YLAA0070 - YLAA0175AIR-COOLED SCROLL CHILLERS

STYLE A, B or C (60 Hz)70 - 175 TON246-613 KW

WIRING

AIR-COOLED LIQUID CHILLERSHERMETIC SCROLL

New Release Form 150.72-W1 (109)

R-410A

Interim

GS560418.jpg

Page 2: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

JOHNSON CONTROLS2

FORM 150.72-W1 (109)

This equipment is a relatively complicated apparatus. During installation, operation, maintenance or service, individuals may be exposed to certain components or conditions including, but not limited to: refrigerants, oils, materials under pressure, rotating components, and both high and low voltage. Each of these items has the potential, if misused or handled improperly, to cause bodily injury or death. It is the obligation and responsibility of operating/service personnel to identify and recognize these inherent hazards, protect themselves, and proceed safely in completing their tasks. Failure to comply with any of these requirements could result in serious damage to the equipment and the property in

IMPORTANT!READ BEFORE PROCEEDING!

GENERAL SAFETY GUIDELINES

which it is situated, as well as severe personal injury or death to themselves and people at the site.

This document is intended for use by owner-authorized operating/service personnel. It is expected that this individual possesses independent training that will enable them to perform their assigned tasks properly and safely. It is essential that, prior to performing any task on this equipment, this individual shall have read and understood this document and any referenced materials. This individual shall also be familiar with and comply with all applicable governmental standards and regulations pertaining to the task in question.

SAFETY SYMBOLSThe following symbols are used in this document to alert the reader to areas of potential hazard:

CAUTION identifies a hazard which could lead to damage to the machine, damage to other equipment and/or environmental pollution. Usually an instruction will be given, together with a brief explanation.

NOTE is used to highlight additional information which may be helpful to you.

DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.

WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or se-rious injury.

External wiring, unless specified as an optional connection in the manufacturer’s product line, is not to be connected inside the micro panel cabinet. Devices such as relays, switches, transducers and controls may not be installed inside the panel. no external wiring is al-lowed to be run through the micro panel. All wiring must be in accordance with YORK’s published specifications and must be performed ONlY by qualified YORK personnel. YORK will not be responsible for damages/problems resulting from improper connections to the controls or application of improper control signals. Failure to follow this will void the manufacturer’s warranty and cause serious damage to property or injury to persons.

Page 3: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

FORM 150.72-W1 (109)

3JOHNSON CONTROLS

CHANGEABILITY OF THIS DOCUMENT

In complying with Johnson Controls policy for continuous product improvement, the information contained in this document is subject to change without notice. While Johnson Controls makes no commitment to update or provide current information automatically to the manual owner, that information, if applicable, can be obtained by contacting the nearest Johnson Controls Service office.

It is the responsibility of operating/service personnel to verify the applicability of these documents to the equipment in question. If there is any question in the mind of operating/service personnel as to the applicability of these documents, then prior to working on the equipment, they should verify with the owner whether the equipment has been modified and if current literature is available.

LIST OF FIGURES

YLAA 0070-0080-0090-0091-0100-0101-0115-0120-0125-0135-0150-0155

FIG. 1 - 4 – ELEMENTaRy DiaGRaMS .................................................................................................... 6-12

FIG. 5 - 9 – CONNECTiON DiaGRaMS .................................................................................................. 14-23

YLAA 0141-0156

FIG. 10 - 13 – ELEMENTaRy DiaGRaMS .............................................................................................. 24-30

FIG. 14 - 18 – CONNECTiON DiaGRaMS .............................................................................................. 32-41

YLAA 0170-0175

FIG. 19 - 22 – ELEMENTaRy DiaGRaMS .............................................................................................. 42-48

FIG. 23 - 27 – CONNECTiON DiaGRaMS .............................................................................................. 50-59

FIG. 28 - PuMP WiRiNG DiaGRaM ..............................................................................................................60

FIG. 29 - LOW aMbiENT WiRiNG DiaGRaM ................................................................................................60

1

2

3

4

5

Page 4: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

JOHNSON CONTROLS4

FORM 150.72-W1 (109)

LEGENDDESIGNATION DESCRIPTION

aCC aCCESSORy-aDiS DiSPLay bOaRD-aMb MiRCObOaRD

-baMb aMbiENT-bDP DiSCHaRGE PRESSuRE

-bECT ENTERiNG CHiLLED TEMP.-bLCT LEaviNG CHiLLED TEMP.

