7SA632 Linea a Tocache

Embed Size (px)

Citation preview

  • 8/19/2019 7SA632 Linea a Tocache

    1/14

    ELOR_SM / SE Juanjui / LT a Tocache / 7SA632V4.7 Var 

    ML… 7SA63255BB927PR4

    Versión del juego de parámetr… V04.70.07

    Ruta del equipo: C:\Siemens\Digsi4\D4PROJ\ELOR_SM\P7DI\GV\ST\00000013

     Autor:

    Creado el: 27.01.14 18:44:51

    Mod. por última vez el: 27.01.14 22:47:46

    Modo de operación: Sin línea

    Comentar…

    Valores de ajust… Presentación secundaria de los valores

    C O N T E N I D O D E L A I M P R E S I Ó N

    ..........................................................................................................................................................................................................................................…1 General Device Settings

    ..........................................................................................................................................................................................................................................................…1.1 Grupo Device

    ..............................................................................................................................................................................................................................................…2 Power System Data 1

    ................................................................................................................................................................................................…2.1 Grupo Power System Data 1; Grupo Transformers

    ..............................................................................................................................................................................................…2.2 Grupo Power System Data 1; Grupo Power System

    .........................................................................................................................................................................................................…2.3 Grupo Power System Data 1; Grupo Breaker ............................................................................................................................................................................................................................................…3 Grupos de parámetros

    ..............................................................................................................................................................................................…3.1 Grupo Power System Data 2; Grupo Power System

    ....................................................................................................................................................................................................…3.2 Grupo Power System Data 2; Grupo Line Status

    ................................................................................................................................................................................................…3.3 Grupo Power System Data 2; Grupo Trip 1-/3-pole

    .................................................................................................................................................................................…3.4 Grupo Distance protection, general settings; Grupo General

    ............................................................................................................................................................................…3.5 Grupo Distance protection, general settings; Grupo Earth faults

    ..........................................................................................................................................................................…3.6 Grupo Distance protection, general settings; Grupo Time Delays

    ...........................................................................................................................................................................................…3.7 Grupo Distance zones (quadrilateral); Grupo Zone Z1

    ..............................................................................................................................................................................…3.8 Grupo Distance zones (quadrilateral); Grupo Zone Z1B-exten.

    ...........................................................................................................................................................................................…3.9 Grupo Distance zones (quadrilateral); Grupo Zone Z2

    ...........................................................................................................................................................................................…3.10 Grupo Distance zones (quadrilateral); Grupo Zone Z3

    ...........................................................................................................................................................................................…3.11 Grupo Distance zones (quadrilateral); Grupo Zone Z4

    ...........................................................................................................................................................................................…3.12 Grupo Distance zones (quadrilateral); Grupo Zone Z5

    ...........................................................................................................................................................................................…3.13 Grupo Distance zones (quadrilateral); Grupo Zone Z6

    ................................................................................................................................................................................................................................................…3.14 Grupo Power Swing

    ..................................................................................................................................................................................................................…3.15 Grupo Teleprotection for Distance prot.

    ..............................................................................................................................................................................................................................…3.16 Grupo DTT Direct Transfer Trip

    .............................................................................................................................................................................................…3.17 Grupo Instantaneous HighSpeed SOTF Overcurrent

    ...................................................................................................................................................................................................................…3.18 Grupo Weak Infeed (Trip and/or Echo)

    ...................................................................................................................................................................................…3.19 Grupo Measurement Supervision; Grupo Balance / Summ.......................................................................................................................................................................................…3.20 Grupo Measurement Supervision; Grupo Fuse Fail. Mon.

    ..................................................................................................................................................................................................…3.21 Grupo Measurement Supervision; Grupo VT mcb

    ............................................................................................................................................................................................…3.22 Grupo Measurement Supervision; Grupo Load Angle

    ........................................................................................................................................................................................................…3.23 Grupo Earth fault overcurrent; Grupo General

    ..........................................................................................................................................................................................................…3.24 Grupo Earth fault overcurrent; Grupo 3I0>>>

    ............................................................................................................................................................................................................…3.25 Grupo Earth fault overcurrent; Grupo 3I0>>

    ..............................................................................................................................................................................................................…3.26 Grupo Earth fault overcurrent; Grupo 3I0>

    .........................................................................................................................................................................................…3.27 Grupo Earth fault overcurrent; Grupo 3I0 InverseTime

    .....................................................................................................................................................................................................… 3.28 Grupo Earth fault overcurrent; Grupo Direction

    .......................................................................................................................................................................................................… 3.29 Grupo Teleprotection for Earth fault overcurr.

