CLIENT
VICINITY MAP
PROJECT
LOCATION
SAN SIMEON
BRADLEY
SAN MIGUEL
PASO ROBLES
TEMPLETON
ATASCADERO
CAYUCOS
CAMBRIA
LOS
OSOS
MORRO
BAY
o
101
1
1
P
A
C
I
F
I
C
O
C
E
A
N
MONTEREY COUNTY
SANTA BARBARA COUNTY
KERN COUNTY
AVILA BEACH
PISMO BEACH
ARROYO GRANDE
NIPOMO
GROVER BEACH
SANTA MARIA
CUYAMA
SHANDON
46
46
41
SAN LUIS OBISPO
CITY OF MORRO BAY/CAYUCOS SANITARY DISTRICT
WASTEWATER TREATMENT PLANT
HEADWORKS IMPROVEMENTS
REVIEWED BY:
REVIEWED BY:
PO BOX 1604
ARROYO GRANDE, CA 93421 (805) 904-6530
Know what's
R
JUNE 11, 2014
1 10
DATE
OF
SHEET
G-1
PROJECT
WASTEWATER
TREATMENT PLANT
HEADWORKS
IMPROVEMENTS
ROB LIVICK, PE/PLS DATE
DATE
Eileen K. Shields, PE
No. C74757 Exp. 12/31/2015
ENGINEER OF RECORD
AREA MAP
PUBLIC SERVICES DIRECTOR/CITY ENGINEER
OWNER FURNISHED
EQUIPMENT STORAGE AREA
MCC ROOM
MOTOR ROOM
CONTRACTOR
STAGING AREA
SCREENINGS AREA
ATASCADERO ROAD
CITY OF MORRO BAY
/ CAYUCOS SANITARY
DISTRICT
DATE
DESCRIPTION
REV
14 23
APPR
PROJECT ENGINEER
REG NUMBER
EXP DATE
DATE:
DESIGNED:
APPROVED:
CHECKED:
DETAILED:
SHEET
0 11/2
CIT
Y O
F M
OR
RO
BA
Y/C
AY
UC
OS
SA
NIT
AR
Y D
ISTR
ICT
WA
STE
WA
TER
TR
EA
TME
NT
PLA
NT
HE
AD
WO
RK
S IM
PR
OV
EM
EN
TS
Know what's
R
JUNE 11, 2014
PO B
OX
160
4A
RRO
YO G
RAN
DE,
CA
934
21
(80
5) 9
04-6
530
ES/JH
ES/RL
JH
EILEEN K. SHIELDS
C74757
12/31/2015
G-2
1. LOCATE AND PROTECT EXISTING UTILITIES AND
STRUCTURES.
2. VERIFY DIMENSIONS AND CONDITIONS AT THE SITE BEFORE
STARTING WORK. PROMPTLY REPORT ANY CONFLICT
BETWEEN DETAILS OR DIMENSIONS ON THE DRAWINGS TO
THE OWNER'S REPRESENTATIVE.
3. LOCATIONS OF UTILITIES AND STRUCTURES SHOWN ON THE
PLANS HAVE BEEN DETERMINED BY AVAILABLE
INFORMATION. CONTRACTOR SHALL VERIFY BEFORE
STARTING WORK AND PROMPTLY NOTIFY OWNER'S
REPRESENTATIVE OF ANY DISCREPANCIES.
4. RESTORE ALL PAVEMENT, CONCRETE, ASPHALT, GRAVEL
AND DRIVEWAY SURFACES REMOVED OR DAMAGED DURING
CONSTRUCTION. SURFACES SHALL BE RESTORED IN-KIND
UNLESS INDICATED OTHERWISE.
5. MAINTAIN ON SITE THE LATEST SIGNED CONSTRUCTION
DOCUMENTS AT ALL TIMES. MAINTAIN A COMPLETE AND
ACCURATE RECORD OF ALL CHANGES IN CONSTRUCTION
FROM THAT SHOWN ON THE PLANS AND SPECIFICATIONS
FOR THE PURPOSE OF PROVIDING A BASIS FOR RECORD
DRAWINGS. NO CHANGES SHALL BE MADE WITHOUT PRIOR
WRITTEN APPROVAL OF THE OWNER'S REPRESENTATIVE.
6. FURNISH AND MAINTAIN CHEMICAL TOILETS FOR USE BY
WORKERS AND SUBCONTRACTORS. COORDINATE
LOCATION WITH OWNER'S REPRESENTATIVE.
7. PREVENT CONSTRUCTION TRAFFIC FROM TRACKING
SEDIMENT ONTO ROADWAYS.
8. MAINTAIN OWNER ACCESS TO PROJECT SITE THROUGHOUT
CONSTRUCTION.
9. ALL SPECIFICATIONS, DRAWINGS, AND DETAILS INCLUDED IN
THE CONTRACT DOCUMENTS SHALL FULLY APPLY TO THE
WORK WHETHER SPECIFICALLY REFERENCED OR NOT.
10. PROVIDE VIDEO TO DOCUMENT THE PRE-EXISTING
CONDITIONS OF THE PROJECT SITE AND SURROUNDING
ARES. SUBMIT THE VIDEO TO THE CITY PRIOR TO THE START
OF CONSTRUCTION.
11. MAINTAIN THE WORK AREA IN A NEAT, CLEAN AND SANITARY
CONDITION AT ALL TIMES AND TO THE SATISFACTION OF
THE OWNER.
12. SEE AREA MAP ON SHEET G-1 FOR THE APPROXIMATE
LIMITS OF CONTRACTOR STAGING AREA AND
OWNER-FURNISHED EQUIPMENT STORAGE AREA. VERIFY
LOCATIONS AND LIMITS WITH CITY PRIOR TO START OF
WORK. MAINTAIN MINIMUM 10-FOOT SETBACK FROM
EXISTING STRUCTURES.
GENERAL NOTES:
GE
NE
RA
L N
OT
ES
, A
BB
RE
VIA
TIO
NS
, A
ND
S
HE
ET
IN
DE
X
1. THE PROJECT HAS BEEN DESIGNED TO MINIMIZE THE
POTENTIAL NEED FOR BYPASS PUMPING. THE CITY CAN
PLACE STOP GATES IN THE CHANNEL TO AID THE
CONTRACTOR DURING WORK IN THE BAR SCREEN
CHANNEL. SEE SPECIFICATION SECTION 015800. THE
CONTRACTOR SHALL COORDINATE WITH THE OWNER'S
REPRESENTATIVE TO EVALUATE THE DIVERSION
CAPABILITIES, SCHEDULE AND AVAILABILITY. PROVIDE A
MINIMUM OF 72 HOURS NOTICE PRIOR TO THE NEED FOR
CHANNEL DIVERSION. SHOULD THE CONTRACTOR
DETERMINE THAT SEWAGE BYPASSING IS REQUIRED TO
COMPLETE THE PROJECT, THE CONTRACTOR SHALL
CONFORM TO THE REQUIREMENTS IN SPECIFICATION
SECTION 015800.
2. CONTRACTOR WILL BE LIABLE FOR FINES AND OTHER
COSTS ASSOCIATED WITH SEWAGE SPILLS BY THE
CONTRACTOR OR OTHER PROBLEMS CAUSED BY
INADEQUATE FLOW HANDLING BY THE CONTRACTOR.
