Bosnia and Herzegovina, Istanbul April 2010
Bosnia and Herzegovina, Istanbul, April 2010
1
"Examples of usage of HFC and ammonia systems in
public buildings and industry in Bosnia and Herzegovina"
Dr. sc. Gordana Tica, University of Banja Luka
Mr.sc. Fahrudin Kulić, University of Sarajevo
2
EXAMPLES AND HISTORY OF HFC EQUIPMENT IN BOSNIA AND HERZEGOVINA
• All A/C equipment sold and installed in Bosnia and Herzegovina that uses refrigerants (split systems, chillers) is imported, only some auxiliary components such as ducts, piping and vents are produced locally.
• Most of this equipment is supplied by large, globally leading manufacturers of HVAC equipment such as YORK, TRANE, CARRIER, McQUAY.
• Other low cost brands are also present in the market but mostly for split systems. Bosnia and Herzegovina, as an Article 5 country of the Montreal Protocol, was obligated to stop using CFCs by January 1st, 2010 and replace them with HCFCs.
• However, these companies have started much earlier than required to supply HCFC and even HFC equipment to Bosnia and Herzegovina.
• The main reason is that the market of Bosnia and Herzegovina is small so they deliver the equipment according to EU requirements (non-A5) even though they are not required to do so.
3
“Clima trade company” from Sarajevo, – is the authorized distributor of YORK equipment for Bosnia and
Herzegovina
A/C SPLIT SYSTEMS
• For the period 1997-2004, – employed exclusively R22 and approximately 3000 units were
sold in BiH.
• For the period 2005-2009, – employed R407c and approximately 3500 units were sold in BiH.
• For 2010– plans to sell around 400 split systems with HFCs (R407c and
R410a).
4
LARGE A/C SYSTEMS
– For the period 1997-2000, • employed exclusively R22 and approximately 40 units were
sold in BiH
– For the period 2000-2004 • employed R407c and approximately 60 units were sold in BiH
– For the period 2004-2009, YORK A/C • chillers with cooling capacity under 150 kW employed R407c• units above 150 kW employed R134a and approximately 80
units were sold in BiH
5
EXAMPLES OF HFC EQUIPMENT IN FBiH
-air cooled liquid chiller, cooling capacity 36 kW-
Refrigerant R407c:
1. Hotel Europa Garni, Sarajevo,, installed in 2003
2. Volksbank branch, Tuzla, installed in 2003
3. Hotel Bosnia, Sarajevo, installed in 2004
4. Avaz Twist Tower, Sarajevo, installed in 2009• air-cooled screw liquid chiller 570 kW cooling capacity, 3
units, refrigerant R134a
• air cooled liquid chiller, 70 kW cooling capacity, 2 units, refrigerant R407c
6
Figure 1. Avaz Twist Tower/tollest building in BiH, 175m
7
The next figure shows: a./the installation of the chiller
8
9
b./ the drawing of the installation area
Examples of HFC A/C equipments air cooled chiller has been provided by “Clima systems company” from Sarajevo, installed in 2009
• which is an authorized distributor of TRANE equipment for BiH,
1.Kumrovec Business and Shopping Centre,
1. 80 kW cooling capacity, 2 units, refrigerant R134a 2. 40 kW cooling capacity, refrigerant R407c
2. Alta Business and Shopping Centre,
1. 310 kW cooling capacity, 2 units, refrigerant R 134a
10
Figure 3. Buildings with TRANE HFC chillers
Alta Business and Shopping Centre Kumrovec Business and Shopping Centre 11
• According to the available information, in Sarajevo there was very little usage of CFCs in A/C equipment since the end of the war in 1995,– only HCFC and later HFC equipment has been installed.
• The equipment sold in the rest of the Federation of BiH used the same refrigerants.
• Sarajevo market is estimated at 1500 small split system annually and 20-50 large systems annually.
• YORK and LG equipment cover about 70% of the Sarajevo market, and rest of market are covered with McQuay, Ciat, Trane, Daikin, Carrier and low cost brands.