    ........................................................................................................................................................................................................… 3.30 Grupo Automatic Reclosure; Grupo General

    ...................................................................................................................................................................................................… 3.31 Grupo Automatic Reclosure; Grupo 1st AR-cyle

    ........................................................................................................................................................................................…3.32 Grupo Automatic Reclosure; Grupo 3pTRIP/DLC/RDT

    ..............................................................................................................................................................................................… 3.33 Grupo Automatic Reclosure; Grupo Start AR with..

    .....................................................................................................................................................................................…3.34 Grupo Synchronism and Voltage Check; Grupo General

    ......................................................................................................................................................................................…3.35 Grupo Synchronism and Voltage Check; Grupo with AR

    ...................................................................................................................................................................…3.36 Grupo Synchronism and Voltage Check; Grupo Man.Close+CNTRL

    ...............................................................................................................................................................................................… 3.37 Grupo Voltage Protection; Grupo U> Phase-Earth

    ..............................................................................................................................................................................................… 3.38 Grupo Voltage Protection; Grupo U> Phase-Phase.....................................................................................................................................................................................................… 3.39 Grupo Voltage Protection; Grupo 3U0> or Ux>

    ...............................................................................................................................................................................................… 3.40 Grupo Voltage Protection; Grupo U> Postive Seq.

    ..............................................................................................................................................................................................… 3.41 Grupo Voltage Protection; Grupo U> Negative Seq

    ...............................................................................................................................................................................................… 3.42 Grupo Voltage Protection; Grupo U< Phase-Earth

    ..............................................................................................................................................................................................… 3.43 Grupo Voltage Protection; Grupo U< Phase-Phase

    ...............................................................................................................................................................................................… 3.44 Grupo Voltage Protection; Grupo U< Postive Seq.

    ............................................................................................................................................................................................................… 3.45 Grupo Fault Locator; Grupo Fault Locator 

    ..............................................................................................................................................................................................................................… 3.46 Grupo Trip Circuit Supervision

    7SA632 V4_7 Var_prn

    SIMATICELOR_SM / SE Juanjui / LT a Tocache / 7SA632 V4.7Var/7SA632 27.01.14 22:48:03

    Página 1 de 14

  • 8/19/2019 7SA632 Linea a Tocache

    2/14

    1 General Device Settings

    1.1 Grupo Device

    Grupo Device

    Nº Parámetro Valor Grupo

    0610 Fault Display on LED / LCD Display Targets on every Pickup todo

    0615 Spontaneous display of flt.annunciations NO todo

    0625A Minimum hold time of lachted LEDs 0 min todo

    0640 Start image Default Display image 1 todo

    7SA632 V4_7 Var_prnGeneral Device Settings

    SIMATICELOR_SM / SE Juanjui / LT a Tocache / 7SA632 V4.7Var/7SA632 27.01.14 22:48:03

    Página 2 de 14

  • 8/19/2019 7SA632 Linea a Tocache

    3/14

    2 Power System Data 1

    2.1 Grupo Power System Data 1; Grupo Transformers

    Grupo Power System Data 1; Grupo Transformers

    Nº Parámetro Valor Grupo

    0201 CT Starpoint towards Line todo

    0203 Rated Primary Voltage 138.0 kV todo

    0204 Rated Secondary Voltage (Ph-Ph) 100 V todo

    0205 CT Rated Primary Current 600 A todo

    0206 CT Rated Secondary Current   5A todo

    0210 U4 vol tage t ransformer is Usy2 trans former todo

    0211 Matching ratio Phase-VT To Open-Delta-VT 1.… todo

    0212 VT connection for Usy2 L1-L2 todo

    0214A Angle adjustment Usy2-Usy1 0 ° todo

    0215 Matching ratio Usy1 / Usy2 1.…   todo

    0220 I 4 current transformer is not connected todo

    0221 Matching ratio I4/Iph for CT's 1.0… todo

    2.2 Grupo Power System Data 1; Grupo Power System

    Grupo Power System Data 1; Grupo Power Sys tem

    Nº Parámetro Valor Grupo

    0207 System Starpoint is Solid Earthed todo

    0230 Rated Frequency 60 Hz todo

    0235 Phase Sequence L1 L2 L3 todo

    0236 Distance measurement unit km todo

    0237 Setting format for zero seq.comp. format Zero seq. comp. factors RE/RL and XE/XL todo

    0238A Earth Fau lt O/C : set ting for 1po le AR a ll s tages together todo

    2.3 Grupo Power System Data 1; Grupo Breaker 

    Grupo Power System Data 1; Grupo Breaker 

    Nº Parámetro Valor Grupo

    0239 Closing (operating) time of CB 0.06 sec todo

    0240A Minimum TRIP Command Duration 0.10 sec todo

    0241A Maximum Close Command Duration 0.10 sec todo

    0242 Dead Time for CB test-autoreclosure 0.10 sec todo

    7SA632 V4_7 Var_prnPower System Data 1

    SIMATICELOR_SM / SE Juanjui / LT a Tocache / 7SA632 V4.7Var/7SA632 27.01.14 22:48:03