-bMPMOTOR PROTECTOR COMPRESSOR

-bSP SuCTiON PRESSuRE-CPF CaPaCiTOR POWER FaCTOR-ECH CRaNkCaSE HEaTER-EEH EvaPORaTOR HEaTER-EPH PuMP HEaTER

-EXT EXTERNaL TO CONTROL PaNEL

-F FuSE-FHP HiGH PRESSuRE CuTOuT-FSC FaN SPEED CONTROLLER

-FSi FaN SPEED iNHibiT TWO SPEED FaN OPTiON ONLy

GND GROuNDG/y GREEN / yELLOW

J PLuG-k CiRCuiT bOaRD RELay

-kF (iNCLuDiNG COiL SuPPRESSOR)

-kFHFaN CONTaCTOR HiGH SPEED(iNCLuDiNG COiL SuPPRESSOR)

-kFLFaN CONTaCTOR LOW SPEED(iNCLuDiNG COiL SuPPRESSOR)

-kFOL FaN OvERLOaD-kFS RELay FaN SPEED-kH HEaTER RELay

-kMCOMPRESSOR RELay(iNCLuDiNG COiL SuPPRESSOR)

-kCR CONTROL RELay

-kPPuMP CONTaCTOR PaRT(iNCLuDiNG COiL SuPPRESSOR)

-kT RELay TiMER-M COMPRESSOR MOTOR

-MF MOTOR FaN-MP MOTOR PuMPNu NOT uSED

DESIGNATION DESCRIPTIONPE PROTECTivE EaRTH

PWM PuLSE WiDTH MODuLaTiON-QCb CiRCuiT bREakER

-QMMSC MaNuaL MOTOR STaRTER COMPRESSOR

-QMMSPMaNuaL MOTOR STaRTER PuMP

-QSD SWiTCH DiSCONNECTR RESiSTOR

RED REDRP RuN PERMiSSivERu REMOTE uNLOaD 1ST STEP

SCR SCREEN-SF FLOW SWiTCH

-SkP kEyPaD-SOa SWiTCH OFF auTO

-T TRaNSFORMER-TC TRaNSFORMER CuRRENT

-ubR bRiDGE RECTiFiERWHT WHiTE

-XPPLuGS bETWEEN POW./MiCRO SECTiON

-XTbC TERMiNaL bLOCk CuSTOMER-XTbF TERMiNaL bLOCk FaCTORy

-yESv EvaPORaTOR SOLENOiD vaLvE

-yHGSvHOT GaS SOLENOiD vaLvE(iNCLuDiNG COiL SuPPRESSOR)

-yLLSvLiQuiD LiNE SOLENOiD vaLvEFiELD MOuNTED aND WiRED ON REMOTE EvaP. uNiT

-ZCPR COMPRESSOR

NOTE WELL (SEE NOTE)

WiRiNG aND iTEMS SHOWN aRE STaNDaRD yORk aCCESSORiESWiRiNG aND iTEMS SHOWN aRE NOT SuPPLiEDby yORkiTEMS ENCLOSED FORM a COMPONENT OR SET OF COMPONENTS

Page 5: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

FORM 150.72-W1 (109)

5JOHNSON CONTROLS

NOTES1. Refer to installation, commissioning , operation and maintenance manual for customer connections and customer

connection notes. Non-compliance to these instructions WILL invalidate unit warranty.2. Wiring and components for compressor 3 only fitted when unit has 3 compressors on the system. 1-BMP3 is

replaced by a link across terminals 134 & 135. 2-BMP3 is replaced by a link across terminals 234 & 235.3. FHP2 is only fitted on CE YLAA0180 and above. When NOT fitted 1-FHP2 is replaced by a link across termi-

nals 132 & 139. 2-FHP2 is replaced by a link across terminals 232 & 239.4. Fitted on units with Hot Gas Bypass option.5. EMS option is wired as shown.6. This wiring MUST be used for old display 031-01110-000.7. Network connection point.8. Printer port.9. Remote emergency stop can be wired between terminal L and 5 after removing link.