SEWAGE FLOW HANDLING AND BYPASSING
AA AERATION AIR
IA INSTRUMENT AIR
SA SERVICE AIR
D DRAIN
2W UNDISINFECTED PROCESS WATER
3W DISINFECTED PROCESS WATER
W POTABLE WATER
WW WASTEWATER (RAW)
SERVICE ABBREVIATIONS
SCR MECHANICALLY-CLEANED SCREEN
HLS HIGH LEVEL SWITCH
LE ULTRASONIC LEVEL SENSOR
PROCESS EQUIPMENT AND INSTRUMENTATION
2 OF 10
SHEET SHEET SHEET
NUMBER TITLE DESCRIPTION
1 G-1
2 G-2
3 C-1
4 C-2
5 C-3
6 E-1
7 E-2
8 E-3
9 E-4
COVER SHEET
GENERAL NOTES, ABBREVIATIONS, AND INDEX SHEET DEMOLITION PLAN
SITE PLAN
CIVIL DETAILS
GENERAL ELECTRICAL NOTES AND LEGEND
SINGLE LINE DIAGRAM
SCREENING AREA ELECTRICAL PLAN
ELECTRICAL PLANS, MOTOR ROOM, AND MCC ROOM
ELECTRICAL DETAILS
SHEET INDEX
10 E-5
MECHANICALLY-CLEANED
BAR SCREEN AND LOCKOUT
PANEL/PEDESTAL
SLUICE GATE
HIGH
LEVEL SWITCH
SLUICE GATE
SLUICE GATE
OPERATOR
SERVICE AIR
RECEIVER
SHEAR BOX DIFFUSER,
TYP. OF 8
AUTO
SAMPLER
CLEANOUT FOR
BUBBLER LINE
TYP. OF 3
SLUICE GATE
GRINDER AND
TRAVELING SCREEN
A
C-1
SHEAR BOX DIFFUSER,
TYP. OF 8
P
P
P
P
P
D 3
D S
A
D S
A 4
GRINDER
CONTROLS D
S
SAMPLER
CONDUITP
4
SCREENINGS
AREA
4
4
SLIDE
GATES
PRESSURE TRANSDUCER
ULTRASONIC TRANSDUCERP
SLIDE GATE,
TYP OF 6
GRATING,
TYP.
SLIDE GATE
STORAGE AREA
S
EXISTING
MECHANICALLY-CLEANED
BAR SCREEN
SLUICE GATE
MECHANICAL CRANE
4
D
PUMP INLET
CHANNEL
VORTEX SUPPRESSOR
SHEAR BOX
DIFFUSER TYP.
P
P
D 3
A
4A
PRESSURE
TRANSDUCERP
ULTRASONIC
TRANSDUCER
P
S
DATE
DESCRIPTION
REV
14 23
APPR
PROJECT ENGINEER
REG NUMBER
EXP DATE
DATE:
DESIGNED:
APPROVED:
CHECKED:
DETAILED:
SHEET
0 11/2
CIT
Y O
F M
OR
RO
BA
Y/C
AY
UC
OS
SA
NIT
AR
Y D
ISTR
ICT
WA
STE
WA
TER
TR
EA
TME
NT
PLA
NT
HE
AD
WO
RK
S IM
PR
OV
EM
EN
TS
Know what's
R
JUNE 11, 2014
PO B
OX
160
4A
RRO
YO G
RAN
DE,
CA
934
21
(80
5) 9
04-6
530
ES/JH
ES/RL
JH
EILEEN K. SHIELDS
C74757
12/31/2015
C-1
DE
MO
LIT
IO
N P
LA
N
Scale: 1 inch:3 feet
SITE PLAN
1
Scale: 1 inch:3 feet
CROSS SECTION
A
CONSTRUCTION NOTES: KEY NOTES:
A ABANDON
C CITY TO REMOVE
D DEMOLISH AND DISPOSE
P PROTECT IN PLACE
S SALVAGE AND DELIVER TO CITY
1. SEE SPECIFICATION SECTION 024100 FOR DEMOLITION AND
PROTECTION OF EXISTING UTILITIES.
2. VERIFY DIMENSIONS AND CONDITIONS AT THE SITE BEFORE
STARTING WORK. PROMPTLY REPORT ANY CONFLICT BETWEEN
DETAILS OR DIMENSIONS ON THE DRAWINGS TO THE OWNER'S
REPRESENTATIVE.
3. REMOVE MECHANICALLY-CLEANED SCREEN AND APPURTENANCES.
SALVAGE BAR RACK AND DELIVER TO CITY. DEMOLISH AND
DISPOSE OF REMAINING MECHANICALLY-CLEANED SCREEN AND
APPURTENANCES. REMOVE AND DISPOSE OF GROUTING AND
CONCRETE SCREEN SUPPORTS IN CHANNEL AND REPAIR TO FORM
SMOOTH CHANNEL WALLS. THERE EXISTS AN AREA OF EXTENDED
CHANNEL WIDTH IN THE LOCATION OF THE EXISTING
MECHANICALLY-CLEANED SCREEN. THE DIMENSIONS OF EACH
EXTENSION IS APPROXIMATELY 7 INCHES BY 6 FEET FOR FULL
DEPTH OF CHANNEL. RESTORE CHANNEL WALLS TO 3 FOOT WIDTH.
INSTALL #4 EPOXY COATED REBAR 12 INCHES ON CENTER EW.
OVERLAP 12 INCHES MINIMUM. BEND VERTICAL BARS 90°, 6 INCHES
AT TOP AND TIE TO HORIZONTAL BARS. DRILL AND EPOXY 6-INCH
DEEP MINIMUM, CENTERED IN CUT OUT. ENSURE MINIMUM 2-INCH
CONCRETE COVERING OVER REBAR. FORM AND PLACE CONCRETE
TO PROVIDE SMOOTH, UNIFORM CHANNEL WALL. USE TYPE II/V
CEMENT. CONCRETE SHALL HAVE MINIMUM COMPRESSIVE
STRENGTH FC=3,000 PSI. FINISH SURFACE BY REPAIRING
DEFECTIVE CONCRETE, REMOVING FINS, FILLING DEPRESSIONS
1/16 INCH OR DEEPER, FILLING TIE HOLES, REMOVING MORTAR
SPLATTER AND REMOVING BULGES HIGHER THAN 1/16 INCH.
4. REMOVE, SALVAGE AND DELIVER TO CITY TWO SLUICE GATE
OPERATORS AND ASSOCIATED ABOVE-DECK HARDWARE.
DEMOLISH, REMOVE, AND DISPOSE OF TWO 6-INCH SLUICE GATES
AND ASSOCIATED BELOW-DECK HARDWARE. PLUG EXISTING 6-INCH
DRAINS WITH SANDBAG MINIMUM 1 FOOT FROM CHANNEL WALL.
FILL 6-INCH DRAIN PIPE BETWEEN PLUG AND CHANNEL WITH
NON-SHRINK GROUT. APPLY SMOOTH FINISH TO EXPOSED
NON-SHRINK GROUT AT CHANNEL AND INTEGRATE WITH ADJACENT
CHANNEL WALL. FILL 24-INCH DRAIN WITH 2-SACK SLURRY. APPLY A
STIFF BRISTLE BROOM FINISH AT DECK SURFACE AND INTEGRATE
WITH ADJACENT CONCRETE SURFACE.
3 10OF
CHANNEL (UNISTRUT P1000,
OR EQ) MOUNT TO WASH PRESS LOCAL
CONTROL STATION MOUNTING STAND
HIGH
LEVEL SWITCH
SLUICE GATE
SLUICE GATE
OPERATOR
SERVICE AIR
RECEIVER
AUTO
SAMPLER
WASHING PRESS
SLUICE TROUGH
11.1 FT 7.31 FT
HLS-2
LE-3LE-4
SCR-2
5F
T O
C T
YP
.
SCR-1
HLS-1
LE-1
A
C-2
LE-2
NEW 2"-3W CONNECT
TO EXISTING 2"-3W
3
NEW 2"-3W3
NEW 4"-D
6
NEW 2"-3W3
WASHING PRESS LOCAL
CONTROL STATION
4
NEW ALUMINUM
GRATING9
SCREENINGS
AREA
SLIDE GATE
STORAGE AREA
SLUICE GATE
MECHANICAL CRANE
PUMP INLET CHANNEL
EL 105.00
11.1 FT
WASHING PRESS1
EL 99.50
SCREENINGS BAGGER1
4.23 F
T
SCREENING
CONTAINER
(BY OTHERS)
3/4" EPOXY ANCHOR,
316 SST, TYP. OF 2
SCR-11
PIPE SUPPORT, MOUNT TO WASH
PRESS LOCAL CONTROL STATION
MOUNTING STAND PER DETAIL
3/C-3
1
WASHING PRESS1
SLUICE TROUGH
FILL CHANNEL POCKET
WITH NON-SHRINK GROUT,
FLUSH WITH INVERT OF
CHANNEL
3.96 FT
FRONT OF SCREEN
LEVEL
SENSOR,TYP.