    Página 3 de 14

  • 8/19/2019 7SA632 Linea a Tocache

    4/14

    3 Grupos de parámetros

    3.1 Grupo Power System Data 2; Grupo Power System

    Grupo Power System Data 2; Grupo Power Sys tem

    Nº Parámetro Valor Grupo

    1103 Measurement: Full Scale Voltage (100%) 138.0 kV A

    1104 Measurement: Full Scale Current (100%) 600 A A

    1105 Line Angle 74 ° A

    1211 Angle of inclination, d istance charact. 74 ° A

    1107 P,Q operational measured values sign not reversed   A

    1110 x' - Line Reactance per length unit 0.0434 Ohm / km A

    1111 Line Length 124.0 km A

    1116 Zero seq. c omp. factor RE/RL for Z1 0.… A

    1117 Zero seq. c omp. factor XE/XL for Z1 0.… A

    1118 Zero seq. comp.factor RE/RL for Z1B...Z5 0.…   A

    1119 Zero seq. comp.factor XE/XL for Z1B...Z5 0.… A

    3.2 Grupo Power System Data 2; Grupo Line Status

    Grupo Power System Data 2; Grupo Line Status

    Nº Parámetro Valor Grupo

    1130A Pole Open Current Threshold 0.50 A A

    1131A Pole Open Voltage Threshold 30 V A

    1132A Seal-in Time after ALL closures 0.05 sec A

    1133A minimal time for line open before SOTF 0.25 sec A

    1134 Recognition of Line Closures with Manual Close BI only A

    1135 RESET of Trip Command with Pole Open Current Threshold only A

    1136 open pole detector with measurement (U/I ,t rip,pickup,CBaux) A

    1140A CT Saturation Threshold 100.0 A A

    1150A Seal-in Time after MANUAL closures 0.30 sec A

    1151 Manual CLOSE COMMAND generation NO A

    1152 MANUAL Closure Impulse after CONTROL todo

    3.3 Grupo Power System Data 2; Grupo Trip 1-/3-pole

    Grupo Power System Data 2; Grupo Trip 1-/3-pole

    Nº Parámetro Valor Grupo

    1155 3 pole coupling with Trip A

    1156A Trip type with 2phase faults 3pole A

    3.4 Grupo Distance protect ion, general sett ings; Grupo General

    Grupo Distance protection, general settings; Grupo General

    Nº Parámetro Valor Grupo

    1201 Distance protection ON A

    1202 Phase Current threshold for dist. meas. 0.50 A A

    1211 Angle of inclination, d istance charact . 74 ° A

    1208 Series compensated line NO A

    1232 Instantaneous trip after SwitchOnToFault with Zone Z1B A

    1241 R load, minimum Load Impedance (ph-e) oo Ohm A

    1242 PHI load , maximum Load Angle (ph-e) 45 ° A

    1243 R load, minimum Load Impedance (ph-ph) oo Ohm A

    1244 PHI load, maximum Load Angle (ph-ph) 45 ° A

    1317A Single pole trip for faults in Z2 NO A

    7SA632 V4_7 Var_prnGrupos de parámetros

    SIMATICELOR_SM / SE Juanjui / LT a Tocache / 7SA632 V4.7Var/7SA632 27.01.14 22:48:03

    Página 4 de 14

  • 8/19/2019 7SA632 Linea a Tocache

    5/14

    Grupo Distance protection, general settings; Grupo General(2)