10. Power factor correction accessory. Power factor correction fitted to each compressor contactor.11. Not fitted on compressors with internal motor protection. For system 1 terminals 132 & 133, 133 & 134 are

linked. For system 2 terminals 232 & 233, 233 & 234 and 234 & 235 are linked.12. Only fitted on systems with 3 or 4 fans.13. Only fitted on systems with 4 fans.14. Only fitted on systems with 5 fans.15. Only fitted on systems with 6 fans.16. Input disconnect (Standard on CE units) or circuit breaker option replaces input terminal block.17. Input switch disconnect & individual system circuit breaker option replaces input terminal block.18. 115V control circuit requires a 115V supply unless control circuit transformer -T2 & F3 are fitted (standard on

CE units).19. For optional Hydro Kit. Heater -EPH is fitted and wired as shown. On single pump -KP1, -QMMSP1 & -MP1

are fitted & wired as shown. On two pump Hydro Kits -KP2, -QMMSP2 & -MP2 are also fitted as wired as shown.

20. Current measurement option wired as shown.21. Only fitted on systems with single speed fans.22. Only fitted on systems with two speed fans.23. Optional compressor manual motors starters (standard on CE units).24. See sheet 3 of connection diagram for power input options.25. Alternate connections shown for different two speed motor types.26. Only fitted on systems with a maximum of 4 fans.27. 220/230V units require a separate fuse for units with 4 or more fans per system.28. Low Ambient Kit - FSC for fan -MF1 is only fitted on systems with less than 4 fans.29. Only fitted on YLAA0091.30. Only fitted on YLAA0090, 0091, & 0135.31. Input dual point circuit breaker option replaces input terminal block.32. Field installed on remote evaporator units.33. Fitted on units with single phase motors only.34. Fitted on units with low ambient option only.

Page 6: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

JOHNSON CONTROLS6

FORM 150.72-W1 (109)

035-21583-101 Rev. C

FIG. 1 – ELEMENTaRy DiaGRaM

LD13835

ELEMENTARY DIAGRAM(YLAA0070-0080-0090-0091-0100-0101-0115-0120-0125-0135-0150-0155)

YLAA WIRING

Page 7: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

FORM 150.72-W1 (109)

7JOHNSON CONTROLS

FIG. 1 (CON’T) – ELEMENTaRy DiaGRaM

LD13835

ELEMENTARY DIAGRAM (CON’T)(YLAA0070-0080-0090-0091-0100-0101-0115-0120-0125-0135-0150-0155) 1

Page 8: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

JOHNSON CONTROLS8

FORM 150.72-W1 (109)

FIG. 2 – ELEMENTaRy DiaGRaM

LD13837

ELEMENTARY DIAGRAM(YLAA0070-0080-0090-0091-0100-0101-0115-0120-0125-0135-0150-0155)

035-21583-102 Rev. C

YLAA WIRING

Page 9: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

FORM 150.72-W1 (109)

9JOHNSON CONTROLS

FIG. 2 (CON’T) – ELEMENTaRy DiaGRaM

LD13838

ELEMENTARY DIAGRAM (CON’T)(YLAA0070-0080-0090-0091-0100-0101-0115-0120-0125-0135-0150-0155) 1

Page 10: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

JOHNSON CONTROLS10

FORM 150.72-W1 (109)

FIG. 3 – ELEMENTaRy DiaGRaM

LD13992

ELEMENTARY DIAGRAM(YLAA0070-0080-0090-0091-0100-0101-0115-0120-0125-0135-0150-0155)

