Upload
prabraghu
View
214
Download
0
Embed Size (px)
Citation preview
8/3/2019 3_PHASE Solved Problems
1/3
Solved Problems
Example 1. 3 identical coils, each of resistance 20 and inductance 0.5H areconnected in star to a 3phase 400V, 50Hz supply. Determine the line current and thepower consumed.Data given:
R=20, L=0.5H, VL=400V, f=50Hz.
Vph =3
VL = .V94.2303
400
.45.127126.046.14003
126.0cos
cos3
)(sin46.134.158
94.23034.15807.15720
07.1575.05022tan
22
22
xxxP
lagZ
Rwhere
IVPconsumedpower
connectedstarceAII
Z
xxfLXcereacinductive
XRZimpadence
Z
VI
LL
PhL
L
L
ph
ph
Example 2. Three impedances each of (15+j20) are connected in mesh across a 3-phase 400V A.C supply. Determine the phase current, line current, active power andreactive power drawn from the supply.
Data Given Zph=(15+j20), VL=400V=Vph (deltaconnection) and IL= 3 IPh
Iph = ph
ph
Z
V
0
0122
13.5325
13.5315
20tan252015 andZph
.88.15352)13.53sin(7.274003sin3Re
.7.11514)13.53cos(7.274003cos3
7.271633
1625
400
VARxxxIVQractivepowe
WxxxIVpowerPActiv e
AxII
AZ
VI
LL
LL
PhL
ph
ph
ph
8/3/2019 3_PHASE Solved Problems
2/3
Example 3 A balanced 3phase star connected load of 150KW takes a leading currentof 100Amps with a line voltage of 1100V. Find the circuit constants of the load perphase.
Data given:P=150KW, IL=100A=IPh(star connection) VL=1100V, f=50Hz.
Given that current is leading, therefore circuit constants are resistance andcapacitance.
.10.8968.3502
1
2
1
2
1
968.3625.035.6sin
953.478.035.6costan
78.010011003
1000150
3cos
35.6100
08.635
08.6353
1100
3
4
22
FxxxfX
C
fCX
xZXalso
xZxceRresis
xx
x
xIxV
P
factorpower
I
VZalso
XRZimpadence
VV
V
C
C
C
LL
ph
ph
c
L
Ph
Example 4.Two wattcmeters are connected to measure power input to a 3phasebalanced circuit indicate 8KW and 0.8KW; the later reading being obtained afterreversing the current coil connection. Find i) power factor of the load. ii) Active poweriii) reactive power iv) apparent power
Data given: W1=8KW, W2= -0.8KW (because the reading is obtained after reversing the
current coil connection)
.86.16427.0
2.7
cos
24.15)(3Re
2.7)8.0(8
427.0
]}
))8.0(8(
))8.0(8(3[cos{tan
]})(
)(3[cos{tancosfactorPower
21
21
1
21
211
KVAKW
PowerApparent
KVARWWQpoweractive
KWWWPpowerActive
WW
WW
8/3/2019 3_PHASE Solved Problems
3/3
Example 5 Each of two wattmeters connected to measure the input to a 3phasesystem reads 10KW on a balanced load when the power factor is unity. What doeseach instrument reads when the power factor falls to i) 0.866 lagging ii) 0.5 leading thetotal 3phase power remaining unchanged.Data given: W1=W2=10KW, when pf is unity, i.e cos 0:1
Therefore total power =W1+W2=20KW (1)
i) When pf=0.866 lagging
ii) When pf=0.5 leadingKWandWKWWandSolving
KWWWor
WWei
WW
WW
67.633.13)2()1(
)2...(..........66.6
20
)(3577.0.
)(
)(3
577.030tantan
30866.0cos
21
21
21
21
21
01
KWandWKWWandSolving
KWWWor
WWei
WW
WW
99.1901.0)3()1(
)3...(..........99.1920
)(3732.1.
)(
)(3
732.160tantan
605.0cos
21
12
21
21
21
01