    Nº Parámetro Valor Grupo

    1357 Z1B enabled before 1st AR ( in t. or ext .) NO A

    3.5 Grupo Distance protect ion, general sett ings; Grupo Earth faults

    Grupo Distance protection, general settings; Grupo Earth faults

    Nº Parámetro Valor Grupo

    1203 3I0 threshold for neutral current pickup 0.50 A   A

    1204 3U0 thres hold z ero s eq. v oltage pickup 5 V A

    1207A 3I0>-pickup-stabi lisation (3I0> / Iphmax) 0.… A

    1209A criterion of earth fault recognition 3I0> OR 3U0> A

    1221A Loop selection with 2Ph-E faults block leading ph-e loop A

    3.6 Grupo Distance protect ion, general sett ings; Grupo Time Delays

    Grupo Distance protection, general settings; Grupo Time Delays

    Nº Parámetro Valor Grupo

    1210 Condition for zone timer start with distance pickup A

    1305 T1-1phase, delay for single phase faults 0.00 sec A

    1306 T1multi-ph, delay for multi phase faults 0.00 sec A

    1315 T2-1phase, delay for single phase faults 0.40 sec A

    1316 T2multi-ph, delay for multi phase faults 0.40 sec A

    1325 T3 delay 0.80 sec A

    1335 T4 delay 1.20 sec A

    1345 T5 delay oo sec A

    1365 T6 delay 1.50 sec A

    1355 T1B-1phase, delay for single ph. faults 0.00 sec A

    1356 T1B-multi-ph, delay for multi ph. faults 0.00 sec A

    3.7 Grupo Distance zones (quadri lateral); Grupo Zone Z1

    Grupo Distance zones (quadrilateral); Grupo Zone Z1

    Nº Parámetro Valor Grupo

    1301 Operating mode Z1 Forward A

    1302 R(Z1), Resistance for ph-ph-faults 5.217 Ohm A

    1303 X(Z1), Reactance 4.577 Ohm A

    1304 RE(Z1), Resistance for ph-e faults 6.957 Ohm A

    1305 T1-1phase, delay for single phase faults 0.00 sec A

    1306 T1multi-ph, delay for multi phase faults 0.00 sec A

    1307 Zone Reduction Angle (load compensation) 11 ° A

    3.8 Grupo Distance zones (quadrilateral); Grupo Zone Z1B-exten.

    Grupo Distance zones (quadrilateral); Grupo Zone Z1B-exten.

    Nº Parámetro Valor Grupo

    1351 Operating mode Z1B (overrreach zone) Forward A

    1352 R(Z1B), Resistance for ph-ph-faults 6.957 Ohm A

    1353 X(Z1B), Reactance 6.461 Ohm A

    1354 RE(Z1B), Resistance for ph-e faults 7.826 Ohm A

    1355 T1B-1phase, delay for single ph. faults 0.00 sec A

    1356 T1B-multi-ph, delay for multi ph. faults 0.00 sec A

    1357 Z1B enabled before 1st AR (int. or ext.) NO A

    7SA632 V4_7 Var_prnGrupo Distance protection, g eneral settings ; Grupo General

    SIMATICELOR_SM / SE Juanjui / LT a Tocache / 7SA632 V4.7Var/7SA632 27.01.14 22:48:03

    Página 5 de 14

  • 8/19/2019 7SA632 Linea a Tocache

    6/14

    3.9 Grupo Distance zones (quadri lateral); Grupo Zone Z2

    Grupo Distance zones (quadrilateral); Grupo Zone Z2Nº Parámetro Valor Grupo

    1311 Operating mode Z2 Forward A

    1312 R(Z2), Resistance for ph-ph-faults 6.957 Ohm A

    1313 X(Z2), Reactance 6.461 Ohm A

    1314 RE(Z2), Resistance for ph-e faults 7.826 Ohm A

    1315 T2-1phase, delay for single phase faults 0.40 sec A

    1316 T2multi-ph, delay for multi phase faults 0.40 sec A

    1317A Single pole trip for faults in Z2   NO A

    3.10 Grupo Distance zones (quadri lateral); Grupo Zone Z3

    Grupo Distance zones (quadrilateral); Grupo Zone Z3

    Nº Parámetro Valor Grupo

    1321 Operating mode Z3 Forward A

    1322 R(Z3), Resistance for ph-ph-faults 6.957 Ohm A

    1323 X(Z3), Reactance 12.196 Ohm A

    1324 RE(Z3), Resistance for ph-e faults 7.826 Ohm A

    1325 T3 delay 0.80 sec A

    3.11 Grupo Distance zones (quadri lateral); Grupo Zone Z4

    Grupo Distance zones (quadrilateral); Grupo Zone Z4

    Nº Parámetro Valor Grupo

    1331 Operating mode Z4 Reverse A

    1332 R(Z4), Resistance for ph-ph-faults 6.087 Ohm A

    1333 X(Z4), Reactance 2.231 Ohm A

    1334 RE(Z4), Resistance for ph-e faults 6.957 Ohm A

    1335 T4 delay 1.20 sec A

    3.12 Grupo Distance zones (quadri lateral); Grupo Zone Z5

    Grupo Distance zones (quadrilateral); Grupo Zone Z5

    Nº Parámetro Valor Grupo

    1341 Operating mode Z5 Non-Directional A

    1342 R(Z5), Resistance for ph-ph-faults 7.652 Ohm A

    1343 X(Z5)+, Reactance for Forward direction 13.415 Ohm A

    1344 RE(Z5), Resistance for ph-e faults 8.609 Ohm A

    1345 T5 delay oo sec A

    1346 X(Z5)-, Reactance for Reverse direction 6.708 Ohm A

    7SA632 V4_7 Var_prnGrupo Distance zones (quadrilateral); Grupo Zone Z1B-exten.