035-21583-103 Rev. B

YLAA WIRING

Page 11: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

FORM 150.72-W1 (109)

11JOHNSON CONTROLS

FIG. 3 (CON’T) – ELEMENTaRy DiaGRaM

LD13993

ELEMENTARY DIAGRAM (CON’T)(YLAA0070-0080-0090-0091-0100-0101-0115-0120-0125-0135-0150-0155) 1

Page 12: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

JOHNSON CONTROLS12

FORM 150.72-W1 (109)

FIG. 4 – ELEMENTaRy DiaGRaM

LD13992

ELEMENTARY DIAGRAM(YLAA0070-0080-0090-0091-0100-0101-0115-0120-0125-0135-0150-0155)

035-21583-116 Rev. -

YLAA WIRING

Page 13: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

FORM 150.72-W1 (109)

13JOHNSON CONTROLS

THIS PAGE INTENTIONALLY LEFT BLANK

1

Page 14: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

JOHNSON CONTROLS14

FORM 150.72-W1 (109)

FIG. 5 – CONNECTiON DiaGRaM

LD14025

CONNECTION DIAGRAM(YLAA0070-0080-0090-0091-0100-0101-0115-0120-0125-0135-0150-0155)

035-21589-101 Rev. B

YLAA WIRING

Page 15: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

FORM 150.72-W1 (109)

15JOHNSON CONTROLS

FIG. 5 (CON’T) – CONNECTiON DiaGRaM

LD14026

CONNECTION DIAGRAM (CON’T)(YLAA0070-0080-0090-0091-0100-0101-0115-0120-0125-0135-0150-0155) 1

Page 16: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

JOHNSON CONTROLS16

FORM 150.72-W1 (109)

FIG. 6 – CONNECTiON DiaGRaM

LD14027

035-21589-102 Rev. C

CONNECTION DIAGRAM(YLAA0070-0080-0090-0091-0100-0101-0115-0120-0125-0135-0150-0155)

YLAA WIRING

Page 17: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

FORM 150.72-W1 (109)

17JOHNSON CONTROLS

FIG. 6 (CON’T) – CONNECTiON DiaGRaM

LD14027

035-21589-102 Rev. C

CONNECTION DIAGRAM (CON’T)(YLAA0070-0080-0090-0091-0100-0101-0115-0120-0125-0135-0150-0155) 1

Page 18: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

JOHNSON CONTROLS18

FORM 150.72-W1 (109)

FIG. 7 – CONNECTiON DiaGRaM

LD14029

035-21589-103 Rev. B

CONNECTION DIAGRAM(YLAA0070-0080-0090-0091-0100-0101-0115-0120-0125-0135-0150-0155)

YLAA WIRING

Page 19: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

FORM 150.72-W1 (109)

19JOHNSON CONTROLS

FIG. 7 (CON’T) – CONNECTiON DiaGRaM

LD14030

035-21589-103 Rev. B

CONNECTION DIAGRAM (CON’T)(YLAA0070-0080-0090-0091-0100-0101-0115-0120-0125-0135-0150-0155) 1

Page 20: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

JOHNSON CONTROLS20

FORM 150.72-W1 (109)

FIG. 8 – CONNECTiON DiaGRaM

LD14031

035-21589-106 Rev. C

CONNECTION DIAGRAM(YLAA0070-0080-0090-0091-0100-0101-0115-0120-0125-0135-0150-0155)

YLAA WIRING

Page 21: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

FORM 150.72-W1 (109)

21JOHNSON CONTROLS

FIG. 8 (CON’T) – CONNECTiON DiaGRaM

LD14032

035-21589-106 Rev. C

CONNECTION DIAGRAM (CON’T)(YLAA0070-0080-0090-0091-0100-0101-0115-0120-0125-0135-0150-0155) 1

Page 22: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

JOHNSON CONTROLS22

FORM 150.72-W1 (109)

