Transcript
Page 1: Control Stations (GRP) - Three Function Customised Control Station - Walsall LCP300

Cornwallis Road, West Bromwich, West Midlands, B70 7DX, UKTel: +44 (0)121 500 6161 ~ Fax: +44 (0)121 500 6300Web: www.walsall-ltd.com ~ Email: [email protected]

Walsall Middle EastRAK Free Trade Zone, P. O. Box 10559 Ras Al Khaimah, United Arab EmiratesTel: +971 (0) 7 2660039Fax: +971 (0) 7 2660242Email: [email protected]: [email protected]

Walsall North America 11490 Westheimer, Suite 850Houston 77077Texas, USATel: +1 (713) 425 6361Fax: +1 (713) 783 0067

Walsall Asia Pacific10 Upper Aljunied Link,York International Industrial Building #02-05 Singapore 367904Tel: +65 (0) 6858-5259Fax: +65 (0) 6858-6560Email: [email protected]

Walsall South AmericaAv Nilo Pecanha, 50.Sala 1709. Centro, Rio De Janeiro,RJ, Brazil.CEP, 20020-906.Tel: +55 (21) 2025 1059Fax: +55 (21) 3084-1446

Local Control Station - Glass Reinforced Polyester Enclosure

230

110

124

200

116

138

236

120

153

All Dimensions in mm.

Material Box 1.5mm 316L, (1.4404) Stainless

Finish Stainless Steel - electropolished

Weight Empty 1.2Kg

Cover Fixing Captive M6 Stainless Steel hexagon head slotted screws

Gasket One piece fire resistant closed cell neoprene for Ta -40°C

Earthing 6mm brass internal/external earth stud as standardOptional brass earth stud welded to cover

Entries - Base 1x20mm clearance hole in face A, fitted with a nylon Ex e stopping plug. 1x20mm clearance hole in face B, fitted with a nylon Ex e cable gland. 25mm entries are available as an option

Entries - Cover 3 x entries maximum as required by control functions specified.

External Mounting External lugs with 8mm clearance

Security Switches with an off position have a padlock ‘off’ ‘ facility as standard

ENCLOSURE SPECIFICATION

LCS300 - Ex edm Three Function Customised Control Stations

The first function specified in the order code occupies position X in the enclosure, the second function Y and the third function position Z.

Ordering codes are built up as shown in the following examples.

Example 1 Emergency stop with pull release plus green start plus green indicator lamp

Product Code: LCS300 + CF26 + CF11 + CF34

Double green and red pushbutton plus red indicator plus mushroom pushbutton.

Product Code: LCS300 + CF32 + CF33+ CF17

1. Labelling to be specified by customer.2. For 25mm entries add /25 to enclosure code e.g. LCS300/25 + CF26 + CF11 + CF34

ORDERING INFORMATION

CONTROL FUNCTIONSSee CF Range Data Sheet

1,2 and 3 function local control stations can be connected together to engineermore complex systems. The interconnection is made via a specially approvedgland manufactured by Walsall Ltd.

ENCLOSURE INTERCONNECTIONS

HAZARDOUS AREA SPECIFICATION

Marking to 94/9/EC II 2 GD

Type of Protection Ex edm IIC T* GbEx tb IIIC T**°C Db

Ambient Temp.°C Gas Temperature Class (T*C)

Dust Temperature Class (T**)(°C)Min Max

-20*+50

(Contacts or Terminals)

T5 95

-20* +50 (Ammeter)

T5 95

-20* +40 (LED)

T6 80

* -40°C when used with a plug and gland rated to -40°C

For a combination of components the lowest maximum rating applies

Ingress Protection IP64 for rotary switches, IP66 all other functions

Area Classification Zones 1,2,21,22

Certification No. SIRA99ATEX3199, GOST-R POCC GB.Mл14.B00076

ELECTRICAL SPECIFICATIONSee CF Range Data Sheet