower, Perimeter, etc. (see the ZONE RESPONSE TYPEDEFINITIONS section in the separate Programming Guide for a detailedexplanations of each zone type). For 5700 series transmitters, each responsetype uses a certain range of zone numbers. Each range of zone/ID numbers isshown below.

Zone Type Transmitter Zone/ID #––––––––––––––––––––––––––– –––––––––––––––––––––––––––––––––––––––––––––––––––––––––

Entry/Exit Burg ....................... 10 through 47 *Perimeter Burg....................... 10 through 47 *Interior Burg ........................... 10 through 47 *

32 through 47 * (5775)Fire................................ ......... 48 through 63 *

48 through 55 ** (5706)24 Hour Panic ........................ 48 through 63 *(silent or audible) ................... 62 or 63 *** (5701)Day/Night Burglary ................. 10 through 47 *24 Hour Auxiliary.................... 10 through 47 *

  *  Zone/ID numbers 10–63 can be used, but you should note the following in      connection with certain transmitter zone/IDs identified as follows:

  ** Transmitter IDs 48 through 55 have highest signal priority.*** Transmitter IDs 62 and 63 are unsupervised to allow removal of the 5701 off       premises — signal priority is lower than that of fire, but higher than burglary.

Notes: 1. Transmitters set for zone/IDs 48–55 (FIRE) will transmit once every 12seconds while the zone is faulted. Transmitters set for zone/IDs 56–63 willtransmit once every 3 seconds while faulted. These two ranges of zone/IDnumbers have high signal priority and their frequent transmissions whilefaulted ensure re-triggering of the alarm until the cause is removed. Bearin mind that because of this, transmitter battery life could be shortened.

2. Transmitters set for an zone/IDs of 32 through 47 will have a 3-minutelock-out between transmissions. Use this range of zone/ID numbers forsensors protecting frequently used doors or windows to conserve batterylife.

3. Refer also to “Compatible 5700 Series Transmitters” on a following page.

Page 31: ADEMCO N7225V2B

6 –5

DIP SWITCH TABLES FOR 5700 RF SYSTEM WIRELESS DEVICES

HOUSE ID (1 SHOWN)

HOUSE ID (1 SHOWN)

HOUSE ID (1 SHOWN)

1 2 3 4 5 6

UP

DN

1 2 3 4 5

UP

DN

1 2 3 4 5 6 7 8

UP

DN

1 2 3 4 5 6 7 8 9 10

UP

DN

5706/5707 SMOKEDETECTORTRANSMITTER

5775 PIRDETECTOR/TRANSMITTER

HOUSE IDSWITCH SETTING FOR ALL

DEVICES EXCEPT 5716

5727 KEYPAD

DEVICEID

DIP SWITCH POSITION

1 2 3 4 5

1 UP UP UP UP —2 UP UP UP — UP3 UP UP UP — —4 UP UP — UP UP5 UP UP — UP —6 UP UP — — UP7 UP UP — — —8 UP — UP UP UP9 UP — UP UP —10 UP — UP — UP11 UP — UP — —12 UP — — UP UP13 UP — — UP —14 UP — — — UP15 UP — — — —16 — UP UP UP UP17 — UP UP UP —18 — UP UP — UP19 — UP UP — —20 — UP — UP UP21 — UP — UP —22 — UP — — UP23 — UP — — —24 — — UP UP UP25 — — UP UP —26 — — UP — UP27 — — UP — —28 — — — UP UP29 — — — UP —30 — — — — UP31 — — — — —

BIT VALUE: 16 8 4 2 1

DIP

SIDEVIEW (UP)

SIDEVIEW (UP)

SIDEVIEW (UP)

SIDEVIEW (DN)

5701 PANIC TRANSMITTER

POS.6 UP= XMTR ID 62DN= XMTR ID 63

DIP

XMTR IDFIXED AT

“00”

XMTR ID(48 SHOWN)

XMTRID

DIP SWITCH POSITION

6 7 8

48 UP UP UP49 UP UP —50 UP — UP51 UP — —52 — UP UP53 — UP —54 — — UP55 — — —

XMTRID

DIP SWITCH POSITION

6 7 8 9

32 UP UP UP UP33 UP UP UP —34 UP UP — UP35 UP UP — —36 UP — UP UP37 UP — UP —38 UP — — UP39 UP — — —40 — UP UP UP41 — UP UP —42 — UP — UP43 — UP — —44 — — UP UP45 — — UP —46 — — — UP47 — — — —

}

DIP

HOUSE ID (1 SHOWN)

UP = PULSE COUNT— = INST. MODE

XMTR ID(32 SHOWN)

}MIRRORDIP

XMTRID

DIP SWITCH POSITION

6 7 8 9 10 11

1 UP UP UP UP UP —2 UP UP UP UP — UP3 UP UP UP UP — —4 UP UP UP — UP UP5 UP UP UP — UP —6 UP UP UP — — UP7 UP UP UP — — —8 UP UP — UP UP UP9 UP UP — UP UP —

10 UP UP — UP — UP11 UP UP — UP — —12 UP UP — — UP UP13 UP UP — — UP —14 UP UP — — — UP15 UP UP — — — —16 UP — UP UP UP UP17 UP — UP UP UP —18 UP — UP UP — UP19 UP — UP UP — —20 UP — UP — UP UP21 UP — UP — UP —22 UP — UP — — UP23 UP — UP — — —24 UP — — UP UP UP25 UP — — UP UP —26 UP — — UP — UP27 UP — — UP — —28 UP — — — UP UP29 UP — — — UP —30 UP — — — — UP31 UP — — — — —32 — UP UP UP UP UP

BITVALUE: 32 16 8 4 2 1

XMTRID

DIP SWITCH POSITION

6 7 8 9 10 11

33 — UP UP UP UP —34 — UP UP UP — UP35 — UP UP UP — —36 — UP UP — UP UP37 — UP UP — UP —38 — UP UP — — UP39 — UP UP — — —40 — UP — UP UP UP41 — UP — UP UP —42 — UP — UP — UP43 — UP — UP — —44 — UP — — UP UP45 — UP — — UP —46 — UP — — — UP47 — UP — — — —48 — — UP UP UP UP49 — — U UP UP —50 — — UP UP — UP51 — — UP UP — —52 — — UP — UP UP53 — — UP — UP —54 — — UP — — UP55 — — UP — — —56 — — — UP UP UP57 — — — UP UP —58 — — — UP — UP59 — — — UP — —60 — — — — UP UP61 — — — — UP —62 — — — — — UP63 — — — — — —

BITVALUE 32 16 8 4 2 1

5715 UNIVERSAL TRANSMITTER

5711/5711WM DOOR/WINDOW TRANSMITTER

1 2 3 4 5 6 7 8 9 10 11 12

UP

DN

XMTR ID(33 SHOWN)

}

POS.12: UP = N.O.— = N.C

(Avoid ID 32-37 with N.O.)

SIDEVIEW (DN)

1 2

}POS.1: UP = NORMAL RESPONSE

DN = FAST RESPONSEPOS. 2: UP = NO COVER TAMPER

DN = COVER TAMPER (use N.C. setting)

DIPDIP

TERMINALBLOCK

DIP

HOUSE ID (1 SHOWN)

HOUSEID

DIP SWITCH POSITION

5 4 3 2 11 — UP UP UP UP2 UP — UP UP UP3 — — UP UP UP4 UP UP — UP UP5 — UP — UP UP6 UP — — UP UP7 — — — UP UP8 UP UP UP — UP9 — UP UP — UP10 UP — UP — UP11 — — UP — UP12 UP UP — — UP13 — UP — — UP14 UP — — — UP15 — — — — UP16 UP UP UP UP —17 — UP UP UP —18 UP — UP UP —19 — — UP UP —20 UP UP — UP —21 — UP — UP —22 UP — — UP —23 — — — UP —24 UP UP UP — —25 —— UP UP — —26 UP — UP — —27 — — UP — —28 UP UP — — —29 — UP — — —30 UP — — — —31 — — — — —

BITVALUE: 1 2 4 8 16

TRANSMITTERID

DIP SWITCH POSITION

6 5 4 3 2 1

1 — UP UP UP UP UP2 UP — UP UP UP UP3 — — UP UP UP UP4 UP UP — UP UP UP5 — UP — UP UP UP6 UP — — UP UP UP7 — — — UP UP UP8 UP UP UP — UP UP9 — UP UP — UP UP

10 UP — UP — UP UP11 — — UP — UP UP12 UP UP — — UP UP13 — UP — — UP UP14 UP — — — UP UP15 — — — — UP UP16 UP UP UP UP — UP17 — UP UP UP — UP18 UP — UP UP — UP19 — — UP UP — UP20 UP UP — UP — UP21 — UP — UP — UP22 UP — — UP — UP23 — — — UP — UP24 UP UP UP — — UP25 — UP UP — — UP26 UP — UP — — UP27 — — UP — — UP28 UP UP — — — UP29 — UP — — — UP30 UP — — — — UP31 — — — — — UP32 UP UP UP UP UP —33 — UP UP UP UP —34 UP — UP UP UP —35 — — UP UP UP —36 UP UP — UP UP —37 — UP — UP UP —38 UP — — UP UP —39 — — — UP UP —40 UP UP UP — UP —41 — UP UP — UP —42 UP — UP — UP —43 — — UP — UP —44 UP UP — — UP —45 — UP — — UP —46 UP — — — UP —47 — — — — UP —48 UP UP UP UP — —49 — UP UP UP — —50 UP — UP UP — —51 — — UP UP — —52 UP UP — UP — —53 — UP — UP — —54 UP — — UP — —55 — — — UP — —56 UP UP UP — — —57 — UP UP — — —58 UP — UP — — —59 — — UP — — —60 UP UP — — — —61 — UP — — — —62 UP — — — — —63 — — — — — —

BITVALUE: 1 2 4 8 16 32

6 5 4 3 2 1

UP

DN

POS. 6: UP = N.O.DN = N.C.

UP

SW3

6 5 4 3 2 1

XMTR ID (33 SHOWN)HOUSE ID (1 SHOWN)

UP

SW4SIDE

VIEW (UP)

DIP

DIP

SW4

SW3TERMINALS

5716 DOOR/WINDOW TRANSMITTERIMPORTANTSET SWITCHES WITHBATTERY REMOVED

For 5700 series transmitters not shown in this table, refer to the instructions accompanying each transmitter.

Page 32: ADEMCO N7225V2B

6 –6

Compatible 5700 Series TransmittersModel Product Zone/ID # Description5701 Panic Transmitter 62 or 63 • Programmable for either silent or

audible 24-hour alarm.5706 Photoelectric Smoke 48–55 • One-piece smoke detector with

Detector built-in transmitter.• Built-in UL Listed 85dB piezo

electric alarm sounder and audible low battery warning.

5711 Slimline Door/ 10–63 • Can be used with any closed or Window Transmitter open circuit sensor.

5715WH Universal Transmitter 10–63 • DIP switch selectable for fast res- ponse, and open or closed sensor usage.

• Has a tamper protected cover.5716 Door/Window 10–63 • Can be used with any open or5716WM Transmitter closed circuit sensor.

• Features a built-in reed switch.• 5716WM includes magnet.

5742 Audio Discriminator 10–63 • For use in unoccupied areas to detect the sound of shattering glasswhen a window is broken.

5743 Dual Technology 10–63 • Detects the sound and shock ofGlassbreak Detector breaking glass and requires the

presence of both to initiate an alarm condition.

5775 PIR Detector 32–47 • Dual element passive infrareddetector with built-in selectable pulse count.

  Note: There is a 3-minute lock-out  between fault transmissions to con

serve battery life.5727 Wireless Keypad House ID • Can be used to turn the burglary

protection on and off.• Features the same built-in panic

functions as wired keypads.• Identified as zone "00" (on wired

keypads) when it transmits with a low battery.

5827BD Wireless Keypad House ID • Requires use of 5800TM Module.(usable in a 5700 System) • RF House ID must be programmed

in field ✱24, and the wireless key-pad set to the same ID.

• Operates the system similarly to wired keypads

• Can indicate system status via its 3LEDs and sounder.

• Includes 3 panic keys.5799 Magnets • Package of 8 magnets for use with

5716 transmitters

UL The 5711, 5715, and 5716 do not supervise their loop wiring for shorts.

Therefore, for UL Household Burglary installations, the loop wiring may notexceed 3 feet.

Page 33: ADEMCO N7225V2B

6 –7

Programming the Control For a 5700 Wireless System1. With at least one two-line Alpha keypad wired and set to address 31

(default), power up the system temporarily by plugging the AC transformer(previously wired to the control) into a 120VAC outlet.

2. Enter data field programming mode: Installer Code + 8 + 0.3 Set data field ✱22 (RF SYSTEM TYPE) to “1” (5700)4. Enter the House ID (01–31) in data field ✱24. (RF HOUSE ID CODE)

The House ID entered in this field will identify 5700 series transmitters in a5700 RF system (all 5700 type transmitters are set for the same House ID).If a 5827BD wireless keypad is to be used in a 5700 RF system, the sameHouse ID code entered in this field must also set on the 5827BD wirelesskeypad(s).

5. Exit the programing mode by keying ✱99.

The DIP switches in each 5700 series transmitter that is going to be used in thesystem must be set to the appropriate zone/ID number and House ID. Refer to“Setting the DIP Switches On 5700 Series Transmitters” and “Wireless Zone/IDAssignments for 5700 Series Transmitters” on a previous page, if necessary.The system House ID must have been programmed in data field ✱24, and theDIP switches on all transmitters set for the same ID. If using a 5827BD wirelesskeypad, the House ID also applies.Note: The 5827BD is keypad programmable; the 5727 wireless keypad is

programmed via its DIP switches. Refer to the instructions suppliedwith the 5827BD and 5727 for details.

Batteries should be installed in all transmitters.

Using the House ID Sniffer Mode (5700 Systems)4281 series RF receivers respond only to 5700 transmitters (and 5827BDwireless keypads) set to the same House ID (01–31) programmed into thecontrol panel. This prevents system interference from transmitters in othernearby systems. Using the House ID Sniffer Mode will make sure you have notchosen a House ID that is in use in a nearby system.1. Enter your Installer Code + # + 2 .2. The receiver will now "sniff" out any House IDs in the area and display

them. Keep the receiver in this mode for about 2 hours to give a goodindication of the House IDs being used. Be sure you have used a HouseID that is not displayed.

3. To exit the Sniffer Mode, simply enter your Installer Code + OFF .

Since the Sniffer Mode effectively disables wireless point reception, SnifferMode cannot be entered while the system is armed.

Do not permanently mount the transmitters yet; a Go/No Go test (describedlater) must be performed after programming is completed to make surereception of each transmitter's signal at the proposed mounting location isadequate.

Zone Programming For 5700 TransmittersBefore proceeding, each of the 5700 transmitters in the system should havebeen assigned a unique Zone/ID number via its DIP switches, and thisinformation marked on the back of the transmitter. “Wireless Zone/IDAssignments for 5700 Series Transmitters” on a previous page providesinformation concerning the assignment of Zone/ID numbers to transmitters.1. With a 2-line Alpha keypad connected to the keypad terminals, power up

the system temporarily. If you had previously connected the AC transformerto the control panel, you need only plug the transformer in (to 120VACoutlet) to power up the system.

2. Enter the programming mode by keying: Installer Code + 8 + 0.

Page 34: ADEMCO N7225V2B

6 –8

Data field ✱22 RF SYSTEM TYPE, must have been programmed for a 5700RF system (“1”). Also, the House ID should have been entered in field ✱24,and all 5700 transmitters set to the same House ID.

4. Press ✱56. (Zone Programming Mode)Use this mode to program zone numbers, zone types, and alarm reportcodes for all 5700 wireless zones that are going to be used in the system.5700 transmitters are programmed into the system one at a time, startingwith the lowest Zone/ID number that has been assigned to it previously viaits DIP switches.Example: If the first transmitter to be programmed has been set via its DIPswitches to Zone/ID 20, you will program zone types, and alarm reportcodes for that transmitter in zone 20.

Ente r Zn Num.

(0 0 = Q u it) 2 0

Zone 20 entered ↑

5. Enter the zone number that you wish toprogram. As an example, zone 20 is shownentered here.Zone numbers between 10 and 63 can beassigned to transmitters. However, the totalnumber of wireless zones that can be used is 8for 5700 RF systems (see Table 1 on aprevious page).

Zn ZT  – RC In : L

2 0 0 0  – – – : –

6. A summary display will appear, showing thestatus of that zone's program.If it is programmed satisfactorily, press [#] toback up one step and enter another zonenumber, if desired.If the zone is not programmed, or you want tochange it, press [✱ ]. A prompt for Zone Typewill appear.

 ↓ Zone Number

2 0 Zone Type

Pe r ime te r 0 3

Entry for Zone Type03 shown

7. Each zone must be assigned a zone type,which defines the way in which the systemresponds to faults in that zone.

Enter the zone type (or change it, if necessary).Zone types that you can assign are listed below.Enter the desired zone type code as listed.

A detailed explanation ofeach zone type is providedin the ZONE RESPONSETYPE DEFINITIONSsection in the separateProgramming Guide.

00 = Zone Not Used01 = Entry/Exit Burglary03 = Perimeter04 = Interior Follower05 = Trouble Day/Alarm Night

06 = 24 Hr Silent07 = 24 Hr Audible08 = 24 Hr Aux09 = Fire10 = Interior w/Delay23 = No Alarm Response

(e.g., relay activation)When the display shows the zone type youwant, press [✱] to continue.

2 0 Re por t Code

1 st 0 3 2 nd 1 2 3 C

8. Enter the report code.The report code consists of 2 hexadecimaldigits, each in turn consisting of 2 numericaldigits. For example, for a report code of "3C",enter [0][3] for "3" and [1][2] for "C".See the SYSTEM COMMUNICATIONS sectionfor complete information on report codes, ifnecessary.Press [✱] to continue.

2 0 Input De vic e

RF Tr a ns.        RF:

9. For the hardwired zones (HW), and the zonesfor a 5700 system's transmitters (RF), the InputDevice types are automatically assigned (Panic,Duress, and Tamper inputs are not applicable).

Page 35: ADEMCO N7225V2B

6 –9

10. Mark the zone number on the transmitter.

11. After the transmitter has been entered into thesystem, press [✱ ] to continue.

Typical summary display

Zn ZT – RC In: L

20 03 – 3C  RF: –

A summary of the programmed values for theselected zone will now be displayed

If all is okay, press [✱] for the next display.

Pr ogr a m A lpha ?

0 = No 1 = Ye s 0

Alpha descriptors for the zones can be donenow, or may be done at a later time using ✱82interactive mode (enter “0”).Refer to ALPHA DESCRIPTOR PROGRAMMINGsection for performing this procedure in the ✱82interactive menu mode.

Ente r Zn Num.

(0 0 = Q u it) 2 1

If “0” (no) was entered in response to thePr ogr a m A lpha ? question, a prompt willthen be displayed for entry of the number for thenext wireless zone to be programmed.

12.Proceed with the programming of the nextwireless zone, starting at step 5 again.

13.To exit field ✱ 56 when completed, key [0 ][0] atthe “Enter Zone Number” prompt.

14.Exit the programming mode by keying ✱99.

Special Notes on ZoneProgramming (5700 RF

Systems)

• In field *56, at the summary line for each zone, the entered values can bechecked. If you wish to change anything, press [#] to move to the previousentry. Press [#] a number of times to move to earlier entries. Press [✱ ] tomove to later entries again.

• Zone entries can be reviewed by pressing [#][5][6]. Changes cannot bemade here, so this is safer for review. Enter the first zone number to beviewed and press [#]. To view each zone, press [#] and the zone numberwill advance to the next programmed zone. When the end of the list isreached, press [0][0] to exit. This method of exiting may also be done at anytime during the review.

• To either temporarily or permanently remove a zone from the system, gointo programming mode and press [✱][5][6]. Enter the zone number andpress [✱]. At the Zone Type prompt, enter [0][0] and [✱]. This sets the typeof the zone to Not Used. The next prompt will be "Delete Zone?". "Yes" willpermanently remove the zone from the system, while "No" will disable it butretain all data except the original zone type. You can then go back to thiszone later and put back an active Zone Type to re-enable it.

Go/No Go Test Before mounting transmitters permanently, conduct Go/No Go tests to verifyadequate signal strength and reorient or relocate transmitters if necessary.During this mode, wireless receiver gain is reduced by 50%. Testing in thismode assists in determining good mounting locations for the transmitters andverifies that the RF transmission has sufficient signal amplitude margin for theinstalled system.1. Enter the Installer Code + # + 4

2. Once transmitters are placed in their desired locations and the approximatelength of wire to be run to sensors is connected to the transmitter's screwterminals, fault each transmitter. Do not conduct this test with your handwrapped around the transmitter as this will cause inaccurate results.• The keypad will beep three times to indicate signal reception.• If the keypad does not beep, re-orient or move the transmitter to another

location. Usually a few inches in either direction is all that is required.

Page 36: ADEMCO N7225V2B

6 –10

3. Mount the transmitter according to the instructions provided with thetransmitter.

4. Exit the GO/NO GO test mode by entering Installer Code + (OFF ).

You should now proceed to “Check-Out Procedure for Wireless Zones” atthe end of this section.

5800 Series Transmitter SetupGeneral

Information5800 series transmitters have built-in serial numbers that must be enrolled inthe system using the ✱56 or ✱83 interactive mode, or input to the control viathe downloader. 5800 series transmitters (except 5827 described separately)do not have DIP switches.

5800 SeriesTransmitter Input

Loops

Each transmitter's zone number is programmed into the system in ✱56 mode.Some transmitters, such as the 5816 and 5817, can support more than one"zone" (referred to as loops or inputs). On the 5816 for example, the wire con-nection terminal block is loop 1, the reed contact is loop 2. Each loop must beassigned a different zone number and entered separately.

For button transmitters (wireless "keys"), such as the 5804, you must assign aunique zone number to each individual button used on the transmitter. Eachbutton on the transmitter also has a pre-designated loop or input number,which is displayed when entered.Refer to 5800 Series Transmitter Input Loop Identification in the separateProgramming Guide manual

UL The 5816, and 5817 do not supervise their loop wiring for shorts Therefore,for UL Household Burglary installations, the loop wiring may not exceed 3 ft.

Programming an RF House ID (01–31) in field ✱24 is necessary only ifusing 5827 or 5827BD wireless keypads. An RF House ID is not necessaryfor other 5800 series transmitters and the entry should be left at “00” (default)in those cases.

The 5827 wireless keypad reports low battery status as zone "00."

5800 SeriesTransmitter Input

Types

All of the transmitters described have one or more unique factory assignedloop inputs. Each of the inputs requires its own programming zone (e.g., a5803's three button inputs require three programming zones).

5800 Transmitters can be entered into the system as one of the following inputdevice types:

Input Device Type Description

"RF" Sends periodic check-in signals, as well as fault,(Supervised RF) restore, and low battery signals. The transmitter

must remain within the receiver's range.

"UR" Sends all the signals that the "RF" type does,(Unsupervised RF) but the control does not supervise the check-in

signals. The transmitter may therefore be carried off-premises.

"BR" These send only fault signals. They do not send(Unsupervised Button low battery signals until they are activated. The RF) transmitter may be carried off-premises.

Do not install batteries in wireless transmitters until ready to use, as will beindicated under Programming the RF Transmitters (5800 RF Systems laterin this section. Though it is not critical to remove batteries after entering intothe system, it is recommended in order to avoid interference while enteringadditional transmitters into the system.