FIG. 9 – CONNECTiON DiaGRaM

LD14034

CONNECTION DIAGRAM(YLAA0070-0080-0090-0091-0100-0101-0115-0120-0125-0135-0150-0155)

035-21589-107 Rev. A

YLAA WIRING

Page 23: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

FORM 150.72-W1 (109)

23JOHNSON CONTROLS

FIG. 9 (CON’T) – CONNECTiON DiaGRaM

LD14035

CONNECTION DIAGRAM (CON’T)(YLAA0070-0080-0090-0091-0100-0101-0115-0120-0125-0135-0150-0155)

035-21589-107 Rev. A

1

Page 24: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

JOHNSON CONTROLS24

FORM 150.72-W1 (109)

035-21583-101 Rev. C

FIG. 10 – ELEMENTaRy DiaGRaM

LD13835

ELEMENTARY DIAGRAM(YLAA0141-0156)

YLAA WIRING

Page 25: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

FORM 150.72-W1 (109)

25JOHNSON CONTROLS

FIG. 10 (CON’T) – ELEMENTaRy DiaGRaM

LD13835

ELEMENTARY DIAGRAM (CON’T)(YLAA0141-0156)

2

Page 26: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

JOHNSON CONTROLS26

FORM 150.72-W1 (109)

LD13837

035-21583-102 Rev. C

FIG. 11 – ELEMENTaRy DiaGRaM

ELEMENTARY DIAGRAM(YLAA0141-0156)

YLAA WIRING

Page 27: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

FORM 150.72-W1 (109)

27JOHNSON CONTROLS

LD13838

FIG. 11 (CON’T) – ELEMENTaRy DiaGRaM

ELEMENTARY DIAGRAM (CON’T)(YLAA0141-0156)

2

Page 28: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

JOHNSON CONTROLS28

FORM 150.72-W1 (109)

LD14036

FIG. 12 – ELEMENTaRy DiaGRaM

ELEMENTARY DIAGRAM(YLAA0141-0156)

035-21583-116 Rev. A

YLAA WIRING

Page 29: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

FORM 150.72-W1 (109)

29JOHNSON CONTROLS

LD14037

FIG. 12 (CON’T) – ELEMENTaRy DiaGRaM

ELEMENTARY DIAGRAM (CON’T)(YLAA0141-0156)

2

Page 30: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

JOHNSON CONTROLS30

FORM 150.72-W1 (109)

LD14033

FIG. 13 – ELEMENTaRy DiaGRaM

ELEMENTARY DIAGRAM(YLAA0141-0156)

035-21583-116 Rev. -

YLAA WIRING

Page 31: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

FORM 150.72-W1 (109)

31JOHNSON CONTROLS

THIS PAGE INTENTIONALLY LEFT BLANK

2

Page 32: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

JOHNSON CONTROLS32

FORM 150.72-W1 (109)

LD14025

035-21589-101 Rev. B

FIG. 14 – CONNECTiON DiaGRaM

CONNECTION DIAGRAM(YLAA0141-0156)

YLAA WIRING

Page 33: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

FORM 150.72-W1 (109)

33JOHNSON CONTROLS

LD14026

FIG. 14 (CON’T) – CONNECTiON DiaGRaM

CONNECTION DIAGRAM (CON’T)(YLAA0141-0156)

2

Page 34: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

JOHNSON CONTROLS34

FORM 150.72-W1 (109)

FIG. 15 – CONNECTiON DiaGRaM

CONNECTION DIAGRAM(YLAA0141-0156)

LD14027

035-21589-102 Rev. C

YLAA WIRING

Page 35: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

FORM 150.72-W1 (109)

35JOHNSON CONTROLS

FIG. 15 (CON’T) – CONNECTiON DiaGRaM

CONNECTION DIAGRAM (CON’T)(YLAA0141-0156)

LD14028

035-21589-102 Rev. C

2

Page 36: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

JOHNSON CONTROLS36

FORM 150.72-W1 (109)