NEW 4"-D 4
GRATING 5
EFFLUENT
CHANNEL
NEW 2"-3W
7
LEVEL
SENSOR,TYP.
GRATING9
ULTRASONIC
TRANSDUCERP
PRESSURE
TRANSDUCER P
8-INCH SDR-35 PVC
DROP PIPE PER
DETAIL 5/C-3
DATE
DESCRIPTION
REV
14 23
APPR
PROJECT ENGINEER
REG NUMBER
EXP DATE
DATE:
DESIGNED:
APPROVED:
CHECKED:
DETAILED:
SHEET
0 11/2
CIT
Y O
F M
OR
RO
BA
Y/C
AY
UC
OS
SA
NIT
AR
Y D
ISTR
ICT
WA
STE
WA
TER
TR
EA
TME
NT
PLA
NT
HE
AD
WO
RK
S IM
PR
OV
EM
EN
TS
Know what's
R
JUNE 11, 2014
PO B
OX
160
4A
RRO
YO G
RAN
DE,
CA
934
21
(80
5) 9
04-6
530
ES/JH
ES/RL
JH
EILEEN K. SHIELDS
C74757
12/31/2015
C-2
SIT
E P
LA
N
Scale: 1 inch:3 feet
SITE PLAN
1
Scale: 1 inch:3 feet
SCREEN CHANNEL SECTION
A
CONSTRUCTION NOTES:
1. INSTALL OWNER FURNISHED SCR-1 AND SCR-2, SLUICE
TROUGH, WASHING PRESS, LOCAL CONTROL STATION,
CONTROL PANEL, LEVEL SENSORS AND SWITCHES, AND ALL
ASSOCIATED APPURTENANCES PER MANUFACTURER'S
RECOMMENDATIONS AND SPECIFICATION SECTIONS 016400
AND 400200.
2. LOCATIONS SHOWN FOR LEVEL SENSORS AND SWITCHES ARE
APPROXIMATE. MAINTAIN MINIMUM CLEARANCE FROM
SCREEN OF 3 FEET PER MANUFACTURER'S
RECOMMENDATION. COORDINATE FINAL LOCATION OF LEVEL
SENSORS AND SWITCHES WITH CITY. INSTALL ULTRASONIC
TRANSDUCER PER DETAIL 2/C-3. INSTALL HIGH-LEVEL SWITCH
AT ELEVATION 102.5 FEET PER MANUFACTURE'S
RECOMMENDATIONS. PROVIDE AND INSTALL STAINLESS
STEEL MOUNTING HOOK ASSEMBLY (CONERY MHG 1 HB, OR
EQUAL) FOR CABLE SUPPORT. PROVIDE AND INSTALL
3/16-INCH SST CHAIN AND CONNECT TO FLOAT CABLE WITH
MINIMUM TWO 1/4-INCH SST CABLE CLIPS.
3. PROVIDE AND INSTALL 2”-3W PER SPECIFICATION SECTION
402053. CONNECT TO EXISTING 2”-3W SUPPLY AT EXISTING
VALVE AND INSTALL 2"-3W AND BASKET STRAINER PER DETAIL
4/C-3. PROVIDE AND INSTALL FRAMING CHANNEL PIPE CLAMPS
(UNISTRUT P1117 OR EQUAL) ALONG WALL TO SECURE 2”-3W
LINE. CONTRACTOR MAY UTILIZE EXISTING WALL MOUNTS.
PROVIDE AND INSTALL PIPE SUPPORT PER DETAIL 3/C-3.
INSTALL PIPE OVERHEAD AT EL. 113 FEET BETWEEN WALL
AND WASH PRESS LOCAL CONTROL STATION STAND PER
DETAIL. CONNECT 2”-3W TO WASHING PRESS VALVE
MANIFOLD AND TO SLUICE TROUGH. INSTALL 2”-3W LINE
ALONG CONCRETE DECK BELOW SLUICE TROUGH. SECURE
PIPE TO DECK USING 1-5/8 INCH CHANNEL SECTIONS
(UNISTRUT P1000, OR EQUAL, 10 INCHES LONG) AND FRAMING
CHANNEL PIPE CLAMP (UNISTRUT P1117, OR EQUAL). INSTALL
ONE CHANNEL SECTION AND PIPE CLAMP EVERY 4 FEET,
CENTER TO CENTER. CENTER PIPE CLAMP IN CHANNEL
SECTION.
4. PROVIDE AND INSTALL SCH80 PVC 4”-D FROM WASHING
PRESS, ALONG DECK, TO EFFLUENT CHANNEL AS SHOWN.
SECURE PIPE TO DECK USING TWO 1-5/8 INCH CHANNEL
SECTIONS (UNISTRUT P1000, OR EQUAL, 10 INCHES LONG)
AND FRAMING CHANNEL PIPE CLAMP (UNISTRUT P1117, OR
EQUAL). SPACE PIPE CLAMPS APPROXIMATELY 18 INCHES ON
CENTER. CENTER PIPE CLAMP IN CHANNEL SECTION.
REPLACE EXISTING GRATING PER NOTE 9. CUT GRATING TO
ACCOMMODATE 4"-D AND INSTALL 4”-D INTO EFFLUENT
CHANNEL AND INTO DROP PIPE PER DETAIL 5/C-3.
5. PROVIDE AND INSTALL ALUMINUM GRATING UPSTREAM AND
DOWNSTREAM OF SCR-1 AND SCR-2. FIELD FIT TO ENCLOSE
EXISTING CHANNEL OPENING PER DETAIL 1/C-3 AND
SPECIFICATION SECTION 055300.
6. MAINTAIN 6 INCHES CLEARANCE BETWEEN EDGE OF GRATING
AT PUMP INLET CHANNEL AND OUTER EDGE OF WASHING
PRESS.
7. IMBED ANCHOR 6 1/2 INCHES DEEP MINIMUM INTO EXISTING
CONCRETE CHANNEL FLOOR, PER MFR. RECOMMENDATIONS.
8. ALL PIPE SUPPORT CHANNEL, PIPE CLAMPS, AND HARDWARE
SHALL BE TYPE 304 STAINLESS STEEL.
9. REMOVE AND SALVAGE OF EXISTING GRATING SECTION.
PROVIDE AND INSTALL ALUMINUM GRATING PER DETAIL 1/C-3
AND SPECIFICATION SECTION 055300. GRATING SECTION IS
APPROXIMATELY 3'-0.5" BY 3'-1". FIELD VERIFY.
4 OF 10
GRATING
1/2" DIA EPOXY AB
AT 18" OC MAX
NOTE:
1. GRATING PER SPECIFCATION SECTION 055300.
WATER LEVEL
NOTES:
1. REFER TO DWG C-2 FOR CHANNEL DIMENSIONS.
2. FURNISH AND INSTALL MOUNTING BRACKET PER
MANUFACTURER'S RECOMMENDATIONS.
MILLTRONICS FMS-210
MOUNTING BRACKET
5IN TO 19IN
103.50 (LOWEST)
TRANSDUCER
(OWNER FURNISHED)
GRATING
NORTH WALL
WASHING
PRESS
SCR-1
CHANNEL, UNISTRUT P1000 OR EQUAL.