Page 37: ADEMCO N7225V2B

6 –11

Compatible 5800 Series Transmitters

Enter As InputModel Product Device Type Description

5801 Wireless Panic UR or RF • Has four pushbuttons, each with aTransmitter unique input (loop) code.

 • Programmable responses (e.g., Panic, Arm–Stay, Arm–Away, Disarm, etc.

5802 Pendant BR Only • Has single pushbutton.(Personal Emergency • Usually programmed for responseTransmitter) type of 24-Hr Audible or 24-Hr Silent

(other zone responses are possible).• Contains a non-replaceable battery.

At the end of the battery's life, theentire unit must be replaced.

5802CP Belt Clip BR Only Same as 5802.(Personal Emergency)

5802MN Miniature UR or RF • Has single pushbutton.(Personal Emergency • Usually programmed for a responseTransmitter) type of 24-Hr. Audible or 24-Hr.

Silent (other zone responses are possible).

5804 Wireless Key BR Only • Has four pushbuttons, each with aTransmitter unique input (loop) code.

• Programmable responses (e.g.,Arm–Stay, Arm–Away, Disarm, etc.).

5806 Wireless Photoelectric RF • One-piece smoke detectors with a5807 Smoke Detectors built in transmitter.

5808 Wireless Photoelectric RF • One-piece smoke detectors with aSmoke Detector built in transmitter.

• Has built-in thermal circuitry to detect temperatures above 135°F, and tamper switch on base.

5816 Door/Window RF • Has two unique input (loop) codes:Transmitter : one for a wired closed circuit

contact loop; the other for a built-in reed switch (used in conjunction with a magnet).

5816 Low Temperature RF • Transmits a fault condition whenTEMP Sensor temperature drops below 45 °F.

5817 Multi-Point RF • Has three unique input (loop)Universal Transmitter codes: one for a "Primary" contact

loop with programmable options; the others for two "Auxiliary" closed circuit contact loops.

UL The 5816 and 5817 do not supervise their loop wiring for shorts. Therefore, forUL Household Burglary installations, the loop wiring may not exceed 3 feet.

(Continued)

Page 38: ADEMCO N7225V2B

6 –12

Compatible 5800 Series Transmitters (Continued)

Enter As InputModel Product Device Type Description

5819 Shock Processor RF • Connects to externally mountedTransmitter inertia-type shock detector (not

supplied).• Has built-in tampered cover switch.• Has 3 unique input (loop) codes:

Loop 1: Terminals for a wired, N.C.sensor loop.Loop 2: For a closed circuit contactloop using the built-in reed switch inconjunction with a magnet.

Loop 3: Terminals for a wired, closed circuit contact loop.

5827 Wireless Keypad House ID • Can be used to turn the burglary protection on and off.

• Features the same built-in panic     functions as wired keypads.• The keypad is identified as zone

"00" on wired keypads when it transmits with a low battery.

5827BD Wireless Two-Way House ID • Operates the system similarly toKeypad wired keypads.(used with 5800TM) • Can indicate system status via its 3

LEDs and sounder.• Includes 3 panic keys.• House ID must be set.• Requires 5800TM Transmitter

Module.5850 Glass Break Detector RF • Requires both sound and shock of(GBD) breaking glass to cause alarm to be

transmitted.

5890 PIR Detector RF • Dual element passive infrared detector/transmitter with selectable pulse count.

Note: There is a 3-minute lock-outbetween fault transmissions toconserve battery life.

5899 Magnets Package of 4 magnets for use with5816 and 5817 transmitters.

Programming the RF Transmitters (5800 RF Systems)1. With at least one 2-line Alpha keypad connected to the keypad terminals,

power up the system temporarily. If you had previously connected the ACtransformer to the control panel, you need only plug the transformer in (to120VAC outlet) to power up the system.

2. Enter the programming mode by keying: Installer Code + 8 + 0 .

Data field ✱22 RF SYSTEM TYPE, must have been programmed for a 5800RF system before continuing (“2” entered in that field).

3. ✱24. RF HOUSE ID CODEThe House ID identifies a 5827 or 5827BD Wireless keypad if it is used(enter 01–31). The wireless keypads should be set to the same ID. If nowireless keypad is to be used, leave as “00”.

Page 39: ADEMCO N7225V2B

6 –13

Enrolling 5800 Transmitters Into The SystemThere are two methods that may be used to enroll transmitters. The first method is performedin ✱56 zone programming mode (which is contained in this section) and describes how to enrolleach transmitter into the system as you are entering the zone information.

The second method is called "sequential mode" and uses ✱83 (described in the SEQUENTIALMODE section later in this manual. This section describes how to enroll all the transmitters intothe system after all zone information has been entered.

As an option, the zone programming and sequential modes allow you to use a 5803 or 5804button-type transmitter as a "program tool." The advantage of using a program tool is that ittells the control that you are about to enroll a transmitter into the system. You can move to thephysical location of the transmitter to be enrolled, press the upper left-hand button of theprogram tool, and then trip the intended transmitter (see step 10 for operation). This helps toprevent random signals from being accepted into the system until you are ready to enroll theintended transmitter.The transmitter that you use as the program tool can also be used as a transmitter in thesystem. If you plan to use an existing transmitter, it must first be enrolled into the system as itsassociated zones. You may then program it as the tool.

Enrolling Through Zone Programming (✱56)

1. Enter Programming mode [Installer Code] + 8 + 0.Enter Zone Programming by pressing ✱56. If the system has been setup to use 5800 series RF, and a program tool has been entered, skipto step 4. If no program tool has been entered, the following promptwill appear:

Program Tool?0 = No, 1 = Yes 0

2. If a program tool is being used, enter "1." If not using a tool, enter "0"and skip to Step 4.

00 Input S/N:      L A X X X–X X X X

3. If "1" is entered, the system will prompt for the unit’s serial number.Enter the program tool’s serial number using one of the followingmethods:

a) Enter the 7-digit serial number for the transmitteror

b) Press any button on the transmitter. The keypad should beep twiceand display the serial number of the tool.

00 Input S/N:       L

A123-4567     3

In this example, the serial number is A123-4567. Once enrolled, theupper left-hand button of the program tool can be pressed to ready thesystem for enrolling a transmitter into the system.Pressing the [#] key on the keypad will cause the system to back up tothe “Program Tool ?” prompt.

The serial number for the program tool will only remain in thesystem until the programming mode is exited. (Entering ✱97 willnot delete the tool.)

Press [✱] to continue.

Ente r Zn Num.

(0 0 = Q u it) 1 0

Zone 10 entered ↑

4. Enter the zone number that you wish to program. As an example, zone10 is shown here.

Press [✱] to continue.

ZN ZT – RC In :   L

1 0 0 0 – 0 0 RF:  1

5. A display will appear, showing a summary of that zone's programming.If the zone is not programmed, the display will appear as shown here. Ifchecking a zone's programming, and it is programmed satisfactorily,press [#] to back up one step and enter another zone number, ifdesired. Otherwise, press [✱] to continue.

Page 40: ADEMCO N7225V2B

6 –14

↓ Zone Number

1 0 Zone Type

Pe r ime te r 0 3

Entry for Zone Type 03shown

6. Each zone must be assigned a zone type, which defines the way inwhich the system responds to faults in that zone. Enter the zone typedesired (or change it, if necessary). Available zone types are:

00 = Zone Not Used 08 = 24 Hr Aux01 = Entry/Exit #1, Burglary 09 = Fire02 = Not Used 10 = Interior w/Delay03 = Perimeter 20 = Arm–Stay*04 = Interior Follower 21 = Arm–Away*05 = Trouble Day/Alarm Night 22 = Disarm*06 = 24 Hr Silent 23 = No Alarm Response07 = 24 Hr Audible  (EX: Relay activation)

* These are special zone types used with 5800 series wireless pushbuttonunits which will result in arming the system in the STAY or AWAY mode, ordisarming of the system, depending on the selection made. A buttonprogrammed for these functions will report the zone number of the button asthe user number that armed/disarmed to the central station.

Press [✱] to continue.

1 0 Re por t Code1 st 0 3 2 nd 1 2 3 C

7. Enter the report code. The report code consists of 2 hexadecimal digits,each in turn consisting of 2 numerical digits. For example, for a reportcode of "3C", enter [0][3] for "3" and [1][2] for "C."(Refer to the SYSTEM COMMUNICATION section for more informationabout report codes and report code formats.)Press [✱] to continue.

10 Input Dev:    LP #Rf Trans.   RF:   1

8. Enter the transmitter input device type as follows:3 = RF (supervised RF transmitter)4 = UR (unsupervised RF transmitter)5 = BR (button type RF transmitter - unsupervised)(Refer to the separate Programming Guide for input types.)Press [✱] to continue.

10 Input Dev:    LP#RF Trans.  RF:   1

9. The cursor should now be flashing above the loop number. The defaultis "1." To accept this, press [✱]. If a different loop number is being usedon this transmitter, enter the loop number (1–4) and press [✱ ] tocontinue (see the loop designations for various transmitters in theseparate Programming Guide). The loop number must be enteredhere, whether using Zone Programming or Sequential Mode to"enroll" transmitters.

10 Learn S/N?0 = No, 1 = Yes 0

10. If the transmitter’s serial number has not been previously “enrolled,” youmay enter the enrollment mode now by either entering "1" (Yes) or bypressing the upper left-hand button of the “program tool”. If using theprogram tool, move to the physical location of the transmitter to beenrolled before pressing the button. A single short beep will verify thatthe button has been pressed. The system will respond to the first serialnumber transmitted after the [✱] key on the keypad or the button of theprogram tool is pressed.Enter "0" (No) if you wish to enroll the transmitter later, using theSEQUENTIAL MODE described in Section 14.If "0" (No) is entered, go to step 13 (skip steps 11 and 12).

10 Input S/N:      L A X X X–X X X X

11. This prompt is displayed if "1" (Yes) is entered in response to the "LearnS/N?" prompt. The serial number may be enrolled by one of two methods:

a) Enter the 7-digit serial number printed on the transmitter using a Alpha keypad, or

b) Activate the transmitter by faulting or restoring the input you wish touse for that zone (e.g., press a button, open or close a door, etc.).

Page 41: ADEMCO N7225V2B

6 –15

10 Input S/N:        L A002-4064     1

The system will enroll the serial number of the first transmitter heard,add the loop number entered to this serial number, display the serialand loop numbers, and cause the keypad to beep twice.

If the serial and loop number combination is already present in thesystem, a single long beep will be heard from the keypad. If this happens,the system will not display the serial number, but will wait for atransmission from another transmitter or transmitter loop input.

  12. The system will then enter a confirmation mode so that the operationof the actual programmed input can be confirmed. Activate the loopinput or button that corresponds to this zone. We recommend thatyou confirm the programming of every transmitter beforeproceeding to the next zone.

10 Confirmed A022– 4064       1

When the system sees activity on the appropriate input, it will beepthree times and display the confirmation message.

At any time during this step, you may press the [✱] key on the keypad orthe upper left-hand button of the program tool if you are satisfied with theserial and loop number combination that has been enrolled, regardless ofwhether or not the enrolled input has been "confirmed."

If the incorrect transmitter has been enrolled, press the # key on thekeypad or the upper right-hand button of the program tool to delete theserial number and return to the "Learn S/N" prompt. A single long beep willbe heard from the keypad to verify pressing of the upper right-hand button.Then, press "1" (Yes) or press the upper left-hand button of the programtool (a single short beep will verify the system is ready for enrolling) andre-activate the proper transmitter or transmitter loop input.

ZN ZT – RC IN:   L10 03 – 00 RF: 1 s

  13. The summary screen for the zone will appear. Note that an "s"indicates that a serial number has, in fact, been enrolled. The cursorwill be flashing above the loop number. Press [✱ ] to accept the zoneinformation.Note: If you entered “0” in step 10 previously, you will not get anindication that the serial number has been enrolled.

If you want to delete the serial number, enter "0" and press [✱]. Thesystem will then prompt, "Delete S/N?" Press the "1" (Yes) key tocomplete the delete sequence. This process deletes the serial numberonly, not the loop number. The assumption is that the proper loopnumber was programmed, but the wrong serial or loop number wasenrolled. To change the loop number, you must go back through zoneprogramming for that zone and manually enter the loop number overthe existing one.

Program Alpha?0 = NO 1 = YES 0

 14. If you want to program alpha descriptors now, enter "1" (Yes). See theALPHA DESCRIPTOR PROGRAMMING section for more information.If not, enter "0" (No).

Ente r Zn Num.

(0 0 = Q UIT) 1 1

This will bring you back to the “Enter Zn Num.” prompt for the nextzone . When all zones have been programmed, enter “00” to quit.If you plan to enroll serial numbers in the sequential mode, enter “00”to quit, then go to Section 14: SEQUENTIAL MODE later in thismanual to enroll the serial numbers.

When you have finished programming all zones (including all serialnumbers), test each zone using the system's TEST mode. Do not use theTransmitter ID Sniffer mode for this, as it will only check for transmissionof one zone on a particular transmitter, and NOT the zones assigned toeach additional loop.

Page 42: ADEMCO N7225V2B

6 –16

Temporarily Or Permanently Removing A Zone From The System (5800 System)1. Enter the programming mode:

Key Installer Code + 8 + 0 and press [✱ ][5][6].

2. Enter the zone number and press [✱]. A summary display will appear.

3. Press [✱] again.

2 0 Zone Type

Not Use d 0 0

4. The “Zone Type ” prompt will appear. Enter[0][0]. This sets the zone type to “Not Used”.Press [✱] to continue.

2 0 De le te Zone ?

1 = Ye s 0 = No

5. The next prompt will ask whether you want todelete the zone."Yes" will permanently remove the zone fromthe system, while a "No" will disable it but retain

all data except the original zone type. You can then go back to this zone laterand put back an active zone type to re-enable it.A serial number that has been entered for a 5800 system will not bedeleted if the zone is temporarily disabled by answering “No” to theprompt above.

If only the physical transmitter is to be removed or changed (i.e., its serialnumber deleted, as when replacing a unit that has a non-removable battery), itcan be done in ✱56 Mode, as indicated next.

Deleting a Transmitter Serial Number From a Zone in ✱56 Mode (5800 System)

The abbreviated procedure below can be used to delete a serial number froma zone, using the ✱56 Mode.

1. In the programming mode, press [✱ ][5][6] to enter Zone Programmingmode.

2. Then enter the zone number, and press [✱] repeatedly until the cursor isunder the RF Input Loop (L) position. This is the specific input (loop) orbutton on the transmitter that has been entered for that zone.

3. Enter a [0] at this point, then press [✱].

4. A prompt "Delete S/N?" will appear.Enter "Yes" to delete the existing serial number from the system.Note that the other programmed values for that zone will not be deleted.This will allow you to re-instate a new transmitter in its place.

5. A display for the next zone number will appear. To exit, enter “00".

6. Press ✱99 to exit the programming mode.

Check-Out Procedure for Wireless Zones

Transmitter IDSniffer Mode

(5700/5800RF Systems)

When all transmitters have been installed, use the Transmitter Sniffer Mode totest that they have all been properly programmed.

1. Enter Installer Code + # + 3. The keypad will display all zone numbers ofwireless units programmed into the system.

2. Fault each wireless zone, causing each device to transmit. As the systemreceives a signal from each of the transmitters, the zone number of thattransmitter will disappear from the display.

If a 5700 transmitter is not dipswitched correctly, or if a 5800 transmitter isnot enrolled, its zone number will not turn off.

3. To exit the Transmitter Sniffer mode, enter the Installer Code + (OFF).

(Continued)

Page 43: ADEMCO N7225V2B

6 –17

Go/No Go Test(5700/5800

RF Systems)

Before mounting transmitters permanently, conduct Go/No Go tests to verifyadequate signal strength and reorient or relocate transmitters if necessary.During this mode, wireless receiver gain is reduced by 50%. Testing in thismode assists in determining good mounting locations for the transmitters andverifies that the RF transmission has sufficient signal amplitude margin for theinstalled system.

1. Enter the Installer Code + # + 4

2. Once transmitters are placed in their desired locations and the approximatelength of wire to be run to sensors is connected to the transmitter's screwterminals, fault each transmitter. Do not conduct this test with your handwrapped around the transmitter as this will cause inaccurate results.• The keypad will beep three times to indicate signal reception.• If the keypad does not beep, re-orient or move the transmitter to another

location. Usually a few inches in either direction is all that is required.

3. Mount the transmitter according to the instructions provided with thetransmitter.

4. Exit the GO/NO GO test mode by entering Installer Code + (OFF).

Page 44: ADEMCO N7225V2B

6 –18

Page 45: ADEMCO N7225V2B

7 –1

Section 7. RELAY OUTPUT DEVICESRelay Device Basics

Relays are programmable switches that can be used to perform many differentfunctions. They can be used to turn lights on and off, control sounders, or forstatus indications. In this system, each relay must be programmed as to howto act (ACTION), when to activate (START), and when to deactivate (STOP).Each of these is described below, and in the programming procedure for ✱80and ✱81 interactive modes that are provided at the end of this section.The control supports the following relay modules:4204 Relay Module (4 relays).4229 Zone Expander/Relay Module (2 relays).

1. The 4204 and 4229 relays provide Form C (normally open and normallyclosed) contacts.

2. A 4204 cannot be used if a 4219 or 4229 is already being used.

In ✱80 and ✱81 interactive modes, a series of keypad prompts will requestentries for programming of the Relay outputs used in the system. Refer also to“OUTPUT RELAYS WORKSHEET FOR FIELDS ✱80 AND ✱81” in the blankprogramming form provided in the separate Programming Guide manual.

4204 and 4229 Relay Modules4204/4229 Setup The 4204 unit can be mounted either remotely or in the control panel. The

following steps should be taken to properly set up the 4204:

1. Connect the 4204 or 4229 module to the control's remote keypadterminals (4–7), using the connector supplied with the module. Usestandard 4-conductor twisted cable for long wiring runs.

2. Set the 4204 or 4229's DIP switch for a device address of "1" (switch 2"OFF" and switches 3, 4, and 5 "ON"). Switch 1 determines the unit's covertamper response ("ON" = disabled, "OFF" = enabled).

3. Connect the desired field wiring to the unit's relay contact terminals. SeeFigures 10 and 11.

Supervision The 4204 and 4229 modules are supervised against removal. CHECK andzone 09 will be displayed if a module is disconnected from the control’skeypad terminals (4, 5, 6, & 7).

13 14 15 16

C

NC

NODIP SWITCHFOR SETTING DEVICE ADDRESSAND ENABLING/DISABLING TAMPER

COVER TAMPER (REED) SWITCH

TB1

4204

TB2

4-PIN CONSOLE PLUG

1211

109

87

65

43

21

C

NC

NOC

NC

NO

C

NC

NO

RELAY

3

RELAY

2

RELAY

1

RELAY 4TYPICAL

(SHOWN "OFF")

EITHER OR BOTHCAN BE USED

DATA INFROM CONTROL

(–) GROUND

DATA OUTTO CONTROL

(+) 12V

YEL

BLK

GRN

RED

4204

Figure 10.  4204 Connections to Control

Page 46: ADEMCO N7225V2B

7 –2

BR

N

1 2 3 4 5 6 7 8 9 10 11 121

2

3

4GRN DATA OUT

TO CONTROLBLK

(–) GROUND

RED (+) 12V

YEL DATA INFROMCONTROL

432

1

TERMINATE EACHPROGRAMMED ZONEWITH 1000 OHM (1K)END-OF-LINE RESISTOR(EACH ZONE'S MAX.LOOP RESISTANCE:300 OHMS + E.O.L.)

ZONES: A B C D E F G H

1K

DIP SWITCHFOR SETTING ADDRESSAND ZONE “A” RESPONSE

REED(TAMPER)SWITCH

TAMPER JUMPER POSITION4229 IN CABINET (NOT TAMPERED)4229 REMOTE(TAMPER PROTECTED) TB1

4229

TB24-PIN CONSOLE PLUG

EITHER OR BOTH CAN BE USED

➞ ➞

WH

TG

RY

VIO

BLK

YE

LO

RG

NO

NC

CG

ND

NO

NC

C

RLY2

RLY1

RELAYS"OFF"

RELAYCONNECTOR

NO C NC

{ {{➞

RELAY2

}

}

RELAY1

TERMINALS ONCONTROL PANEL

(TERM 6)

(TERM 4)

(TERM 5)

(TERM 7)

4229

Figure 11.  4229 Connections to Control

Programming Options DefinedThe following will help you understand the programming of OUTPUT RELAYSwhen using ✱80 and ✱81 interactive menu modes. The options used to startand stop relays are described below, followed by the actual screen promptsand available entries.The letter(s) in parentheses after each function described below, such as (A)after ACTION, are those that appear in the various summary displays ofprogrammed data during programming.

ACTION (A) The "ACTION" of the relay is how the relay will respondwhen it is activated by the "START" programming. You maywant the relay to activate momentarily, to pulse on and offcontinuously, or to remain activated until some other eventoccurs to stop it. There are four different choices of actions:• ACTIVATE for 2 SECONDS and then reset.• ACTIVATE and REMAIN ACTIVATED until stopped by

some other event.• PULSE ON and OFF until stopped by some other event.• NOT USED when the relay is not used.

START (STT) The "START" programming determines when and under whatconditions the relay will be activated. The following STARToptions are available:

A) 1. EVENT (EV) is the condition (Alarm, Fault, Trouble) that mustoccur to a zone or group of zones (zone list) in order toactivate the relay. These conditions apply only when a zonelist is used. The different choices for "EVENT" are listedbelow and in the “Programming Output Relays” section thatfollows.• ALARM Relay action begins upon any alarm in an

assigned zone in the zone list.

• FAULT Relay action begins upon any opening orshort in an assigned zone in the zone list.

• TROUBLE Relay action begins upon any troublecondition in an assigned zone in the zone list.

• NOT USED Relay action is not dependent upon one ofthe above events.

Page 47: ADEMCO N7225V2B

7 –3

2. ZONE LIST (ZL) is a group of zones to which the “EVENT”applies in order to activate a particular relay. Note that thereare a total of 3 zone lists that can be programmed in field✱81 mode; when the selected EVENT (Alarm, Fault orTrouble) occurs in any zone in the selected “Start” ZONELIST (1, 2, or 3), activation of the selected relay will START.

B) 1. ZONE TYPE/SYSTEM OPERATION (ZT). If a SystemOperation, such as “DISARMING” or “ANY FIRE ALARM,” isto activate the relay, the appropriate choice would also beentered under the “ZONE TYPE” option. “ZONE TYPE” isused independently of the “EVENT/ZONE LIST”combination.If a specific "ZONE TYPE" is chosen, any zone of that re-sponse type going into alarm, trouble, or fault will cause therelay to activate as selected in "ACTION.” If the same “ZONETYPE” is also chosen for the STOP programming, any zoneof that type that restores will de-activate the relay.If a "SYSTEM OPERATION" is chosen (e.g., End of ExitTime), that operation will cause the relay to activate asselected in "ACTION.” The different choices for "ZONETYPE" and "SYSTEM OPERATION" are listed in“Programming Output Relays” later in this section, and in theProgramming Form in the separate Programming Guide.

STOP (STP): The "STOP" programming determines when and under whatconditions the relay will be de-activated. The followingoptions are available:

A) 1. RESTORE ZONE LIST (ZL) . If a "ZONE LIST" is used asthe “Stop” event, the relay will de-activate when all thezones in that list restore from a previous fault, trouble, oralarm condition. This will occur regardless of what isprogrammed to "START" the relay; therefore, a "RESTOREZONE LIST" would normally only be used when a "ZONELIST" is used to start the relay.