    SIMATICELOR_SM / SE Juanjui / LT a Tocache / 7SA632 V4.7Var/7SA632 27.01.14 22:48:03

    Página 6 de 14

  • 8/19/2019 7SA632 Linea a Tocache

    7/14

    3.13 Grupo Distance zones (quadri lateral); Grupo Zone Z6

    Grupo Distance zones (quadrilateral); Grupo Zone Z6

    Nº Parámetro Valor Grupo

    1361 Operating mode Z6 Inactive A

    1362 R(Z6), Resistance for ph-ph-faults 3.000 Ohm A1363 X(Z6)+, Reactance for Forward direction 3.000 Ohm A

    1364 RE(Z6), Resistance for ph-e faults 3.000 Ohm A

    1365 T6 delay 1.50 sec A

    1366 X(Z6)-, Reactance for Reverse direction 0.800 Ohm A

    3.14 Grupo Power Swing

    Grupo Power Swing

    Nº Parámetro Valor Grupo

    2002 Power Swing Operating mode all zones blocked A

    2006 Power swing trip NO A

    3.15 Grupo Teleprotection for Distance prot.

    Grupo Teleprotection for Distance prot.

    Nº Parámetro Valor Grupo

    2101 Teleprotection for Distance protection ON A

    2102 Type of Line Two Terminals A

    2103A Time for send signal prolongation 0.05 sec A

    2109A Transient Block.: Duration external flt. 0.10 sec A

    2110A Transient Block.: Blk.T. after ext. flt. 0.10 sec A

    2112A DIS transient block by EF YES A

    2113 Memorize receive signal NO A

    3.16 Grupo DTT Direct Transfer Trip

    Grupo DTT Direct Transfer Trip

    Nº Parámetro Valor Grupo

    2201 Direct Transfer Trip (DTT) ON A

    2202 Trip T ime Delay 0.05 sec A

    3.17 Grupo Instantaneous HighSpeed SOTF Overcurrent

    Grupo Instantaneous HighSpeed SOTF Overcurrent

    Nº Parámetro Valor Grupo2401 Inst. High Speed SOTF-O/C is ON A

    2404 I>>> Pickup 2.08 A A

    7SA632 V4_7 Var_prnGrupo Distance zones (quadrilateral); Grupo Zone Z6

    SIMATICELOR_SM / SE Juanjui / LT a Tocache / 7SA632 V4.7Var/7SA632 27.01.14 22:48:03

    Página 7 de 14

  • 8/19/2019 7SA632 Linea a Tocache

    8/14

    3.18 Grupo Weak Infeed (Trip and/or Echo)

    Grupo Weak Infeed (Trip and/or Echo)

    Nº Parámetro Valor Grupo

    2501 W eak Infeed function Echo and Trip A

    2502A Trip / Echo Delay after carrier receipt 0.04 sec A2503A Trip Extension / Echo Impulse t ime 0.05 sec A

    2504A Echo Block Time 0.05 sec A

    2505 Undervoltage (ph-e) 42 V A

    2509 Echo logic: Dis and EF on common channel YES todo

    3.19 Grupo Measurement Supervision; Grupo Balance / Summ.

    Grupo Measurement Supervision; Grupo Balance / Summ.

    Nº Parámetro Valor Grupo

    2901 Measurement Supervision ON A

    2902A Voltage Threshold for Balance Monitoring 50 V A

    2903A Balance Factor for Voltage Monitor 0.… A

    2904A Current Balanc e Monitor 2.50 A A

    2905A Balance Factor for Current Monitor 0.… A

    2906A Summated Current Monitoring Threshold 0.50 A A

    2907A Summated Current Monitoring Factor 0.… A

    2908A T Balance Factor for Voltage Monitor 5 sec A

    2909A T Current Balance Monitor 5 sec A

    3.20 Grupo Measurement Supervision; Grupo Fuse Fai l . Mon.

    Grupo Measurement Supervision; Grupo Fuse Fail. Mon.

    Nº Parámetro Valor Grupo

    2910 Fuse Failure Monitor ON A

    2911A Minimum Voltage Threshold U> 30 V A

    2912A Maximum Current Threshold I< 0.50 A A

    2913A Maximum Vol tage Threshold U< (3phase) 15 V A

    2914A Delta Current Threshold (3phase) 0.50 A A

    2915 Voltage Failure Supervision with current supervision A

    2916A Delay Voltage Failure Supervision 3.00 sec A

    3.21 Grupo Measurement Supervision; Grupo VT mcb

    Grupo Measurement Supervision; Grupo VT mcb

    Nº Parámetro Valor Grupo

    2921 VT mcb operating time 0 ms A

    3.22 Grupo Measurement Supervision; Grupo Load Angle

    Grupo Measurement Supervision; Grupo Load Angle

    Nº Parámetro Valor Grupo

    2941 Limit setting PhiA 200 ° A

    2942 Limit setting PhiB 340 ° A

    2943 Minimum value I1> 0.25 A A

    2944 Minimum value U1> 20 V A

    7SA632 V4_7 Var_prnGrupo Weak Infeed (Trip and/or Echo)