MOUNT TO WASH PRESS CONTROL
STATION MOUNTING STAND. (2"-3W
RUNS BEHIND CHANNEL)
2"-3W
STOP
INITIATE
E-STOP
OFF
REVFOR
OFF
AUTOHAND
EL=105FT
CHANNEL,
UNISTRUT P1000,
OR EQUAL
8 F
T
UNION
UNION
SECURE 2"-3W TO
CHANNEL USING
CHANNEL PIPE
CLAMPS (UNISTRUT
P1569, OR EQUAL
1" NPT WATER
CONNECTION
LOCAL
SCREEN
CONTROL
CONNECTIONS OF 2"-3W AND WASHING
PRESS WATER CONNECTIONS NOT
SHOWN FOR CLARITY
PUMP INLET CHANNEL
NEW 4"-D 3
EFFLUENT CHANNEL
NEW ALUMINUM
GRATING
ULTRASONIC
TRANSDUCER CONDUIT P
PRESSURE
TRANSDUCER P
8-INCH SDR-35 PVC 1
NOTES:
1 FURNISH AND INSTALL 8-IN SDR-35 PVC DROP PIPE TO RECEIVE
4"-D. INSTALL 12 INCHES BELOW GRATING, 10 INCHES ABOVE
CHANNEL FLOOR, AND MAINTAIN 6 INCHES BETWEEN DROP PIPE
AND WEST EDGE OF EFFLUENT CHANNEL.
2 MOUNT 8-IN SDR-35 PVC DROP PIPE TO CHANNEL WALL USING TWO
1-5/8 INCH CHANNEL SECTIONS (UNISTRUT P1000, OR EQUAL, 10
INCHES LONG) AND FRAMING CHANNEL PIPE CLAMP (UNISTRUT
P1126 OR EQUAL).
3 FURNISH AND INTALL 4"-D PER C-2. INSTALL 4"-D 4 INCHES INTO 8-IN
SDR-35 PVC DROP PIPE. CENTER 4"-D IN DROP PIPE.
P PROTECT IN PLACE
10"
6"
12"
4"
EL = 99.50
EL = 105.00
CHANNEL AND
2 PIPE CLAMPS
NOTES:
1 EXISTING 2"-3W WITH VALVE AND END
CAP (PROVIDED BY CITY) AT
CONNECTION POINT.
2 CONNECT TO EXISTING 2"-3W.
LOCATION APPROXIMATE. FIELD
VERIFY. FURNISH AND INSTALL 2"-W
PER SPECIFICATION SECTION 402053.
INSTALL UNIONS PER SPECIFICATION
SECTION 402053.
3 FURNISH AND INSTALL 2 INCH BASKET
STRAINER (EATON MODEL 72,
THREADED CONNECTION, SS BODY,
140 MESH MINIMUM, OR EQUAL) AT
CENTERLINE ELEVATION OF 108 FT (3
FT FROM DECK). PROVIDE GALVANIZED
STEEL UNION AT EACH CONNECTION
TO STRAINER. PROVIDE AND INSTALL
1-5/8 INCH X 3-1/4" INCH CHANNEL
SECTION (BACK TO BACK) (UNISTRUT
P1001, OR EQUAL) AND FRAMING
CHANNEL PIPE CLAMP (UNISTRUT
P1117, OR EQUAL) TO SECURE PIPE.
4 PROVIDE AND INSTALL 2"-3W PER
SPECIFICATION SECTION 402053 AT
ELEVATION 111.67 FT
(APPROXIMATELY 6'-8" FROM DECK).
CONTINUE ALONG WEST WALL AND
NORTH WALL PER SITE PLAN ON C-2.
C CITY TO REMOVE
P PROTECT IN PLACE
C
C
C
P
P
EXISTING
2"-3W
6.67 F
T
4
2
3 F
T
3
WEST
WALL
NORTH
WALL
1
C
NOTES:
1. HOT DIPPED GALVANIZED WELDED ASSEMBLY AFTER FABRICATION
PER ASTM A153. IF GALVANIZATION IS DAMAGED DURING ASSEMBLY
OR FROM FIELD WELDING, RECOAT WITH ZRC COLD GALVANIZING
COMPOUND AS MANUFACTURED BY ZRC WORLDWIDE, OR
EQUIVALENT.
2. COORDINATE FINAL LOCATION WITH CONDUIT ROUTING AND
SUBMIT PER ELECTRICAL PLANS AND SPECIFICATIONS.
6"
1"
SECTION A-A
9/16" DIA,
TYP
1"
ELEV. 105 FT CONCRETE DECK
8 F
T M
IN
C
LE
AR
1-5/8" X 3-1/4" CHANNEL (UNISTRUT
P1001, OR EQUAL) CONNECT TO
PLATE WITH 316 SST BOLTS
8" X 8" X 3/8" THICK GALVANIZED
STEEL PLATE
4 INCH DIAMETER GALVANIZED
STEEL PIPE STANCHION WITH 8" X
8" X 3/8" THICK BASE PLATE (ANVIL
FIG. 63P, OR EQUAL
1/2" 316 SST ANCHORS,
EMBED 6 INCHES MIN, TYP.
OF 4
1" GROUT
AA
FIELD WELD AND RECOAT
IF REQUIRED.25
DATE
DESCRIPTION
REV
14 23
APPR
PROJECT ENGINEER
REG NUMBER
EXP DATE
DATE:
DESIGNED:
APPROVED:
CHECKED:
DETAILED:
SHEET
0 11/2
CIT
Y O
F M
OR
RO
BA
Y/C
AY
UC
OS
SA
NIT
AR
Y D
ISTR
ICT
WA
STE
WA
TER
TR
EA
TME
NT
PLA
NT
HE
AD
WO
RK
S IM
PR
OV
EM
EN
TS
Know what's
R
JUNE 11, 2014
PO B
OX
160
4A
RRO
YO G
RAN
DE,
CA
934
21
(80
5) 9
04-6
530
ES/JH
ES/RL
JH
EILEEN K. SHIELDS
C74757
12/31/2015
C-3
CIV
IL D
ET
AIL
S
Scale: NTS
GRATING SUPPORT
1
Scale: NTS
ULTRASONIC LEVEL TRANDUCER
2
Scale: NTS
PIPE SUPPORT
3
5 10OF
Scale: NTS
DROP PIPE FOR DRAIN
5
Scale: NTS
2"-3W AND STRAINER
4
Scale: NTS
PIPE RACK
6
DATE
DESCRIPTION
REV14 23
APPR
PROJECT ENGINEER
REG NUMBER
EXP DATE
DATE:
DESIGNED:
APPROVED:
CHECKED:
DETAILED:
0 11/2
CIT
Y O
F M
OR
RO
BA
Y/C
AY
UC
OS
SA
NIT
AR
Y D
ISTR
ICT
WA
STE
WA
TER
TR
EA
TME
NT
PLA
NT
HE
AD
WO
RK
S IM
PR
OV
EM
EN
TS
Know what's
R
JUNE 12, 2014
JD
AK
LB
AK
SHEET
GE
NE
RA
L E
LEC
TRIC
AL
NO
TES
AN
D L
EG
EN
D
GENERAL ELECTRICAL NOTES1. CODE COMPLIANCE: ALL WORK SHALL CONFORM TO AND BE PERFORMED IN ACCORDANCE WITH CODES, STANDARDS, AND
ORDINANCES AS SET FORTH BY THE AUTHORITIES HAVING JURISDICTION AND THEIR LATEST ADOPTED EDITIONS (IN EFFECT ATTIME OF BUILDING PERMIT APPLICATION) OF THE FOLLOWING PUBLICATIONS:
A. CALIFORNIA CODE OF REGULATIONS TITLE 24; INCLUDES 2011 NATIONAL ELECTRICAL CODE AND 2012 INTERNATIONAL FIRECODE, INTERNATIONAL BUILDING CODE, ETC. WITH CALIFORNIA AND OTHER LOCAL AMENDMENTS AS APPLICABLE.
2. SAFETY: THE ELECTRICAL CONTRACTOR IS RESPONSIBLE TO MAINTAIN ALL EQUIPMENT IN A SAFE AND RESPONSIBLE MANNER.KEEP DEAD FRONT EQUIPMENT IN PLACE WHILE EQUIPMENT IS ENERGIZED. CONDUCT ALL CONSTRUCTION OPERATIONS IN ASAFE MANNER FOR EMPLOYEES AS WELL AS OTHER WORKPERSONS OR ANYONE VISITING THE JOB SITE. PROVIDE BARRIERS,FLAGS, TAPE, ETC. AS REQUIRED FOR SAFETY. THE CONTRACTOR SHALL HOLD ALL PARTIES HARMLESS OF NEGLIGENT SAFETYPRACTICES, WHICH MAY CAUSE INJURY TO OTHERS ON OR NEAR THE JOB SITE.