B) 1. ZONE TYPE/SYSTEM OPERATION (ZT). Instead of usinga "RESTORE ZONE LIST", a specific zone (response) typeor system operation action can be selected to de-activatethe relay.If a specific "ZONE TYPE" is chosen, any zone of thatresponse type that restores from a previous alarm, trouble,or fault condition will cause the relay to de-activate.If a "SYSTEM OPERATION" is chosen, that operation willcause the relay to de-activate. The different choices for"ZONE TYPE" and "SYSTEM OPERATION" are listed in“Programming Relays” later in this section, and in theProgramming Form.

If relay outputs are used, two keypad entries available to theuser are included among the system operation choices (34and 35) that may be programmed. They can manually activateor de-activate the relay(s) for starting or stopping some action,such as turning lights on or off, etc.

These entries are: Security Code + [#] + [7]and Security Code + [#] + [8]

Note: Whichever entry is used to start/stop the actioncannot also be used to stop/start it. The opposite action musteither be performed by the other keypad entry or by someother event or operation offered in the programming section.

Page 48: ADEMCO N7225V2B

7 –4

If a relay is energized before a 4-wire smoke detector isreset, the relay will be stopped by the interruption of Aux.Power that resets the smoke detector. If this is not desired,the power to the relay unit should be supplied from another12V power source (e.g., the same source that is powering ex-ternal equipment through the relay contacts).

Programming Output Relays1. With at least one 2-line Alpha keypad (5137AD or 6139) connected to the

keypad terminals on the control, power up the system temporarily. If youhad previously connected the AC transformer to the control panel, youneed only plug in the transformer (to 120VAC outlet) to power up thesystem.

2. Enter the programming mode by keying the following on the Alpha keypad:INSTALLER code (4 1 1 1) + 8 + 0.

Field ✱25 OUTPUT MODULE must have been programmed for a 4204 module(enter “3”).

3 Press ✱80. Note that this is an interactive menu programming mode. It isused to program all output relays used in the system (4204 Relaymodules). Refer to the Programming Form worksheet in the separatePROGRAMMING GUIDE for ✱80 Interactive Mode.

Output Relay Displays

Enter Relay No.(00 = Quit) 01

Upon pressing ✱80, this screen will appear. Enter the Relay Number 01, 02,03, or 04 for a 4204 (or 00 to end these entries). Press the [✱ ] key tocontinue.

The [✱ ] key is used to accept an entry and advance to the next prompt. The[#] key is used to revert back to the last question to check or change anentry. Press [✱] to go forward again.

02     A  EV  ZL  ZTSTT   0   0   0   00

This screen displays a summary of the current Relay START programming(for this example, relay 02 has been selected).Press the [✱] key to continue.

02     A EV ZL ZTSTP  – – 0 00

This screen displays a summary of the current Relay STOP programming.Press the [✱] key to continue.

02 Relay ActionNo Response 0

Enter the desired relay action as listed below. Press the [✱] key to continue.  0 = No response 2 = Close and Stay Closed 1 = Close for 2 seconds 3 = Continuous Pulse on & off (1 sec ON, 1 sec OFF)

02 Start EventNot Used 0

Enter the event to START the relay:0 = Not used; 2 = Fault; 1 = Alarm; 3 = TroubleA zone list must be used in conjunction with an event. If a zone type/systemoperation is to be used instead of an event, enter 0.Press the [✱] key to continue.

02 Start: Zn ListNo List 0

If a zone list will be used to START the relay action, enter the zone list number(to be programmed in field ✱81): 1, 2, or 3. If not used, enter 0. Press the [✱]key to continue.

Page 49: ADEMCO N7225V2B

7 –5

02 Start: Zn TypNot Used 00

If a zone type or system operation will be used to START the relay action,enter the appropriate two-digit code (see table that follows). If not, enter 00.Press the [✱] key to continue.

CHOICES FOR ZONE TYPES00 = Not Used 05 = Trouble Day/Alarm Night 08 = 24 Hr Aux01 = Entry/Exit 06 = 24 Hr Silent 09 = Fire03 = Perimeter 07 = 24 Hr Audible 10 = Interior w/Delay04 = Interior Follower

CHOICES FOR SYSTEM OPERATION20 = Arming–Stay 33 = Any Burglary Alarm 39 = Any Fire Alarm21 = Arming–Away 34 = Code + # + 7 Key Entry 40 = Bypassing22 = Disarming (Code + OFF)  35 = Code + # + 8 Key Entry 41 = AC Power Failure31 = End of Exit Time 36 = At Bell Timeout** 42 = System Batt. Low32 = Start of Entry Time 38 = Chime 58 = Duress

**Or at Disarming, whichever occurs earlier.

02 Stop: Zn ListNo List 0

If a zone list will be used to STOP, or restore, the relay action, enter the zone list(ZL) number 1, 2, or 3 (to be programmed in ✱81 mode). If not used, enter 0.Press the [✱] key to continue.

02 Stop: Zn TypNot Used 00

If a zone type or system operation will be used to STOP the relay action, enterthe appropriate two digit code (see the "ZT" choices listed above). If not, enter00. Press the [✱ ] key to continue.

02    A EV ZL ZTSTT 0 0 0 00

This screen again displays a summary of the current relay STARTprogramming.Press the [✱] key to continue.

02 A EV ZL ZTSTP   – – 0 00

This screen again displays a summary of the current relay STOP programming.Press the [✱] key to continue.

The display then returns again to the first screen so that the next relay numberto be programmed can be entered, or enter [0][0] to end relay programming.

Previously entered data can be reviewed by pressing [#] [8] [0]. After therelay number is chosen, press [✱ ] to go to the next screens. This is a reviewmode only, and data cannot be changed.

Example ofOutput Relay

Programming

A lamp is to be turned on when any one of 3 specific zones are faulted orwhen any 24-hour auxiliary zone is disturbed. We want to turn off thelamp manually without affecting the arming status of the system.In field *80 we choose Output Relay 01 and program the Action (A) to be "2"(Close and stay closed). The Event we are looking for to start the relay actionis a fault, so we will program "2" in (EV). We will use Zone List 1 for the 3specific zones, so will program "1" in (ZL), (and will program these 3 zones infield *81's Zone List 1).The second condition for turning on the indicator is triggering a 24 hour aux.zone (Zone Type 08), so we will program (ZT) as "08".

To stop relay action and turn off the indicator, we do not want to use a restoreof any zone, so we will program a "0" for the "Restore of" Zone List (ZL). Tochoose a manual entry of User Code + [#] + [7] to turn it off, we will program(ZT) as "34".If no other relay is to be programmed, go to field *81 and program the 3specific zones in Zone List 1.

Page 50: ADEMCO N7225V2B

7 –6

Press ✱81. (Zone Lists for Output Relays). This interactive mode is applicableonly if you have programmed ✱80 mode.

Refer to the Programming Form worksheet for ✱81 Mode.Zone List Displays ↓

Zone List No.

(00 = Quit) 01

Upon keying ✱81, this screen will appear. Enter the Zone List Number 01, 02,or 03 to program (or 00 to end these entries). Press the [✱ ] key to advance.In the following displays, zone list 01 has been selected for programming.

01 Enter Zn Num.

(00 = Quit) 00

Enter each zone number to add to the zone list by first entering the zonenumber, then the [✱ ] key (example, 01✱, 02✱, 03✱). After all zones desiredare entered, press 00 to advance.

01 Del Zn List?

0 = No 1 = Yes 0

To delete the zone list, enter 1 (Yes). All zones in the zone list will be deletedautomatically. and programming will return to the first screen.To save the zone list, enter 0 (No) to advance.

01 Delete Zone?

0 = No 1 = Yes 0

To delete a zone or zones in a zone list enter 1 (Yes) to advance.

01 Zn to Delete?

(00 = Quit) 00

Enter each zone to be deleted from the list, followed by the [✱] key. After allzones to be deleted are entered, enter 00 to return to the first screen so thatanother list can be programmed, if desired.

Notes:• Any list may include any or all of the system's zone numbers.

• A zone list can be assigned to more than one output relay.

• If you only want to review what has been programmed previously, enter[#][8][1]. The review can be advanced by using the [✱] key. When finished,enter [0][0] ✱ to quit. No programmed values can be changed in this mode.

When programming in ✱80 and ✱81 interactive modes is completed, exitthe programming mode by keying ✱99.

Page 51: ADEMCO N7225V2B

8 –1

Section 8. 4285 PHONE MODULEThis section provides instructions for mounting the 4285 Phone module, wiringthe Phone module and for programming the system for phone access via thePhone module.

Installing the Phone moduleGeneral

InformationThe 4285 Phone module is an add-on accessory for the VIA-30PSE thatpermits access to the security system via a Touch-tone phone (either onpremises or by a call-in when away).

The Phone module can announce many of the same words that wouldnormally be displayed on an Alpha keypad under the same system conditions.

When using the 4285 Phone module, addressable keypads must be used inthe system, but set to the non-addressable mode (address 31), i.e., do notuse a 4127 or 6127 keypad.

When properly connected, the 4285 Phone module will enable the user to dothe following via a Touch-tone telephone:

a. Receive synthesized voice messages over the phone regarding the statusof the security system.

b. Arm and disarm the security system and perform most other commandsusing the telephone keypad, with voice annunciation being provided overthe phone as confirmation after a command is entered.

The phone used for phone access must have Touch-tone capability, thoughTouch-tone service is not necessary (if premises uses PULSE dialing,switchable phones must be set for Touch-tone temporarily before attemptingphone access).

A Phone Access User's Guide for phone access to the security system isprovided with the Phone module for the user of the system.

UL The Phone module is not Listed for UL installation use..

Mounting The4285 Phone

module

The Phone module may be mounted in the control cabinet if space is availableor, if this is not possible, on the side of the cabinet or adjacent to it.

When mounting the Module outside the cabinet, use the screw holes at its rearwhich will permit it to be mounted horizontally or vertically (2-faced adhesivetape may be used, if preferred). Wires can be brought out from the side orback (a round breakout is also available on the back).Affix the Phone module’s connections label (supplied separately) to the insideof the Phone module's cover if the cover is used. If you have installed themodule within the cabinet, affix the label to the inside of the control cabinet'sdoor.

Phone ModuleWiring

The 4285 is wired between the control panel and the premises handset(s). Itlistens for touch tones on the phone line and reports them to the control panel.During on-premises phone access, it powers the premises phones; during off-premises phone access, it seizes the line from the premises phones and anyanswering machines.Note: The phone lines must be in service for the phone module to function,

even when accessing the system from an on-premises phone.

Page 52: ADEMCO N7225V2B

8 –2

1. Make 12V (+) and (–) and data in and data out connections from the Phonemodule to the control, using the connector cable supplied with the Phonemodule (see Figure 12).

Color Lead Terminal On Control *

GREEN DATA IN (terminal 6)

BLACK AUX – (terminal 4)

RED AUX + (terminal 5)

YELLOW DATA OUT (terminal 7)

* These are the same connectionsas those used for remotekeypads .

2. Insert the keyed connector at the other end of the connector cable into themating header on the Phone module (see diagram on next page for locationof the header).

3. Connect terminals 1 through 5 on the Phone module as shown in the WiringTable and in the 4285 wiring diagram that follows.

Use an RJ31X jack with a direct-connect cord and make all connectionsexactly as shown. If the leads on the direct-connect cord are too short toreach their assigned terminals, splice additional wires to them, as required.

4285 WIRING TABLE

 4285 Terminal Connects to:

1: Phone In (Tip) Terminal (17) on control.

2: Phone In (Ring) Terminal (18) on control.

3: Phone Out (Tip) BROWN lead from direct-connect cord.

4: Phone Out (Ring) GRAY lead from direct-connect cord.

5: Ground Earth ground terminal (21) on control.

6: Not Used

7: Not Used

If no touch tones are produced following access to the security system fromon-premises (this problem may arise in rare cases), it may be necessary toreverse the wires connected to terminals 3 and 4 on the Phone module andthe wires connected to terminals (17) & (18) on the control. The wiringdiagram shows the wiring connections that will provide proper operation inmost cases.

Caller ID UnitsIf the telephone system on the premises includes a Caller ID unit, connect theID unit directly to the “Handset” terminals (17 &18) on the control, as shown in4285 Phone module Wiring Connections diagram that follows.

Page 53: ADEMCO N7225V2B

8 –3

4285 WIRING NOTES:1. Wire the 4285 Phone module exactly as shown, using a direct-connect cord and RJ31X jack.2. If Touch-tones are not heard when pressing keys following phone access to the security system via an

on-premises phone, try reversing the pair of wires connected to terminals 3 & 4 on the 4285, and thepair of wires connected to terminals 17 & 18 on the control.

3. If an error signal (fast busy signal) is heard when trying to access the system via the phone, check forcorrect line seizure wiring, as described in note 4.

4. Connection to the incoming Telco line via a RJ31X jack and direct-connect cord, as shown in thisdiagram, is essential, even if the system is not connected to a central station. The 4285 will notfunction if this is not done.The house phone lines (gray and brown wires) must be wired to the Phone module terminals,not to the control terminals. Otherwise, an error signal (fast busy signal) will occur when tryingto access the system from an on-premises phone.

5. If the telephone system on the premises includes a Caller ID unit, connect the ID unit directly to the“Handset” terminals (17 & 18) on the control, as shown.

18

ANSWERING MACHINE

@@@@@@@@e?@@@@@@@@e?@@h?@@h?@@h?@@h?@@h?@@h?

@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?

@@@@@@@@@@@@@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

?@@?@@?@@?@@?@@?@@

?@@@@@@@@?@@@@@@@@

?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@

@@g@@g@@g@@g@@g@@g@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

TERMINALS ON CONTROL EARTH GROUND (COLD WATER PIPE)

INCOMING TELCO LINE

NOT INSTALLERADJUSTABLE

UNUSED

KEYEDHEADER

4285VOICE MODULE

12

34

56

7

YELLOW: TO DATA OUT (term. 7)NO CONNECTIONRED: TO AUX (+) (term. 5)BLACK: TO AUX. GROUND (–) (term. 4)GREEN: TO DATA IN (term. 6)

CONNECTORWITH FLYINGLEADS

TO CONTROL PANELTERMINALS USEDFOR KEYPADCONNECTIONS

PREMISESANSWERINGMACHINE ANDPHONES

HandsetIncoming

Telco Line

TIP

RIN

G

RJ31XJACK

PLUG

DIRECTCONNECT

CORD

➧TIPRING

GR

OU

ND

MU

ST

CO

NN

EC

T T

O

ON

428

5 (T

IP)

MU

ST

CO

NN

EC

T T

O

ON

428

5(R

ING

)

GR

EE

N (

TIP

)

RE

D (

RIN

G)

1

2

▲▲

IMPORTANTIF THE PANEL IS NOT CONNECTED TOA PROPER EARTH GROUND, YOU MAYGET FALSE LINE CUT INDICATINS (IFTELEPHONE LINE MONITOR HAS BEENPROGRAMMED).

@@@@@@@@e?@@@@@@@@e?@@h?@@h?@@h?@@h?@@h?@@h?

@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e

@@@@@@@@@@@@@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

?@@?@@?@@?@@?@@?@@

?@@@@@@@@?@@@@@@@@

?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@

@@g@@g@@g@@g@@g@@g@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

@@@@@@@@@@@@@@@@

TO GND TERMINAL (21)ON CONTROL

GR

AY

(R

)

BR

OW

N (

T)

4285 TERMINAL ASSIGNMENTS

1 - TIP2 - RING

PHONE INPUT

3 - TIP4 - RING

PHONE OUTPUT

5 - GROUND6 - 7 -

AUDIO OUT 1(FOR FUTURE USE)

}}

}

{ {IMPORTANT NOTEFOR EXISTINGINSTALLATIONS:EXISTING WIRESCONNECTED TO THE"HANDSET" TERMINALSON CONTROL MUST BEMOVED FROM THERETO TERMINALS 3 AND 4ON THE 4285.

17 19 20 21

CALLER IDUNIT

*NOTE: IF THE TELEPHONE HAS BUILT-IN CALLER ID,THE CALLER ID FUNCTION MAY NOT WORK.

*

*

Figure 12. 4285 Phone module Wiring Connections

Page 54: ADEMCO N7225V2B

8 –4

Programming The Control For Phone Access

1. With at least one addressable keypad (but set to the non-addressablemode, address 31) connected to the keypad terminals on the control,power up the system temporarily. If you had previously connected the ACtransformer to the control panel, you need only plug in the transformer (to120VAC outlet) to power up the system.

2. Enter the programming mode by keying the following on the keypad:    INSTALLER code (4 1 1 1) + 8 + 0.

3. Press ✱26. VOICE (PHONE) MODULE ACCESS CODE. If using a 4285 Phone module, enter the 2-digit phone access code asfollows: For first digit, enter 1–9; for second digit, enter # +11 for "✱ ", or# +12 for "#". Example: if desired access code is 7✱ , 7 is the first entry,and # + 11 (for ✱) is the second entry.Enter “00” if not using a Phone module (this is the default).NOTE: a “0” in either digit will disable the phone module.

4. Press ✱95. RING DETECTION COUNT . Refer to the chart below and program this field accordingly.

Voice Answering Module   Machine Downloading Field ✱95 Programming

Yes No No Set for value other than “0” (1–14). This will enable the control panel toanswer the phone call. Otherwise, it will not be possible to access thePhone module.

Yes Yes No Set for a value higher than thenumber of rings for which theanswering machine is set.Example: if the machine is set for 4rings, use a value of 5 or higher.This is recommended so that thePhone module can still be accessedif the answering machine is turnedoff and does not answer the phonecall.

Yes No Yes Set for value other than “0” (1–14).

Yes Yes Yes Enter “15” to bypass the answeringmachine. See Important Note below.

Important Note: If “15” is entered in field ✱95 to bypass an answering machine,and a 4285 Phone Module is included in the installation, you should note thefollowing:When calling in from an off-premises phone (to receive a status report or execute acommand), the user should make the initial call, allow 1 to 3 rings only, and hangup. Then call in again – the Phone Module will now seize the line, and 2 long toneswill be heard, followed by the usual voice prompt for the 2-digit phone access code.If this procedure is not followed, Phone Module operation will not be possible.

5. Zone descriptors should also be programmed, regardless of the type ofkeypads in use. If this is not done, the Phone module will not annunciate adescription of the zone(s) in alarm, trouble, etc. (the Phone module willannunciate zone numbers only).You can enter zone descriptors now or later using interactive mode ✱82.See the ALPHA DESCRIPTOR PROGRAMMING section for a detailedprocedure.

6. Exit the programming mode by entering ✱99.

Perform a preliminary check of the 4285 Phone module, as indicated next.

Page 55: ADEMCO N7225V2B

8 –5

Checking the Operation of the 4285 Phone module

To Check Phone Module Operation From an On-Premises Phone1. Pick up phone and enter the programmed 2-digit phone code (entered in

field ✱ 26, VOICE (PHONE) MODULE ACCESS CODE). Annunciation of asystem status report should automatically start. See the User’s Guideaccompanying the Phone module for detailed information regarding thenature of the status report, if necessary.

2. During any pause in the status report, or immediately following it, key thefollowing via the keypad on the phone:

INSTALLER Code (4111), then press key 1 (OFF).

3. A ”beep” should be heard on the phone and from a wired keypad, and thewords DISARMED...READY TO ARM or DISARMED...NOT READY TO ARM*should be heard, indicating that the command was entered successfully.* DISARMED...NOT READY TO ARM would indicate an open zone.

4. Hang up the phone.

To Check Phone Module Operation From an Off-Premises Phone:1. Have someone dial the premises phone number, using a Touch-tone

phone.• If the phone system does not include an answering machine, 2 long

tones will be heard in the caller’s phone, followed by a voice prompt"HELLO, ENTER PHONE CODE NOW" . The caller should then enter theprogrammed 2-digit phone code (entered in field ✱26, VOICE (PHONE)MODULE ACCESS CODE).

• If the premises phone system includes an answering machine, the 2-digit phone code should be entered during a pause at the beginning of,or during, the outgoing answering machine message.

2. When the 2-digit phone code is entered, the caller will hear a voice promptasking for entry of the 4-digit system code ("ENTER SYSTEM CODE NOW").

3. The caller should then enter the INSTALLER code (4111). As a safetyfeature, there is a 3-try limit in which to enter each code (phone code andsystem code), after which time the call-in will be aborted. Also, if no keysare pressed for a period of 20 seconds, the call-in will be aborted.

4. Annunciation of a system status report will start if both codes were enteredcorrectly.

5 During any pause in the status report, or immediately following it, the callershould key the following via the keypad on the phone:

INSTALLER Code (4111), then 1 (OFF).

6. A ”beep” should be heard (and from a wired keypad on the premises), andthe words DISARMED...READY TO ARM or DISARMED...NOT READY TOARM* should be heard on the caller’s phone, indicating that the commandwas entered successfully.* DISARMED...NOT READY TO ARM would indicate an open zone.

7. At this point, the caller can hang up the phone.

8. Verify with the caller that there was successful access to the system andthat the appropriate annunciations were heard over the phone.

Page 56: ADEMCO N7225V2B

8 –6

Page 57: ADEMCO N7225V2B

9 – 1

Section 9. EXTERNAL SOUNDERSThis section provides a list of compatible sounders, connection information foran external sounder and programming procedures for those options that affectthe operation of external sounders.

Compatible Sounders

Ademco AB-12M 10”Motorized Bell & Box

Motor bell & box. UL Grade A. 100mA currentdraw.

Ademco 1011BE12M10” Motorized Bell &Box

Motor bell & box. UL Listed. 100mA current draw.

Ademco 702Outdoor Siren

Self-contained 6–12 volt siren (driver built-in) andweatherproof for outdoor use. Can be wired foreither a steady or warble sound. 117dB @ 10feet. 1500mA current draw.

Ademco 7192-Channel Siren

Self-contained 6–12-volt siren (driver built in).Steady or warble sound. 109dB @ 10 feet.550mA current draw.

Ademco 747Indoor Siren

Self-contained 6–15 volt siren (driver built-in) forindoor wall mount. 747F available for flushmounting. 105dB @ 10 feet. 400mA current draw.

Ademco 747ULIndoor Siren

Self-contained 6–15 volt siren (driver built-in) forindoor wall mount. UL Listed. 85dB @ 10 feet.320mA current draw.

Ademco 744Siren Driver

6 jumper-selected sound outputs. Rated at 119dBwith use of an 8-ohm 30 watt speaker. 1.3 ampscurrent draw.

Ademco 745X3*Voice Siren Driver

12 volt voice siren driver with English, Spanishand French voice messages. Separate messagesfor Fire and Burglary. Use with 8-ohm speaker.UL Listed. 1100mA current draw.

Ademco 705–820,5-inch Round Speaker

20-watt, 8-ohm indoor or outdoor speaker.Requires a driver.

Ademco 713 Speaker 40-watt, 8-ohm, indoor/outdoor speaker. Requiresa driver.

System Sensor PA400B(beige)/PA400R (red)Indoor Piezo Sounder

Indoor piezo sounder (red or beige), rated at 90dB @ 10 feet.

* Requires special power wiring, using additional components.

UL  • Use only UL Listed sounding devices for UL installations.