    SIMATICELOR_SM / SE Juanjui / LT a Tocache / 7SA632 V4.7Var/7SA632 27.01.14 22:48:03

    Página 8 de 14

  • 8/19/2019 7SA632 Linea a Tocache

    9/14

    3.23 Grupo Earth fault overcurrent; Grupo General

    Grupo Earth fault overcurrent; Grupo General

    Nº Parámetro Valor Grupo

    3101 Earth Fault overcurrent function ON A

    3102 Block E/F for D istance protection with every Pickup A3174 Block E/F for Distance Protection Pickup in zone Z1/Z1B A

    3103 Block E/F for 1pole Dead time YES A

    3104A Stabilisation Slope with Iphase 0 % A

    3105 3Io-Min threshold for Teleprot. schemes 0.50 A A

    3109 Single pole trip with earth flt.prot. YES A

    3170 2nd harmonic ratio for inrush restraint 15 % A

    3171 Max.Current, over riding inrush restraint 37.50 A A

    3172 Instantaneous mode after SwitchOnToFault with Pickup and direction A

    3173 Trip time delay after SOTF 0.00 sec A

    3.24 Grupo Earth fault overcurrent; Grupo 3I0>>>

    Grupo Earth fault overcurrent; Grupo 3I0>>>

    Nº Parámetro Valor Grupo

    3110 Operating mode Inactive A

    3111 3I0>>> Pickup 20.00 A A

    3112 T 3I0>>> Time delay 0.30 sec A

    3113 Instantaneous trip via Teleprot./BI NO A

    3114 Instantaneous trip after SwitchOnToFault NO A

    3115 Inrush Blocking NO A

    3.25 Grupo Earth fault overcurrent; Grupo 3I0>>

    Grupo Earth fault overcurrent; Grupo 3I0>>

    Nº Parámetro Valor Grupo

    3120 Operating mode Forward A

    3121 3I0>> Pickup 3.75 A A

    3122 T 3I0>> Time Delay 0.25 sec A

    3123 Instantaneous trip via Teleprot./BI NO A

    3124 Instantaneous trip after SwitchOnToFault NO A

    3125 Inrush Blocking NO A

    3.26 Grupo Earth fault overcurrent; Grupo 3I0>

    Grupo Earth fault overcurrent; Grupo 3I0>

    Nº Parámetro Valor Grupo

    3130 Operating mode Forward A

    3131 3I0> Pickup 0.50 A A3132 T 3I0> Time Delay 30.00 sec A

    3133 Instantaneous t rip v ia Teleprot. /BI NO A

    3134 Instantaneous trip after SwitchOnToFault NO A

    3135 Inrush Blocking YES A

    7SA632 V4_7 Var_prnGrupo Earth fault overcurrent; Grupo General

    SIMATICELOR_SM / SE Juanjui / LT a Tocache / 7SA632 V4.7Var/7SA632 27.01.14 22:48:03

    Página 9 de 14

  • 8/19/2019 7SA632 Linea a Tocache

    10/14

    3.27 Grupo Earth fault overcurrent; Grupo 3I0 InverseTime

    Grupo Earth fault overcurrent; Grupo 3I0 InverseTime

    Nº Parámetro Valor Grupo

    3140 Operating mode Forward A

    3141 3I0p Pickup 0.50 A A3143 3I0p Time Dial 0.18 sec A

    3147 Additional Time Delay 0.00 sec A

    3148 Ins tantaneous trip v ia Teleprot./BI NO A

    3149 Instantaneous trip after SwitchOnToFault NO A

    3150 Inrush Blocking NO A

    3151 IEC Curve Normal Inverse A

    3.28 Grupo Earth fault overcurrent; Grupo Direct ion

    Grupo Earth fault overcurrent; Grupo Direction

    Nº Parámetro Valor Grupo

    3160 Polarization with U0 + IY or U2 A

    3162A ALPHA, lower angle for forward direction 338 ° A

    3163A BETA, upper angle for forward direction 122 ° A

    3164 Min. zero seq.vol tage 3U0 for polar iz ing 1.4 V A

    3166 Min. neg . seq. polarizing vol tage 3U2 1 .4 V A

    3167 Min. neg . seq. polarizing current 3I2 0 .25 A A

    3168 Compensat ion angle PHI comp. for Sr 255 ° A

    3169 Forward di rec tion power threshold 1 .0 VA A

    3186A 3U0 min for forward direction 0.0 V A

    3187A Reactance X of ser ies capaci tor 0.000 Ohm A

    3.29 Grupo Teleprotection for Earth fault overcurr.

    Grupo Teleprotection for Earth fault overcurr.