3. FIRE RATED ASSEMBLIES SHALL MAINTAIN RATINGS AS SPECIFIED IN THE CALIFORNIA BUILDING CODE CHAPTER 7.CONTRACTOR SHALL PROVIDE AND INSTALL PHYSICAL ENCLOSURE AROUND FIXTURES, PANELS, ETC. AS REQUIRED. ALLASSEMBLIES TO BE PENETRATED SHALL BE INSTALLED WITH APPLICABLE THROUGH-PENETRATION FIRESTOP SYSTEM ASDETERMINED BY UL CLASSIFICATION. BEFORE CONSTRUCTION, VERIFY AND COMPLY WITH REQUIREMENTS OF LOCALAUTHORITY HAVING JURISDICTION.
4. MOUNTING HEIGHTS SHALL BE AS FOLLOWS UNLESS OTHERWISE NOTED:
+15" AFF: RECEPTACLES, TELEPHONE, TV & DATA OUTLETS. (MEASURED BOTTOM OF OUTLET BOX)+48" AFF: LIGHT SWITCHES. (MEASURED TOP OF OUTLET BOX)+79" AFF: TOP OF HIGHEST HANDLE POSITION OF ANY CIRCUIT BREAKER
5. LABEL PANELS, CABINETS, BACKBOARDS, MAIN DEVICES, SAFETY SWITCHES, CONTACTORS AND OTHER SPECIFICALLYDESIGNATED EQUIPMENT SHOWN ON PLANS. USE ENGRAVED LAMINATED PLASTIC NAMEPLATES ATTACHED BY SCREWS ORRIVETS. FOR FEEDERS, NEATLY AND INDELIBLY LABEL CONDUIT DESTINATIONS ON BOTH VISIBLE ENDS OF CONDUIT RUNSWHERE CONDUITS TERMINATE AT DESIGNATED ENCLOSURES, STRUCTURES OR EQUIPMENT (INCLUDING PULL AND SPLICEBOXES).
6. EQUIPMENT ANCHORAGE NOTEALL MECHANICAL AND ELECTRICAL EQUIPMENT SHALL BE ANCHORED OR BRACED TO MEET THE HORIZONTAL AND VERTICALFORCES PRESCRIBED IN THE 2010 CBC, SECTION 1615A.1.20 AND ASCE 7-05 SECTIONS 13.3, 13.4 & 13.6.
THE ATTACHMENT OF THE FOLLOWING ITEMS SHALL BE DESIGNED TO RESIST THE FORCES PRESCRIBED ABOVE, BUT NEED NOTBE DETAILED ON THE PLANS:
A. EQUIPMENT WEIGHING LESS THAN 400 POUNDS SUPPORTED DIRECTLY ON THE FLOOR OR ROOF.B. FURNITURE REQUIRED TO BE ATTACHED IN ACCORDANCE WITH PART 2, TITLE 24, C.C.R..C. TEMPORARY OR MOVABLE EQUIPMENT.D. EQUIPMENT WEIGHING LESS THAN 20 POUNDS SUPPORTED BY VIBRATION ISOLATORS.E. EQUIPMENT WEIGHING LESS THAN 20 POUNDS SUSPENDED FROM A ROOF OR FLOOR OR HUNG FROM A WALL.
FOR THOSE ELEMENTS THAT DO NOT REQUIRE DETAILS ON THE APPROVED DRAWINGS, THE INSTALLATION SHALL BE SUBJECTTO THE APPROVAL OF THE ENGINEER AND THE FIELD REPRESENTATIVE.
PIPING, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEM BRACING NOTE
PIPING, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEMS SHALL BE BRACED TO RESIST THE FORCES PRESCRIBED IN ASCE7-05 SECTION 13.3 AS DEFINED IN ASCE 7-05 SECTION 13.6.8, 13.6.7, AND 13.6.5.5, ITEM 6, RESPECTIVELY.
MECHANICAL SYSTEMS
1. MECHANICAL UNIT CONDUITS: TO PREVENT DAMAGE DUE TO VIBRATION, BOTH POWER AND CONTROL WIRING CONDUITSFEEDING EXTERIOR MECHANICAL UNITS SHALL BE PROVIDED AND INSTALLED BY ELECTRICAL CONTRACTOR WITH LIQUID TIGHTFLEXIBLE TYPE AT FINAL CONNECTION TO UNIT AND BETWEEN ROOF JACK AND DISCONNECT SWITCH WHERE DISCONNECT ISMOUNTED ON UNIT.
2. MECHANICAL CONTROLS: PROVIDE AND INSTALL CONDUIT AND REQUIRED CABLING FROM EACH MECHANICAL CONTROLSLOCATION TO CONTROLLED MECHANICAL UNITS. COORDINATE WITH APPROVED SCREENING EQUIPMENT SHOP DRAWINGS.
3. PULLROPES: ANY RACEWAY WITHOUT CABLE OR WIRE SHALL BE INSTALLED WITH MINIMUM 200 POUND TEST PULL LINE. ANYNEW OR EXISTING COMMUNICATION OR SIGNAL RACEWAY ROUTED BETWEEN SIGNAL CABINETS, CONTROLS LOCATION, AND TOCONTROLLED MECHANICAL UNITS WITH FUTURE CAPACITY SHALL BE INSTALLED WITH MINIMUM 200 POUND TEST PULL LINE ASWELL AS WELL AS CABLING SHOWN ON RISER DIAGRAMS AND APPROVED SHOP DRAWINGS.
EXISTING BUILDINGS/INSTALLATIONS
1. ASBESTOS: IF DURING THE COURSE OF WORK THE CONTRACTOR OBSERVES THE EXISTENCE OF ASBESTOS, ORASBESTOS-BEARING MATERIALS, THE CONTRACTOR SHALL IMMEDIATELY TERMINATE FURTHER WORK ON THE PROJECT ANDNOTIFY THE OWNER OF THE CONDITION. THE OWNER WILL, AFTER CONSULTATION WITH THE OWNER'S REPRESENTATIVE,DETERMINE A FURTHER COURSE OF ACTION.
2. ANY DEMOLITION WORK SHOWN WAS PREPARED FOR THE CONVENIENCE OF THE CONTRACTOR. THE ENGINEER DOES NOTREPRESENT THAT ALL ITEMS WHICH MAY REQUIRE DEMOLITION HAVE BEEN SHOWN. IT SHALL BE THE RESPONSIBILITY OF THECONTRACTOR TO CAREFULLY EXAMINE THE SITE AND THE CONTRACT DOCUMENTS AND TO PERFORM ALL DEMOLITION ANDRECONSTRUCTION WHICH MAY BE REQUIRED FOR THE PROPER EXECUTION AND COMPLETION OF THE WORK.
3. EXISTING CONDITIONS: INFORMATION SHOWN FOR EXISTING CONDITIONS WAS PRIMARILY GAINED FROM "AS BUILT" DRAWINGSAND/OR LIMITED FIELD INVESTIGATION. BEFORE BID, VISIT SITE TO VERIFY EXISTING CONDITIONS AND MAKE ALLOWANCE FORVARIATIONS FROM THAT SHOWN.
4 EXISTING CONDUCTORS: INTERCEPT, EXTEND, REROUTE, REPULL CONDUCTORS, SPLICE AND OTHERWISE MODIFY EXISTINGCONDUCTORS OF ALL SYSTEMS AS REQUIRED TO MAINTAIN AND/OR ESTABLISH PROPER FUNCTION AND SATISFY DESIGNINTENT. REMOVE ABANDONED CONDUCTORS.