• The total current drawn from the alarm output and the auxiliary poweroutput, combined, cannot exceed 600mA. In addition, the sounding devicemust be a UL Listed audible signal appliance rated to operate in a 10.2-13.8VDC voltage range, and must be mounted indoors. Example: WheelockSignals Inc. siren model 34T-12 (provides 85dB[A] for NFPA 74 & Standard985).

Non-ULInstallations

The total current drawn from the alarm output terminals cannot exceed 2amps. The back-up battery must be installed since this current is supplied bythat battery.

Going beyond the limits indicated (2 amps) will overload the power supply, ormay cause the electronic circuit protecting the sounder output to trip.

Page 58: ADEMCO N7225V2B

9 – 2

This control complies with NFPA requirements for temporal pulsesounding of fire notification appliances.

Temporal pulse sounding for a fire alarm consists of the following:3 pulses – pause – 3 pulses – pause – 3 pulses. . . repeated.

Sounder ConnectionsThe VIA-30PSE provides a 12 VDC output which can power external alarmsounders (bells or sirens, see compatible sounders listed previously). Thisoutput will activate a sounder when an alarm occurs.Make connections to alarm output terminals 3 (+) and 4 (–). See Figure 13.

3

4

ALARMOUTPUT

CONTROL BOARD

+

+

No. 702 SIREN

Figure 13. Typical Sounder Wiring

Programming for External Sounders1. With at least one 2-line Alpha keypad (5137AD or 6139) connected to the

keypad terminals on the control, power up the system temporarily. If youhad previously connected the AC transformer to the control panel, youneed only plug in the transformer (to 120VAC outlet) to power up thesystem.

2. Enter the programming mode by keying the following on the Alpha keypad:    INSTALLER code (4 1 1 1) + 8 + 0.

3. Press ✱28. Single Alarm Sounding per Zone/Armed Period .Enter “1” for yes, “0” for no (default).

4. Press ✱29. Fire Sounder Timeout.Enter “1” for no timeout, “0” for timeout (default).

5. Press ✱30. Alarm Bell Timeout.Enter 0 for no timeout, 1 for 4 min (default), 2 for 8 min, 3 for 12 min,4 for 16 min.

6. Press ✱51. Confirmation of Arming Ding.Enter “0” for no (default), “1” for yes, “2” for yes, but with RF arming only.

7. Exit the programming mode by entering ✱99.

Testing the SounderAfter installation of the sounder is completed, the Security System should becarefully tested, as follows.1. Connect the battery wires from the control board to the battery, observing

correct polarity.

2. Enter the INSTALLER code (4 1 1 1) and press the TEST key on the wiredkeypad.The external sounder should sound for 1 second if the sounder is good andproper connections have been made. Note that if the backup battery isdischarged, the sounder will not turn on.

3. To turn off the test mode, enter the INSTALLER code (4 1 1 1) and pressthe OFF key.

Page 59: ADEMCO N7225V2B

10 – 1

Section 10. LONG RANGE RADIO

General InformationCheck availability of Model 7720PLUS or 7820 long range radio.If output to long range radio is selected, all messages that are programmed togo to the primary telephone line receiver will also be sent to the 7720PLUS or7820 long range radio. These messages will be in Contact ID format (notaffected by entry in field ✱46).The data line is supervised, as well as certain functions in the radio. Ifcommunication is lost or a trouble develops, a message will be attempted to besent via both radio and telephone to the central station.For complete information, see the manual that accompanies the radio.

Wiring ConnectionsConnect the data in/data out terminals and voltage input terminals of the LongRange Radio to the control's keypad connection points, terminals 4, 5, 6, and 7as shown below.

7720 PLUS/7820 LONG RANGE RADIO

BLACK

RED

GREEN

YELLOW

4

5

6

7CONTROLTERMINALS

Figure 14. Long Range Radio Connections

Programming for Long Range Radio1. With at least one keypad connected to the keypad terminals on the control,

power up the system temporarily. If you had previously connected the ACtransformer to the control panel, you need only plug in the transformer (to120VAC outlet) to power up the system.

2. Enter the programming mode by keying the following on the Alpha keypad:    INSTALLER code (4 1 1 1) + 8 + 0.

3. Press ✱27 OUTPUT TO LONG RANGE RADIOEnter 1 when using a Long Range Radio; enter 0 if not (default is 0).If yes is selected, any dialer report programmed to report to the PRIMARYphone number (in field ✱47) will be sent, as well, via long range radio. Alldialer and long range radio reports will be in Contact ID format (regardlessof the selection made in field ✱46).Full Trouble and Restore messages are sent.

5. Program the long range radio for device address “3” on the keypad lines.

6. Exit the programming mode by keying ✱99.

Page 60: ADEMCO N7225V2B

10 – 2

Page 61: ADEMCO N7225V2B

11 – 1

Section 11. AUDIO ALARM VERIFICATION (AAV)UNIT

General InformationAn Audio Alarm Verification (AAV) module, such as the Eagle 1241, is an add-on accessory that permits voice dialog between an operator at a central stationand a person at the alarm installation, for the purpose of alarm verification.

Alarm reports must be programmed for the primary phone number to enablethis feature.

AAV should not be used when Paging or Alarm Reports are being sent to aSecondary number. If this is done, the call to the Secondary number by thecommunicator after the alarm report will prevent the AAV from taking controlof the telephone line, and the AAV “Listen in” session cannot take place.

UL The AAV option cannot be used in UL installations.

After all messages have been sent during a reporting session to the primaryphone number, the control will trigger the AAV if at least one of the messageswas an alarm report. If Contact ID format is selected for the primary phonenumber, the control will send a "listen-in to follow" message (event code 606),which signals the 685 receiver at the central station to hold the phoneconnection for 1 minute.

Once the digital message is “kissed off”, the control will give up the phone lineto the AAV module, without breaking connection with the central station. At thistime, all sirens and all continuous keypad sounds will be shut off.

You must connect a 4204 relay module when using an AAV unit. Do not userelay output number 1 for any other usage.

Wiring ConnectionsThe method used to trigger AAV is via the use of a 4204 relay module, asshown in the AAV connection diagrams that follow (one diagram forconnections when a 4285 Phone module is used, the other when the 4285 isnot used).

Programming1. With at least one 2-line Alpha keypad (5137AD or 6139) connected, power

up the system. If you had previously connected the AC transformer to thecontrol panel, you need only plug in the transformer (to 120VAC outlet) topower up the system.

2. Enter the programming mode by keying the following on the Alpha keypad:                          Installer code (4 1 1 1) + 8 + 0.

3. Press ✱91. OPTION SELECTION. Enter “4” for AAV monitoring. Enter “0”for none. For UL installations, enter “0” (no AAV).

4. Relay programming in field ✱80: Do not program anything for Relay #1.

5. Exit the programming mode by keying ✱99.

Page 62: ADEMCO N7225V2B

11 – 2

TERMINALS ON CONTROL EARTH

GROUND17 18 19 20➡

1

23

45

67

8 9

10

1112

13

1415

16

PREMISESANSWERINGMACHINE ANDPHONES

ANSWERING MACHINE

TIP

RIN

G

RJ31XJACK

PLUG

DIRECTCONNECT

CORD➧

TIPRING

(TIP

)

(RIN

G)

▲▲

INCOMING TELCO LINE

BR

OW

N (T

IP)

GR

AY (R

ING

)▲

ON

MO

DE

L E

AG

LE

SE

CU

RIT

Y12

41

GNDV+

GND

1 2 3

RELAY 1, SHOWN“OFF”

NO NC C

4204 MODULE

RINGTIP

INPUT TRIGGER

REFER TO AAV MODULEINSTRUCTIONS FOR CONNEC-TIONS TO AUDIOSPEAKERS ANDMICROPHONE

13141516

GR

EE

N(T

IP)

RE

D (R

ING

)

NOTE: DO NOT USERELAY 1 FORANY OTHERPURPOSE.

21

Figure 15. Connection Of AAV Unit When Not Using A 4285 Phone module

1 2

34

56

78

9

1011

12

13

1415

16▲

ON

MO

DE

L E

AG

LE

SE

CU

RIT

Y12

41

GND+VDC

RING TIP

REFER TO AAV MODULEINSTRUCTIONS FOR CONNEC-TIONS TO AUDIOSPEAKERS ANDMICROPHONE

TERMINALS ON CONTROL

EARTHGROUND

17 18 19 20➡

PREMISESANSWERINGMACHINE ANDPHONES

ANSWERING MACHINE

TIP

RIN

G

RJ31XJACK

PLUG

DIRECTCONNECT

CORD

➧TIPRING

(TIP

)

(RIN

G)

▲▲

INCOMING TELCO LINE

GRAY (RING)BROWN (TIP)

GR

EE

N (T

IP)

RE

D (R

ING

)

1 2

3 44285

V+

GND

1 2 3

RELAY 1, SHOWN“OFF”

NO NC C

4204 MODULE13

141516

NOTE: DO NOT USERELAY 1 FORANY OTHERPURPOSE.

21

Figure 16. Connection Of AAV Unit When Also Using A 4285 Phone Module

Page 63: ADEMCO N7225V2B

12 – 1

Section 12. FINAL POWER UPIn previous sections, you made temporary power connections for the purposeof programming and testing. This section provides information about finalpower-up procedures and battery size calculations.

Earth Ground ConnectionsThe designated earth ground terminal (21) must be terminated in a good earthground for the lightning transient protective devices in this product to beeffective. See the INSTALLING THE CONTROL section earlier in this manual.

AC Power-Up1. Plug the 1321/TF2 transformer into a 24-hour, uninterrupted 120VAC

outlet.2. Following power-up, AC, dI (disabled), or System Busy (Alpha keypads) or

NOT READY (fixed-word keypads) will be displayed. Also the green"READY" LED* on the keypad(s) should light.* Some keypads are equipped with a "POWER" LED in place of a "READY" LED.

After approximately 1 minute, the initial displays will revert toDISARMED...READY TO ARM for Alpha keypads, or READY for Fixed-word keypads (if there are no faulted zones). This 1-minute delay allowsPIRs, etc. to stabilize.To bypass this delay, press: [#] + [0].

Note: If you do not get the “Ready” displays described above, refer to“Trouble Conditions” in the SYSTEM OPERATION section, and alsoto the TROUBLESHOOTING GUIDE section.

Connecting The Back-Up BatteryIn the event of an AC power loss, the Control panel is supported by a back-up,rechargeable gel cell battery. The minimum battery size recommended is theNo. 467 (12V, 4AH) battery. See “Calculating Battery Size Needed” below. Thebattery is installed in the control cabinet.The standby battery connection is automatically checked every 3 minutes(CSFM requirement). In addition, entry into the test mode will cause a batterytest to be initiated. If there is no battery or a low battery, a low battery messageis displayed and, if so programmed, will be reported to the central station.

Calculating theBattery Size

Needed

Determine the total device current draw after filling in the AUXILIARY DEVICECURRENT DRAW WORKSHEET on the next page. To this figure add the100mA that is drawn by the control panel itself. Then, to determine the batterysize needed, use the following formula:Total Current Drawn* x Number of hours standby wanted = Battery Ampere/Hours.

* Convert mA figure to decimal Amps (see example).

Example:If total auxiliary device current drawn is 450mA, add 100mA for the controlpanel, for a total of 550mA (0.55 amps); if 24-hour standby is wanted, thecalculation will be:

0.55mA x 24 hours = 13.2 Ampere/Hour battery needed.

In this example, two 7 Amp/Hr batteries (connected in parallel) must be used.

Making theBattery

Connections1. Use the battery standby formula (shown on previous page) to select the

appropriate battery for the installation.

Remember, when calculating the battery size needed, you must add the100mA drawn by the control itself to the total Auxiliary current draw in theworksheet that follows.

Page 64: ADEMCO N7225V2B

12 – 2

Do not connect the battery until all devices have been wired to the control.

2. Attach the Red and Black wires on the battery connector cable as follows:a) Red to the positive (+) battery tab on the control board.*b) Black to the negative (–) battery tab on the control board.** This not required if wires are already connected to the battery tabs on the control.

3. Attach the Red and Black wires at the other end of the battery connectorcable to the battery, as follows:a) Red to the positive (+) terminal on the battery.

b) Black to the negative (–) terminal on the battery.

AUXILIARY DEVICE CURRENT DRAW WORKSHEET

DEVICE CURRENT # UNITS TOTAL CURRENT(device mA x # of units)

4127 Keypad 20mA

4137AD Keypad 60mA

5137AD/ADR Keypad 90mA

6127 Keypad 20mA

6128 Keypad 30mA

6137 Keypad 85mA

6138 Keypad 100mA

6139/6139R Keypad 100mA

4281/5881/5882 Type RF Receiver 35mA

4204 Relay Unit 15/180mA‡

4219 Zone Expander Module 35mA

4229 Zone Expander/Relay Module 35/100mA‡

4285 Phone module 160mA

Long Range Radio Depends on typeof Radio used (seeits instructions).

*

*

*

*

TOTAL =      (Current available from Aux. terminals = 500mA max.)**

  * If using hard-wire devices such as PIRs, refer to the specifications for that particular unit's currentdraw, and include on worksheet.

 ‡ Figures are for relays OFF/relays ON.

** In UL installations, maximum current draw from the Auxiliary Output and the Alarm Output combinedmust not exceed 600mA.

Page 65: ADEMCO N7225V2B

13 – 1

Section 13.ALPHA DESCRIPTOR PROGRAMMING

This section provides instructions for programming Alpha descriptors This isrecommended for systems using Alpha keypads, and necessary if a 4285Phone module is used. Alpha descriptors cannot be displayed on fixed-wordkeypads.If using a 4285 Phone module, select from those words in the AlphaVocabulary list (on a following page) shown in boldface type . The Phonemodule will not provide annunciation of the other words.

If a 4285 Phone module is added to an existing VIA-30PSE system, the Alphadescriptors presently in the system should be re-programmed, selecting fromthose words shown in boldface type in the Alpha Vocabulary list. The Phonemodule will not provide annunciation of any other words.

The ALPHA VOCABULARY LIST and CHARACTER CHART will be found ona following page.

Assigning Zone DescriptorsThe Alpha Keypad used with the VIA-30PSE can have a user-friendlyEnglish language descriptor/location of all protection zones, keypad panics,and RF receiver supervision faults programmed into the system. Eachdescriptor can be composed of a combination of words (up to a maximum of3) selected from a vocabulary of words stored in memory (see the list on afollowing page). In addition, up to 5 installer-defined words can be added tothose already in memory. Thus, when an alarm or trouble occurs in a zone, anappropriate descriptor for that zone's location will be displayed at the keypad.Note: Alpha Descriptor entry can be done locally at the Alpha Keypad or re-

motely using Downloading software. The Alpha keypad procedure isdescribed below.

Entering Zone Descriptors (program menu mode ✱82)The descriptor can be entered when the zone is being defined in field ✱ 56.Alternatively, zone descriptors can be entered in field ✱82.There are two methods that can be used to enter Alpha descriptors.The easiest method requires that you simply enter the 3-digit referencenumber for the desired word(s). The 3-digit number for each word is providedin the Alpha Vocabulary list (on a following page).An alternate method allows you to pick the desired words by scrolling throughthe Alpha Vocabulary list.

Programming the Descriptors1. With the system powered up, enter the programming mode by keying:

Installer code (4 1 1 1) + 8 + 0. The following display will appear:

Installer Code20

Pr ogr a m A lpha ?0 = No, 1 = Ye s 0 0

2. Press ✱82.The “Program Alpha ?” prompt willappear.

Custom Wor ds ?0 = No, 1 = Ye s   0 0

3. Press “1” (Yes).The “Custom Words” prompt willappear.

Page 66: ADEMCO N7225V2B

13 – 2

4. Press “0” (No).* The system will thenautomatically display the defaultdescriptor for zone 1.

 * The procedure for adding custom words tothe built-in vocabulary will be found laterunder “Adding Custom Words”.

   Default Descriptor ↓

✱ ZN 0 1   ZO NE 0 1

If a descriptor was not entered previouslyfor zone 1, the default descriptor for zone1 will be displayed.Note that no entries can be made. Entriescan be made only when the displaycontains a flashing cursor, which signifiesthe “entry mode”.

Flashing Cursor (system isready for entry of word).

✱ ZN 0 1   A

5. To delete or change the defaultdescriptor for zone 1, press [✱] plusthe same zone number (01). This willclear that descriptor and gain access tothe entry mode with flashing cursor,allowing changes to be made.NOTE: If you do not wish to change theexisting descriptor for zone 1, enter [✱]

plus the next zone number for whichyou wish to enter (or check) adescriptor. A summary display for thatzone will appear. You must then press[✱] plus the same zone number againto gain access to the entry mode(flashing cursor) for that zone.

Flashing Cursor↓

✱ ZN 0 1         B ACK

✱ ZN 0 1      BACK

A

↑Flashing Cursor if “6” is     pressed (system is     ready for next word).

6. Press # plus 3-digit number for thefirst word from the “ALPHAVOCABULARY LIST” on a followingpage. Example: The descriptor that wewish to enter for zone 1 is BACKDOOR. From the list, BACK = 013.Therefore, you would enter # 0 1 3 .Note:  If you accidentally enter thewrong word, simply press # plus thecorrect 3-digit number for the word youwant.

7. Press “6” to accept the selectedword and continue.Note: If this is the only word you areusing for the descriptor, press “8”instead of “6” to save that word inmemory, and then go to step 11.

✱ ZN 0 1      BACK

D O O R

↑ Flashing Cursor

8. Enter the 3-digit number for the nextword. In our example, the word isDOOR, whose number is “057”.Enter # 0 5 7. This display will appear:

Page 67: ADEMCO N7225V2B

13 – 3

✱ ZN 0 1      BACK

DO O R    A

↑Flashing Cursor if “6” ispressed (system ready fornext word).

 9. Press “6” to accept the selectedword.Note: If these are the only wordsyou  are using for the descriptor,press “8”  instead of “6” to save themin  memory.

10. The two words in our example have now been entered. Note, however,that  up to three words may beentered  (provided the number ofcharacters will  fit on the screen).Press “8” to save  all words inmemory.

✱ ZN 0 1      BACKDO O R 

The “A” with the flashing cursor overit will disappear, indicating that theword(s) are stored in memory for thatzone, as shown in the display at theleft.

11. To enter a descriptor for the nextzone,  press [✱ ] plus the desiredzone number  (e.g., ✱02. Thesummary display  following step 4previously will appear. Now repeat steps 6 through 10 forthe  descriptor for the next zone.

12. To exit the Alpha descriptor mode, press “✱00” at the summary display.

Pr ogr a m A lpha ?0 = No, 1 = Ye s 0 0

This prompt will be displayed.

Alpha Pgm8 2

13. Press “0”. This will be displayed.

14. Press ✱99 to exit the programming mode.

Alternate Method For Programming Zone Descriptors

When entering the ZoneDescriptors using thismethod, the keypad keysperform the followingfunctions:[3] Scrolls both alphabet and

actual words in ascendingalphabetical order.

[1] Scrolls both alphabet andactual words in descend-ing alphabetical order.

[6] Selects between alphabetand actual word list; alsoused to save words.

[8] Stores the zone descrip-tion in memory.

1. Perform steps 1 through 5 of the previous method.

2. Note that the first letter of the alphabet appears after the zone number,and that the zone number is automatically included with the description. Ifthere already is a description for the zone, the description will appear (withno cursor, since this is a display mode). To enter or change a description,press [✱ ] + Zone Number again. A flashing cursor will now appear.Assume, for example, that the desired description for zone 1 is BACKDOOR.

3. Select the first letter of the desired description (note that "A" is alreadydisplayed).Press key [3] repeatedly to advance through the alphabet (e.g., to "B"), orkey [1] to go backward. Then press [6] to display the first available wordbeginning with the desired letter (e.g., BABY).Next, press [3] repeatedly to move forward, or [1] to move backward, untilthe desired word is displayed (e.g., BACK). Then press [6] to accept theword and toggle back to the alphabet list.

Page 68: ADEMCO N7225V2B

13 – 4

4. For selection of the next word (e.g., DOOR), repeat step 3, as follows:Press key [3] until the first letter of the next word appears (e.g., "D"). Thenpress [6] to display the first available word beginning with that letter (e.g.DAUGHTERS). Press [3] repeatedly until the desired word (e.g., DOOR)appears. To accept the word, press [6], which toggles back to the alphabetlist.

5. When all desired words have been entered, press [8] to store thedescription in memory.

6. Enter ✱NN, where NN is the next zone that you want to review or for whichyou want to program a descriptor. To modify the descriptor, enter ✱ NNagain. To exit this mode, press “✱00”.

Adding Custom Words (will not be annunciated by 4285 Phone module)You can add up to five installer-defined words can be added to the built-in vo-cabulary. Each of the five "words" can actually consist of a "word string" of oneor more words, but no more than ten characters can be used for each word orword string.

Custom words must begin with an alphabetic character. If anumber or symbol is used as the first character, the word will notbe saved.

When adding CustomWords in steps 3–6, thekeypad keys perform thefollowing functions:[3] Advances through the

alphabet in ascendingorder.

[1] Moves through thealphabet in descend-ing order.

[6] Selects desired letter;moves cursor onespace to right.

[4] Moves cursor onespace to left.

[7] Inserts a space at thecursor location, eras-ing any character lo-cated there.

[8] Saves the new wordin the system's mem-ory.

1. Perform steps 1, 2, and 3 of Programming the Descriptors on a previouspage.Select CUSTOM WORD mode (enter “1”) when the prompt CUSTOMWORD ? is displayed.

2. Enter the number ([1]–[5]) of the custom word or word string to be created(for example, if you are creating the first custom word or word-string, enter[1], for the second, enter [2], etc.). A cursor will now appear at the be-ginning of the second line.

3. One of two methods of entering the custom word's characters cannow be used (refer to the CHARACTER (ASCI) LIST of letters, numbers,and symbols on a following page):Method 1:Press the [#] key, followed by the two-digit entry for the first letter youwould like to display (e.g., [6][5] for "A"), or...

Method 2:Use the [3] key to advance through the list of symbols, numbers, andletters. Use the [1] key to move back through the list.

4. When you have reached the desired character, press [6] to select it. Thecursor will then move to the right, in position for the next character.

5. Repeat steps 3 and 4 to create the desired word(s). Note that the [4] keycan be used to move the cursor to the left, if necessary, and that key [7]can be used to enter a blank (or erase an existing character). Remember,no word or word-string can exceed 10 characters.

6. Press the [8] key to save the custom word(s) and return to the "CUSTOMWORD ?" display.Repeat steps 2–5 for other custom words to be entered. To change acustom word, just overwrite it. If no more are to be entered now, press [0]to return to the Descriptor entry. The custom word(s) will be automaticallyadded to the built-in vocabulary.

When zone descriptors are being entered as described in step 6 ofProgramming the Descriptors , the custom word numbers are 250 to 254 forwords 1 to 5 respectively.When being entered as described in step 3 in Alternate Method ForProgramming Zone Descriptors, each word will be found at the end of thegroup of words that begin with the same letter as it does.

Page 69: ADEMCO N7225V2B

13 – 5

ALPHA VOCABULARY LIST(For Entering Zone Descriptors)

NOTE: Some rarely-used words appearing in previously published lists have been deleted fromthe list below. Use only this list for selecting zone descriptors.