• Sarajevo market represents about 50% of the market in Federation of Bosnia and Herzegovina
12
A few factories in Republic of Srpska work in continuity:1.Brewery “Pivara”2.“Vitaminka”- factory for thermics treatment of food
(coagulation, cooling, storage), etc.3.“Levita”- factory for thermics treatment of food4.“Frigo”- factory for thermics treatment of food
The big stores, with big refrigerant consumption:1.“Tempo”2.“Merkator 3.Interex”4.“Pevec” itd.
13
Big consumption of cooling energy, i.e. refrigerants, hotels:
1. Hotel “Bosna” in the centre of town.
Big construction works that finished lately that on next objects in RS:
1. Building for Government2. Ministry buildings3.Television building and building
Alternative TV4. GP “Elektrodistribucija”
14
.
All above mentioned works on bigger objects were performed by leading companies for A/C and cooling systems from Banja Luka.
This paper mainly covers the capital and bigger companies.
15
I.
In a brewery, “Pivara” – refrigerant NH3 has been used as a main refrigerant
ever since the company was open (first beer production factory).
16
• the factory owns the following equipment in which the refrigerant is:
R-22, R-134 A, and R-404a
1. A/C equipment - producer LG and YORK– Installated insade “Pivara”
- installed: 52 units ( 32 LG + 20 YORK )- middle cooling capacity: 1500 W - refrigerant : R 22- installation period 2005 - 2010 year
17
2. Engine for beer infusion from barrels
– Installated in hotel-objects in RS and FBiH
- producer : VIČELI Italy , OTPREMA
Ludbreg, CRO- install : 700 parts.- middle cooling capacity: 1000 W- refrigerant: 134 a- installation period : 1976 - 2010.
18
3. . Refrigerant show case – installated in hotel-objects in RS and FBiH
- producer: UGUR Turky . LTH Slovenia- install: 2500 parts- middle cooling capacity: 1200 W - refrigerant: 134 a- installation period : 1996 - 2010 .
4. Compressed air drier – installated in compr. station
- producer : ATLAS COPCO Belgium- install : 2 parts.- middle cooling capacity: 8050 W- refrigerant: R 404 a ( 16 kg )- installation period : 1998.
19
II. “Vitaminka”
• In process of thermic treatments, the factory has been using NH3.
• in production process, – are built 2 piston compressors Bitzer, evaporator and
condensator
– Used R-407C
20
III.Maxi -delta market “Tempo”
There are two units for cooling built:1. compressors with cooling capacity of 36,8kW, ti/tk
(-35/+45oC). Refrigerent: R-404A
2. compressors with cooling capacity of 197 kW, ti/tk (-10/+45oC). Refrigerent: R-404A.
21
22
Company “ HOLLODEX” •is legal reperesentativer by firm YORK:
• time period from 1999 -2003:
Typ -unit MINI-SPLIT
Cooling capacity 2500 kW
Number of units Cca 550
refrigeration R-22
• time period from 2003-2008:
Typ unit MINI-SPLIT MINI-SPLIT Chiller Chiller
Cooling capacity 700 kW 2000 kW 1000 kW 60 kW
Number of units Cca 200 Cca 500 Cca 12 Cca 3
refrigeration R-22 R-407 R-407 R-410
23
•time period from 2009 - april 2010
Typ unit MINI-SPLIT MINISPLIT Chiller Chiller
Cooling capacity 300 kW 150 800 kW 400 kW
Built, year 2009 - APRIL 2010
Number of units Cca 70 Cca 30 Cca 5 Cca 5
refrigeration R-407 R-410 R-407 R-410
Company “KOSMITEH”, Banja Luka, • an official representative of the firm has “CARRIER”
performed the following works:
A/C SPLIT SYSTEMS- For period 1997-2004
• employed exclusively R22 – approximately 1800 units were sold in RS, power 3,5 to
3,8 kW.– For period 2005-2009
• approximately 1000 units were sold in RS, employed R22 (cca700) and R407c (cca300).
- For 2010, • around 100 split systems with HFCs (R407c and R410a).