5. EXISTING COMMUNICATIONS, DATA AND CATV AND OTHER LOW VOLTAGE TYPE SYSTEM OUTLET LOCATIONS SHOWN ON THEPLAN TO BE RELOCATED SHALL BE PERFORMED BY THE ELECTRICAL CONTRACTOR. MODIFY EXISTING SYSTEM AS REQUIREDFOR FULL FUNCTION (SAME AS EXISTING) IN NEW LOCATION.
6. WHERE EXISTING BUILDING CONSTRUCTION, MECHANICAL UNITS AND OTHER EQUIPMENT IS SHOWN TO BE REMOVED,DISCONNECT AND REMOVE ALL ASSOCIATED ELECTRICAL AND CONTROLS INSTALLATION.
7. CLOSELY COORDINATE OUTAGE AND FACILITY DISRUPTION TIME WITH CIVIL ENGINEER AND OWNER. MINIMUM 7 DAYS ADVANCENOTICE IS REQUIRED BEFORE ANY CIRCUIT SHUTDOWN OR DISRUPTION OF FACILITY PERSONNEL FUNCTIONING. SEE CIVILPLANS AND THE PROJECT DOCUMENTS FOR ADDITIONAL OUTAGE REQUIREMENTS.
NUMBERED SHEET NOTES: REFERS TO NOTESON SAME SHEET AS REFERENCE
DETAIL REFERENCE:
-DETAIL DESIGNATION-SHEET NUMBER REFERENCE
CONVENTIONSX
-
1
2003 FEEDER SCHEDULE DESIGNATION(EXAMPLE: 2003 = 200 AMPERE, 600V, 3 CURRENT CARRYING CONDUCTORS,'CO14' INDICATES CONDUIT ONLY,QUANTITY (1) AND SIZE 4"
JUNCTION BOX
MAIN SWITCHBOARD
NOT IN CONTRACT
NIGHT LIGHT
RELOCATE(D)
TO BE REMOVED
TYPICAL
UNDERCABINET
UNDERGROUND
VOLT AMPERES
WATT, WIRE
WEATHERPROOF (NEMA 3R)
UNLESS OTHERWISE NOTED
MAIN TELEPHONE TERMINAL BOARD
TELEPHONE OUTLET
DATA OUTLET
SAFETY DISCONNECT
TELEVISION OUTLET
VOLTV
WP
VA
W
(R)
UC
UG
UON
TBR
TYP
NIC
NL
P POLE
MSB
MTTB
(N) NEW
ABBREVIATIONSAMPERE
AMP FUSE RATING
ABOVE FINISH FLOOR
ABOVE FINISH GRADE
AMPERES INTERRUPT CAPACITY
AMP SWITCH RATING
BELOW FINISH GRADE
CIRCUIT BREAKER
CIRCUIT
CONDUIT
EXISTING
ELECTRICAL CONTRACTOR
EXHAUST FAN
CA. ELECTRICAL CODE
(E) IN (N) LOCATION
(E) TO BE (R)
FIRE ALARM
FIRE ALARM CONTROL PANEL
GROUNDING CONDUCTOR
GENERAL CONTRACTOR
GROUND
GALVANIZED RIGID STEEL
MECHANICAL CONTRACTOR
ISOLATED GROUND
GANGED WITH SWITCH
MAIN CIRCUIT BREAKER
LIGHTING
MAIN LUGS ONLY
FUTURE
GROUND FAULT CKT INTERRUPTER
POWER/COMM.SINGLE RECEPT.
DUPLEX RECEPT.
DUPLEX- HALF SWITCHED
DOUBLE DUPLEX
SPECIAL CONFIGURATION
DUPLEX- FLOOR OUTLET
FLUOR. STRIP UON
DIRECTIONAL FLOOD
FA
DPST
OCCUPANCY SENSOR
W/THERMAL OVERLOAD
DUAL LEVEL SWITCHING
SWITCHLEG DESIGNATION
W/PILOT LIGHT
KEY OPERATED
3-WAY
4-WAY
DIMMER
TIMER SWITCH
MC
MCB
MLO
IG
GWS
LTG
GFI
GND
GRS
G
FACP
GC
SWITCHESSPST
(E)
(EXN)
(EXR)
(F)
EC
EF-#
CEC
CKT
C
AS
BFG
CB
NOTE: INTERPRET IN CONTEXT
LIGHT FIXTURESWALL SURFACEMOUNT
LEGEND
AFF
AFG
AIC
A
AF
PHONE/DATA COMBO OUTLET
UNDERWRITERS LABORATORIESUL
NORMALLY OPENNO
NORMALLY CLOSEDNC
AUXILIARY (CONTACT)AUX
AND POWER PACK
- REFER TO CIVIL SHEETS FOR ADDITIONAL DEMOLITION REQUIREMENTS.
- EQUIPMENT SHOWN TO BE REMOVED IS SHOWN FOR REFERENCE ONLY. INFORMATION WAS OBTAINED FROM LIMITED FIELDINVESTIGATION AND MAY NOT REPRESENT ALL ELECTRICAL DEMOLITION. FIELD VERIFY CONDITIONS ANDDISCONNECT/REMOVE ALL EQUIPMENT AS REQUIRED TO MEET THE INTENT OF THAT SHOWN ON THE CIVIL AND ELECTRICALDRAWINGS.
- ALL ELECTRICAL EQUIPMENT SHOWN ON DRAWING (OR REQUIRED) TO BE DEMOLISHED SHALL BE DISCONNECTED, REMOVEDAND DISPOSED OF BY ELECTRICAL CONTRACTOR. NO EQUIPMENT (RACEWAYS, BOXES, CABLING, ETC.) SHALL BEABANDONED IN PLACE AND COVERED BY NEW CONSTRUCTION.
- SCHEDULE ANY OUTAGES WITH CIVIL ENGINEER AND OWNER PRIOR TO DE-ENERGIZATION OF ANY SERVICE EQUIPMENT,BRANCH CIRCUITS OR FEEDERS. SEE EXISTING BUILDINGS/INSTALLATIONS, NOTE 7 ON THIS SHEET.
- DISCONNECTION/REMOVAL OF EXISTING COMMUNICATIONS SYSTEMS COMPONENTS SHALL BE SCHEDULED WITH THE CIVILENGINEER AND OWNER AND COORDINATED WITH THEIR VENDORS.
- DISPOSE OF ALL REMOVED EQUIPMENT UNLESS OTHERWISE DIRECTED BY THE OWNER. THE OWNER SHALL BE GIVEN FIRSTRIGHT TO SALVAGE PRIOR TO DISPOSAL.
- COORDINATE REMOVAL OF EXISTING EQUIPMENT WITH CONSTRUCTION SCHEDULE AND PHASING. VERIFY REMOVAL OFEQUIPMENT WITH CIVIL ENGINEER AND OWNER PRIOR TO SCHEDULING WORK. COMPLETE NEW CONSTRUCTION INCOORDINATION WITH EQUIPMENT INSTALLATION AND PHASING. KEEP EXISTING EQUIPMENT IN SERVICE UNTIL NEWEQUIPMENT IS OPERATIONAL.
GENERAL ELECTRICAL DEMOLITION PLAN NOTES
MANUFACTURERMFR
REQUIREMENTSREQT'S
P/S POWER SUPPLY
FUSIBLE SWITCH
GROUNDING ELECTRODE CONDUCTOR
PHASE
MISCELLANEOUS
CIRCUIT BREAKER
GENERATOR
MOTOR
GROUNDING ELECTRODE SYSTEMAND GROUND BUS BAR
UTILITY METERING EQUIPMENT ANDUTILITY APPROVED METERING PROVISIONS
TRANSFORMER (XFMR)
TERMINATION LUGSSUITED FOR CONDUCTORS SHOWN
KIRK-KEY INTERLOCK DEVICE
SURGE PROTECTOR DEVICE
H.O.A. STARTER WITH INTEGRAL OVERLOADAND CONTROL TRANSFORMER
SOLID STATE SOFT STARTER
MOMENTARY CONTACT SWITCH (N.O.)