000 (Word Space)A

• 001 AIR• 002 ALARM

004 ALLEY005 AMBUSH

• 006 AREA• 007 APARTMENT• 009 ATTIC

010 AUDIOB

• 012 BABY• 013 BACK• 014 BAR• 016 BASEMENT• 017 BATHROOM• 018 BED• 019 BEDROOM

020 BELL• 021 BLOWER• 022 BOILER

023 BOTTOM025 BREAK

• 026 BUILDINGC

028 CABINET• 029 CALL

030 CAMERA031 CAR033 CASH034 CCTV035 CEILING036 CELLAR

• 037 CENTRAL038 CIRCUIT

• 040 CLOSED• 046 COMPUTER

047 CONTACTD

• 048 DAUGHTERS049 DELAYED

• 050 DEN051 DESK

• 052 DETECTOR• 053 DINING

054 DISCRIMINATOR055 DISPLAY

• 057 DOOR• 059 DOWN• 060 DOWNSTAIRS

061 DRAWER• 062 DRIVEWAY• 064 DUCT

E• 065 EAST

066 ELECTRIC067 EMERGENCY068 ENTRY

• 069 EQUIPMENT• 071 EXIT

072 EXTERIORF

• 073 FACTORY075 FAMILY

• 076 FATHERS• 077 FENCE• 079 FIRE• 080 FLOOR

081 FLOW082 FOIL

• 083 FOYER084 FREEZER

• 085 FRONTG

• 089 GARAGE• 090 GAS

091 GATE• 092 GLASS

093 GUEST094 GUN

H• 095 HALL• 096 HEAT

098 HOLDUP099 HOUSE100 INFRARED

• 101 INSIDE102 INTERIOR103 INTRUSION

J104 JEWELRY

K• 105 KITCHEN

L• 106 LAUNDRY• 107 LEFT

108 LEVEL• 109 LIBRARY• 110 LIGHT

111 LINE• 113 LIVING• 114 LOADING

115 LOCK116 LOOP117 LOW

• 118 LOWERM

• 119 MACHINE121 MAIDS122 MAIN

• 123 MASTER• 125 MEDICAL

126 MEDICINE128 MONEY129 MONITOR

• 130 MOTHERS• 131 MOTION

132 MOTORN

• 134 NORTH135 NURSERY

O• 136 OFFICE• 138 OPEN

139 OPENING• 140 OUTSIDE

142 OVERHEADP

143 PAINTING• 144 PANIC

145 PASSIVE• 146 PATIO

147 PERIMETER• 148 PHONE

150 POINT151 POLICE152 POOL

• 153 POWERR

155 RADIO• 156 REAR

R155 RADIO

• 156 REAR157 RECREATION159 REFRIGERATION160 RF

• 161 RIGHT• 162 ROOM

163 ROOFS

164 SAFE165 SCREEN166 SENSOR

• 167 SERVICE• 168 SHED

169 SHOCK• 170 SHOP

171 SHORT• 173 SIDE

174 SKYLIGHT175 SLIDING

• 176 SMOKE• 178 SONS• 179 SOUTH

180 SPRINKLER• 182 STATION

184 STORE• 185 STORAGE

186 STORY190 SUPERVISED191 SUPERVISION192 SWIMMING193 SWITCH

T194 TAMPER196 TELCO197 TELEPHONE

• 199 TEMPERATURE200 THERMOSTAT

• 201 TOOL202 TRANSMITTER

U• 205 UP• 206 UPPER• 207 UPSTAIRS• 208 UTILITY

V209 VALVE210 VAULT212 VOLTAGE

W213 WALL214 WAREHOUSE

• 216 WEST• 217 WINDOW• 219 WING

220 WIRELESSX

222 XMITTERY

223 YARDZ

224 ZONE (No.)• 225 ZONE• 226 0• 227 1• 228 1ST• 229 2• 230 2ND• 231 3• 232 3RD• 233 4• 234 4TH• 235 5• 236 5TH• 237 6• 238 6TH• 239 7• 240 7TH• 241 8• 242 8TH• 243 9• 244 9TH

250 Custom Word #1

251 Custom Word #2

252 Custom Word #3

253 Custom Word #4

254 Custom Word #5

Note: Bulleted ( •) words in boldface type are those that are also available for use by the 4285 Phone Module. If using aPhone module, and words other than these are selected for Alpha descriptors, the module will not provideannunciation of those words.

CHARACTER (ASCII) CHART(For Adding Custom Words)

32 (space)33 !34 "35 #36 $37 %38 &39 '40 (41 )

42 *43 +44 ,45 –46 .47 /48 049 150 251 3

52 453 554 655 756 857 958 :59 ;60 <61 =

62 >63 ?64 @65 A66 B67 C68 D69 E70 F71 G

73 I74 J75 K76 L77 M78 N772 H9 O80 P81 Q

82 R83 S84 T85 U86 V87 W8889 Y90 Z

Page 70: ADEMCO N7225V2B

13 –6

Page 71: ADEMCO N7225V2B

14 –1

Section 14.  SEQUENTIAL MODE(for 5800 Series Wireless Transmitters)

(Use this mode only after all other zone information hasbeen programmed, including transmitter loop numbers).

There are two methods of enrolling – you can enroll each transmitter into the system as you areentering the zone information in field ✱56 (the procedure will be found in the WIRELESS (RF) ZONEEXPANSION section), or you can enroll all the transmitters in ✱83 menu mode after all other zoneinformation has been entered in field ✱56.The enrollment method in ✱83 is called "sequential mode" and is described in this section.As an option, the new enrollment mode allows you to use a 5804 button-type transmitter as a"program tool." The advantage of using a program tool is that it tells the control that you are about toenroll a transmitter into the system. You can move to the physical location of the transmitter to beenrolled, press the upper left-hand button of the program tool, and then trip the intended transmitter(see step 10 for operation). This helps to prevent random signals from being accepted into the systemuntil you are ready to enroll the intended transmitter. The transmitter that you use as the program toolcan also be used as a transmitter in the system. If you plan to use an existing transmitter, it must firstbe enrolled into the system as its associated zones. You may then program it as the tool.A Alpha keypad is required for the following procedures.

To enroll transmitters sequentially, after all other zone information hasbeen programmed, do the following:

1. Enter Programming mode [Installer Code ] + 8 + 0 on a Alpha keypad.Enter the Serial Number Sequential mode by pressing ✱ 83. Thefollowing prompt will be displayed.

Program Tool?0 = No, 1 = Yes 0

2. If using a program tool, enter "1." If not using a tool, enter "0." If a toolhas already been programmed, this prompt will not appear. If eithernot using a tool or one has already been programmed, skip to step 4.

00 Input S/N:      L Ax x x-x x x x

3. If "1" is entered, the system will prompt for the transmitter’s serialnumber. Enter the program tool’s serial number using one of thefollowing methods:a) Enter the 7-digit serial number printed on the transmitter

orb) Press any button on the transmitter. The keypad should beep

twice and display the serial number of the tool.

00 Input S/N:     L A123-4567   3

In this example, the serial number is A123-4567. Once enrolled, theupper left-hand button of the program tool can be pressed to ready thesystem for enrolling a transmitter into the system.The serial number for the program tool will only remain in thesystem until the programming mode is exited. (Entering ✱97 willnot delete the tool.)Press [✱] to continue.

Note that pressing the [#] key on the keypad will cause the system toback up to the "Program Tool ?" prompt.

Ente r Zn Num.(0 0 = Q u it) 1 0

Zone Number Entered ↑

4. Enter the first zone number to be enrolled (e.g., zone 10).Press [✱] to continue.

The system will, starting with this zone number, search for the firsttransmitter which has all of the following attributes pre-programmed inZone Programming:a) An input type of RF, UR, or BR programmedb) A loop number programmedc) No serial number programmed

If the first zone number entered does not have one or more of the aboveattributes, the system will search its database for the first zone that doesand will display it on the next screen.

Page 72: ADEMCO N7225V2B

14 –2

10 Input S/N:        L Axxx xxxx

5. This prompt is displayed when the system has found the next zonewhich needs to be enrolled.The system will respond to the first serial number transmitted. A serialnumber may be enrolled by one of two methods:

a) Enter the 7 digit serial number printed on the transmitteror

b) Activate the transmitter by faulting or restoring the input you wish touse for that zone (e.g., press a button, open or close a door, etc.).

If you do not wish to enroll the zone displayed, press the [#] key on thekeypad or the upper right-hand button on the program tool (a long beepwill be heard to verify). The following prompt will appear:

10 Learn S/N?0 = No, 1 = Yes 0

To learn now, enter "1" (Yes). If "0" (No) is entered, the following promptwill appear if a program tool has already been programmed:

Ente r Zn Num.(0 0 = Q u it)       1 2

   Zone Number Entered ↑

Enter the next zone number to be enrolled (e.g., zone 12). The systemwill search for that zone and will display the prompt shown in thebeginning of step 5. If you wish to exit the Sequential mode completely,enter 00 and press [✱ ].

10 Input S/N:         L A 022-4064    3

Serial #↑ Loop #↑

The system will enroll the serial number of the first transmitter heard, addthe loop number entered to this serial number, display the serial and loopnumbers, and cause the keypad to beep twice.

If the serial and loop number combination is already present in thesystem, a single long beep will be heard from the keypad. If this happens,the system will not display the serial number, but will wait for atransmission from another transmitter or transmitter loop input.

6. The system will then enter a confirmation mode so that the operationof the actual programmed input can be confirmed. Activate the loopinput or button that corresponds to this zone. We recommend thatyou confirm the programming of every transmitter beforeproceeding to the next zone.

10 Confirmed A022-4064      3

When the system sees activity on the appropriate input, it will beepthree times and display the confirmation message. Press [✱] or theupper left-hand button of the program tool when you are ready to enrollthe next transmitter.

At any time during this step, you may press the [✱] key on the keypad orthe upper left-hand button of the program tool if you are satisfied with theserial and loop number combination that has been enrolled, regardless ofwhether or not the enrolled input has been "confirmed." This will readythe system to enroll the next transmitter.

If the incorrect transmitter has been enrolled, press the [#] key on thekeypad or the upper right-hand button of the program tool to delete theserial number and return to the "LEARN S/N?" prompt. A single longbeep will be heard from the keypad to verify pressing of the upper right-hand button. Then, press "1" (Yes) or press the upper left-hand button ofthe program tool (a single short beep will verify the system is ready forenrolling) and re-activate the proper transmitter or transmitter loop input.

Page 73: ADEMCO N7225V2B

14 –3

7. The system will search for the next zone that does not have a serialnumber associated with it. If one is found, the prompt in step 5, alongwith the appropriate zone number, will be displayed. Follow steps 5and 6 for the remaining wireless zones.

If you are enrolling transmitters which have already been physicallyinstalled, move to the location of the transmitter to be enrolled beforepressing the upper left-hand button of the program tool. Press the buttonand then immediately activate the transmitter to be enrolled. This willminimize the possibility of the system accepting a random transmissioninstead of one from the intended transmitter.

Ente r Zn Num.(0 0 = Q u it) 1 5

8. After all wireless zones have been displayed, whether enrolled or not,the "Enter Zn Num." prompt will appear.

Enter "00" to exit the Sequential mode and return to the data fieldprogramming mode.

When you have finished programming all zones, test each using thesystem's TEST mode (see TESTING THE SYSTEM section).Do not use the Transmitter ID Sniffer mode for testing, as it will onlycheck for transmission of one zone on a particular transmitter, andNOT the zones assigned to each additional loop.

Page 74: ADEMCO N7225V2B

14 –4

Page 75: ADEMCO N7225V2B

15 –1

Section 15. SYSTEM COMMUNICATIONThis section provides an explanation of formats this system accommodates forreporting alarms and other system conditions to the central station. Theprocess of a successful transmission consists of both the method ofcommunication between the control panel and the central station receiver andthe actual way the information is sent and displayed at the central station.

Report Code FormatsWhen the panel calls the central station receiver, it waits to hear a“handshake” frequency from the receiver to confirm that the receiver is on-lineand ready to receive its message. Once the panel hears the handshake it isprogrammed to listen for, it sends its message. The panel then waits for a“kissoff” frequency from the receiver acknowledging that the message wasreceived and understood.

If the handshake frequency is not given or is not understood by the panel, thepanel will not send its message. Once the handshake frequency is receivedand understood by the panel, the panel will send its message. If there is anerror in the transmission (the receiver does not receive a “valid” message), thekissoff frequency will not be given by the central station receiver.The panel will make a total of eight attempts to the primary telephone numberand eight attempts to the secondary telephone number (if programmed) to geta valid message through. If the panel is not successful after its numerousattempts, the keypad will display “Communication Failure” (Alpha keypad) or“FC” (Fixed-word keypad).

The following chart defines the three sets of (handshake/kissoff) frequenciesthat the panel supports and the different formats that can be sent for each.

FORMAT HANDSHAKE TRANSMITS DATA KISSOFF TRANSMIT TIME

Low Speed 1400Hz 1900Hz (10PPS) 1400Hz Under 15 secs.3+1 (Standard report)4+14+2

Sescoa/Rad 2300Hz 1800Hz (20PPS) 2300Hz Under 10 secs.3+1 (Standard report)4+14+2

Express 1400–2300Hz DTMF (10 cps) 1400Hz Under 3 secs.4+2

Contact ID 1400–2300Hz DTMF (10 cps) 1400Hz Under 3 secs.

The following describes each format in greater detail.

3+1 and 4+1 Standard Formats Comprise a 3- (or 4-) digit subscriber number and a single digitreport code (e.g. Alarm, Trouble, Restore, Open, Close, etc.).

3+1 and 4+1 Expanded Formats Comprise a 3- (or 4-) digit subscriber number, and a two-digit re-port code. The first digit is displayed on the first line, followed bya second line where the first digit is repeated 3 (or 4) times andfollowed by the second digit. This is the “expanded” digit.

4+2 Format Comprises a 4-digit subscriber number and 2-digit report code.

Ademco Contact ID Comprises a 4-digit subscriber number, 1-digit event qualifierReporting Format ("new" or "restore"), 3-digit event code, and 3-digit zone number,

user number, or system status number (see the following page).

Page 76: ADEMCO N7225V2B

15 –2

3+1/4+1 3+1/4+1Report Standard Expanded 4+2

Alarm SSS(S) A SSS(S) A SSSS AZAAA(A) Z

Trouble SSS(S) T SSS(S) T SSSS TtTTT(T) t

Bypass SSS(S) B SSS(S) B SSSS BbBBB(B) b

AC Loss SSS(S) E SSS(S) E SSSS EACEEE(E) AC

Low Batt SSS(S) L SSS(S) L SSSS LLBLLL(L) LB

Open SSS(S) O SSS(S) O SSSS OUOOO(O) U

Close SSS(S) C SSS(S) C SSSS CUCCC(C) U

Test SSS(S) G SSS(S) G SSSS GgGGG(G)g

Restore SSS(S) R SSS(S) R SSSS RZAlarm RRR(R) ZAC Restore SSS(S) RA SSS(S) RA SSSSRA Ac

RARARA(RA)AcLoBat Res. SSS(S) RL SSS(S) RL SSSS RLLB

RLRLRL(RL)LBTrouble Res. SSS(S) RT SSS(S) RT SSSS RTt

RTRTRT (RT)t

Bypass Res. SSS(S) RB SSS(S) RB SSSS RBbRBRBRB (RB)b

Where:

Where:SSS or SSSS =  Subscriber ID C = Close Code–1st Digit

A = Alarm Code–1st digit U = User Number (in hex)Z = Typically Zone Number*–2nd digit Gg = Test Code (1st & 2nd digits)

T t = Trouble Code (1st & 2nd digits) R = Restore Code (Alarm)Bb = Bypass Code (1st & 2nd digits) R T t = Restore Code (Trbl)1st & 2nd digits

EAC = AC Loss Code (1st & 2nd digits) R Bb = Restore Code (Byps)1st & 2nd digits

LLB = Low Battery Code(1st & 2nd digits) R AAC = Restore Code (AC)1st & 2nd digits

O = Open Code–1st Digit R LLB = Restore Code (Bat)1st & 2nd digits

*Zone numbers for: [✱] & [#], or [B] = 99 [1] + [✱], or [A] = 95 Duress = 8[3] + [#], or [C] = 96 Tamper = 9

Ademco Contact ID Reporting takes the following format:

CCCC Q EEE GG ZZZ

where: CCCC = Customer (subscriber) IDQ = Event qualifier, where:

E = new event , and R = restoreEEE = Event code (3 hexadecimal digits)

Note: For a complete list of event codes, refer to thecentral office receiver manual.

GG = Always 00.ZZZ = Zone/contact ID number reporting the alarm, or user

number for open/close reports. System statusmessages (AC Loss, Walk Test, etc.) contain zeroesin the ZZZ location.

Page 77: ADEMCO N7225V2B

15 –3

TABLE OF CONTACT ID EVENT CODES

Code Definition110 Fire Alarm121 Duress122 Alarm, 24-hour Silent123 Alarm, 24-hour Audible Panic131 Alarm, Perimeter, Burg.132 Alarm, Interior, Burg.134 Alarm, Entry/Exit, Burg.135 Alarm, Day/Night, Burg.150 Alarm, 24 Hour Auxiliary301 AC Power302 Low System Battery/Battery Test Fail333 Expansion Module Fail353 Long Range Radio Trouble373 Fire Loop Trouble

Code Definition374 Exit Error Alarm380 Trouble (Global)383 RF Sensor Tamper384 RF Sensor Low Battery401 O/C by User406 Cancel by User407 Remote Arm/Disarm (Download)408 Quick Arm AWAY/MAX441 Armed STAY/INSTANT, Quick Arm

STAY/INSTANT570 Bypass601 Test, Manually Triggered602 Periodic Test606 AAV to follow

Communication ProgrammingIntroduction This section provides instructions for programming those fields that affect

communications between the control and the central station.

ProgrammingProcedure

1. With at least one Alpha keypad (5137AD or 6139) connected to thesystem, power up the system. If necessary, refer to the FINALPOWER UP section for the power-up procedure. If you had previouslyconnected the AC transformer to the control panel, you need only plugin the transformer (to 120VAC outlet) to power up the system.

2. Enter the programming mode by keying the following on the Alphakeypad: Installer code (4 1 1 1) + 8 + 0.

Fields ✱40, ✱41, ✱42:Enter up to the numberof digits shown. Do notfill unused spaces.

Enter 0–9,# + 11 for ‘✱’# + 12 for ‘#’

# + 13 for a pause(2 secs)

Press ✱40 PABX ACCESS CODEEnter up to 4 digits if PABX is needed to access an outside line.If fewer than 4 digits are needed to be entered, exit by pressing[✱] and next field number (e.g., 41). To clear entries from field,press ✱40✱.

Press ✱41 PRIMARY PHONE No .Enter up to 12 digits. If fewer than 12 digits entered, exit bypressing [✱] and next field number (e.g., 42). To clear entriesfrom field, press ✱41✱.

Press ✱42 SECONDARY PHONE No.Enter up to 12 digits. If fewer than 12 digits entered, exit bypressing [✱] and next field number (e.g., 43). To clear entriesfrom field, press ✱42✱. If using the Paging feature, enter thepager number as the secondary phone number.

Press ✱ 43 SUBSCRIBER ACCOUNT. No.Field ✱43 is alsoused as the LongRange RadioSubscriber AccountNumber

Central Station Account Number).Enter 0–9; # + 11 for B; # + 12 for C; # + 13 for D; # + 14 for E; # + 15 for F(default).Enter ✱ as the fourth digit if a 3-digit account number (for 3+1 dialer reportingformat) is used. Enter 0 as the first digit of a 4-digit account number for Nos.0000–0999. End field by pressing ✱ (and press next field).

See the blank Programming Form in the separate Programming Guide forexamples of Account No. entries.

Page 78: ADEMCO N7225V2B

15–4

Press ✱ 45 PHONE SYSTEM SELECT    Enter 1 digit (default = 0)If Central Station Receiver is not on WATS line:0 = Pulse Dial, 1 = Tone Dial.If Central Station Receiver is on WATS line:2 = Pulse Dial, 3 = Tone Dial.

Press ✱46 REPORT FORMAT, PRIMARY/SECONDARYDetermines which format is to be used to report to the centralstation.0 = 3+1; 4+1 ADEMCO Lo Speed Standard (this is the default)1 = 3+1; 4+1 Radionics Standard2 = 4+2 ADEMCO Lo Speed Standard3 = 4+2 Radionics Standard6 = 4+2 ADEMCO Express7 = ADEMCO Contact ID Reporting8 = 3+1; 4+1 ADEMCO Lo Speed Expanded9 = 3+1; 4+1 Radionics Expanded(Enter ✱ as the 4th digit of ✱ 43 if 3+1 dialer report ing is to beused.)

Note: The maximum number of alarm and alarm restore reportsduring one armed period is determined by field ✱92.

Press ✱ 47 SPLIT/DUAL REPORTINGEnter 0 to disable (Backup report only). This is the default.

* Can only be used ifPrimary reporting formatis Ademco Contact ID.If reporting to Pager,choose from 6, 7, 8, or 9,as desired.

TO PRIMARY PHONE No. TO SECONDARY PHONE No.

 1 = Alarms, Restore, Cancel Other Reports

  2 = All except Open/Close, Test Open/Close, Test

  3 = Alarms, Restore, Cancel All reports

 4 = All except Open/Close, Test All reports

  5 = All reports All reports

TO PRIMARY PHONE # TO PAGING NUMBER *

  6 = All reports except Open/Close Alarms, Open/Close, Troubles

  7 = All reports Alarms, Troubles

  8 = All reports Alarms, Open/Close, Troubles

 9 = All reports except Open/Close Alarms, Open/Close for UserNos. 5–25‡, Troubles

‡ Will report only Users 5–8. If using wireless button-type devices, the zone    number of the arm or disarm button (10–25) will be sent as the user number.

Entries 6 through 9 will send a report to a pager (in addition to the selectedprimary phone number), but you must enter the pager number as thesecondary phone number in field ✱42.

A 10-digit code is sent to the pager which will take the following format:† 4-digit Subscriber No. →  SSSS–EEE–NNN  ← 3-digit User or Zone No. (as entered in field ✱43)

  ↑3-Digit Event Code, as follows:

911 = Alarm (NNN = Zone No.)001 = Open, System disarmed (NNN = User No.)002 = Close, System armed ( NNN = User No.)811 = Trouble ( NNN = Zone No.)

† The first digit of the Subscriber No. entered in field ✱ 43 must be 1–9 (DO NOT    USE “0”); the last 3 digits can be 0–9. Failure to observe this requirement may    interfere with paging services.

Page 79: ADEMCO N7225V2B

15–5

Example 1.   Pager displays:   1 2 3 4 – 9 1 1 – 0 0 4  This indicates that Subscriber No. 1234’s system is reporting an Alarm (911),due to zone 4 being faulted (004).

Example 2.   Pager displays:  1 2 3 4 – 0 0 1 – 0 0 5This indicates that Subscriber No. 1234’s system is reporting an opening (001)by User 5 (005).Note that no restore reports are sent to the pager.

Important: Do not use AAV when Paging or Alarm Reports are being sent toa Secondary number. If this is done, the call to the Secondary number by thecommunicator after the alarm report will prevent the AAV from taking controlof the phone line, and the AAV “Listen in” session cannot take place.

Press ✱48 15-SECOND DIALER DELAY, BURGLARYEnter 0 for no, or 1 for yes. Default is 0 (no delay).

Press ✱49 PERIODIC TEST REPORTSelect the desired test report interval.0 = none; 1 = 24 hours; 2 = weekly; 3 = 30 days. Default is 0(none).  Test Report Code entered in field ✱ 64 is sent.Reports with Subscriber No.

Press ✱50 SESCOA/RADIONICS SELECT0 = Radionics (0–9, B–F reporting)1 = SESCOA (0–9 only reporting)Select 0 for all other formats. Default is 0.