24
LARGE A/C SYSTEMS
– For the period 1997-2002, “• employed exclusively R22 • approximately 50 units were sold in RS, power from 40 to
160 kW.
– For the period 2002-2004, • employed R407c • approximately 50 units with cooling capacity up 40 kW sold
in RS.
– For the period 2004-2009, • cooling capacity from 40 to 750 kW employed R410 a and
R134 a, approximately 80 units were sold in RS.
25
• List of installed “CARRIER” HFC equipments in RS:
1. Elektroprivreda Trebinje, heat pump, 2 x 240 kW, refrigerant R407c, installed in 2003
2. Narodno pozorište, Banja Luka, 1 x 140 kW cooling capacity, chiller , refrigerant R407c, installed in 2003
3. Building for Uprava indirektnog oporezivanja, I part, 2 x 70 kW, 1 x 40 kW, refrigerant R407c, heat pump, 2004
4. Hotel “Bosna”, cooling capacity 1 x x160 kW, and 1 x 60 kw, refrigerant R407c, 2005 to today.
5. MUP RS Banja luka 2x240, tp, chiller, 407c, 2004.6. Robna kuća “Damjan”, heat pump, cooling capacity 1x115vkW,
refrigerant R407c, 2005
26
7. Robna kuća “Beneton”, heat pump, cooling capacity 66kW, refrigerant R407c, 2005
8. Robna kuća “Merkator”, Gradiška, cooling system, cooling capacity 262kW, refrigerant R410a, 2009
9. “Takovo”, Trebinje, Tool industry, cooling capacity 300 kW, refrigerant R410a, 2010
10. Integra “Termomontaža”, cooling system, 2 x 750 kW, refrigerant R134a, 2010.
11. Salon automobile “Vidović”, heat pump, cooling capacity 1x115vkW, refrigerant R407c, 2006/07.
12. Park “Petar Kočić”, heat pump, cooling capacity 1x115vkW, refrigerant R407c, 2007
13. Auto servis “Luburić, heat pump, cooling capacity 70 kW, refrigerant R407c, 2007
14. Mali “Merkator” na Starčevići , heat pump, cooling capacity 70 kW, refrigerant, R407c, 2008
15. Alf-om, poslovna jedinica, cooling capacity 1x200 kW and 1x 160 kW,2006
16. Kulturni centar, Gradiška , cooling capacity 300 kW, refrigerant R410a, 2007.
17. Robna kuca “Best”, 140 kW chiler R407c, 2008.27
28
“Termomonaža”, contractor
• Difference provider by equipments
1. Typ unit Chiller
2. Cooling capacity 102.6 kW 125 kW 486 kW 275 kW 444 kW 291 kW
3. Producer "YORK" "YORK" "CARRIER" “CLIMAVENETA”
"CARRIER" “HITACHI”
4. Place of built AQUA PARK, BANJA LUKA
PO RAIFFEISEN BANKA, B. LUKA
ZGRADA VLADE RS, B. LUKA
DOM KULTURE, M. GRAD
TC „PEVEC“, B. LUKA
FOND ZDRAVSTVENOG OSIGURANJA RS, B. LUKA
5. Built, year 2006 2006 2007 2007 2008 2008
6. Number of units 1 1 3 1 2 17. refrigeration R407C R407C R134A R410A R134A R134A
29
Typ unit With air cooling machine, typ 30RB0602
With air cooling machine, typ 30XA0752
Cooling agregat, typ KVA/Y/SSL 3602-B SPU
Chiller typ YLAE-HP0480
Cooling capacity 524 kW 706 kW 806 kW 469 kW
Producer "CARRIER" "CARRIER" “HIDRIA” “”
Place of built Hemofarm, B. LUKA
INTEGRA, B. LUKA
TC “MERCATOR”, B. LUKA
PRIVREDNI SUD, B. LUKA
Built, year 2008 2009 2009 2010
Number of units 1 2 2 1
refrigeration R134A R134A R134A R410A
• Uplift chillers
30
• Lift up the chillers to goverment building in Banja Luka
31
32
33