NFPA 80 – Fire Doors Russell J Corriveau CFDI, CAI, RL

Fire Doors - NFPA 80

Embed Size (px)

Citation preview

NFPA 80 – Fire Doors

Russell J Corriveau CFDI, CAI, RL

Copyright © 2016, 2017 ASSA ABLOY Sales and Marketing Group, Inc., an ASSA ABLOY Group company.. All

rights reserved. Reproduction in whole or in part without the express written permission of ASSA ABLOY Sales

and Marketing Group, Inc. is prohibited.

NFPA 80:

Swing Fire Doors & NFPA 101:

Delayed Egress Devices20170429 R1

Fire Door Overview

±

±

×

×

6.4.4 Locks or Latches.

6.4.4.2.2 Fire exit hardware shall have a permanently attached

label that bears the serial number and shows the manufacturer’s

name and type of approval. 60

Chapter 6 Swinging Doors with Builders Hardware6.4.4.2.2 Fire exit hardware

60 Copyright 2015 NFPA 80 2013 Edition Chapter 6.4.4.2.2

Fire Exit Hardware must be labeled with Serial Number,

Manufacturer and type of approval.

6.4.4 Locks or Latches.

6.4.4.2.3 The label shall differentiate between panic

hardware, which is not acceptable for use on fire

doors, and fire exit hardware. 61

Panic HardwareFire Exit Hardware

Chapter 6 Swinging Doors with Builders Hardware6.4.4.2.3 The label shall differentiate

61 Copyright 2015 NFPA 80 2013 Edition Chapter 6.4.4.2.3

Labels for Panic and Fire Rated Device must be different and

Panic Hardware can not be used on Fire Rated Doors.

4.5.3.1 Number of Means of Egress. Two

means of egress, as a minimum, shall be

provided in every building or structure,

section, and area where size, occupancy, and

arrangement endanger occupants attempting

to use a single means of egress that is

blocked by fire or smoke. The two means of

egress shall be arranged to minimize the

possibility that both might be

rendered impassable by the same emergency

condition.

A minimum of 2 means of egress are required for all occupied

building and structures.

13 Point Fire Door Inspection Check list

1) Labels are clearly visible and legible.

2) No open holes or breaks exist in surfaces of either the door or frame.

3) Glazing, vision light frames, & glazing beads are intact and securely

fastened in place, if so equipped

4) The door, frame, hinges, hardware, and noncombustible threshold are

secured, aligned, and in working order with no visible signs of damage.

5) No parts are missing or broken.

6) Door clearances do not exceed clearances listed in 4.8.4 and 6.3.1.7.

7) The self-closing device is operational; that is, the active door

completely closes when operated from the full open position.

13 Point Fire Door Inspection Check list

8) If a coordinator is installed, the inactive leaf closes before the active

leaf.

9) Latching hardware operates and secures the door when it is in the

closed position.

10) Auxiliary hardware items that interfere or prohibit operation are not

installed on the door or frame.

11) No field modifications to the door assembly have been performed

that void the label.

12) Meeting edge protection, gasketing and edge seals, where

required, are inspected to verify their presence and integrity.

13) Signage affixed to a door meets the requirements listed in 4.14.