TO PROGRAM SYSTEMSTATUS AND

RESTORE REPORTCODES

(✱60 – ✱68, ✱70 – ✱75)

With a 3+1 or 4+1 Standard Format: Enter a code in the first digit box:1–9, 0, B, C, D, E, or F. Enter "# + 10" for 0, "# + 11" for B, "# + 12" for C,"# + 13" for D, "# + 14" for E, "# + 15" for F.

A "0" (not "# + 10") in the first digit box will disable a report.A "0" (not "# + 10") in the second digit box (if any) will result in automaticadvance to the next field when programming.

With an Expanded or 4+2 Format: Enter codes in both boxes (1st and 2nddigits) for 1–9, 0, or B–F, as described above.

A "0" (not "# + 10") in the second box will eliminate the expanded messagefor that report.A "0" (not "# + 10") in both boxes will disable the report.

With Ademco Contact ID Reporting: Enter any digit (other than "0") in thefirst box, to enable zone to report This is an "enabling" code only and isdisregarded in the actual reporting to the central office. Entries in the secondboxes will be ignored.

A "0" (not "# + 10") in the first box will disable the report.Examples:For Code 3 (Single Digit), enter:     3         0    

For Code 32 (Two Digits), enter:     3         2    

For Code B2 (Hexadecimal) enter: # +  11      2    

Press ✱60 TROUBLE REPORT CODEThis will be sent if a zone goes into trouble.

Press ✱61 BYPASS REPORT CODEThis will be sent when a zone is manually bypassed.

Page 80: ADEMCO N7225V2B

15–6

Press ✱62 AC LOSS REPORT CODEReports with Subscriber No. Timing of this report is random withup to a 48-minute delay. The Restore report has a random delayof up to about 12 minutes. If AC restores before the report goesout, there is no AC restore report.

Press ✱63 LOW BAT REPORT CODEThis will be sent when a low battery condition exists in thesystem’s standby battery (connection to the standby battery ischecked every 3 minutes (CSFM requirement)).

Press ✱64 TEST REPORT CODEThis is sent periodically to test that the communicator and phonelines are operational (frequency of report is selected in field ✱51).

Press ✱65 OPEN/EXIT ALARM REPORT CODE, 1st DIGITSOpen Report Code : To enable, enter a code (or 0 to disable) inthe left-hand box.For expanded or 4+2 reporting, 2nd digit = User #.Exit Alarm Report Code: To enable, enter a code (or 0 todisable) in the right-hand box. If enabled, any alarm from anexit or interior zone occurring within two minutes after theend of the exit delay will send a special message indicating exitalarm to the central station, and a zone indication and "ExitAlarm" or "EA" is displayed on the keypad.If an exit or interior zone contains a fault as the exit delayends, the local bell and keypad sound continuously.a) If the subscriber then disarms the system before the ensuingENTRY delay ends, no message is transmitted to the centralstation, but a zone indication and "Canceled Alarm" or "CA" isdisplayed on the keypad.b) If the system is not disarmed before that entry delay ends, aspecial message indicating Exit Alarm is sent to the centralstation and a zone indication and "Exit Alarm" or "EA" is displayedon the keypad.For expanded or 4+2 reporting, a 2nd digit is sent, and is thesame as the 2nd digit of the zone alarm report code programmedin field ✱56.For Contact ID reporting, Event code 374 and the zone number issent.There is no restore message for an Exit Alarm report.

Press ✱66 ARM AWAY/STAY REPORT CODES  This option allows for independent programming of AWAY andSTAY reports . 2nd digit of Report is User No., if expanded or 4+2reporting is selected.

Press ✱67 RF XMTR. LOW BATTERY REPORT CODEThis is sent in the event that a wireless transmitter low batterycondition exists.

Press ✱68 CANCEL REPORT CODEThis is sent upon disarming of the system after an alarm conditionwas reported.

Press ✱70 ALARM RESTORE REPORT CODE, 1st DIGITThis is sent when the zone that caused an alarm is restored to itsnon-faulted condition. 2nd digit is automatically sent as the 2nddigit of the zone alarm report code programmed in field ✱56, ifexpanded or 4+2 reporting is selected.

Press ✱71 TROUBLE RESTORE REPORT CODE

This is sent when a trouble in a zone is restored.

Press ✱72 BYPASS RESTORE REPORT CODE

This is sent when a zone that has been bypassed is un-bypassed.

Page 81: ADEMCO N7225V2B

15–7

Press ✱73 AC RESTORE REPORT CODEThis is sent when AC power has been restored after an AC poweroutage.

Press ✱74 LOW BAT RESTORE REPORT CODEThis is sent when a system low battery condition is restored tonormal.

Press ✱75 RF XMTR. LOW BATTERY RESTORE CODEThis is sent when a transmitter that previously sent in a low batterymessage has sent a message indicating it no longer has a lowbattery condition.

Press ✱92 NUMBER OF REPORTS IN ARMED PERIODThis option can be used to limit the number of messages (alarm &alarm restore reports) sent to the central station in an armedperiod. “0” limits reports to a total of 10; “1” allows an unlimitednumber of reports.

Press ✱94 DOWNLOAD PHONE NUMBEREnter up to 12 digits;0–9, # + 11 for “✱ ”, # + 12 for “#”, # + 13 for a pause. Do not fillunused spaces. End field by entering “✱ ”. To clear entries, press✱94✱.

Press ✱95 RING DETECTION COUNT FOR DOWNLOADINGRefer to the chart below and program this field accordingly.

Voice Answering Module   Machine Downloading Field ✱95 Programming

Yes No No Set for value other than “0” (1–14). This will enable the control panel to answer the phone call. Otherwise, it will not be possible to access the module.

Yes Yes No Set for a value higher than the number of rings for which the answering machine is set. Example: if machine is set for 4 rings, use value 5 or higher. This is recommended so that the Phone module can still be accessed if the answering machine is turned off and does not answer the phone call.

Yes No Yes Set for value other than “0” (1–14).

Yes Yes Yes “15” to bypass answering machine.

No No No Enter “0”

No Yes No Enter “0”

No No Yes Enter 1–14

No Yes Yes Enter 15. See Imortant Note below.

Important Note: If “15” is entered in field ✱95 to bypass an answering machine, and a4285 Phone Module is included in the installation, you should note the following:When calling in from an off-premises phone (to receive a status report or execute acommand), the user should make the initial call, allow 1 to 3 rings only, and hang up.Then call in again – the Phone Module will now seize the line, and 2 long tones willheard, followed by the usual voice prompt for the 2-digit phone access code. If thisprocedure is not followed, Phone Module operation will not be possible.

✱96 INITIALIZE DOWNLOAD ID AND SUBSCRIBER ACCT. No. FORDOWNLOADING (No data entry required)

This completes the communication programming.

Exit the programming mode by keying ✱99.

Refer to the TESTING THE SYSTEM section to check system operation.

Page 82: ADEMCO N7225V2B
Page 83: ADEMCO N7225V2B

16 –1

Section 16. TESTING THE SYSTEM

Test ProcedureAfter installation is completed, the System should be carefully tested, as follows:

1. With the System in the disarmed state, check that all zones are intact. If aNOT READY message is displayed, press the [✱] key to display the faultedzone(s). Restore faulted zone(s) if necessary, so that the READY message isdisplayed.

2. Enter the security code and press the TEST key.The external sounder will sound for 1 second. If the backup battery isdischarged or missing, the sounder may not turn on and a LOW BATTERYreport will be transmitted with a TEST report.Note that the keypad will beep once every 40 seconds as a reminder that thesystem is in the Test Mode.

3, Fault and restore every sensor individually to assure that it is being monitored

by the system. Each time a protection zone is faulted, the keypad will sound 3

beeps, and the identification of each faulted protection zone should appear on

the keypad display.Note: For 5800 wireless systems, triggering a zone set to Arm–Away, Arm–

Stay, or Disarm will take the system out of the TEST mode and causethat action.

4. Walk in front of any interior motion detectors (if used) and listen for therequired sound as movement is detected. The identification of the detectorshould appear on the display when it is activated.Note: Wireless motion detectors (Passive Infrared units) will send signals out

only if they have been inactive for 3 minutes.

5. Follow the manufacturer's instructions to test all smoke detectors, to ensurethat all are functioning properly. The identification of each detector shouldappear on the display when each is activated.

6 Turn off the test mode by entering the security code and pressing the OFF key.

Alarm messages will be sent to the Central Station during the following tests.Notify them in advance that tests will be in progress.

7. Arm the system (STAY) and fault one or more perimeter zones. After 15seconds, silence alarm sounder(s) by entering the security code and pressingOFF .Arm the system AWAY, and check the Entry/Exit zones for the programmedexit and entry delays.

8. Check the keypad-initiated alarms that are in the system by using the Panickeys (or key pairs on some keypads). If a key (or key pair) has beenprogrammed for audible emergency, the keypad will emit a steady alarmsound, and ALARM and zone number will be displayed.If a key (or key pair) has been programmed for silent emergency, there will beno audible alarms or displays, but a report will be sent to the Central Station.If a key (or key pair) has been programmed for Fire, the keypad and externalsounder will emit an interrupted alarm sound, and ALARM, FIRE, and zonenumber will be displayed.Silence alarms by entering the security code and pressing OFF.

9. If Output Relay Units have been installed, test their programmed action.

10. Notify the Central Station when all tests are finished, and verify results withthem.

(Continued)

Page 84: ADEMCO N7225V2B

16 –2

To test the wireless part of the system and the RF Receiver, perform the twofollowing tests: Transmitter Sniffer Mode and Go/NoGo Test Mode .

TRANSMITTER SNIFFER MODEMake sure the system is disarmed before trying to enter this mode.Key Installer code + # + 3. This initiates a procedure that will check thatall 5700 series transmitters have been properly programmed.Note: If the communicator is in the process of sending a report to the

Central Station, the system will not go into the Sniffer mode. If so,wait a few minutes, and try again.

The keypad will display all zone numbers of wireless units programmedinto the system. As the system receives a signal from each of thetransmitters, the zone number of that transmitter will disappear from thedisplay. The transmitter codes may be checked upon installation, or in aninstalled system.All the wireless zone numbers should disappear after about 1-1/2 hours.Note: Any transmitter that is not properly entered into the system will not

turn off its zone number.

Exit the Transmitter Sniffer mode by keying Installer code + OFF.

GO/NO GO TEST MODEBy keying Installer code + # + 4 , a mode similar to the test mode isentered, but the wireless receiver gain is reduced. Checking in this modenot only assists in determining good mounting locations for the transmitterswhen the system is being installed, but also verifies that the RFtransmission has sufficient signal amplitude margin for the installedsystem.

1. Enter the Installer Code + # + 4

2. Once transmitters are placed in their desired locations and theapproximate length of wire to be run to sensors is connected to thetransmitter's screw terminals, fault each transmitter. Do not conduct thistest with your hand wrapped around the transmitter as this will causeinaccurate results.• The keypad will beep three times to indicate signal reception.• If the keypad does not beep, re-orient or move the transmitter to

another location. Usually a few inches in either direction is all that isrequired.

3. Exit the G0/NoGo mode by keying Installer code + OFF.

TO THE INSTALLERRegular maintenance and inspection (at least annually) by the installer and frequent testing bythe user are vital to continuous satisfactory operation of any alarm system.The installer should assume the responsibility of developing and offering a regularmaintenance program to the user as well as acquainting the user with the proper operation andlimitations of the alarm system and its component parts. Recommendations must be includedfor a specific program of frequent testing (at least weekly) to insure the system's proper opera-tion at all times.

Page 85: ADEMCO N7225V2B

17 –1

Section 17. SYSTEM OPERATIONSecurity Codes

Installer Code The installer programs the 4-digit Installer Code initially as part of theprogramming procedure. The factory default Installer code is "4-1-1-1", butmay be changed in field ✱20. Note: The Installer Code is defined as User #1.The Installer code is the only code that can allow re-entry into programmingmode. In normal operation mode, only the Master code can be used to enterthe User codes (refer to Assigning the Master Code).See MECHANICS OF PROGRAMMING section in the PROGRAMMINGGUIDE manual for details on exiting the programming mode via ✱98 or ✱99.

Assigning theMaster Code

In normal operation mode, assign the 4-digit Master Code as follows:

  Installer Code + 8 + 2 + 4-digit Master Code

Note: The Master Code is defined as User #2.

Changing theMaster Code

In normal operation mode, the Master code can be changed by entering:

  Master Code + 8 + 2 + New Master Code + New Master Code again

User Codes In normal operation mode, the Master security code can be used to assign upto 4 secondary 4-digit security codes. It can also be used to remove sec-ondary codes from the system (individually).

To assign (or change) a Secondary security code, enter (via keypad):

Master Code + [CODE key] + User # (3–6) + desired 4-digit Secondary Code

The system will emit a single beep when each secondary code has been suc-cessfully entered.

To delete a Secondary security code, enter (via keypad):

Master Code + [CODE key] + User # (3–6)

Notes: • All Master and Secondary security codes permit access to the system forarming, disarming, etc.

• If a secondary code is inadvertently repeated for different users, the loweruser number will take priority.

• Opening and closing reports are sent for the Master code as No. 02, withthe appropriate subscriber number. Secondary user codes are sent as Nos.3 through 6 respectively, with the appropriate subscriber number.

Duress Code

Important: This code isuseful only when thesystem is connected to acentral station.

This feature is intended for use when you are forced to disarm or arm thesystem under threat. When used, the system will act normally, but can silentlynotify the central station of your situation, if that service has been provided.The Duress code may be any 4-digit code assigned to User Number 8.To program a Duress code:1. Enter Master Code.2. Press the CODE [8] key.3. Press the [8] key again (8 = Duress code User No.).4. Enter the desired 4-digit Duress Code. The keypad will beep once.

Note: The Duress code must differ from the Master Code or any otherUser’s Code.

To change the Duress code:Repeat steps 1, 2, and 3, and then step 4 with the new Duress Code.

To delete the Duress code:Perform steps 1, 2, and 3, and then stop. When the keypad beeps once itsignifies that the code has been deleted.

Page 86: ADEMCO N7225V2B

17 –2

Keypad Functions

GeneralInformation

Note that if you enabled QUICK ARM (field ✱21), the [#] key can be pressedinstead of entering the security code, for any of the arming procedures (Away,Stay, Instant, Maximum, etc.). The security code is always required, however,when disarming the system.NOTE: The “Quick Arm” feature will function only if the Master Code has beenprogrammed (see Assigning the Master Code on the previous page).

The keypad allows the user to arm and disarm the system, and perform othersystem functions, such as bypassing zones, and display zone descriptors.Zone and system conditions (alarm, trouble, bypass) are displayed in theDisplay Window.When an alarm occurs, keypad sounding and external sounding will occur, andthe zone(s) in alarm will be displayed on the keypad. Pressing any key willsilence the keypad sounder for 10 seconds. Disarming the system will silenceboth keypad and external sounders. When the system is disarmed, any zonesthat were in an alarm condition during the armed period will be displayed(memory of alarm). To clear this display, simply repeat the disarm sequence(enter the security code and press the OFF key) again.The keypads also feature chime annunciation, and 3 panic key pairs, orindividual panic keys (depending on keypad type – see Panic Keys on nextpage), for silent, audible, fire or personal emergency alarms. These keys cannotify the central station of an alarm condition, if that service is connected.

Arming Functions The following is a brief list of system commands. For detailed informationconcerning system functions, refer to the User's Manual.Disarmed, Not Ready ........... Before arming, the system must be in the

READY condition (all zones must be intact). Ifthe "NOT READY" message appears, press theREADY [✱ ] key to display faulted zones.

Arming Away ........................ Enter code + AWAY [2].

Arming Stay .......................... Enter code + STAY [3].

Arming Instant ...................... Enter code + INSTANT [7].

Arming Maximum ................. Enter code + MAXIMUM [4].

Quick Arming ....................... Simply press [#] key in place of code, then press    (if enabled) ......................... AWAY, STAY, INSTANT, or MAXIMUM to arm

system as desired. Note that the [#] key cannotbe used in place of code when disarming thesystem.

Disarming ............................. Enter code + OFF [1].

Bypassing Zones ................. Enter code + BYPASS [6] + zone number(s).

Forced (Quick) Bypass ........ To automatically bypass all faulted zones, use      (if enabled) ........................ the "Quick Bypass" method:

Enter code + BYPASS, then wait for all openzones to be displayed. Arm when displayindicates “Bypass” and “Ready to Arm”.

Chime Mode .......................... Enter code + CHIME [9].To turn chime off, enter code + CHIME again.

SUMMARY OF ARMING MODES

Features for Each Arming ModeArmingMode

ExitDelay

EntryDelay

PerimeterArmed

InteriorArmed

AWAY Yes Yes Yes YesSTAY Yes Yes Yes No

INSTANT Yes No Yes NoMAXIMUM Yes No Yes Yes

Page 87: ADEMCO N7225V2B

17 –3

Panic Keys There are three individual panic keys or, on some keypads, panic key pairs. Ifprogrammed, they can be used to manually initiate alarms and send a reportto the central station.Each key (or key pair) can be individually programmed for 24-hour Silent,Audible, Personal or Fire Emergency responses. The panic function isactivated when both keys of the appropriate key pair are pressed at the sametime, or the appropriate lettered key is pressed for at least 2 seconds.

1 2 3A

4 5 6B

7 8 9C

* 0 #D

OFF AWAY STAY

MAX TEST BYPASS

INSTANT CODE CHIME

READY

READYARMED

PANIC

A

B

C

D

Shown on the left is a typicalkeypad with individual Panickeys (shown lettered).

The panic functions are identified by the system as follows:

      Keys Displayed as Zone

[A], or [1] & [✱] 95

[B], or [✱] & [#] 7

[C], or [3] & [#] 96

Notes:• Keys [A], [B], [C] are not on all

keypads.• Key [D], if present, is not active

here.

Important:  For the Silent Panic functions to be of practical value, the systemmust be connected to a central station.

4285 Phone module(if used)

Refer to the separate instructions supplied with the Phone module forinformation concerning its operating procedures.

Note: The Phone module cannot be used to add user codes in this system.User codes must be added by using a wired keypad.

Relay Outputs(if used)

If relay outputs are used, two keypad entries available to the user are includedamong the system operation choices (34 and 35) that may be programmed(see the RELAY OUTPUTS section). They can manually activate or de-activate the relay(s) for starting or stopping some action, such as turning lightson or off, etc.

These keypad entries are: Security Code + [#] + [7]and Security Code + [#] + [8]

Note: Whichever entry is used to start/stop the action cannot also be usedto stop/start it. The opposite action must either be performed by theother keypad entry or by some other event or operation offered in theprogramming section.

Exit Alarm Displays

(if programmed)

• A display of "CANCELED ALARM" or "CA" and a zone indication willappear if an exit or interior zone contained a fault during closing at the timethe exit delay ended (e.g., exit door left open), but the system wasdisarmed during the entry delay time. The alarm sounder and keypadsound continuously, but stop when the system is disarmed. No messagewill be transmitted to the central station.

• A display of "EXIT ALARM" or "EA" and a zone indication will appear if anexit or interior zone contained a fault during closing at the time the exitdelay ended, but the system was NOT disarmed during the entry delaytime. The alarm sounder and keypad sound continuously until the system isdisarmed (or timeout occurs). An "exit alarm" message is sent to the centralstation. (Continued)

Page 88: ADEMCO N7225V2B

17 –4

• The "EXIT ALARM" display, etc. will also result if an alarm from an exit orinterior zone occurs within two minutes after the end of an exit delay.

In any of the previous cases, use a second OFF sequence (code plus OFFkey) to clear the display.

Trouble Conditions (See Troubleshooting Guide also)

General Information

The word "CHECK" on the keypad's display, accompanied by a rapid"beeping" at the keypad, indicates that there is a trouble condition in thesystem. The audible warning sound can be silenced by pressing any key.Instruct users to call for service immediately upon seeing any of the followingmessages.

"Check" and"Battery"Displays

• A display of "CHECK" and one or more zone numbers indicates that aproblem exists with the displayed zone(s) and requires attention.

• A display of “CHECK ” and 09 indicates that communication between controland a zone expander or wireless receiver is interrupted. Check the wiringand DIP switch settings on the units.

• If there are wireless sensors in the system, the CHECK condition mayalso be caused by some change in the environment that prevents thereceiver from receiving signals from a particular sensor.

• A display of "BAT" (Fixed-word keypads) or “SYSTEM LO BAT” (Alphakeypads) with no zone number indicates that the system's main standbybattery is weak.

• A display of "BAT" (Fixed-word keypads) or “LO BAT” (Alpha keypads)with a zone number and a once per minute "beeping" at the keypadindicates that a low battery condition exists in the wireless sensor displayed(zone "00" indicates a wireless keypad). If the battery is not replaced within30 days, a CHECK display may occur.Note: Some wireless sensors contain a non-replaceable long-life batterywhich requires replacement of the entire unit at the end of battery life(e.g., Nos. 5802, 5802CP, 5803).

Power Failure • If there is no keypad display at all, and the POWER indicator (ifpresent) is not lit, operating power for the system has stopped and thesystem is inoperative.Note: The control panel will power up in its previous state (armed or

disarmed) after a complete power failure, but will not retain anymemory of bypasses.

• If the message "AC LOSS" (Alpha keypads) or "NO AC" (Fixed-wordkeypads) is displayed, and the POWER indicator (if present) is off, thekeypad is operating on battery power only.Note: There is a random delay up to 48 minutes before the system willreport an AC failure to the central station. The keypad response is about 6seconds. The restore report has a random delay of up to 12 minutes (if theAC failure report was sent).

• If the battery standby capacity is used up during a prolonged ACpower outage, the control's auxiliary power will shut down to minimizedeep discharge of the battery.

Other Displays(Fixed Word displays

are in parentheses)

Busy-Standby (dI).  If this remains displayed for more than 1 minute, thesystem is disabled.

Modem Comm (CC)  The system is in communication with the central stationfor change of function or status verification.

Comm. Failure (FC)  A communication failure has occurred.

Open Circuit (OC)  The keypad is not receiving signals from the control andsees an open circuit.

Long Rng Trbl (bF)  Back-up LRR communication failure.

Page 89: ADEMCO N7225V2B

18 –1

Section 18. TROUBLESHOOTING GUIDE

SYSTEM (including Wireless)

SYMPTOM POSSIBLE CAUSE REMEDY1. Transmitter signal not

received at 4281/5881.1a. Transmitter or 4281/5881 not properly pow-

ered.1b. If Transmitter is 5827/5827BD, house ID

code not set in field ✱24, or transmitter notset to same house code set in that field.

1c. Transmitter located too for from 4281/5881.1d. Metal shielding between transmitter and

4281/5881.1e. Transmitter malfunctioning.

1f. 4281/5881 malfunctioning.

1g. Transmitter No. (zone) not programmed.1h. 4281/5881 address incorrect.1i. Field ✱22 not set properly.

1a Check or change transmitter's bat tery.Check the control's AC power.

1b. Check code switches inside transmit ter.Must match with RF House Code pro-grammed in control.

1c. Move transmitter or 4281/5881.1d. Check for large metal obstructions, then

relocate transmitter if necessary.1e. Verify by activating 4281/5881 with an-

other, similar transmitter. If O.K. now,return defective transmitter.

1f. Verify by making sure other transmit terscannot activate 4281/5881. If defective,replace and return original 4281/5881.

