P Sundelin: Econet - matalaenergiajärjestelmä ilmanvaihtoon

Embed Size (px)

DESCRIPTION

Peter Sundelin's (Fläkt Woods) presentation in SAVE ENERGY Workshop arranged in Helsinki 4.5.2009 about building automation and HVAC technologies.

Citation preview

Page 1: P Sundelin: Econet - matalaenergiajärjestelmä ilmanvaihtoon

© Fläkt Woods 1

Page 2: P Sundelin: Econet - matalaenergiajärjestelmä ilmanvaihtoon

© Fläkt Woods 2

The year was 1920 and the place a mill at the Dunkehalla river in Jönköping.

The first employees !

Page 3: P Sundelin: Econet - matalaenergiajärjestelmä ilmanvaihtoon

© Fläkt Woods 3

Businesses and Product Offerings

Non ResidentialBuildings

Infrastructure Light Industry

Air Climate: 60% of T/O

System diffusers

Air Handling Units

Fans

Buildings Markets

Special Structures

Industry Markets

Coolers

Fans for Infrastructure

Diffusers

Box fans

Air Movement: 40% of T/O

Cement, PowerSteel

TunnelsMetros

IndustrialProcesses

Fans for Industry

Electro-Mec

General Industry

Hygiene Buildings

Ducts

Chillers

Fire dampers

Traction

Dehumidification Energy Recovery Acoustical

3300 employees worldwide

Page 4: P Sundelin: Econet - matalaenergiajärjestelmä ilmanvaihtoon

© Fläkt Woods 4

ECONET® Air Handling Unit

Page 5: P Sundelin: Econet - matalaenergiajärjestelmä ilmanvaihtoon

© Fläkt Woods 5

Fläkt Woods is a world leader in energy recovery systems for air handling units. The most popular systems are:

Run around coils solutions, ECONET or EcotermNo risk of odour and bacteria transferFree to separate the supply air unit from the exhaust air unit

Rotary heat exchangerGood heat recovery efficiencyRisk of odour and bacteria transfer

Plate heat exchangerSimple solutionModerate heat recoverySmall risk of odour and bacteria transfer

High Efficient Energy recovery systems

Page 6: P Sundelin: Econet - matalaenergiajärjestelmä ilmanvaihtoon

© Fläkt Woods 6

ECONET® The new heat/cooling recovery system

The traditional wayThe ECONET way

Unique for ‘run around coils’Flexible installation and performance

No leakage between the supply and return air

(no odour and bacteria transfer)

Can also be used for corrossive and polluted air

Page 7: P Sundelin: Econet - matalaenergiajärjestelmä ilmanvaihtoon

© Fläkt Woods 7

ECONET® The new heat/cooling recovery system

The traditional wayThe ECONET way

Unique for the ECONET way1 component, 4 functions

lower pressure drops,shorter AHU

Increased heat recovery efficiency 60…75% performance

Able to use cooling recovery

Allways prepared for cooling and cooling recovery

Possibility to utilize process/waste heat

Perfect for district cooling/heating

Fitted for VAV systems

Page 8: P Sundelin: Econet - matalaenergiajärjestelmä ilmanvaihtoon

© Fläkt Woods 8

ECONET reduces the investment costs Reduces the size of the chiller Reduced cold water flows, pipe work dimensions

Reduces the size of the boilerReduced hot water flows, pipe work dimensions

Can utilize cheap waste heat

Reduced energy costsBetter energy recoveryPossibility to use waste heat

Smaller foot-print1 component instead of 3 components in the supply air unit

Shorter installation timePre-fabricated pump unit with pre-programmed control box.

ECONET® Benefits (investment)

Page 9: P Sundelin: Econet - matalaenergiajärjestelmä ilmanvaihtoon

© Fläkt Woods 9

22ºC 11°C

32°C 16°C

18°C 24°C 28°C 19°C 24°C

The exhaust air

The supply air

(95 kW)

Reduction of cooling power by utilizing cooling recovery and IEC

(120 kW)

44% of the cooling power needed taken from cooling recovery

238 kW

ECONET® Case cooling

Page 10: P Sundelin: Econet - matalaenergiajärjestelmä ilmanvaihtoon

© Fläkt Woods 10

26ºC 11°C

32°C 16°C

18°C 24°C 29°C 24°C

The exhaust air

The supply air

(50 kW)

Reduction of cooling power by utilizing cooling recovery

(167 kW)

23% of the cooling power needed taken from cooling recovery

ECONET® Case cooling

Page 11: P Sundelin: Econet - matalaenergiajärjestelmä ilmanvaihtoon

© Fläkt Woods 11

ECONET reduces the investment costs Reduces the size of the chiller Reduced cold water flows, pipe work dimensions

Reduces the size of the boilerReduced hot water flows, pipe work dimensionsCan utilize cheap waste heat

Reduced energy costsBetter energy recoveryPossibility to use waste heat

Smaller foot-print1 component instead of 3 components in the supply air unit

Shorter installation timePre-fabricated pump unit with pre-programmed control box.

ECONET® Benefits (investment)

Page 12: P Sundelin: Econet - matalaenergiajärjestelmä ilmanvaihtoon

© Fläkt Woods 12

-12°C +20°C

+23°C

27°C

18°C

The supply air

The exhaust air

Reduction of heating power by utilizing superior heat recovery

(239 kW)

(99 kW)

70% of the heating power needed taken from heat recovery

149 kW

ECONET® Case heating

Page 13: P Sundelin: Econet - matalaenergiajärjestelmä ilmanvaihtoon

© Fläkt Woods 13

ECONET reduces the investment costs Reduces the size of the chiller Reduced cold water flows, pipe work dimensions

Reduces the size of the boilerReduced hot water flows, pipe work dimensions

Can utilize cheap waste heat

Reduced energy costsBetter energy recoveryPossibility to use waste heat

Smaller foot-print1 component instead of 3 components in the supply air unit

Shorter installation timePre-fabricated pump unit with pre-programmed control box.

ECONET® Benefits (LCC, investment/running costs)

Page 14: P Sundelin: Econet - matalaenergiajärjestelmä ilmanvaihtoon

© Fläkt Woods 14

EU-53 (8,8 m³/s, 31 680m³/h) Running time: 24 hour/day, 365 d/y, CAV system Duration curve: Berlin Supply air temperature: 20°C…16°C Exhaust air temperature: 22°C…24°C Efficiency variants for the coils ECONET Ecoterm 5/supply air coil 2/supply air coil 3/exhaust air coil 3/exhaust air

ECONET® Benefits (impact of running costs)

No recovery Ecoterm ECONET®

Heating energy

Cooling energy

769 MWh 211 MWh 136 MWh

155 MWh 155 MWh 129 MWh

Page 15: P Sundelin: Econet - matalaenergiajärjestelmä ilmanvaihtoon

© Fläkt Woods 15

Everywhere where there is a need of a ‘run around coil’ solution

Everywhere, where You have ‘waste’ heat available

Everywhere, where You want to optimise Your cooling system

Everywhere, where You have too small equipment rooms

Everywhere, where You want to protect Your supply air filter

In 9 Years more than 1500 systems sold