NORMALLY CLOSED (N.C.) CONTACT
NORMALLY OPEN (N.O.) CONTACT
ROTARY SELECTOR SWITCH
MOMENTARY CONTACT SWITCH (N.C.)
VARIABLE FREQUENCY DRIVE
CONDUIT STUB (W/MARKER)
VERTICAL CONDUIT RUN
FLEXIBLE CONNECTION
SURFACEMOUNT RACEWAY
LOW VOLTAGE
CONDUIT/WIRE
NEW POWER HOMERUN(3 HOTS & 3 NEUT SHOWN)
NEW, UNDERGROUND
EXISTING, UNDERGROUND
NEW, ABOVE GROUND
EXISTING, ABOVE GROUND
TYPE 316 STAINLESS STEELSS
CUSTOMER POWER METERING EQUIPMENT
CONTROLS CABLINGCTRL
PWR POWER AND GROUNDING CONDUCTORS
E-1
MECHANICAL EQUIPMENT TAGXX-XXREFER TO CIVIL PLANS AND EQUIPMENT SUBMITTALS
DATE
DESCRIPTION
REV14 23
APPR
PROJECT ENGINEER
REG NUMBER
EXP DATE
DATE:
DESIGNED:
APPROVED:
CHECKED:
DETAILED:
0 11/2
CIT
Y O
F M
OR
RO
BA
Y/C
AY
UC
OS
SA
NIT
AR
Y D
ISTR
ICT
WA
STE
WA
TER
TR
EA
TME
NT
PLA
NT
HE
AD
WO
RK
S IM
PR
OV
EM
EN
TS
Know what's
R
JUNE 12, 2014
JD
AK
LB
AK
SHEET
SIN
GLE
LIN
E D
IAG
RA
M
1
PARTIAL SINGLE LINE DIAGRAM
SINGLE LINE DIAGRAM NOTES- ALL CONDUCTORS SHALL BE COPPER WITH INSULATION TYPE LISTED FOR WET LOCATION (EITHER XHHW OR THWN).
- ALL SWITCHES, CIRCUIT BREAKERS AND OTHER EQUIPMENT, AS SPECIFIED, SHALL HAVE TERMINATION PROVISIONS LISTEDAND IDENTIFIED FOR USE WITH 75 DEG. CONDUCTORS. ALL FEEDER CONDUCTORS AND CONDUITS ARE SIZED BASED ON USEOF 75 DEG. C COPPER WIRES TYPE THWN/THHN.
- ALL EQUIPMENT SHALL BE APPROVED HAVE AN APPROVED TESTING LABORATORY LABEL ATTACHED [UL, CSA, ETC.] (CEC110-2).
503
REFERENCE NOTES1. NEW CIRCUIT BREAKER STYLE AND AIC RATING TO MATCH EXISTING.
PROVIDE CIRCUIT BREAKER HARDWARE MOUNTING COMPATIBLE WITHEXISTING ELECTRICAL EQUIPMENT.
2. CONNECT TO SCREENING MAIN CONTROL PANEL (OWNER-FURNISHED).COORDINATE POWER AND CONTROLS CONNECTIONS WITH EQUIPMENTSUBMITTALS PROVIDED IN SPECIFICATIONS APPENDIX A.
3. NEW 30A, 480V SAFETY SWITCH, NEMA 7/9 ENCLOSURE WITH O-RINGSEAL, EXPLOSIONPROOF CLASS 1 DIV 1, DOUBLE COATED CASTALUMINUM WITH TYPE 316 STAINLESS STEEL HINGES AND HARDWARE,PAD-LOCKABLE HANDLE. EATON CAT. NO. DS361UX OR APPROVEDEQUAL.
4. CONNECT TO CONTROLS ENCLOSURE AT EQUIPMENT(OWNER-FURNISHED). COORDINATE POWER AND CONTROLSCONNECTIONS WITH EQUIPMENT SUBMITTALS PROVIDED INSPECIFICATIONS APPENDIX A.
2
(1) 1"C (3) #8 THWN & (1) #8 GND.503
E-2
SCREENING EQUIPMENT CONTROL RISER DIAGRAM
253
(1) 1"C (3) #12 THWN & (1) #12 GND.253
253 253
3
4
LE-1
LE-2
HLS-1
LE-3
LE-4
HLS-2
NOTE:REFER TO CIVIL PLANS FOR LOCATIONS OF COMPONENTSAND EQUIPMENT. ITEMS SHOWN ON ELECTRICAL PLAN AREAPPROXIMATE LOCATION AND SHALL BE VERIFIED WITHCIVIL PLANS AND APPROVED EQUIPMENT SUBMITTAL SHOPDRAWINGS.
SCR-1 SCR-2WASHING PRESS
MAIN CONTROLTO MCC ROOM
PANEL
PROVIDE EXPLOSION PROOFSEALS, CLASS 1 DIV1
GROUP D AREA, FOR ALLPOWER AND CONTROLS
CONDUITS ENTERINGSCREENING AREA.
HLS-1
LE-1 LE-2
LE-4LE-3HLS-2
4
5
WASHING PRESS
SCR-1
SCR-2
POWER ANDCONTROLS
CONDUITS ANDCABLING. SEE RISER
ON SHEET E-2 FORSIZE AND QUANTITY.
ROUTE HIGHON EAST
WALL.
ROUTEOVERHEAD
BETWEEN WALLAND PIPE RACK.
MINIMUMHEIGHT = 8 FT
APPROXIMATEPWR & CTRL
CONDUITROUTING
SHOWN WITHBOLD LINE.
TRANSITION DOWN TOFLOOR AND ROUTE TO
CONTROL BOXES,FLOATS, AND
TRANSDUCERS.
ROUTEAROUNDEXISTING
DUCT.
6
4
7
TO "MCC-C1"
(E) 1"C SPARE
(E)JB
(E)JB
TO "HCP"
(E) 3/4"C SPARE(E)
LTI-2105
(E)JB
(E)1"C, CTRL
(E)3/4"C, PWR
(E)JB
(E)1"C, PWR & CTRL
TO "HCP"& "MCC-C1"
TO "HCP"
"MCC-C1"TO
(TBR)MECH. SCREEN
(TBR)GRINDER
(E)LDS-2103
(E) 3/4"C(2)#14
1
2
3
4
5
DATE
DESCRIPTION
REV14 23
APPR
PROJECT ENGINEER
REG NUMBER
EXP DATE
DATE:
DESIGNED:
APPROVED:
CHECKED:
DETAILED:
0 11/2
CIT
Y O
F M
OR
RO
BA
Y/C
AY
UC
OS
SA
NIT
AR
Y D
ISTR
ICT
WA
STE
WA
TER
TR
EA
TME
NT
PLA
NT
HE
AD
WO
RK
S IM
PR
OV
EM
EN
TS
Know what's
R
JUNE 12, 2014
JD
AK
LB
AK
SHEET
SC
RE
EN
ING
AR
EA
ELE
CTR
ICA
L P
LAN
REFERENCE NOTES1. DISCONNECT AND REMOVE EXISTING MECHANICAL SCREENING
EQUIPMENT.
2. DISCONNECT AND REMOVE EXISTING SCREENING EQUIPMENTCONTROLS, POWER AND CONTROLS CABLING BACK TO SOURCE.EXISTING UNDERGROUND CONDUIT TO REMAIN.
3. DISCONNECT AND REMOVE EXISTING GRINDER CONTROLS, POWERAND CONTROLS CABLING BACK TO SOURCE. EXISTING UNDERGROUNDCONDUIT TO REMAIN.
4. PROVIDE DISCONNECT SWITCH AND CONNECT TO SCREENINGEQUIPMENT CONTROL BOX. MOUNT ON TYPE 316 STAINLESS STEELSTRUT, P1000 WITH P1887 BASE, ANCHOR TO FLOOR WITH (4) 3/8" 316SS ANCHORS, 1" EMBED. SEE SINGLE LINE DIAGRAM AND RISER ONSHEET E-2 FOR ADDITIONAL REQUIREMENTS.