1g. Verify programming.1h. Set DIP switch for address “0”.1i. Set field ✱22 to “1” for 4281 RF receiver,

or “2” for 5881 RF receiver

2. Transmitter zone numberappears during Go/NoGotest mode, but does notclear.

2a. Transmitter zone type (ZT) is set to 00 (NotUsed).

2b. Transmitter battery not installed.2c. 5700 System transmitter's DIP switch not set

properly (house ID and transmitter ID).2d. 5800 System transmitter serial No. not

entered in system.2e. With 5700 System, no response at all to any

transmitter.

2a. Set ZT to a valid active zone type in field*56.

2b. Install proper battery.2c. Check and set the DIP switch.

2d. Enter unit’s serial No. in field ✱56.

2e. Check 4281 receiver.

3. Low Battery message onkeypad.

3a. "Bat" or “System Lo Bat” (no zone Nos.)3b. "Bat" or “Lo Bat” + "00".3c. "Bat" or “Lo Bat” + "nn".

3a. System battery is low or missing.3b. Remote RF keypad battery is low.3c. Transmitter for zone “nn” has a low

battery.

4. Periodic beep(s) fromkeypad.

4a. System is in TEST mode.4b. A wireless transmitter low battery has

occurred and is displayed.4c. A supervision CHECK has occurred.

4a. Enter "Code" + OFF to exit TEST mode.4b. Enter "Code" + OFF and replace the

battery.4c. Check the wireless transmitter indicated.

Restore communication to the RF receiverto cancel the condition.

5. With 5800 RF System, noresponse to a transmitter innormal operation, althoughzone number clears duringGo/NoGo mode.

Put control in TEST mode. If zone does not re-spond, try operating the tamper switch or anotherinput to the transmitter.5a. If another input causes the zone to be dis-

played, the wrong loop input was enteredwhen programming.

5b. If no response at all from this transmitter, thisphysical transmitter has not been enteredinto the system. Go/NoGo display is beingcleared by another unit programmed for thiszone.

5a. Delete input's serial number (not thezone), and enter the proper loop input(see field *56).

5b. Determine which transmitter is pro-grammed for this zone and reprogram asnecessary.

6. Nuisance or phantom alarm. 6a. Sensors not properly installed, wired, ormonitored.

6b. Universal transmitter (5715/5817) pro -grammed wrong.

6a. Check installation to see if in accordancewith established procedure.

6b. Check programming switches on transmit-ter.

7. Intrusion alarm for no ap-parent reason.

7a. Protected door or window opened whilesystem armed.

7b. Improper user operation of exit/entry delays.

7c. Magnets located too far from switches,and/or doors and windows not properlyaligned.

7a. Check with all occupants of protectedpremises.

7b. Check setting of entry delay . Exit delay is15 seconds longer than the entry delaytime. Remind user of same.

7c. Check all openings for proper switch andmagnet orientation.

(Continued)

Page 90: ADEMCO N7225V2B

18 –2

TROUBLESHOOTING GUIDE (continued)

SYMPTOM POSSIBLE CAUSE REMEDY7. Intrusion alarm for no ap-

parent reason. (continued)7d. Magnetic contacts improperly connected or

wire broken.

7e. Entry door programmed as “Instant”

7f. Loose fitting door or window being rattledby wind or vibrations.

7d. Check wiring connections. Be sure wiresare properly stripped and are tightlyfastened to screw terminals.

7e. Check and revise programming. Re-program transmitter number.

7f Mount magnet closer to magnet.

8. Repeated low battery signal. 8a. Transmitter located where temperaturedrops below 32°F.

8b. Poor quality or unspecified battery intransmitter.

8c. Transmitter malfunctioning.

8a. Change location. Use magnetic contacts toprotect opening.

8b. Check battery. Use only batteries specifiedin the instructions (does not apply totransmitters with non-replaceablebatteries).

8c. Replace faulty transmitter.

9. Local bell and keypad soundcontinuously after arming.

9. Exit or interior zone contained a fault at endof Exit Delay (e.g., Exit door left open).

The "Exit Alarm" display, etc. will alsoresult if an alarm from an exit or interiorzone occurs within two minutes after theend of an exit delay.  →

9a. If system disarmed before ensuing entrytime runs out, "CA" or "Canceled Alarm"will be displayed. Sounding will stop.

9b. If system not disarmed before entry timeends, "EA" or "Exit Alarm" will be displayedand Exit Alarm message will be sent tocentral station. Sounding will continue untilsystem is disarmed or timeout occurs.

Clear display by entering code + OFF a secondtime. Avoid fault when re-arming.

CONTROL

SYMPTOM POSSIBLE CAUSE REMEDY1. "POWER" light off or

“NO AC” displayed1a. Interrupted AC power supply. 1a. Check transformer connection and power

line circuit breaker.

2. Digital communicator mes-sage not being received.

2a. Control in TEST mode.

2b. Telephone connection not secure.

2c. Digital communicator malfunctioning

2d. Telephone number in program needs prefixor access code.

2e. Telephone call to central monitoring stationrequires operator assistance.

2a. Remove from TEST mode.

2b. Check all connections.

2c. Check with a different VIA-30PSE.

2d. Program prefix or access code into thecontrol

2e. System cannot work in this situation.

3. Does not arm properly. 3a. READY light not on. 3a. Check for faulted zone(s) by pressing [ ✱] ;make faulted zone(s) intact, or useBypass arming, if desired.

4. VIA-30PSE doesn't respond tokeystrokes on keypad.

4a. "CC" or "MODEM COMM" displayed.

4b. "d1" or "System Busy" displayed.

4c. "E4" or "E8" displayed.

4d. Keypad address setting incorrect.

4a. System is in communication with down-loader at central station. Wait until down-load session is finished.

4b. System has just been powered and is inits one minute initialization. To bypassthis time, press '#' + '0'.

4c. More zones have been programmed thanthe zone expansion modules can handle.Delete some zones or use a highercapability RF receiver.

4d. Keypads must be set for address 31 (non-addressable mode).

S M O K E D E T E C T O R

SYMPTOM POSSIBLE CAUSE REMEDY1. Detector alarms, no apparent

reason.1a. Dust, dirt in sensing chamber.

1b. Improper location.

1c. Unit malfunctioning.

1a. Clean unit's sensing chamber with vacuumcleaner per unit's instructions.

1b. See unit's instructions for locations toavoid. Relocate as necessary.

1c. Replace detector.

2. Detector's siren sounds. 2a. Unit not receiving required power.

2b. Unit malfunctioning.

2a. Check for proper installation of battery. Trynew battery.

2b. Replace detector.

Page 91: ADEMCO N7225V2B

18 –3

CONTACTING TECHNICAL SUPPORT

PLEASE,

Before you call Technical Support, be sure you:

• READ THE INSTRUCTIONS!

• Check all wiring connections.

• Determine that the power supply and/or backup battery are supplying proper voltages.

• Verify your programming information where applicable.

• Note the proper model number of this product, and the version level (NXXXX number onlarge circuit module in center of control board) along with any documentation that camewith the product.

• Note your ADEMCO customer number and/or company name.

Having this information handy will make it easier for us to serve you quickly and effectively.

You may contact Technical Support via Toll-Free FAX. Please include your return FAX number. Youwill receive a reply within 24 hours. You may also contact Technical Support via modem to ATLIS–BBS, Technical Support's Electronic Bulletin Board System. Replies are posted within 24 hours.

East Coast Technical Support: 1–800–645–7492 (8 a.m.–6 p.m. E.S.T.)

West Coast Technical Support: 1–800–458–9469 (8 a.m.–5 p.m. P.S.T.)

Technical Support FAX Number: 1–800–447–5086

ATLIS–BBS Electronic Bulletin Board System: 1–516–496–3980(1200 – 9600 Baud, 8 Data Bits, 1 Start/Stop Bit, No Parity)

ATLIS FAX – Automated Fax Retrieval System:  1–800–573–0153 1–516–921–6704/Ext. 1667

ADEMCO World Wide Web Page: HTTP//: WWW. ADEMCO. COM

INTERNET E-Mail Address: Ademco_Tech_SPRT @ Ademco–165 . Ademco . com

Page 92: ADEMCO N7225V2B

18 –4

Page 93: ADEMCO N7225V2B

19 –1

Section 19. SPECIFICATIONS & ACCESSORIES

Specifications

VIA-30PSE SECURITY CONTROL

1. Physical: 12-1/2" W x 14-1/2" H x 3" D (318mm x 368mm x 76mm).

2. Electrical:VOLTAGE INPUT: 16.5VAC from plug-in 25VA transformer, Ademco No.1321/TF2 (in U.S.A.).RECHARGEABLE BACK-UP BATTERY: 12VDC, 4AH (Gel type).Charging Voltage: 13.8VDC.ALARM SOUNDER: 12V, 2.0 Amp output can drive 12V BELLS or candrive one or two 702 (series connected) self-contained 20-watt sirens. Donot connect two 702s in parallel.AUXILIARY POWER OUTPUT: 12VDC, 500mA max. Interrupts for 4-wiresmoke detector reset.Note: For UL installations, Alarm Sounder plus Auxiliary Power currents

should not exceed 600mA total.STANDBY TIME: (see Table in the FINAL POWER UP section)FUSE: Battery (3A) No. 90–12.

3. Communication:FORMATS SUPPORTED:

Ademco Express,10 characters/sec, DTMF (Touch-Tone) Data Tones, 1400/2300Hz ACK,1400Hz KISSOFF.Ademco Contact ID Reporting,10 characters/sec., DTMF (Touch-Tone) Data Tones, 1400/2300Hz ACK,1400Hz KISSOFF.Ademco Low Speed, 10 pulses/sec, 1900Hz Data Tone,1400Hz ACK/KISSOFF.Radionics/SESCOA, 20 pulses/sec, 1800Hz Data Tone, 2300Hz.ACK/KISSOFF. Can report 0–9, B–F.

Line Seize: Double Pole.Ringer Equivalence: 0.7B.FCC Registration No.: AC 398U–68192–AL–E.

4. Maximum Zone Resistance: Zones 5 and 6 = 300 ohms excluding EOLR.

5. Zone Response: Zones 5 and 6: 300–500 msec.

4127REMOTE KEYPAD

1. Physical: 5-5/8" W x 4-11/16" H x 7/8" D (143mm x 119mm x 22mm).

2. Electrical: Voltage Input: 12VDC, Current Drain: 20mA.

3. Interface Wiring: To control panel's keypad connection points.RED: 12VDC input (+) aux power.

GREEN: Data Out to Control.YELLOW: Data In from Control.

BLACK: Ground.

4137AD & 5137ADREMOTE KEYPADS

1. Physical: 8-2/5" W x 4-3/4" H x 1-1/10" D (213mm x 121mm x 28mm).

2. Electrical: Voltage Input: 12VDC.Current Drain: 60mA (4137AD).

90mA(5137AD).

3. Interface Wiring: Same as 4127.

Page 94: ADEMCO N7225V2B

19 –2

6127REMOTE KEYPAD

1. Physical: 5-3/4" W x 4-3/4" H x 1" D (146mm x 121mm x 26mm).

2. Electrical: Voltage Input: 12VDC; Current Drain: 20mA.

3. Interface Wiring: Same as 4127.

6128REMOTE KEYPAD

1. Physical: 5-3/4" W x 4-3/4" H x 1" D (146mm x 121mm x 26mm).

2. Electrical: Voltage Input: 12VDC; Current Drain: 30mA.

3. Interface Wiring: Same as 4127.

6137REMOTE KEYPAD

1. Physical: 6-1/4" W x 4-3/4" H x 1" D (159mm x 121mm x 26mm).

2. Electrical: Voltage Input: 12VDC; Current Drain: 85mA.

3. Interface Wiring: Same as 4127.

6138 & 6139REMOTE KEYPADS

1. Physical: 6-1/4" W x 4-3/4" H x 1" D (159mm x 121mm x 26mm).

2. Electrical: Voltage Input: 12VDC; Current Drain: 100mA.

3. Interface Wiring: Same as 4127.

4281L, 4281M, 4281HRF RECEIVERS

(5700 System)and

5881L, 5881M, 5881HRF RECEIVERS

(5800 System)

1. Physical: 7-3/8" (188mm) W x 4-3/8" (112mm) H x 1-7/16" (37mm) D.Note: 10-7/8" (277mm) H with antenna.

2. Electrical: Voltage Input: 12VDC; Current Drain: 35mA.

3. Interface Wiring: Same as 4127.

4. Range: 200ft (60m) nominal indoors from wireless transmitters (theactual range to be determined with system in TEST mode).

5. Zones: (With the Ademco VIA-30PSE)4281L: accepts up to 4 transmitters.4281M or 4281H: accepts up to 8 transmitters.5881L: accepts up to 8 transmitters.5881M/5881H: accepts up to 30 transmitters.

5800TMTRANSMITTER

MODULEused with 5827BD

Wireless 2-Way Keypad

1. Physical: 2-1/4" W x 4-1/8" H x 7/8" D (57mm x 105mm x 22mm).

2. Electrical: Voltage Input: 12VDC; Current Drain: 20mA.

3. Interface Wiring: Same as 4127.

4219WIRED EXPANSION

MODULE

1. Physical: 6-1/2" W x 4-1/4" H x 1-1/4" D (169mm x 108mm x 32mm)

2. Electrical: Voltage Input: 12VDC; Current Drain: 35mA

3. Interface Wiring: Same as 4127.

4229WIRED EXPANSION/

RELAY MODULE

1. Physical: 6-1/2" W x 4-1/4" H x 1-1/4" D (169mm x 108mm x 32mm)

2. Electrical: Voltage Input: 12VDC; Current Drain: 35mA (Relays off) 100mA (Relays on)

3. Two Output Relays: SPDT Contacts. Rating: 2A max at 28VDC/AC.

4204RELAY MODULE

1. Physical: 6-1/2" W x 4-1/4" H x 1-1/4" D (169mm x 108mm x 32mm).

2. Electrical: Voltage Input: 12VDC; Current Drain: 15mA (Relays off).180mA (Relays on).

3. Interface Wiring: Same as 4127.

4. Four Output Relays: SPDT Contacts. Rating: 2A max at 28VDC/AC.

Page 95: ADEMCO N7225V2B

19 –3

4285PHONE MODULE

1. Physical: 6-1/2" W x 4-1/4" H x 1-1/4" D (169mm x 108mm x 32mm).

2. Electrical: Voltage Input: 12VDC; Current Drain: 160mA.

3. Device Address: Permanently set to address 4.

4. Interface Wiring: See 4285 PHONE MODULE section.

5. Telephone Line Connections: See 4285 PHONE MODULE section.

7720PLUS/7820 1. Physical: 8-1/2" W x 9-1/2" H x 1-3/4" D (216mm x 242mm x 45mm).

2. Electrical: Voltage Input: 12VDC; Current Drain: 150mA.

3. Device Address: Set to address 3.

4. Interface Wiring: Same as 4127 above.

Accessories (Compatible Devices)

No. 1321 16.5VAC, 25VA Plug-In Transformer (in U.S.A.)No. 1321CN 16.5VAC, 25VA Plug-In Transformer (in Canada)

SoundersAdemco AB-12M 10”Motorized Bell & Box

Motor bell & box. UL Grade A. 100mA currentdraw.

Ademco 1011BE12M 10”Motorized Bell & Box

Motor bell & box. UL Listed. 100mA currentdraw.

Ademco 702 OutdoorSiren

Self-contained 6–12 volt siren (driver built-in)and weatherproof for outdoor use. Can be wiredfor either a steady or warble sound. 117dB @ 10feet. 1500mA current draw.

Ademco 7192-Channel Siren

Self-contained 6–12-volt siren (driver built in).Steady or warble sound. 109dB @ 10 feet.550mA current draw.

Ademco 747Indoor Siren

Self-contained 6–15 volt siren (driver built-in) forindoor wall mount. 747F available for flushmounting. 105dB @ 10 feet. 400mA currentdraw.

Ademco 747ULIndoor Siren

Self-contained 6–15 volt siren (driver built-in) forindoor wall mount. UL Listed. 85dB @ 10 feet.320mA current draw.

Ademco 744

Siren Driver

6 jumper-selected sound outputs. Rated at119dB with use of an 8-ohm 30 watt speaker.1.3 amps current draw.

Ademco 745X3*Voice Siren Driver

12 volt voice siren driver with English, Spanishand French voice messages. Separatemessages for Fire and Burglary. Use with 8-ohm speaker. UL Listed. 1100mA current draw.

Ademco 705–820,5-inch Round Speaker

20-watt, 8-ohm indoor or outdoor speaker.Requires a driver.

Ademco 713 Speaker 40-watt, 8-ohm, indoor/outdoor speaker.Requires a driver.

System Sensor PA400B(beige)/PA400R (red)Indoor Piezo Sounder

Indoor piezo sounder (red or beige), rated at 90dB @ 10 feet.

* Requires special power wiring connections.

Page 96: ADEMCO N7225V2B

19 –4

Compatible 4-WireSmoke/Combustion

Detectors

System Sensor Models

1412 4-wire ionization products of combustion detector.

2412 4-wire photoelectric smoke detector.

2412TH 4-wire photoelectric smoke detector w/135º F (57º C) heatdetector.

A77–716B EOL relay module (supervisory module for wired 4-wire firezone).

2112/24T Low-profile 4-wire photoelectric smoke detector w/135º F(57º C) heat detector.

Page 97: ADEMCO N7225V2B

A –1

APPENDIX A:REGULATORY AGENCY STATEMENTS

FEDERAL COMMUNICATIONS COMMISSION (FCC) Part 15 STATEMENTThis equipment has been tested to FCC requirements and has been found acceptable for use. The FCC requires thefollowing statement for your information:This equipment generates and uses radio frequency energy and if not installed and used properly, that is, in strictaccordance with the manufacturer's instructions, may cause interference to radio and television reception. It has beentype tested and found to comply with the limits for a Class B computing device in accordance with the specifications inPart 15 of FCC Rules, which are designed to provide reasonable protection against such interference in a residentialinstallation. However, there is no guarantee that interference will not occur in a particular installation. If this equipmentdoes cause interference to radio or television reception, which can be determined by turning the equipment off and on,the user is encouraged to try to correct the interference by one or more of the following measures:• If using an indoor antenna, have a quality outdoor antenna installed.• Reorient the receiving antenna until interference is reduced or eliminated.• Move the radio or television receiver away from the receiver/control.• Move the antenna leads away from any wire runs to the receiver/control.• Plug the receiver/control into a different outlet so that it and the radio or television receiver are on different branchcircuits.If necessary, the user should consult the dealer or an experienced radio/television technician for additionalsuggestions. The user or installer may find the following booklet prepared by the Federal Communications Commissionhelpful: "Interference Handbook"This booklet is available from the U.S. Government Printing Office, Washington, DC 20402.The user shall not make any changes or modifications to the equipment unless authorized by the InstallationInstructions or User's Manual. Unauthorized changes or modifications could void the user's authority to operate theequipment.

FEDERAL COMMUNICATIONS COMMISSION (FCC) Part 68 STATEMENTThis equipment complies with Part 68 of the FCC rules. On the front cover of this equipment is a label that contains,among other information, the FCC registration number and ringer equivalence number (REN) for this equipment. Ifrequested, this in formation must be provided to the telephone company.This equipment uses the following jacks: An RJ31X is used to connect this equipment to the telephone network.The REN is used to determine the quantity of devices which may be connected to the telephone line. Excessive RENson the telephone line may result in the devices not ringing in response to an incoming call. In most, but not all areas,the sum of the RENs should not exceed five (5.0). To be certain of the number of devices that may be connected to theline, as determined by the total RENs, contact the telephone company to determine the maximum REN for the callingarea.If this equipment causes harm to the telephone network, the telephone company will notify you in advance thattemporary discontinuance of service may be required. If advance notice is not practical, the telephone company willnotify the customer as soon as possible. Also, you will be advised of your right to file a complaint with the FCC if youbelieve necessary.The telephone company may make changes in its facilities, equipment, operations, or procedures that could affect theoperation of the equipment. If this happens, the telephone company will provide advance notice in order for you tomake the necessary modifications in order to maintain uninterrupted service.If trouble is experienced with this equipment, please contact the manufacturer for repair and warranty information. If thetrouble is causing harm to the telephone network, the telephone company may request you remove the equipment fromthe network until the problem is resolved.There are no user serviceable components in this product, and all necessary repairs must be made by themanufacturer. Other repair methods may invalidate the FCC registration on this product.This equipment cannot be used on telephone company-provided coin service. Connection to Party Line Service issubject to state tariffs.This equipment is hearing-aid compatible.When programming or making test calls to an emergency number, briefly explain to the dispatcher the reason for thecall. Perform such activities in the off-peak hours; such as early morning or late evening.

Page 98: ADEMCO N7225V2B

A –2

UL NOTICES1. This is a "Grade A" residential system.

2. The 4285 Phone module and 7720PLUS or 7820 Long Range Radios have not been ULtested and cannot, therefore, be used in a UL installation.

3. The Entry Delay (field ✱38) cannot be greater than 45 seconds for UL installations.

4. The maximum number of reports per armed period (field ✱92) must be unlimited (set to 1)for UL installations.

5. Periodic testing (field ✱49) must be at least every 24 hours (set to 1) for UL installations.

6. Alarm Sounder plus Auxiliary Power currents must not exceed 600mA total for ULinstallations.

7. Downloading is not permissible for UL installations.

CALIFORNIA STATE FIRE MARSHAL (CSFM)24 HOUR BATTERY BACK-UP REQUIREMENTS

The California State Fire Marshal has published new regulations which require that all residential fire alarmcontrol panels installed after June 30, 1993 must be provided with a back-up battery which has sufficientcapacity to operate the panel and its attached peripheral devices for 24 hours in the intended standbycondition, followed by at least 4 minutes in the intended fire alarm signaling condition.This control panel can meet these requirements without using a supplementary power supply, provided thatthe panel's auxiliary power and bell output currents are limited as indicated below.

OUTPUT LIMITATIONS TO MEET CSFM 24 HOUR BATTERY BACK-UP REQUIREMENTSFOR UL LISTED RESIDENTIAL FIRE INSTALLATIONS

OUTPUT CURRENT LIMITATIONS BATTERY INFORMATION

OUTPUT CURRENTTOTAL

MAXIMUMAUXILIARY CURRENT

BATTERY CAPACITYTO USE (Amp/Hrs)

RECOMMENDED BATTERY(Yuasa Model No.)

600mA maximum totalof

auxiliary powerplus bell output currents.

45mA160mA200mA425mA

4AH7AH8AH

14AH

NP4-12NP7-12NP4-12 (two)‡

NP7-12 (two)‡

‡Note: Use two batteries, connected in parallel. Obtain an Ademco No. 4100EOLR Resistor Kit. A dual batteryharness is provided with the kit. The kit also contains EOL resistors with spade lug/heat shrink tubingconstruction which has been approved by UL and CSFM for fire zone usage. Both batteries will fit inside thepanel's cabinet.