    Nº Parámetro Valor Grupo

    3201 Telep rotec tion for Earth Fau lt O/C ON A

    3202 Line Configuration Two Terminals A

    3203A Time for send signal prolongation 0.00 sec A

    3209A Transient Block.: Duration external flt. 0.10 sec A

    3210A Transient Block.: Blk.T. after ext. flt. 0.10 sec A

    3212A EF transient block by DIS YES A

    3.30 Grupo Automatic Reclosure; Grupo General

    Grupo Automatic Reclosure; Grupo General

    Nº Parámetro Valor Grupo

    3401 Auto-Reclose function ON A3402 CB ready interr ogation a t 1st trip NO A

    3403 Reclaim time after successful AR cycle 11.00 sec A

    3404 AR blocking duration after manual close 10.00 sec A

    3406 Evolving faul t recognition w ith Trip A

    3407 Evolving fault (during the dead time) blocks AR A

    3408 AR start-signal monitor ing t ime 0.20 sec A

    3409 Circuit Breaker (CB) Supervision Time 3.00 sec A

    3410 Send delay for remote close command oo sec A

    3411A Maximum dead t ime extension oo sec A

    7SA632 V4_7 Var_prnGrupo Earth fault overcurrent; Grupo 3I0 InverseTime

    SIMATICELOR_SM / SE Juanjui / LT a Tocache / 7SA632 V4.7Var/7SA632 27.01.14 22:48:03

    Página 10 de 14

  • 8/19/2019 7SA632 Linea a Tocache

    11/14

    3.31 Grupo Automatic Reclosure; Grupo 1st AR-cyle

    Grupo Automatic Reclosure; Grupo 1st AR-cyle

    Nº Parámetro Valor Grupo

    3450 S tart o f AR a llowed in this cycle YES A

    3451 Action time 0.20 sec A3456 Dead time a fter 1pole trip 0 .50 sec A

    3457 Dead time after 3pole trip o o sec A

    3458 Dead t ime after evolv ing fault 0 .50 sec A

    3459 CB ready interrogation before reclosing NO A

    3460 Request for synchro-check after 3pole AR NO A

    3.32 Grupo Automatic Reclosure; Grupo 3pTRIP/DLC/RDT

    Grupo Automatic Reclosure; Grupo 3pTRIP/DLC/RDT

    Nº Parámetro Valor Grupo

    3430 3pole TRIP by AR YES A

    3431 Dead Line Check or Reduced Dead Time Without A

    3438 Supervision time for dead/ live voltage 0.10 sec A

    3440 Voltage threshold for l ive l ine or bus 48 V A

    3441 Voltage threshold for dead line or bus 30 V A

    3.33 Grupo Automatic Reclosure; Grupo Start AR with..

    Grupo Automatic Reclosure; Grupo Start AR with..

    Nº Parámetro Valor Grupo

    3420 AR with d istance protection YES A

    3421 AR with switch-onto-fault overcurrent NO A

    3422 AR with weak infeed tr ipping NO A

    3423 AR with earth fault overcurrent prot. YES A

    3424 AR wi th d irec t t rans fer trip NO A

    3.34 Grupo Synchronism and Voltage Check; Grupo General

    Grupo Synchronism and Voltage Check; Grupo General

    Nº Parámetro Valor Grupo

    3501 Synchronism and Voltage Check function ON A

    3502 Vol tage threshold dead l ine / bus 5 V A

    3503 Vol tage threshold l ive l ine / bus 90 V A

    3504 Maximum permis sible voltage 110 V A

    3507 Maximum duration of synchronism-check 180.00 sec A

    3508 Synchronous condition stability timer 0.30 sec A

    3509 Synchron izable c ircui t breaker INT todo

    7SA632 V4_7 Var_prnGrupo Automatic Reclosure; Grupo 1st AR-cyle

    SIMATICELOR_SM / SE Juanjui / LT a Tocache / 7SA632 V4.7Var/7SA632 27.01.14 22:48:03