5. PROVIDE DISCONNECT SWITCH AND CONNECT TO WASHING PRESSCONTROL BOX. MOUNT ON TYPE 316 STAINLESS STEEL STRUT, P1000WITH P1887 BASE, ANCHOR TO FLOOR WITH (4) 3/8" 316 SS ANCHORS,1" EMBED. SEE SINGLE LINE DIAGRAM AND RISER ON SHEET E-2 FORADDITIONAL REQUIREMENTS.
6. FIELD VERIFY EXISTING CONDITIONS AND ROUTE NEW CONDUIT TOAVOID EXISTING PIPING AND EQUIPMENT TO REMAIN.
7. ROUTE OVERHEAD ON PIPE RACK, WITH TYPE 316 STRUT ATTACHMENTAND CONDUIT CLAMPS. MINIMUM HEIGHT 8 FEET. CONDUITS ANDSUPPORTS SHALL BE ROUTED AND INSTALLED WHILE MAINTAININGACCESS TO EQUIPMENT AND REMOVABLE METAL GRATING. SEE CIVILPLANS DETAIL 6 SHEET C-3 FOR ADDITIONAL REQUIREMENTS.
NORTH
SCALE:
SCREENING AREA ELECTRICAL PLAN1/4" = 1'-0"
ELECTRICAL DEMOLITION PLAN ELECTRICAL PLAN
E-3
ELECTRICAL PLAN NOTES- SEE SPECIFICATIONS APPENDIX A FOR OWNER-FURNISHED EQUIPMENT
DETAILS.
- ALL EQUIPMENT AND WIRING METHODS AT SCREENING AREA SHALL BESUITABLE FOR HAZARDOUS LOCATION, CLASS 1 DIVISION 1, GROUP D,AND SUITABLE FOR WET LOCATION, HIGHLY CORROSIVEENVIRONMENT. ALL EXPOSED METAL PARTS, FASTENERS, ANDCOMPONENTS SHALL BE TYPE 316 STAINLESS STEEL.
- CONDUIT ROUTING SHALL BE COORDINATED WITH EQUIPMENTINSTALLATION, EQUIPMENT DIMENSIONS, SPACING AND LOCATIONS.COORDINATE WITH CIVIL PLANS AND OWNER-FURNISHED EQUIPMENT,DETAILS, AND INSTALLATION REQUIREMENTS. SUBMIT CONDUITROUTING PLAN INCLUDING PROPOSED CONDUIT, TRADE SIZES,SUPPORT TYPE AND LOCATION, FOR OWNER REVIEW PRIOR TOROUGH-IN. PROVIDE 304 STAINLESS STEEL WALK-OVER TRIPPROTECTION WHERE INSTALLED ON GROUND/FLOOR LEVEL IN WALKAREAS ACCESSIBLE BY PERSONNEL. PROVIDE PIPE RACKING SYSTEMWHERE ROUTED OVERHEAD. PROVIDE EXPLOSIONPROOF NEMA 7/4XPULL BOXES INSIDE THE SCREENING AREA AS REQUIRED TO COMPLYWITH THE MAXIMUM ALLOWED BENDING ANGLES PER SPECIFICATIONREQUIREMENTS. WHERE PRACTICAL, ROUTE CONDUIT BELOWGRATING AND AT TOP OF CHANNEL TO FLOATS AND TRANSDUCERS.
(E)"HCP"
(E)"MCC-C1"
TOSCREENING
MAINCONTROLPANEL IN
MCC ROOM
(1)1
"C,
(1)3
/4"C
CTR
L
1"C
, PW
R
CORE DRILLAND SEAL
2
3(N)
SCREENINGMAIN CONTROL
PANEL
PWR & CTRL CONDUITSTO SCREENING AREA.SEE RISER ON SHEET
E-2 FOR SIZE ANDQUANTITY.
PWRHOMERUN TO
"MCC-C1"1"C
HOMERUN TO"HCP"
(E)"MCC-C"
CORE DRILLAND SEAL
ALL CONDUITPENETRATIONS
1
DATE
DESCRIPTION
REV14 23
APPR
PROJECT ENGINEER
REG NUMBER
EXP DATE
DATE:
DESIGNED:
APPROVED:
CHECKED:
DETAILED:
0 11/2
CIT
Y O
F M
OR
RO
BA
Y/C
AY
UC
OS
SA
NIT
AR
Y D
ISTR
ICT
WA
STE
WA
TER
TR
EA
TME
NT
PLA
NT
HE
AD
WO
RK
S IM
PR
OV
EM
EN
TS
Know what's
R
JUNE 12, 2014
JD
AK
LB
AK
SHEET
ELE
CTR
ICA
L P
LAN
S, M
OTO
R R
OO
M A
ND
MC
C R
OO
M
REFERENCE NOTES1. SCREENING AREA MAIN CONTROL PANEL, OWNER-FURNISHED,
CONTRACTOR INSTALLED. PROVIDE POWER AND CONTROLSCONNECTIONS. SEE SPECIFICATIONS APPENDIX A FOR ADDITIONALREQUIREMENTS.
2. CONNECT TO EXISTING MCC EQUIPMENT. SEE SINGLE LINE DIAGRAMSHEET E-2 FOR ADDITIONAL REQUIREMENTS.
3. CONNECT TO EXISTING HEADWORKS CONTROL PANEL. COORDINATEWITH OWNER FOR LANDING WIRING ON EXISTING TERMINALS.
NORTH
SCALE:
ELECTRICAL PLANS, MOTOR ROOM AND MCC ROOM1/4" = 1'-0"
MOTOR ROOMMCC ROOM
E-4
ELECTRICAL PLAN NOTES- SEE SPECIFICATIONS APPENDIX A FOR OWNER-FURNISHED EQUIPMENT
DETAILS.
- CONDUIT ROUTING SHALL BE COORDINATED WITH EQUIPMENTINSTALLATION, EQUIPMENT DIMENSIONS, SPACING AND LOCATIONS.COORDINATE WITH CIVIL PLANS AND OWNER-FURNISHED EQUIPMENT,DETAILS, AND INSTALLATION REQUIREMENTS. SUBMIT CONDUITROUTING PLAN INCLUDING PROPOSED CONDUIT, TRADE SIZES,SUPPORT TYPE AND LOCATION, FOR OWNER REVIEW PRIOR TOROUGH-IN. PROVIDE 304 STAINLESS STEEL WALK-OVER TRIPPROTECTION WHERE INSTALLED ON GROUND/FLOOR LEVEL. PROVIDEPIPE RACKING SYSTEM WHERE ROUTED OVERHEAD.
DATE
DESCRIPTION
REV14 23
APPR
PROJECT ENGINEER
REG NUMBER
EXP DATE
DATE:
DESIGNED:
APPROVED:
CHECKED:
DETAILED:
0 11/2
CIT
Y O
F M
OR
RO
BA
Y/C
AY
UC
OS
SA
NIT
AR
Y D
ISTR
ICT
WA
STE
WA
TER
TR
EA
TME
NT
PLA
NT
HE
AD
WO
RK
S IM
PR
OV
EM
EN
TS
Know what's
R
JUNE 12, 2014
JD
AK
LB
AK
SHEET
ELE
CTR
ICA
L D
ETA
ILS
E-5
ELEVATION AT EXISTING "MCC-C1"
PROVIDE NEW CIRCUIT BREAKER INEXISTING SPACE, SEE SINGLE LINEDIAGRAM SHEET E-2. PROVIDE NEWCIRCUIT BREAKER MOUNTINGHARDWARE AND DEADFRONT COVERTO MATCH EXISTING WESTINGHOUSEEQUIPMENT.LABEL "SCREENING EQUIPMENTCONTROL PANEL".
ROUTE NEW POWER CONDUCTORSDOWN EXISTING WIREWAY.
TOP ENTRY CONDUIT HUBPENETRATION AT EXISTING MCCENCLOSURE.
NEW POWER FEEDER TO SCREENINGMAIN CONTROL PANEL AT MCC ROOM.
EXISTING "MCC-C1"LOCATED IN MOTOR ROOM.