LD14029

FIG. 16 – CONNECTiON DiaGRaM

CONNNECTION DIAGRAM(YLAA0141-0156)

035-21589-103 Rev. B

YLAA WIRING

Page 37: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

FORM 150.72-W1 (109)

37JOHNSON CONTROLS

LD14030

FIG. 16 (CON’T) – CONNECTiON DiaGRaM

CONNECTION DIAGRAM (CON’T)(YLAA0141-0156)

035-21589-103 Rev. B

2

Page 38: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

JOHNSON CONTROLS38

FORM 150.72-W1 (109)

LD14031

FIG. 17 – CONNECTiON DiaGRaM

035-21589-106 Rev. C

CONNNECTION DIAGRAM(YLAA0141-0156)

YLAA WIRINGYLAA WIRING

Page 39: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

FORM 150.72-W1 (109)

39JOHNSON CONTROLS

LD14032

FIG. 17 (CON’T) – CONNECTiON DiaGRaM

035-21589-106 Rev. C

CONNECTION DIAGRAM (CON’T)(YLAA0141-0156)

2

Page 40: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

JOHNSON CONTROLS40

FORM 150.72-W1 (109)

FIG. 18 – CONNECTiON DiaGRaM

CONNNECTION DIAGRAM(YLAA0141-0156)

LD14034

035-21589-107 Rev. A

YLAA WIRING

Page 41: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

FORM 150.72-W1 (109)

41JOHNSON CONTROLS

FIG. 18 (CON’T) – CONNECTiON DiaGRaM

CONNECTION DIAGRAM (CON’T)(YLAA0141-0156)

LD14035

035-21589-107 Rev. A

2

Page 42: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

JOHNSON CONTROLS42

FORM 150.72-W1 (109)

035-21583-101 Rev. C

FIG. 19 – ELEMENTaRy DiaGRaM

LD13835

ELEMENTARY DIAGRAM(YLAA0170-0175)

YLAA WIRING

Page 43: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

FORM 150.72-W1 (109)

43JOHNSON CONTROLS

FIG. 19 (CON’T) – ELEMENTaRy DiaGRaM

LD13835

ELEMENTARY DIAGRAM (CON’T)(YLAA0170-0175)

3

Page 44: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

JOHNSON CONTROLS44

FORM 150.72-W1 (109)

LD13837

035-21583-102 Rev. C

FIG. 20 – ELEMENTaRy DiaGRaM

ELEMENTARY DIAGRAM(YLAA0170-0175)

YLAA WIRING

Page 45: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

FORM 150.72-W1 (109)

45JOHNSON CONTROLS

LD13838

FIG. 20 (CON’T) – ELEMENTaRy DiaGRaM

ELEMENTARY DIAGRAM (CON’T)(YLAA0170-0175)

3

Page 46: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

JOHNSON CONTROLS46

FORM 150.72-W1 (109)

FIG. 21 – ELEMENTaRy DiaGRaM

ELEMENTARY DIAGRAM(YLAA0170-0175)

LD13994

035-21583-104 Rev. C

YLAA WIRING

Page 47: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

FORM 150.72-W1 (109)

47JOHNSON CONTROLS

FIG. 21 (CON’T) – ELEMENTaRy DiaGRaM

ELEMENTARY DIAGRAM (CON’T)(YLAA0170-0175)

LD13995

3

Page 48: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

JOHNSON CONTROLS48

FORM 150.72-W1 (109)

LD14033

FIG. 22 – ELEMENTaRy DiaGRaM

ELEMENTARY DIAGRAM(YLAA0170-0175)

035-21583-116 Rev. -

YLAA WIRING

Page 49: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

FORM 150.72-W1 (109)

49JOHNSON CONTROLS

THIS PAGE INTENTIONALLY LEFT BLANK3

Page 50: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

JOHNSON CONTROLS50

FORM 150.72-W1 (109)

LD14025

035-21589-101 Rev. B

FIG. 23 – CONNECTiON DiaGRaM

CONNECTION DIAGRAM(YLAA0170-0175)