Page 99: ADEMCO N7225V2B

A –3

CANADIAN DEPARTMENT OF COMMUNICATIONS(DOC) STATEMENT

NOTICEThe Canadian Department of Communications label identifies certified equipment. This certification means that theequipment meets certain telecommunications network protective, operational and safety requirements. TheDepartment does not guarantee the equipment will operate to the user's satisfaction.Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of thelocal telecommunications company. The equipment must also be installed using an acceptable method ofconnection. In some cases, the company's inside wiring associated with a single line individual service may beextended by means of certified connector assembly (telephone extension cord). The customer should be aware thatcompliance with the above conditions may not prevent degradation of service in some situations.Repairs to certified equipment should be made by an authorized Canadian maintenance facility designated by thesupplier. Any repairs or alterations made by the user to this equipment, or equipment malfunctions, may give thetelecommunications company cause to request the user to disconnect the equipment.Users should ensure for their own protection that the electrical ground connections of the power utility, telephonelines and internal metallic water pipe system, if present, are connected together. This precaution may be particularlyimportant in rural areas.Caution: User should not attempt to make such connections themselves, but should contact the appropriateelectric inspection authority, or electrician, as appropriate.The Load Number (LN) assigned to each terminal device denotes the percentage of the total load to be connectedto a telephone loop which is used by the device, to prevent overloading. The termination on a loop may consist ofany combination of devices subject only to the requirement that the total of the Load Numbers of all the devicesdoes not exceed 100.

AVISL'étiquette du ministère des Communications du Canada identifie le matériel homologué. Cette étiquette certifieque le matériel est conforme à certaines normes de protection, d'exploitation et de sécurité des réseaux detélécommunications. Le ministère n'assure toutefois pas que le matériel fonctionnera à la satisfaction de l'utilisateur.Avant d'installer ce matériel, l'utilisateur doit s'assurer qu'il est permis de le raccorder aux installations del'entreprise locale de télécommunications. Le matériel doit également être installé en suivant une méthode acceptéede raccordement. Dans certains cas, les fils intérieurs de l'entreprise utilisés pour un service individuel à la ligneunique peuvent être prolongés au moyen d'un dispositif homologué de raccordement (cordon prolongateurtéléphonique interne). L'abonne ne doit pas oublier qu'il est possible que la conformité aux conditions énoncées ci-dessus n'empèche pas la dégradation du service dans certaines situations. Actuellement, les entreprises detélécommunications ne permettent pas que l'on raccorde leur matériel aux prises d'abonnés, sauf dans les casprecis prévus par les tarifs particuliers de ces entreprises.Les réparations du matériel homologué doivent être effectuées pas un centre d'entretien canadien autorisé désignépar le fournisseur. La compagnie de télécommunications peut demander à l'utilisateur de débrancher un appareil àla suite de réparations ou de modifications effectuées par l'utilisateur ou à cause de mauvais fonctionnement.Pour sa propre protection, l'utilisateur doit s'assurer que tous les fils de mise en terre de la source d'énergieélectrique, des lignes téléphoniques de réseau de conduites d'eau, s'il y en a, soient raccordés ensemble. Cetteprécaution est particulièrement importante dans les régions rurales.Avertissement: L'utilisateur ne doit pas tenter de faire ces raccordements lui-même; il doit avoir recours à unservice d'inspection des installations électriques, ou à un électricien, selon le cas.L'indice de charge (IC) assigné à chaque dispositif terminal pour éviter toute surcharge indique le pourcentage de lacharge totale qui peut être raccordé à un circuit téléphonique bouclé utilisé par ce dispositif. La terminaison ducircuit bouclé peut être constituée de n'importe quelle combinaison de dispositifs, pourvu que la somme des indicesde charge de l'ensemble des dispositifs ne dépasse pas 100.

Page 100: ADEMCO N7225V2B

A –4

Page 101: ADEMCO N7225V2B

B –1

APPENDIX B:WARNING!

THE LIMITATIONS OF THIS ALARM SYSTEMWhile this System is an advanced design security system, it does not offer guaranteed protection againstburglary, fire or other emergency. Any alarm system, whether commercial or residential, is subject to compromiseor failure to warn for a variety of reasons. For example:• Intrusion detectors (e.g., passive infrared detectors), smoke detectors, and many other sensing devices will

not work without power. Battery-operated devices will not work without batteries, with dead batteries, or if thebatteries are not put in properly. Devices powered solely by AC will not work if their AC power supply is cut offfor any reason, however briefly.

• Signals sent by wireless transmitters may be blocked or reflected by metal before they reach the alarmreceiver. Even if the signal path has been recently checked during a weekly test, blockage can occur if a metalobject is moved into the path.

• A user may not be able to reach a panic or emergency button quickly enough.• While smoke detectors have played a key role in reducing residential fire deaths in the United States, they

may not activate or provide early warning for a variety of reasons in as many as 35% of all fires, according todata published by the Federal Emergency Management Agency. Some of the reasons smoke detectors usedin conjunction with this System may not work are as follows. Smoke detectors may have been improperlyinstalled and positioned. Smoke detectors may not sense fires that start where smoke cannot reach thedetectors, such as in chimneys, in walls, or roofs, or on the other side of closed doors. Smoke detectors alsomay not sense a fire on another level of a residence or building. A second floor detector, for example, may notsense a first floor or basement fire. Finally, smoke detectors have sensing limitations. No smoke detector cansense every kind of fire every time. In general, detectors may not always warn about fires caused bycarelessness and safety hazards like smoking in bed, violent explosions, escaping gas, improper storage offlammable materials, over loaded electrical circuits, children playing with matches, or arson. Depending on thenature of the fire and/or location of the smoke detectors, the detector, even if it operates as anticipated, maynot provide sufficient warning to allow all occupants to escape in time to prevent injury or death.

• Passive Infrared Motion Detectors can only detect intrusion within the designed ranges as diagrammed in theirinstallation manual. Passive Infrared Detectors do not provide volumetric area protection. They do createmultiple beams of protection, and intrusion can only be detected in unobstructed areas covered by thosebeams. They cannot detect motion or intrusion that takes place behind walls, ceilings, floors, closed doors,glass partitions, glass doors, or windows. Mechanical tampering, masking, painting or spraying of anymaterial on the mirrors, windows or any part of the optical system can reduce their detection ability. PassiveInfrared Detectors sense changes in temperature; however, as the ambient temperature of the protected areaapproaches the temperature range of 90° to 105°F (32° to 40°C), the detection performance can decrease.

• Alarm warning devices such as sirens, bells or horns may not alert people or wake up sleepers if they arelocated on the other side of closed or partly open doors. If warning devices are located on a different level ofthe residence from the bedrooms, then they are less likely to waken or alert people inside the bedrooms. Evenpersons who are awake may not hear the warning if the alarm is muffled by noise from a stereo, radio, airconditioner or other appliance, or by passing traffic. Finally, alarm warning devices, however loud, may notwarn hearing-impaired people.

• Telephone lines needed to transmit alarm signals from a premises to a central monitoring station may be outof service or temporarily out of service. Telephone lines are also subject to compromise by sophisticatedintruders.

• Even if the system responds to the emergency as intended, however, occupants may have insufficient time toprotect themselves from the emergency situation. In the case of a monitored alarm system, authorities maynot respond appropriately.

• This equipment, like other electrical devices, is subject to component failure. Even though this equipment isdesigned to last as long as 20 years, the electronic components could fail at any time.

The most common cause of an alarm system not functioning when an intrusion or fire occurs is inadequatemaintenance. This alarm system should be tested weekly to make sure all sensors and transmitters are workingproperly. The security keypad (and remote keypad) should be tested as well.Wireless transmitters (used in some systems) are designed to provide long battery life under normal operatingconditions. Longevity of batteries may be as much as 4 to 7 years, depending on the environment, usage, and thespecific wireless device being used. External factors such as humidity, high or low temperatures, as well as largeswings in temperature, may all reduce the actual battery life in a given installation. This wireless system,however, can identify a true low battery situation, thus allowing time to arrange a change of battery to maintainprotection for that given point within the system.Installing an alarm system may make the owner eligible for a lower insurance rate, but an alarm system is not asubstitute for insurance. Homeowners, property owners and renters should continue to act prudently in protectingthemselves and continue to insure their lives and property.We continue to develop new and improved protection devices. Users of alarm systems owe it to themselves andtheir loved ones to learn about these developments.

Page 102: ADEMCO N7225V2B

B –2

ADEMCO LIMITED WARRANTYAlarm Device Manufacturing Company, a Division of Pittway Corporation, and its divisions,subsidiaries and affiliates ("Seller"), 165 Eileen Way, Syosset, New York 11791, warrants its productsto be in conformance with its own plans and specifications and to be free from defects in materials andworkmanship under normal use and service for 24 months from the date stamp control on the productor, for products not having an Ademco date stamp, for 12 months from date of original purchaseunless the installation instructions or catalog sets forth a shorter period, in which case the shorterperiod shall apply. Seller's obligation shall be limited to repairing or replacing, at its option, free ofcharge for materials or labor, any product which is proved not in compliance with Seller'sspecifications or proves defective in materials or workmanship under normal use and service. Sellershall have no obligation under this Limited Warranty or otherwise if the product is altered or improperlyrepaired or serviced by anyone other than Ademco factory service. For warranty service, returnproduct transportation prepaid, to Ademco Factory Service, 165 Eileen Way, Syosset, New York11791.THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, OF MERCHANTABILITY, OR FITNESSFOR A PARTICULAR PURPOSE OR OTHERWISE, WHICH EXTEND BEYOND THE DESCRIPTIONON THE FACE HEREOF. IN NO CASE SHALL SELLER BE LIABLE TO ANYONE FOR ANYCONSEQUENTIAL OR INCIDENTAL DAMAGES FOR BREACH OF THIS OR ANY OTHERWARRANTY, EXPRESS OR IMPLIED, OR UPON ANY OTHER BASIS OF LIABILITYWHATSOEVER, EVEN IF THE LOSS OR DAMAGE IS CAUSED BY THE SELLER'S OWNNEGLIGENCE OR FAULT.Seller does not represent that the products it sells may not be compromised or circumvented; that theproducts will prevent any personal injury or property loss by burglary, robbery, fire or otherwise; or thatthe products will in all cases provide adequate warning or protection. Customer understands that aproperly installed and maintained alarm may only reduce the risk of a burglary, robbery, fire or otherevents occurring without providing an alarm, but it is not insurance or a guarantee that such will notoccur or that there will be no personal injury or property loss as a result. CONSEQUENTLY, SELLERSHALL HAVE NO LIABILITY FOR ANY PERSONAL INJURY, PROPERTY DAMAGE OR OTHERLOSS BASED ON A CLAIM THE PRODUCT FAILED TO GIVE WARNING. HOWEVER, IF SELLERIS HELD LIABLE, WHETHER DIRECTLY OR INDIRECTLY, FOR ANY LOSS OR DAMAGE ARISINGUNDER THIS LIMITED WARRANTY OR OTHERWISE, REGARDLESS OF CAUSE OR ORIGIN,SELLER'S MAXIMUM LIABILITY SHALL NOT IN ANY CASE EXCEED THE PURCHASE PRICE OFTHE PRODUCT, WHICH SHALL BE THE COMPLETE AND EXCLUSIVE REMEDY AGAINSTSELLER. This warranty replaces any previous warranties and is the only warranty made by Seller onthis product. No increase or alteration, written or verbal, of the obligations of this Limited Warranty isauthorized.

Page 103: ADEMCO N7225V2B

OPTIONAL FOR UP TO 30 ADDITIONAL ZONES

(ONE FROM EITHER OR BOTH GROUPS)

AD

EM

CO

428

1 or

588

1 T

ype

RF

RE

CE

IVE

RW

IRE

LES

S Z

ON

ES

4281

L:

UP

TO

442

81M

/588

1L:

UP

TO

858

81M

: U

P T

O 1

642

81/5

881H

:U

P T

O 3

0

AD

EM

CO

No.

421

9W

IRE

D E

XP

AN

SIO

N M

OD

ULE

(8 A

DD

'L E

OLR

WIR

ED

ZO

NE

S)

-OR

-A

DE

MC

O N

o. 4

229

WIR

ED

EX

PA

NS

ION

/RE

LAY

MO

DU

LE(8

AD

D'L

EO

LR W

IRE

D Z

ON

ES

PLU

S 2

OU

TP

UT

RE

LAY

S)

-OR

-A

DE

MC

O N

o. 4

204

RE

LAY

MO

DU

LE(4

OU

TP

UT

RE

LAY

S)

BLK

RE

DG

RN

YE

L

CO

NN

EC

TIO

N O

F T

HE

FIR

E A

LAR

M S

IGN

AL

TO

A F

IRE

ALA

RM

HE

AD

QU

AR

TE

RS

OR

A C

EN

TR

AL

ST

AT

ION

SH

ALL

BE

PE

RM

ITT

ED

ON

LY W

ITH

TH

E P

ER

MIS

SIO

N O

F T

HE

LO

CA

L A

UT

HO

RIT

Y H

AV

ING

JUR

ISD

ICT

ION

. TH

E B

UR

GLA

R A

LAR

M S

IGN

AL

SH

ALL

NO

T B

E

CO

NN

EC

TE

D T

O A

PO

LIC

E E

ME

RG

EN

CY

NU

MB

ER

.

US

E U

L LI

ST

ED

LIM

ITE

DE

NE

RG

Y C

AB

LE F

OR

ALL

CO

NN

EC

TIO

NS

12

34

56

78

910

1112

1314

1516

1718

1920

21

LOC

AT

ED

AT

LOW

ER

RIG

HT

OF

CIR

CU

ITB

OA

RD

EA

RT

HG

RO

UN

DS

EE

INS

TR

UC

TIO

NS

FO

RP

RO

PE

R G

RO

UN

DIN

G

TE

LEP

HO

NE

WIR

ING

(VIA

RJ3

1X*

JAC

K D

IRE

CT

CO

NN

EC

T C

OR

D)

*IN

CA

NA

DA

, CA

38A

JA

CK

DO

C L

OA

D N

O.:

3

RE

MO

TE K

EY

PA

DS

SY

STE

M M

US

TB

E

PR

OG

RA

MM

ED

WIT

H A

N

o. 5

137A

D O

R 6

139.

IT N

EE

DN

OT

RE

MA

IN IN

SY

STE

M.

AFT

ER

PR

OG

RA

MM

ING

, TH

E S

YS

TEM

CA

N U

SE

:N

o. 4

127(

20m

A),

4137

AD

(60m

A),

5137

AD

(90m

A),

6127

(20m

A),

6128

(30m

A),

6137

(85m

A),

6138

(100

mA

), O

R 6

139

(100

mA

).

MU

LTIP

LE K

EY

PA

DS

MA

Y B

EU

SE

D, B

UT

US

E M

AX

. OF

220

FT.

OF

#22

WIR

E O

R 5

50 F

T. O

F #1

8.

BLACK: KEYPAD GROUND (–) RETURN

RED: KEYPAD PWR (+)

GREEN: DATA IN FROM KEYPAD

YELLOW: DATA OUT TO KEYPAD▲

RE

MO

TE

KE

YP

AD

AU

X. P

OW

ER

OU

TP

UT

10.5

-13.

8VD

C50

0mA

MA

X.

INT

ER

RU

PT

SF

OR

FIR

EA

LAR

M R

ES

ET

NO

TE

:K

EY

PA

D

CU

RR

EN

TM

US

T B

EIN

CLU

DE

DIN

AU

X.

CU

RR

EN

TD

RA

IN

CA

LCU

LAT

ION

S

}

GE

L LE

AD

AC

ID T

YP

E.

DO

NO

T U

SE

GA

TE

S B

AT

TE

RY

.

BA

TT

ER

Y N

OR

MA

LLY

NE

ED

NO

T B

E

RE

PLA

CE

D F

OR

AT

LE

AS

T 3

YR

S.

BA

TT

ER

Y C

AP

AC

ITY

FO

R E

ME

RG

EN

CY

ST

AN

DB

Y U

SE

AT

LE

AS

T 4

HO

UR

S.

TH

IS D

EV

ICE

CO

MP

LIE

S W

ITH

PA

RT

15

OF

FC

C R

ULE

S.

OP

ER

AT

ION

IS S

UB

JEC

T T

O T

HE

FO

LLO

WIN

G T

WO

C

ON

DIT

ION

S: (

1) T

HIS

DE

VIC

E M

AY

NO

T C

AU

SE

HA

RM

FU

LIN

TE

RF

ER

EN

CE

, AN

D (

2) T

HIS

DE

VIC

E M

US

T A

CC

EP

T A

NY

INT

ER

FE

RE

NC

E R

EC

EIV

ED

, IN

CLU

DIN

G IN

TE

RF

ER

EN

CE

T

HA

T M

AY

CA

US

E U

ND

ES

IRE

D O

PE

RA

TIO

N.

CO

MP

LIE

S W

ITH

FC

C R

ULE

S, P

AR

T 6

8F

CC

RE

GIS

TR

AT

ION

NO

. AC

398U

-681

92-A

L-E

RIN

GE

R E

QU

IVA

LEN

CE

: 0.7

B.

WA

RN

ING

:T

O P

RE

VE

NT

RIS

K O

F S

HO

CK

,D

ISC

ON

NE

CT

TE

LEP

HO

NE

LIN

EA

T T

ELC

O J

AC

K B

EF

OR

ES

ER

VIC

ING

TH

IS U

NIT

.TH

IS E

QU

IPM

EN

T S

HO

ULD

BE

INS

TALL

ED

IN

AC

CO

RD

AN

CE

WIT

H T

HE

NAT

ION

AL

FIR

E

PR

OTE

CTI

ON

AS

SO

CIA

TIO

N'S

STA

ND

AR

D 7

4 (N

ATIO

NA

L FI

RE

PR

OTE

CTI

ON

AS

SO

C.,

BAT

TER

YM

AR

CH

PA

RK

, QU

INC

Y, M

A 0

2269

). P

RIN

TED

INFO

RM

ATIO

N D

ES

CR

IBIN

G P

RO

PE

R

INS

TALL

ATIO

N, O

PE

RAT

ION

, TE

STI

NG

, M

AIN

TEN

AN

CE

, EVA

CU

ATIO

N P

LAN

NIN

G A

ND

R

EPA

IR S

ER

VIC

E IS

TO

BE

PR

OV

IDE

D W

ITH

TH

IS E

QU

IPM

EN

T.

CH

AR

GIN

GV

OLT

AG

E13

.8V

DC

BA

TT

ER

Y12

V, 4

AH

(e.g

. AD

EM

CO

No.

467

)O

R 1

2V, 1

.2A

H

– +

–+

CO

NN

EC

TO

R T

AB

S

FO

R C

OM

PLE

TE

INF

OR

MA

TIO

N,

SE

E IN

ST

RU

CT

ION

S

PLU

G-I

NT

RA

NS

FO

RM

ER

16.5

VA

C, 2

5VA

(e.g

. AD

EM

CO

No.

132

1.U

SE

No.

132

1CN

IN C

AN

AD

A)

TO 1

10V

AC

UN

SW

ITC

HE

DO

UTL

ET

(24H

R)

–+

ALA

RM

OU

TPU

T10

.5-1

3.8V

DC

, 2A

MA

X.

(600

mA

MA

X F

OR

UL

US

AG

E,

INC

LUD

ING

AU

X. P

OW

ER

)

ST

EA

DY

FO

R B

UR

GLA

RY

/PA

NIC

,P

ULS

ING

FO

R F

IRE

(e.

g. U

SE

A

DE

MC

O N

o. 7

40 S

OU

ND

ER

, N

o.70

2 O

R 7

19 S

IRE

N, O

R 1

2V B

ELL

)

BA

TT

ER

Y F

US

E(e

.g. A

DE

MC

O N

o. 9

0-12

)F

OR

RE

PLA

CE

ME

NT

US

E S

AM

E V

ALU

E

3A

BLK

RE

DG

RN

YE

L

BLK

RE

DG

RN

YE

L

AN

D/O

R

1000

O

HM

SE

OLR

1000

O

HM

SE

OLR

ZONE 5

ZONE 6

HI

LO

HI

LO

WA

RN

ING

:O

WN

ER

'S IN

ST

RU

CT

ION

NO

TIC

E N

OT

TO

BE

RE

MO

VE

D.

WE

EK

LY T

ES

TIN

G IS

RE

QU

IRE

D T

OE

NS

UR

E P

RO

PE

R O

PE

RA

TIO

N O

FT

HIS

SY

ST

EM

.

• M

AX

IMU

M L

OO

P R

ES

ISTA

NC

E:

(EA

CH

ZO

NE

) 30

0 O

HM

S (

PLU

S E

OLR

)•

RE

SP

ON

SE

, ZO

NE

S 5

, 6:3

00-5

00M

SE

C•

ZON

E 5

CA

N B

E P

RO

GR

AM

ME

D F

OR

US

E A

S A

FIR

E Z

ON

E.

SE

E D

IAG

RA

M.

TIP

(BR

OW

N)

RIN

G(G

RA

Y)

TIP

(GR

EE

N)

RIN

G(R

ED

)

}} IN

CO

MIN

GP

HO

NE

LIN

E

HA

ND

SE

T

BLA

CK

RE

D

N83

72V

1 4

/97

Co

pyr

ight

©19

97 P

ITT

WA

Y C

OR

PO

RA

TIO

N

ALA

RM

DE

VIC

E M

AN

UF

AC

TU

RIN

G C

O.

A D

IVIS

ION

OF

PIT

TW

AY

CO

RP

OR

AT

ION

165

Eile

en W

ay, S

yoss

et, N

ew Y

ork

117

91

–+

NO

T U

SE

D(Z

ON

ES

1-4

NO

T P

RE

SE

NT

)

OP

TIO

NA

L:N

o. 5

800T

MTR

AN

SM

ITTE

R M

OD

ULE

(20m

A)

(for

No.

582

7BD

Wire

less

Bid

irect

iona

l Key

pad)

AN

D/O

RN

o. 4

285

VO

ICE

MO

DU

LE(1

60m

A)

AN

D/O

RN

o. 7

720E

CP

LON

GR

AN

GE

RA

DIO

MA

Y A

LSO

BE

CO

NN

EC

TE

D.

SE

E IN

ST

RU

CT

ION

S A

CC

OM

-P

AN

YIN

G T

HO

SE

DE

VIC

ES

.

VIA

-30P

SE

SU

MM

AR

Y O

F C

ON

NE

CT

ION

S

SE

T U

NIT

’S D

IP S

WIT

CH

FOR

DE

VIC

E A

DD

RE

SS

OF

“1”.

See

uni

t’s in

stru

ctio

ns.

AU

X P

WR

OU

TP

UT

TE

RM

S

+ -

TO H

I SID

E O

F S

ELE

CT

ED

ZO

NE

TO L

O S

IDE

OF

SE

LEC

TE

D Z

ON

E

+ -

-+

••

EO

LP

OW

ER

SU

PE

R-

VIS

ION

RE

LAY

MO

DU

LEA

77-7

16B

• •

5 4

4-W

IRE

SM

OK

EO

R C

OM

BU

ST

ION

D

ET

EC

TOR

1000

OH

MS

EO

LR

HE

ATD

ET

EC

TOR

ZO

NE

S 2

–7*

+R

ED

BLK

VIO

LET

*IF

PR

OG

RA

MM

ED

FO

R F

IRE

SE

T R

EC

EIV

ER

’SD

IP S

WIT

CH

FO

RD

EV

ICE

AD

DR

ES

SO

F “0

”. S

ee re

ceiv

er’s

inst

ruct

ions

.E

AR

TH

GR

OU

ND

TE

RM

INA

L

TO

ZO

NE

5*

}

Figure 17. VIA-30PSE SUMMARY OF CONNECTIONS DIAGRAM

Page 104: ADEMCO N7225V2B

àN7225V2UäN7225V2 Rev B 4/99

AL ARM DEVICE MANUFACTURING CO.A DIVISION OF PITTWAY CORPORATION

165 Eileen Way, Syosset, New York 11791Copyright © 1997 PITTWAY CORPORATION