    Página 11 de 14

  • 8/19/2019 7SA632 Linea a Tocache

    12/14

    3.35 Grupo Synchronism and Vol tage Check; Grupo wi th AR

    Grupo Synchronism and Voltage Check; Grupo with AR

    Nº Parámetro Valor Grupo

    3510 Operating mode with AR without consideration of CB closing time A

    3511 Maximum voltage difference 10.0 V A3512 Maximum frequency difference 0.10 Hz A

    3513 Maximum angle difference 20 ° A

    3515A AR at Usy2>, Usy1>, and Synchr. YES A

    3516 AR at Usy1< and Usy2> NO A

    3517 AR at Usy1> and Usy2< NO A

    3518 AR at Usy1< and Usy2< NO A

    3519 Override of any check before AR NO A

    3.36 Grupo Synchronism and Voltage Check; Grupo Man.Close+CNTRL

    Grupo Synchronism and Voltage Check; Grupo Man.Close+CNTRL

    Nº Parámetro Valor Grupo

    3530 Operating mode with Man.Cl without consideration of CB closing t ime A

    3531 Maximum voltage difference 10.0 V A

    3532 Maximum frequency difference 0.10 Hz A

    3533 Maximum angle difference 20 ° A

    3535A Manual Close at Usy2>, Usy1>, and Synchr YES A

    3536 Manual Close at Usy1< and Usy2> YES A

    3537 Manual Close at Usy1> and Usy2< YES A

    3538 Manual Close at Usy1< and Usy2< YES A

    3539 Override of any check before Man.Cl NO A

    3.37 Grupo Voltage Protection; Grupo U> Phase-Earth

    Grupo Voltage Protection; Grupo U> Phase-Earth

    Nº Parámetro Valor Grupo

    3701 Operating mode Uph-e overvoltage prot. Alarm Only A

    3702 Uph-e> Pickup 66.4 V A

    3703 T Uph-e> Time Delay 4.00 sec A

    3704 Uph-e>> Pickup 72.2 V A

    3705 T Uph-e>> Time Delay 1.10 sec A

    3709A Uph-e>(>) Reset ratio 0.… A

    3.38 Grupo Voltage Protection; Grupo U> Phase-Phase

    Grupo Voltage Protection; Grupo U> Phase-Phase

    Nº Parámetro Valor Grupo

    3711 Operating mode Uph-ph overvoltage prot. OFF A3712 Uph-ph> Pickup 150.0 V A

    3713 T Uph-ph> Time Delay 2.00 sec A

    3714 Uph-ph>> Pickup 175.0 V A

    3715 T Uph-ph>> Time Delay 1.00 sec A

    3719A Uph-ph>(>) Reset ratio 0.… A

    7SA632 V4_7 Var_prnGrupo Synchronism and Voltage Check; Grupo with AR

    SIMATICELOR_SM / SE Juanjui / LT a Tocache / 7SA632 V4.7Var/7SA632 27.01.14 22:48:03

    Página 12 de 14

  • 8/19/2019 7SA632 Linea a Tocache

    13/14

    3.39 Grupo Voltage Protect ion; Grupo 3U0> or Ux>

    Grupo Voltage Protection; Grupo 3U0> or Ux>

    Nº Parámetro Valor Grupo

    3721 Operating mode 3U0 (or Ux) overvoltage OFF A

    3722 3U0> Pickup (or Ux>) 30.0 V A3723 T 3U0> T ime Delay (or T Ux>) 2.00 sec A

    3724 3U0>> Pickup (or Ux>>) 50.0 V A

    3725 T 3U0>> Time Delay (or T Ux>>) 1.00 sec A

    3728A 3U0>(>): Stabilization 3U0-Measurement ON A

    3729A 3U0>(>) Reset ratio (or Ux) 0.… A

    3.40 Grupo Voltage Protect ion; Grupo U> Postive Seq.

    Grupo Voltage Protection; Grupo U> Postive Seq.

    Nº Parámetro Valor Grupo

    3731 Operating mode U1 overvoltage prot. OFF A

    3732 U1> Pickup 150.0 V A

    3733 T U1> Time Delay 2.00 sec A

    3734 U1>> Pickup 175.0 V A

    3735 T U1>> Time Delay 1.00 sec A

    3739A U1>(>) Reset ratio 0.… A

    3.41 Grupo Voltage Protect ion; Grupo U> Negative Seq

    Grupo Voltage Protection; Grupo U> Negative Seq

    Nº Parámetro Valor Grupo

    3741 Operating mode U2 overvoltage prot. OFF A

    3742 U2> Pickup 30.0 V A

    3743 T U2> Time Delay 2.00 sec A

    3744 U2>> Pickup 50.0 V A

    3745 T U2>> Time Delay 1.00 sec A

    3749A U2>(>) Reset ratio 0.… A

    3.42 Grupo Voltage Protection; Grupo U< Phase-Earth

    Grupo Voltage Protection; Grupo U< Phase-Earth

    Nº Parámetro Valor Grupo

    3751 Operating mode Uph-e undervoltage prot. OFF A

    3752 Uph-e< Pickup 30.0 V A

    3753 T Uph-e< Time Delay 2.00 sec A

    3754 Uph-e

  • 8/19/2019 7SA632 Linea a Tocache

    14/14

    3.43 Grupo Voltage Protection; Grupo U< Phase-Phase

    Grupo Voltage Protection; Grupo U< Phase-Phase

    Nº Parámetro Valor Grupo

    3761 Operating mode Uph-ph undervoltage prot. OFF A

    3762 Uph-ph< Pickup 50.0 V A3763 T Uph-ph< Time Delay 2.00 sec A

    3764 Uph-ph