YLAA WIRING

Page 51: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

FORM 150.72-W1 (109)

51JOHNSON CONTROLS

LD14026

FIG. 23 (CON’T) – CONNECTiON DiaGRaM

CONNECTION DIAGRAM (CON’T)(YLAA0170-0175)

3

Page 52: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

JOHNSON CONTROLS52

FORM 150.72-W1 (109)

FIG. 24 – CONNECTiON DiaGRaM

CONNECTION DIAGRAM(YLAA0170-0175)

LD14027

035-21589-102 Rev. C

YLAA WIRING

Page 53: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

FORM 150.72-W1 (109)

53JOHNSON CONTROLS

FIG. 24 (CON’T) – CONNECTiON DiaGRaM

CONNECTION DIAGRAM (CON’T)(YLAA0170-0175)

LD14028

035-21589-102 Rev. C

3

Page 54: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

JOHNSON CONTROLS54

FORM 150.72-W1 (109)

FIG. 25 – CONNECTiON DiaGRaM

CONNECTION DIAGRAM(YLAA0170-0175)

LD14029

035-21589-103 Rev. B

YLAA WIRING

Page 55: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

FORM 150.72-W1 (109)

55JOHNSON CONTROLS

FIG. 25 (CON’T) – CONNECTiON DiaGRaM

CONNECTION DIAGRAM (CON’T)(YLAA0170-0175)

LD14030

035-21589-103 Rev. B

3

Page 56: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

JOHNSON CONTROLS56

FORM 150.72-W1 (109)

FIG. 26 – CONNECTiON DiaGRaM

CONNECTION DIAGRAM(YLAA0170-0175)

LD14031

035-21589-106 Rev. C

YLAA WIRING

Page 57: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

FORM 150.72-W1 (109)

57JOHNSON CONTROLS

FIG. 26 (CON’T) – CONNECTiON DiaGRaM

CONNECTION DIAGRAM (CON’T)(YLAA0170-0175)

LD14032

035-21589-106 Rev. C

3

Page 58: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

JOHNSON CONTROLS58

FORM 150.72-W1 (109)

FIG. 27 – CONNECTiON DiaGRaM

CONNECTION DIAGRAM(YLAA0170-0175)

LD14034

035-21589-107 Rev. A

YLAA WIRING

Page 59: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

FORM 150.72-W1 (109)

59JOHNSON CONTROLS

FIG. 27 (CON’T) – CONNECTiON DiaGRaM

CONNECTION DIAGRAM (CON’T)(YLAA0170-0175)

LD14035

035-21589-107 Rev. A

3

Page 60: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

JOHNSON CONTROLS60

FORM 150.72-W1 (109)YLAA WIRING

FIG. 28 – PuMP WiRiNG DiaGRaM

PUMP WIRING DIAGRAM

LD14038

035-21583-105 Rev.B

Page 61: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

FORM 150.72-W1 (109)

61JOHNSON CONTROLS

THIS PAGE INTENTIONALLY LEFT BLANK

4

Page 62: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

JOHNSON CONTROLS62

FORM 150.72-W1 (109)YLAA WIRING

FIG. 29 – LOW / HiGH aMbiENT WiRiNG DiaGRaM (6OHZ)

LOW / HIGH AMBIENT WIRING DIAGRAM

LD14038

035-21583-114 Rev. C

Page 63: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

FORM 150.72-W1 (109)

63JOHNSON CONTROLS

FIG. 29 (CON’T) – LOW / HiGH aMbiENT WiRiNG DiaGRaM (60HZ)

LOW / HIGH AMBIENT WIRING DIAGRAM (CON’T)

LD14038

5

Page 64: YLAA0070 - YLAA0175 AIR-COOLED SCROLL CHILLERS …

©2009 Johnson Controls, inc. P.O. box 423, Milwaukee, Wi 53203www.johnsoncontrols.com

Printed in uSa 150.72-W1 (109)NEW RELEaSE